HomeMy WebLinkAboutSite PlanONSITE WASTEWATER TREATMENT GENERAL NOTES.• . _. 1. THIS SHEET /S PART OF A CIVIL ENGINEERING DESIGN COMPRISED OF 2 SHEETS, WITH ACCOMPANYING REPORT AND SUPPORTING INFORMATION. THE INSTALLER SHALL REVIEW THESE DOCUMENTS AND BECOME FAMILIAR WITH THEM PRIOR TO THE CONSTRUCTION OF THIS ON -SITE WASTEWATER TREATMENT SYSTEM (OWTS). 2. THE INSTALLER SHALL BE FAMILIAR WITH GARFIELD COUNTY OWTS REGULATION 43. ALL COMPONENTS OF THE;=, OWTS SHALL MEET APPLICABLE REGULATIONS J. THE INSTALLER SHALL NOTIFY GARFIELD COUNTYS OWTS INSPECTOR AND THE CIVIL ENGINEER AT LEAST THREE DAYS IN ADVANCE OF COMPLETING THE OWTS INSTALLATION, SO REQUIRED INSTALLATION OBSERVATIONS OF THE SEPTIC TANK, SOIL TREATMENT AREA, AND RELATED COMPONENTS CAN BE MADE PRIOR TO BACKF/LLING. -. INSTALLAT/ON OF THE SEPTIC TANK AND SOIL TREATMENT AREA SHALL BE SUBSTANTIALLY COMPLETE AND READY TO BE BACKFILLED PRIOR TO REQUESTING INDIVIDUAL OR SIMULTANEOUS INSTALLATION OBSERVATIONS FOR THESE COMPONENTS. 4. THE OWTS SHALL BE INSTALLED IN ACCORDANCE WITH SGM PLANS, DETAILS AND SPECIFICATIONS, IN ADDITION TO MANUFACTURERS' RECOMMENDATIONS SUBSTITUTIONS OF COMPONENTS OR MATERIALS WILL NOT BE ALLOWED WITHOUT THE WRITTEN APPROVAL OF THE CIVIL ENGINEER. INSTALLER SHALL PROVIDE CATALOG CUT WHEN REQUESTING SUBSTITUTIONS. s 5. ALL ELEVATIONS SHALL BE DEVELOPED /N THE FIELD BASED ON TANK INLET AND OUTLET INVERTS INVERT E ELEVATIONS SHALL BE ESTABLISHED FROM THE COVER THICKNESS OVER THE TANK, MINIMUM TO BE 12" AND .0 MAXIMUM TO BE 48" PIPE GRADES SHALL BE KEPT BETWEEN 2.0 TO 10.0 PERCENT FROM RESIDENCE TO TANK i AND TANK TO DISTRIBUTION BOX. PIPE FROM DISTRIBUTION BOX TO INFILTRATOR TRENCHES SHALL BE LEVEL AND INFILTRATORS SHALL BE SET ON LEVEL TRENCH FLOORS THE INSTALLER SHALL FIELD VERIFY GRADES AND ELEVATIONS PRIOR TO SETTING OWTS FEATURES QUESTIONS SHALL BE DIRECTED TO THE ENGINEER PRIOR To CONTINUING INSTALLATION OF FEATURES. 6. THE SOIL TREATMENT AREA (STA) SHALL BE PROTECTED FROM COMPACTION. VEHICULAR TRAFFIC SHALL BE KEPT =, OFF OF THE STA AND VEHICLES SHALL NOT BE PARKED ON THE STA. DUMP TRUCKS AND HEAVY TIRED VEHICLES SHALL NOT BE ALLOWED ON THE SOIL TREATMENT AREA. ALL SOIL RUTTED OR COMPACTED SHALL BE REMOVED AND REPLACED WITH SAND, 7. ALL PVC PIPE CONNECTIONS SHALL BE SOLVENT WELDED, UNLESS OTHERWISE SPECIFIED. >e 8. ALL RISERS AND VALVE BOXES SHALL BE CONSTRUCTED PER THE QUICK-4 DETAIL ON SHEET C.02. 9. SEWER PIPE AND EFFLUENT PIPE SHALL BE PROPERLY BEDDED PER THE TRENCH DETAIL PROVIDED ON SHEET C.02. 10, REVEGETATION OF ALL AREAS DISTURBED FOR OWTS CONSTRUCTION SHALL BE SEEDED. SEEDING SHALL BE THE RESPONSIBILITY OF THE OWNER AND CONTRACTOR. 11. SEPTIC TANK ASSEMBLIES SHALL BE CONSTRUCTED WATER TIGHT TO ASSURE NO GROUND OR STORM WATER WILL EFFECT DESIGN VOLUMES OF THE ASSEMBLIES 12. INSTALLER TO PROVIDE CLEANOUTS PER DETAIL ON SHEET C.02 WITHIN SO' OF THE BUILDING /N ADD/TLON TO UP -SLOPE OF TWO OR MORE BENDS CLOSER THAN 10' MAXIMUM DISTANCE BETWEEN CLEANOUTS TO BE 50.0: ,! 13. ALL 90' BENDS SHALL BE CONSTRUCTED FROM TWO 45' ELBOWS."r 14. SETBACK LOCATIONS ARE APPROXIMATED AND ADJUSTMENTS TO ACTUAL LOCATIONS MAY BE NECESSARY IN THE FIELD. IF ADJUSTMENTS ARE MADE THAT REDUCE SETBACK DISTANCES TO AN OWTS FEATURE, THE 007S FEATURE SHALL BE MOVED AT LEAST EQUAL DISTANCE TO MAINTAIN REQUIRED SETBACK DISTANCE. , 15. LOCAL BENCH MARK TO BE DETERMINED IN THE FIELD. BASIS OF DESIGN Kehr Single Famility Residential OWTS Design # Bedrooms Auxilliary Bldngs Bath/Shower Dishwasher Kitchen Sink w/Garbage Grinder Laundry Washer Lavatory Water Closet (toilet) Total Design Flows SITE CRITERIA Soil Type 1 2 2A 3 3A 4 4A 5 Design Flow (GPD) 525 i s2s gpd 0.2 Soil Loading Rate = 0.20 Based on Table 10.1 Soil Treatment Area = STA = Design Flow/LTAR 2625 ft' Size Adjustment Factors for Method of Application in STA Type of Absorption Area Method of Effluent Appication Dosed (siphon or Pressure Gravity pump) Dosed Trench X Bed Size Adjustment Factors for Types of Distribution Media in STA Category 2 Category 3 - Category 1- -Other Chambers or Rock or Tire MFG Enhanced Chips Media Media Type of Absorption Area X Size Adjustment for Method of Application = 1 Size Adjustment for Type of Distribution = 0.7 Adjusted STA Size = 1837.5 ft' Number of Infiltrators = 153 Total Length of Infiltrators = 612 ft Maximum Distribution Length = 100 ft Maximum Distribution Length w/Distribution Box Centered = 88 ft Number of Trenches = 6.95454545 Septic Tank Size = 1250 gallons TP--2 DISTRIBUTION' BOK SEWER LINE. SEPTIC TANK CONCRETE OR OTHER - ACCEPTASLE MATERIAL.' ru. F� ncNT` Su,` DE 4 L A ,Q NO u`+ Sr �c C , 02.�` ask s I Graphic Scale d 10 20 40 In Feet: 1" = 20' E O U (NO c Z)00 E Z) 00 NO a)U 3 � N Ln x Q0 U) VLO 0 cn v> O r 3 30, 00 N LO O N 0 O O r U �-: C O U O U� Q) O 1` O N M m 0 a� c 0 N N U � � o a Job No. 2020-575.001 Drawn by: TLB Date: 11 /24/2020 101e: OWTS Plan l Dwg No. C.01 Of: 2 Top View 7E TA6 LFSIGN &NOTES - Design per performance test. Per ASTM C1227 f'e 02$ days' F•ulh concrete = 6,000 PS! 7ANI m ZEN AT70N: ZO" Clear Acce , TAN o BE SET ON 5'" MN SAND BED OR PEA GRAVEL : t TANK TO BE BACKFILLED UNIFORMLY ON ALL SIDES IN LIFTS LESS THAN T^ANx 24' AND MECHANICALLY COMPACTED. { /p�: : EXCAVA TED MA IERIAL MA Y BE USED FOR BACKF/LL, PROVIDED LARGE T , . , • .: . STONES ARE REMOVED. EXCAVA77ON SHOULD BE DEWATEREO ANO TANK FILLED W,TH WATER PRIOR sets to Grade TO BEING PUT IN SERI9CE FOR /' JNSTALLA77ON WITH WATER TABLE LESS THAN 2' BELOW GRADE. O " Butyl Rubber Flexibl 5 Sealant Boot 4" PVC FROM HOUSE la%FOOT MIN. SLOPE r 4" SOLID WALL SCHEDULE 40 PVC PIPE AT 1/4 %FOOT SLOPE (MIN.) TO OIS7RIBUTION BOX z 4' Section View p C TA1250 GALL NTS SEPTIC TANK N07ES.• 1 PURPOSE OF INSPECON THATAISN DREADILY WSIIBRLE WHEN INSPECTED 8FOFOREE BACKFILUNG. 2. SEPTIC TANKS MUST BE ON THE COLORADO DEPARTMENT OF PUBLIC HEAG771 AND ENVIRONMENT'S ACCEPTED SEPTIC TANK UST. 3 MAXIMUM COVER DEPTH MEASURED FROM TANK 70P TO SURFACE COVER TO BE 4.0', MINIMUM 1.0: 4, AN EFFLUENT SCREEN SHALL BE INSTALLED AT THE OUTLET OF THE TANK. THE HANDLE OF THE SCREEN SHALL BE WITHIN 120 OF THE SURFACE 7RENCH N07€S. 1. TRENCHES MUST BE ;3.0' WIDE. 2. SEPARA17NG DISTANCE BETWEEN TRENCHES MUST BE 4.0, MEASURED FROM S/DEWALL TO SIDEWALL. J. NFILIRA 7M- SURFACE MUST BE NO DEEPER THAN 4,0, MEASURED ON THE UPSLOPE SIDE OF THE TRENCH 4, 7RDI FLOORS MUST BE LEVEL, WHICH MAY REOUIRE PLACEMENT OF AN ACCEPTABLE MEDIA DICTA7ED BY CHAMBER MANUFACTURER. CHAMBER NOTES.' 1. CHAMBERS MUST BE INSTALLED WITH THE BASE OF THE UNIT ON IN—S7SOIL OR IF PLACED ON ACCEPTABLE MEDIA, THE MANUFACTURERS INSTALLATIOON INSTRUCTIONS MUST BE FOLLOWED SO AS TO PREVENT CHAMBERS FROM SETTUNG INTO THE MEDIA 2. INSTALLATION MUST BE /N ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. INSPECTION PORT NOTES 1 EACH LgO7ER L ACCORDING T O CHAMBER MANUFACTURERSD 7ERMINAL ENDS OF PORTS SHALL INSMUCT70NS' ITS MAY BE BELOW FINAL GRADE BUT WILL NEED 2. TOP OF INSTALLEDC7H APO ER T THE SURFACE, I.E. IRRIG.4 ON VALVE BOX. 3. PLACE A REMOVABLE PVC CAP OVER THE TOP OPENING OF ALL INSPECTION PORTS. FINAL COVER MATERIAL NOTES' 1. FINAL COVER OF SOIL SUITABLE FOR VEGETATION AT LEAST 10" DEEP SHALL BE PLACED OVER TRENCHES. 2 EXCAVATED MATERIAL MAY BE USED FOR BACKFILL FROM BOTTOM OF VEGETATIVE MATERIAL TO 7RENCH FLOOR. EXCAVATED MATERIAL MUST BE FREE OF ROCK AND PLACED IN ACCORDANCE WITH CHAMBER a MANUFACTURER'S INS7RUC77ONS. m To ER 3. DRALFCECOVERETAE FINAL COVER W7H NA77VEGRILL �TAT0RRVE DROUGHT —TOLERANT GRASSES THE STA SMALL NOT BE IRRIGATED. R. N Npp i a U a a N 0 yNy l k U SURFACE FILL £XIS77NG DIRT OR — TOPSOIL AREA �? ON FOR SEWER UNE NSULA77 r. NEW SEWER LINE (SEE INSULATION SECTION BELOW) i (14.12 r ! ELEI/ATION Inlet ,..._, 4" OF POLYSTYRENE INSULATION (LOCATED ALONG LASS '' '' 6 PER TRENCH SIDES AND ON TOP OF PIPE) CROSS SEC77ON" j \—SEWER LINE `° t -- SE_ SEWER PIPE INSULATIONSEWERINSULATION D TAIL NO SCALE *USE 7UF. TITE 9HD OR EQUAL. DISTRIBUTION BOX — 9 HOLE NTS PLUG —45 M✓ ELBOW CONCRETE SUPPORT COLLAR 45 M✓ e� FLOW TO SOIL TREATMENT AREA PIIC ME ELBOW OR ELBO CLEAN —OUT DETAIL NOT TO SCALE FLOW FROM HOUSE ION 6' MIN (10' SHOWN) QUICK4 ; )?ENCH DETAIL NOT TO SCALE IF 6- D/A. PVC lS77NG DIRT OR VARIES TOPSOIL AREA SLOPE TRENCH WALLS FOR SAFETY PER CURRENT OSHA & COSH. REQUIREMENTS COMPACTED CLASS 6 AGGREGATE OR ON —SITE FILL MATERIAL W/C0MPAC770N 0 CL 0 DENSITY OF 95X PER ASTM D698 L 2' 10 GAUGE INSULATED C :x h TRACER WIRE CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95X PER ASTM D698 NOTES.' � e 1. INSULATAION OVER SEWER PIPING IS REQUIRED WHEN MINIMUm COVER DEPTH IS LESS PIPE INSUT ON DETAIL THISSHEET. (42�. SEE S ran TOCAI!'u CAp$S—SECTION NO SCALE INFILTRATOR SYSTEMS INC. QUICK4 STANDARD CHAMBER QUICK4 STANDARD MULTIPORT END CAP 1> Graphic Scale 18 36 In Feet: 1" = 36' E O u NO c .p Sao U O` S N i77 NN O 4) N �. 3 a C (OD (j) (> OWTS Details ------------ No. o. 2