HomeMy WebLinkAboutEngineering Letter from Boise 10.11.23It is assumed that the stair stringers shown
in the attached photo are fully supported by
a header beam with jamb studs on each
side and not supported by the cantilevered
joist ends shown beyond the bearing wall
(see attached photo).
With this understanding, the condition
requires no additional reinforcing for the
web penetrations noted on this
documentation. If the stringers are
supported by the joists, a revision to this
assessment will be required.10/11/2023
It is assumed that this is a
bearing wall and the stair
stringers shown are fully
supported by a header beam
with jamb studs on each side
and not supported by the
cantilevered joist ends
shown.
With this understanding, the
condition requires no
additional reinforcing for the
web penetrations noted on
this documentation. If the
stringers are supported by the
joists, a revision to this
assessment will be required.
10/11/2023
It is assumed that the stair
stringers shown in the
attached photo are fully
supported by a header beam
with jamb studs on each side
and not supported by the
cantilevered joist ends shown
beyond the bearing wall (see
attached photo).
With this understanding, the
condition requires no
additional reinforcing for the
web penetrations noted on
this documentation. If the
stringers are supported by
the joists, a revision to this
assessment will be required.
10/11/2023