HomeMy WebLinkAboutState Final Electrical Inspection Report COLORADO STATE ELECTRICAL BOARD 1560 Broadway, Suite 1350 Denver, CO 80202 Inspection Report Date Inspected: 10/03/2023 Permit #: 961368 Permit Holder: KEYSTONE SERVICE GROUP LLC MICHAEL WESTHOFF 6886 S PITKIN ST FOXFIELD 800161519 Phone: (970) 230-2539 Fax: Email: bbablitz@ksgllc.net Site: 7006 Cr 312 New Castle, Garfield County, Owner: Don Reboul Status: Partial Inspection Type: Final NEW RESIDENTIAL Inspector: Norman Feck 303-869-3442 Corrections: At shed: a. 300.5J Missing PVC expansion fitting at shed. b. 334.15B Protect NM from physical damage. Horizontal exposed runs below 7' are subject to physical damage. c. 110.3B Water heater has a field installed cord and plug. Hard wire it and provide disconnecting means. d. 110.7 Water heater circuit short circuits. e. 406.12(1) Tamper Resistant type (TR) receptacles required for garage and accessory buildings at residential premises. f. 225.33A No more than 6 switches allowed, per power source (see 225.30A), to de-energize that power source at separate building shed. g. 250.32A Building or structure supplied by feeder or branch circuit shall have a grounding electrode or grounding electrode system installed in accordance with Part III of 250. No rebar/concrete at shed. Two ground rods work for missing GE system. Comments: 1) House final ok 2) Shed UG was looked at with house UG The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.