HomeMy WebLinkAboutEngineer's OWTS Design ReportProposed Single-FamilY OWTS
Onsite Wastewater Treatment System Design
3-BR Single-Family Residence
Harvey Gap Road/CR 237
^ùdress
TBD
silt, co 81652
Parcel N o. 2127 -241,'01-002
Prepared for:
CMH Homes Tnc.
5000 Clayton Road
Maryville, TN 37804
October 2023
Prepared By:
ôNest Water E n g i n eeri n g
ê consulting Engineers & Scientisìs
2s1 6 FORESIGHT CIRCLE, f1 GRAND JUNCTION, COLORADO 8l 505 197 O) 241 -7 07 6 - F N (97 Ol 241 -7 O97
I.O SITE CONDITIONS
The proposed onsite wastewater treatment system (OWTS) will serve a 3-BR single-family
residince ona2.43-acre vacant parcel located at Harvey Gap Road CR237 Address TBD, Silt,
CO (Figure Al). Proposed 3-BR dwelling will be served by a new 1,000-gallon septic tank and
tftt.È (:J trenches eacL with fifteen (15) Q4 Standard Plus units for a minimum 77' x 64'
footprint with end caps (Figure A2). The trenches will be configured in serial distribution using
a total of 45 Standutd pt.6Qnick4 Infiltrator@ units generally oriented north to south parallel to
topographic contours in a soil treatment area (STA)/leachfield sloping approximately l8% east.
Soils and percolation data were collected by WestWater Engineering Septembet 19,2023 in
accordancè with Garfield County On-Site Wastewater Treatment System (OWTS) Regulations
(Regulations). Soil profile in the vicinity of proposed STA shows dark yellowish brown silty
Àand with some tabular gravel-sized sandstone clasts from 0.0 to 2.3 feet overlying dark
yellowish brown silty sand interbedded with colluvial soil with sub-angular to angular tabular
ólasts gravel to smaliboulder sized from 2.3-4.0 feet. Dark yellowish brown mix of colluvial
and alluvial soils with a pebbly sand matrix supporting sub-angular to sub-rounded tabular
reddish brown sandstonó clasts (up to 50o/o volume rock near 6.0-foot depth interval) from 4.0-
g.0 feet maximum depth of excavation. The high seasonal water table is estimated to be greater
than 8.0 feet below ground surface (bgs).
percolation rates for the 5 percolation test holes completed in the silty sand and colluvial-alluvial
soils range from 6 to 26 minutes per inch (min/in) with a 15 min/in average. Site soils are
classifieã as soil Type2 in accordance with Table 10-1 of the Regulations based on silty sand
texture, granular structure, and percolation rates generally faster than the 16-25 minlin range.
The long-lsrm acceptance rate (LTAR) used to design the OWTS (Table 10-l Regulations) is
0.60 gall,ons per day per square foot area (WdlfÒ'
2.0 WASTEWATER FLOWS
Maximum Daily Wastewater Flow (gpd): 3-BR Single-Fam.ily Dwelling
3 bedrooms x 150 gpd/bedroom :450 gpd
Septic Tank
rn"ãtti-.ttn required septic tank capacity for a 3-BR plumbed structure is 1,000 gallons (Table
9-1 Regulations). For this design, use a two-compartment 1,000 gallon septic tank approved for
use in Garfield. The proposed new 1,OO0-gallon septic tank will provide at least 48 hours of
detention time for influent wastewater flow from the proposed dwelling. The 48 hour (2-day)
particle detention time volume requirement is 900 gallons (a50 gpd x 2-days : 900 gallons). The
intemal septic tank outlet effluent filter and inlet tee must be installed per Regulations.
3.0 OWTS DESIGN
Silty sand and colluvial-alluvial soils occurring at the 2.0 to 4.0 feet depth interval will be used
for itre upper infiltrative surface for the proposed STA (Figure A3). Shallow STAs promote
secondary effluent treatment due to available soil oxygen optimizing bacteria and fungi
pro..rr... Trench excavation will remove approximately 2.0 to 4.0 feet of soil and upper root
Page I
mass to prepare a level surface for installing the infiltrators in the three (3) trenches configured in
serial distribution. Soil should not be wet at the time of excavation. Place approximately 1.5-
foot of frnal cover (1g-inches minimum per Regulations) using the silty sand soil' Final grade
shall match existing grade over proposed trenches so water runs off and will not pond over any
area of STA"/leachfield. Prior to backfilling, cover the Q4 infiltrator trenches with non-woven
geotextile fabric or similar permeable material to prohibit soil intrusion into the chamber louver
vents.
All setback distances in accordance with the Regulations are applicable to septic system
installation. The septic tank must be at least 5 feet, and STA at least 20 feet from plumbed
modular structure(sjwith a basement, crawl space, and or footing drains. STA's must be outside
of any easements and at least 10 feet from property lines. Setback distances also apply to natural
and artificial waterways, including a 50-foot setback from STA/leachfield to natural waterways
or open irrigation ditcles. Propoied water supply cistern located north of the 3-BR dwelling
,ourì b" at lèast 100 feet from the leachfield and 50 feet minimum to the septic tank. A variance
by the Board of Examiners of Water Well Construction and Pump lnstallation Contractors can
,ðd.r"" this setback to a minimum of 25 feet. Potable water lines serving the residence must be
25 feetfrom the STA/leachfield and 5 feet from building sewer or effluent lines. Designated
leachfield repair area must be retained per Regulations as idle land set aside for future use once
primary fields fail and no longer accepts wastewater'
The new 1,ggg-gallon septic tank will provide at least 48 hours of detention time for influent
wastewater flow from thå proposed dwelling. Intemal septic tank inlet tee must be installed per
Regulations. An effluent filter must be installed instead of tee on the septic tank outlet. Effluent
filtãrs typically require cleaning and maintenance every 6 months. If chosen, use the Orenco
Systems-Biotube Effluent Filter OSI Model FTW0444-36 (or equivalent).
The following design calculations propose to discharge septic tank effluent to three (3) Quick 4
plus trenches each using fifteen (15) Q4 units for a total minimum disturbed area of
approximat ely 17 feet by 64 feetwith infiltrator end caps. A total of 45 Quick 4 Standard Plus
Inirltrator uniis will be installed in the 3-Trench Serial Distribution System generally oriented
north-south.
Soil Absorption Area Calculations
Absorption Area (A) : Design Flow (Q)/LTAR
Field percolation rate (t): 6 to 26 min/in
Leachfield Area: 4: Q/LTAR,
Where:
A: Leachfield area square feet
Q: Design Flow/maximum daily wastewater flow
: max. daily wastewater flow 3-BRs @ 150 gpd/bedroom
Page2
: 3 bedrooms x 150 gpd/bedroom:450 gpd
LTAR: Long Term Acceptance Rate (max. hydraulic loading rate)
:0.60 gallons per day/ft:2
A:450 gpd/0.60 Wdlft2 : 750 ff
Ouick4 Trench Confizuration:
750 f& x 1.0 (appl. method adjustmentl¡ x 0.7 (distribution media adjustment2): 525 ff
525 ff lI2 ftz : 43.75 Q4 units; Use 45 units.
I Regulations Table l0-2 size adjustment factor for Methods of Application in STAs
2 Regulations Table l0-3 size adjustment factor for Types of Media in STAs
Note: County and State approved bottom chamber area for Quick 4 Plus Standard lnfiltrator
Unit : 12ft2.
The 3-Trench Q4 Infiltrator Serial Distribution System will use a total of forty-five (45) units.
Each trench will have fifteen (15) Q4 Plus chamber units. Wastewater flow into the proposed
trenches will be in serial distribution. Use the top port of the Infiltrator faceplate for all influent
piping.
4.0 SYSTEMINSTALLATIONREOUIREMENTS
Minimum setback requirements must be in accordance with the Regulations. All sewer pipe
couplings must be completed with primed and glued or bell and spigot joints using 4-inch SDR
¡S pVCpipe. Schedule 40 PVC 4-inch pipe with a minimum l-foot soil cover must be used if
pipe is insølled in a vehicular traffic crossing. Drain-waste-vent (DWV) rated Schedule 40 PVC
pipe is called out for crossings but may also be used instead of SDR 35 PVC pipe.
Building sewer pipe must be installed at a slope between Y*-inch and Yo-inch per foot slope (1 to
2yo),préferably uiing the Yo-inchper foot slope as recommended by the International Plumbing
CoáelIfC¡ as administered by the County. Fittings shall be sweep 9O-degree curves or two (2)
45-degree elbows at all influent pipe turns. Fittings must be DWV for schedule 40 PVC pipe'
Cleariouts (2-way) are required between dwelling and tank and beyond tank where pipe lengths
exceed 100 feet from tank to STA/leachfield and at all pipe bends greater than 45 degrees.
The installer must adhere to minimum depth requirements for leachfield and ensure gravity
drainage into all septic system components to avoid using a lift pump. System components must
be placed on native soils or re-stabilized soils in excavated areas.
Infiltrator trenches must be excavated level to ensure the prepared infiltrative surface is level
along the entire length of STA. Solid 4-inch pipe is used in the header network and sanitary tees.
Page 3
The owner will ultimately be responsible for septic system maintenance including pumping the
septic tank once every 3-4 years and cleaning the effluent filter every 6 months.
5.0 SYSTEM INSPECTION
WestWater Engineering is responsible for inspecting OWTS to ensure construction conforms to
the design plan and meets all aspects of County Regulations including:
o Inspect system prior to backfilling including piping and septic system components.
o Complete an as-built drawing of the system.
6.0 DESIGN LIMITATIONS
The OWTS design is based on site-specific soil conditions and percolation data collected in the
vicinity of the proposed STA/leachfield and local experience of designing OWTS's in Colorado.
The design is only valid for the proposed new OWTS serving the proposed single-family
residence at the referenced location provided in this report. 'WestVy'ater Engineering assumes no
liability for inaccurate information or conditions that vary from the design assumptions listed
above. Netify WustWater Engineering and/or thc Gorfield County official immediately if actual
site conditions differ from those assumed herein.
please do not hesitate to contact us if you have any questions regarding this report.
Respectfully,
Dean Goebel, M.S., P.G. Hydrogeologist
Reviewed By:
Keith
ONAL
Page 4
APPENDIX A
SOILS AND PERCOLATION DATA
ôNest Water E n g i n eeri n g
ê consulting Engineers & scientisìs
251 6 FORESIGHT ClRCLE, #1 GRAND JUNCTION, COLORADO 8'1505 (97 Ol 241 -7 07 6 - F AX 197 Ol 241 -7 O97
AI. SOILS AND PERCOLATION REPORT
Date: September 19,2023
Consultant Dean Goebel, M.S., P.G. Hydrogeologist
WestWater Engineering
2516 Foresight Circle #1
Grand Junction, CO 81505
(e70) 24r-7076
Client:CMH Homes lnc.
5000 Clayton Road
Maryville, TN 37804
Land Parcel: Harvey Gap Rd CR237 Address TBD, Silt, CO 81652
2127-241-01-002
A2. SOLS LOG
Site soils were invcstigatcd úthe 2.43-acre vacant parcel to collect site-spec.ific design criteria
for an onsite wastewater treatment system (OWTS) to serve a proposed 3-BR single-family
dwelling located at Harvey Gap Road/CR237 address TBD. Percolation testing procedures were
conducted in accordance with Garfield County On-Site Wastewater Treatment System (OWTS)
Regulations (Regulations). The Percolation Test Site is located approximately 80 feet west of
the east property line and 340 feet north of the south property line (Figure Al).
The proposed soil treatment area (STA)/leachfield is located in the east-central portion of the
parcel approximately 30 feet east of proposed 3-BR dwelling in anarea sloping approximately
l8% east. Harvey Gap Reservoir is located approximately Yo-mile north-northeast of the
proposed building site. The excavated soils observation pit shows silty sand interbedded with
colluvium and alluvial sediments supporting tabular sub-angular to sub-rounded pebble- to small
boulder-sized sandstone clasts down to 8.0 feet maximum depth of the excavation. Groundwater
was not encountered in the 8.0-foot soils observation pit. Estimated high seasonal groundwater
is greater than 8.0 feet.
The soils profile log is summarizedbelow and in Table Al. Dark yellowish brown (lOYR 3/4)
silty sand with some sub-angular reddish brown (5YR 5/6) sandstone clasts up to gravel size
from 0.0-2.3 feet. Dark yellowish brown (1OYR 3/4) silty sand with sub-angular to angular
gravel- to small boulder-sized clasts occurs from2.3-4.0 feet overlying colluvial and alluvial
soils with pebbly sand matrix from 4.0-8.0 feet maximum depth of excavation. Groundwater
was not encountered in the 8.Q-foot soils observation pit with an estimated seasonal high water
table greater than 8.0 feet. The lack of antecedent soil moisture and redoximorphic soil coloring
indicating prolonged saturation near the 7.5-foot depth interval supports the greater than 8.0 feet
estimate for high seasonal groundwater.
A1
Table Al. Soil Log Descrþtion
vf : very fine; f : fine; m: medium and; crs: coarse for sand sized particles
percolation rates summanzedin Table A2 show a range from 6 to 26 minutes per inch (mir/in)
with a 15 min/in Ðvcr&ge. Bosed on percolation data, macroscopic/tac.tile soil analysis and lack
of shallow groundwater or bedrock, the bottom of leachfield (top of infiltrative surface) should
be no deeper than 4.0 feet per Regulations. Site soils are categorized as Type 2 soils based on
silty sandy loam alluvial matrix texture, granular structure, and percolation rates predominantly
less than the 16-25 min/in range. Soils should not be excavated under wet conditions to avoid
compaction and smearing leading to a reduction in permeability.
Table A2. Percolation Test Results
Depth Interval (ft)Soil Description
0-2.3 1OYR 3 (vÐ some
clasts up to gravel slze;moderate OM;granular structure;dty;sagebrush,
greasewood,and rabbitbrush desert vegetation
2.3-4.0 Dark with
colluvium with to angular
gravel-to small sandstone clasts;
granular strucfure;dry
brown )
pebbly sand (Ð supporting sub-angular to sub-rounded tabularmatnx
reddish brown
structure, dry
(5YR st6)sandstone up to 50%volume rock;granular
0-8.0
ID Depth
(ft)
Time Final
Drop
(in)
Percolation
Rate
(min/in)
ll:25
(start)
I 1:40 12:10 12:40 12:55
(end)
I 2.0-2.8 3.25"4.25"5.75"6.75"
@r2:25
dry 3.5 l8
2 3.0-3.7 3.25"6.0"dry dry dry 2.75 6
J 2.s-3.3 3.75-5.5"8.0"dry dry 4.25 11
4 3.0-3.6 3.5"4.25"5.375"6.375"dry 2.875 26
5 3.0-3.8 3.75"s.75"8.25"dry dry 4.5 l0
A2
APPENDIX B
FIGURES
a
f
F
¡,
.i'ç
¿
F\
{J
,'lt
.. 1
¡ ,4 .'Ò.t.t
.l '.,'*
rr
I
,l
ú
!
b
$i
t
!.4 ¡
d .t
È$è
N
|¡
ìlI
t
ú'#
!
v
b
a
tr
$P
gF
tc¡
ri;ôñi:E
={ - X "'t \r=I
?Iaø
o ô5 -
o æã-
fll)(r=gll>
ãH_okı
=lc,
5Øl> m
Øl.o >
-ttÞo
-loflÈz.'
,
a'
a
1
t
ir¡
I
t'
J
t
1¿
.t.',1t.
\
\
\
}rr
I
aair
t
\
\
J\
"f
t
ftt
/
N-
+
ì{r
Eì
I
Ò-
.r\
t1,
t
t
1
{
nortfl
rio
ll
r{;I.
n1rqæz,>nR
.\
,a
-{
or
Joz
-lm
i\
\'hF
\_-_-+,-_
*t
-r.¡þ
¡\)-(¡'
t
t
rrl
-t
7)o
><
{rrl
.-\
€n'o
ll
*Ë
r
z.
o,q
noÉ
n
I
FI
U)
oÐñ(¡¡
-__
\
t
!
r"r--i
t
:fr'Y¡r. '
&
t
.¡
---
I
{t
I
*fl
..
..s'i
*1
t
t
N)OO
OO
O
f\)OO
(n
c)
t-If
il
N)O
,53
{
åI
ù.
PROP
{
1(
AREA
TY
OLATI
rYP)TEST SITE
L
F
RST
64'
ILS P
Q4 IN
HES W
co
TREN
TEX
REP
17'
FIGURE A2
HARVEY GAP ROAD
PROPOSED OWTS LAY-OUT
^\ìþstUJ¡ate¡êEnglneering
25 l6 Foresight Circle, #l
Grand Junction, CO 8 I 505
(970) 24t-7076
www.westwaterco.com
NOTE:
3 INFILTRATOR TRENCHES
15 Q4 UNITS EACH
45 TOTAL Q4 CHAMBERS
SERIAL DISTRIBUTION
EXI
LINE
E 2 -TRA
PROPOSED ATER-
SUPPLY C
POTABLE
&
TER-
LINE TO H SE
OPOSED
c N_OUT
D\1,000
G SEP C TANK
5 TILITIES 4.9'
T
NOTE:
MINIM M DWELLING SETBACKS
20'LEACHFIELD
5'SEPTIC TANK Iq
,-({'
c)st-()
,--
. I¿,
S:=
40200
SCALE: 1":40'
40
^\ñlêstlt/hter:ãEnglneerlng
2516 Foresight Circl€, #l
Gmd Junction, CO 81505
(9701 24t-7016
w.wosfivâterco,com
FIGURE A5
HAR\EY GAP ROAD
OWTS CROSS SECTION
3 INFILTRATOR TRENCHES SERIAL DISTRIBUTION
USE TOP FACEPLATE PORT
COVER INFILTRATORS WTH GEOTEXTLE FABRIC
MAÏCH GRADE
BACKFILL OVER TRENCHES
EXISTING
GROUND
@ 4'
þI
MAXIMUM DEPTH 4.0 FEET
MINIMUM DEPTH 2.0 FEET
SCALE 1":5'
INSTALLATION NOTES:
1) FOLLOW MANUFACTURERS INSTRUCTION
www. in fil trotors¡ætem s. com
2) SCREW P|PE TOP PORT CHAMBER FACEPLATE
5) SCREW FACEPLATES AND UNITS TOGETHER
4) TNSTALL MONITORING PORTS END OF TRENCH
ALL FOUR BED CORNERS
\