HomeMy WebLinkAboutEngineer's Design129 CAINS LANE CARBONDALE, CO 41623 970.309.5259 CARLA.OSTBERG@GMAIL.COM sir.:rD.r.r(i (j()ñÍsit f -'l\ r trt(; November 21,2023 Project No. C1848 Ashly Ditlow ashlvditlow@qmail. com Subsurface lnvestigation and Onsite Wastewater Treatment System Design 5-Bedroom Residence 3683 CR 241 Garfield County, Colorado Ashly, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 1O-acre property is located outside of New Castle, in an area where OWTSs and wells are necessary. Legal Description: Section: 6 Township: 5 Range: 90 TR lN SWSE LYING NWLY OF CO. RD.241 & SELY OF E. ELK CRK. Parcel lD: 2123-064-00-006 SITE CONDITIONS The property was previously developed with a residence that has been demolished. A S-bedroom residence is proposed. The previous residence was served by an OWTS. No documents were available on Garfield County Land Explorer. The existing septic tank must be located and properly abandoned. The existing soil treatment area (STA) may be abandoned in place. The previous residence was served by a spring located near East Elk Creek. A new well will be drilled to serve the proposed residence. The well must be at least S0-feet from the proposed septic tank and at least 1OO-feet from the proposed STA. The water line must be at least 1O-feet from the proposed septic tank and at least 2S-feet from the proposed STA. East Elk Creek runs along the western portion of the property. The creek is greater than '1O0-feet from any proposed OWTS component. The proposed STA location has an approximate five percent slope to the northwest. The proposed area is vegetated with sage and native grasses. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. Page2 SUBSURFACE The subsurface was investigated on October 18,2023 by digging two soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l The materials encountered in Test Pit #1 consisted of dark brown topsoil to 1-foot, underlain by light brown silt loam to a maximum depth explored of 7.O-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #2 consisted of dark brown topsoil to 1.O-foot, underlain by light brown silt loam to a maximum depth explored of 8.O-feet. No bedrock or groundwater was encountered. A sample of the soil was taken from Test Pit #1 at 3-feet below grade. Soil structure grade was moderate. The soilformed a balland a ribbon between 1 and 2-inches in length before breaking. Soil structure shape was blocky and consistence was friable. Soil texture was smooth. The soil is consistent with Soil Type 2, Silt Loam, with moderate structure grade. A long-term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the STA. tCarla Ostberg holds a Certificate of Attendance and Examination from the CPOWVisual and Tactile Evaluation of Soils Training. Page 3 Test Pit #1 near the tree line Backfill Test Pit #1 in foreground / Test Pit #2 beyond Sieved sample Ribbon less than 1-inch Page 4 Test Pit #2 Test Pit #2 Backfill DESIGN SPECIFICATIONS The existing septic tank must be located and abandoned by pumping the tank and removing it or crushing the top, bottom, and sides and filling in the void with onsite materials. The existing STA will be abandoned in place. Desiqn Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 150 GPD (4thand 5th Bedrooms) = $gg GPD LTAR = 0.6 GPD/SF 600 GPD / 0.6 GPD/SF = 1000 SF x (1.0 gravity trenches) x 0.7 (chambers) = 7gg 5t The OWTS design is based on S-bedrooms. An average daily wastewater flow of 600 GPD will be used. Page 5 For the purposes of this OWTS design, Benchmark Elevation at grade 6251' has been established as 100' (Finished Floor of Lower Level). CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. "Elevations are based upon standard OWTS installation practices. installation due to site conditions. Minimum grade refers to piping Component elevations may change during between components. The 4-inch SDR-35 sewer line exiting the residence must have a double-sweep clean out and a minimum 2o/o grade to the sePtic tank. The system installation must include a 150O-gallon, two-compartment lnfiltrator@ poly septic tank with an Orenio@ Biotube effluent filter on the outlet tee. Any state-approved concrete or poly septic tank may be substituted. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Effluent will gravity flow to a distribution box, and then to four gravelless chamber trenches. The distribution box must be accessible from grade with flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each trench. Each trench will consist of 15 'Quick 4' Standard Plus lnfiltrator@ chambers for a total of 60 chambers and 720 square feet of infiltrative area. There must be at least 4-feet of undisturbed soil between each trench. lnspection ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO lnc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. Construction must be according to the jurisdiction's adopted On-Site Wastewater Treatment System Regulations, the OWTS Permit, and this design. OWTS Com Minimum Elevation Primary Tank lnlet lnvert Approximate horizontal distance 11' I min.2o/o fall I min.2.75" fall Distribution Box Approximate horizontal distance 80' / min. 1% fall I min. 10" fall lnfiltrative Surface Approximate horizontal distance 37' to furthest trench I min.1o/o fall to STA I min.4.625" fall COMPONENT MANUFACTURER MODEL NO GOMMENTS Septic Tank lnfiltrator@ tem # |M1530-2CP 150O-gallon, 2- oompartment poly septic lank Effluent Filter Orenco@ 4" diameter full size effluent filter Distribution Box, risers, lid and flow equalizers Polylok 4'Roto-flow' Chambers lnfiltratoKÐ 'Quick 4' Plus Standard 60 cambers Page 6 PERMIT APPLICATION INSTRUGTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department. https://www.qarfield-countv.com/environmental-health/filesocco/sites/16/OWTS-Application-Complete- Packet-Dec.-2019.pdf. lf the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-661 4 x81 50. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. ¡NSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet \Â2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUI REMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be .used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. PageT lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions Sincerely, CBO lnc. C.6j,[ø }stfung Carla Ostberg, MPH, REHS I 5q E¡ L s¡¿{ÀÀ¡¿rR ***'^iåifff,f ------ x II I I \ II \ o TÕ*-c)åð5q8þı9V=gqo= oqÈä3 äähä I NX N \\ \\ foo H?Ë oıo>1ø Å9=ìã9 N+Hñocs)m6xørmôvzz ll- z. á n* sF9< co I U)m -{o --l zx \ t -1 I -G, E|ı3. ÉEd'o1 ^-E f = 2270ú¡r¡19!DS4(' ^ QqCLY=-(Dàå ı oo o ñ NoNa oo gË €8. do:lO6 TDo ã b (t Joo oï \ -+t>- (to- !T¡ il q llI É Êã3< T.< \t nøÞm>zio-azaÕ1¡omqhrm ËEñn'itF =EÈ>¡-> =fËE9flãä?ïHã5í 3;flP=xå 1sg99i3 ËãËãääË eiå-âÅÉ¡qıäí9 ñäË:Ëg"3¿ 9àmz Ørt z ,/ v' l¿ CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 ærla.ostberg@gma¡1.æm \d' I I G&GE 5.BEDROOM RESIDENCE AENCHES w¡ü 15 CHMEERS PER TREEH 60 CHAMBERSAND 720 SF.,lrr"r,/ r?2 / ,t ,? ,/ 4'DhSÐR-35 rum io (MrN,1% SLOPETOTÈNCH) 4'ÞA (MrN, 1% FALLTOSA) MIN 2%TO TANK LINE z/7 fltll l¡ltltltllIt I¡ Itll lt IItt t--_/----J-..- _t I I \ \ il \\ * I I /z Ditlow Residence 3683 CR 241 Garl¡eld County, Colorado Project Number: C1848 t¿ 1',U2112023 Designed by: CBO Drawn by: DD r., //' SEPTCTNK WIff EFÉUEM ilæOMPARruENT Sheet 2 0F 4 w2.0 .¡Ax U.///DAVIDG&KAMMYSYOUNG REC. # 68451 1 N ,_ !. e'-lu/ I I -/ I $SCALE: 1'= 30L0" 't 'lr).¡Ì èso 7 't /CALL811 FOR UTILITY LOCATESIIlrN CBO lnc. 129 Cains Lane Carbondale, ColoEdo 81623 Phone 970.309.5259 carla.ostberg@gmail.æm INFILIRATOR END PUÍE ,QUICK-4 CH,qMBER (4 x 3') SDR.35 DISTRIBUTìON LINETO EACH ÌRENCH (MtN. 1% SLOPE TO TRENCH) DISNIBUTION BOXWITH DIA SDR-35GWEINSPÉCTON PORT 4 4'DlA SDR-35 EFFLUENT PIPE FROM SEPTICTANK L sotL 2 LIMIT PLACEO IN EXCAVATION TOP PORT OF CHAMBER END PLATES GRAVELLESS 'QUICK4' CHAMBER (4 x 3) /ã CHAMBER TRENCH SECTIONV,' DIA SDR¿s INSPEfrION PORTAT BEGINNING AND END OF EACHTRENCH /^CHAMBER 'TRËNCH PLAN\rr- SMALL VALVE COVER BOXOR IRRIGATION V{W BOX AT GMDE FINISHED GRADE CÆ ORTHREADED BOX AND COVER BROUGHT TO GRADE CLENOUT ASSEMBLY 24" MlN.CONCRETE WC PIPE CUTTO 4' DIA SDR-35 SEWER LINE (MtN 2ôlo SLOPE TO TANK, MtN. 1% TO STA) ffiãÑE- BASE TO SUPPORT BOX FT USE HOLE SAW TO CW THRU TOP OF SREENED END CR SAND FÕR BEDDING 3'MIN. 8'MlN. BAFFLE OR ANGLED PIPE TO BE USED /i INSPECTION PORT DETAIL\¿r--ffi AT INLET A'IRENCH DETAIL\3r-ffi /â, DIS'IRIBUïON BOX DETAIL\9r- 15 CHAMBERS PERTRENCH é IIIIIIIIIIT IIIIIIIIIII III OUTLETS oooo Ditlow Residence 3683 CR 241 Garf¡eld County, Colo€do PrcjectNumber: C1848 baþ: 11t2'l2123 lo*,n*o o* "ro lDrawn bv: DD w3.0 Sheet 3 0F 4 CBO lnc. 129 Ca¡ns Lane Carbondale, CdoEdo 81 623 Phone 970"309.5259 ærla.ostberg@gmail.æm DESIGN STA TO WATER COURSE 50'292' STA TO WELL 100'MUST BE >1OO' STA TO HOUSE 20'1 15' SEPTIC TANKTO WATER COURSE 50'MUST BE >50' SEPTIC TANK TO WELL 50'300' HOUSE TO SEPTIC TANK 5'11' OWTS COMPONENTS AND PIIYSICAL FEATURES MINIMUM REQUIRED SFTBACK APPROXIMATE PROPOSED SETBACKs-BEDROOM RESIDENCE 75 GPD x 2 PERSONS/BEDROOI, x 3 BEDROOMS + 150 GPD (4th and sth BEDROOMS) WASTEWATER FLOW = 600 GPD TANK MIN,15OO GALLONS USE,ISOO,GALLON, TWO-COMPARTMENT SEPTIC TANK SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.6 GAU SF CALCULATED STA = CIiLTAR = 600 / 0.6 = 1000 SF GRAVITY, TRENCHES = 1000 SF X 1.0 = 1000 SF CHAMBERS = 1000 SF X 0.7 = 700 SF / 12 SF / CI-IAMBER = 59 CHAI,IBERS FOUR GRAVELLESS CHAMBER TRENCHES 15 'OUICK 4' CHAMBERS IN EACH TRENCH TOTAL 60'OUICK 4' CHAMBERS /^ SE'IBACK CHARTlér-ffi SO¡L PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO. 2 LEGEND lsl topso¡l f,!ll sirtroam TFÈ H -0 -1 -2 3 -4 -5 DARK BROWN TOPSOIL DARK BROWN TOPSOIL SLIP-ON PVC DO NOT GLUE LIGI{T BROWN SILT LOAM LIGHT BROWN SILT LOAM INSUI-ATED TRACERWRE FINISHED GRADE 4" DIA 6 SEWER LINE -7 Lf-' L-,0 TO TANK HOUSE NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION /ã,CL-EAN OUT DETAIL\gr-ñffi /ãSOILS LOG\v Ditlow Residence 3683 CR 241 Garfield Couniy, ColoEdo ProjectNumber: C1848 loate: lttzllzozg I o""¡sn"o ov' ceo I Dnwn bV: DD w4.0 Sheet 4 0F 4 tÐqPublic.nef" Garfield County, Co 81647 2019 Total Actual Value Overview Legend [-l Parcels Roads Parcel/Account Numbers Owner Name ill Lakes&Rivers - CountyBoundary Line $258,ó50 Last2Sales Date Price 3/70/2017 $350,000 nla $ Account R013121 Physical 3ó83241COUNTYRD Number Address Parcel 272306400006 NEWCASTLE Number OwnerAddress YOUNG, DAVID G & Acres 10 KAMMYS LandSqFt 0 32B5COUNryROAD2AI TaxArea 013 NEWCASTLE COB!647 2019 MÍll Levy 55.1ó10 Dale created: 17/ 7/ 2O23 Last Data Uploadeú 7t/ tl2Ù23 2t$8t49 AM Dever ooed bv¡f) Ð,9å,9,S^14çf '1111123, 11:08ltM Garñeld CounW, CO 5ummary Account Parcel Propcrty Addæs l€gd Description Acrcs LândSqFt TilAÞ qPublic.net - Garfield County, CO - Property Record Card: R013121 RO13121 212æ6,40000ó 3683 241 COUNTY RD, NEW CASTLE, CO 87647 Section: ó Tov¡rship:5 Rânge: 9OTR lN SI rSE LYING i{WLY OF CO. RD. 241&SELY OF E EtK CRK 10 0 13 55.1ó10Mllll..r4f Subdiv'rio View MaD Owner YOUNG- DAVIDG& KAMMYS 3285 COUNTY ROAD 241 NEW CASttE CO 81ó47 Land Unlt Typc I RRIGATED LAN D-AGRICLTRL. - 4117 (AGRICULTURAL PROPERTY) SquãreFeet 0 UnitType GRAZING LANÞAGRICULruRAL - 4147 (AGRICUL-ÍURAL PROPERTY) SquereFeet 0 Buildings Building* Units BulldngTypê Abstract Code / (PropertyTypel Aftñitech¡ral Style Storlês Frðme ActulYear Built Bå6ernentArea GræLivingArea Total HeetedsqFt Bedroons Bãths HeatlngFæl HeâtlngTtDè AirCmditíoning RoofTypê Roof C.drÊr 1 t FARM/RAI.ICH FARM/RANCH RESIDENCE-IMPS42Z7 (RESIDENTAL PROPERTY) I.STRY/BSM t WOODFRAME L973 420 420 840 72æ L 1 wooD wooDsrovE NONE GABtr COMPSHNGL htþs:/lqpublic.schneidercorp.cornlApplication.aspx?ApplD=1038&LaprlD=22381&PageTypelD=48PagelD=9447&Q=175953350{tKeyvalue=R013121 1t2 '1111123,1'l.08ItM Actual Values AssessedYear Lånd Actual lmprorrement Aculal TotalAch¡al AssessedValues AssessedYs Lild Asses-sed lmprolementAssessed ToÊalAssessed TaxHistory TaxYear TãEBilled Click heretoviewthetax infomation forthis sarælontheGarñeld CountyTræsurer'swebs¡te. Trans,fers SâlÊDâte DeedTyp. qPublic.net - Garfield County, CO - Property Record Card: R013121 m23 $4200.00 $254,4s0.00 $258,óso.m M3 $1,110.m $17270.ú $18,3æ.00 2tz¿N2L $ós2.00 $761,æ R€cc¡donNumbêr Contâct Us ilLOtnLT QUIT CLAIM DEED 889975 3tLO|20L7 WARRANTYDEËD 989974 u2g20r7 DEED 889476 !2A2eL7 STATEMENT OFAUTHORITY ULTTæT5 DEED 864739 qælnß STATEMENTOFAUTHORITY 8647L5 4t4t2W DEATH CERTIFICATE 746æ2 LU!911995 QUITCTAIM DEED ¿l85288 ru79Ir995 QUITCIÂIMDEED ß5247 il2s[rn2 WARRANTYDEED 253497 1U28t7977 WARRANTYDEED 252203 Property Related Public Documents Click hereto v¡ew Propertv Releted Public Dæuments No data mllable forthefollour¡ng modulæ Photc,Sketdt6 The Garñeld County Assessor's Office makes every effort to produce the most accurate information possible. No wârrañtiês, expressed or Ìmplied are provided for the dãta here¡n, its use or ¡nterpretat¡on. Datâ ¡s subject to constant change ând its âccurâcy ând completeness cannot be guaranteed. I User Privacv Policy I GDPR Pr¡vacv Notice Last Data UÞload: 1U1l2O23. 12:08:49 AM Book- Pa¡ê 09544292 0958{.289 o4i¡1{200 0d.2æ125 20.22 $3,1ó0.00 $158,050.00 s1óf"210¡O 2ù22 $8¿tt.0O $10,980.00 $1r,æfìrx, ñn $6re72 Developed by Ni¿l Í,3,1ó0.00 $1s8,050.00 f1ór,210.æ N¿7 $9'20.00 $11,300.00 $t22nffi 2079 s593,92 SalePrlcc $o $3s0,000 $o $o $o $0 $o $o $o $o $o ()FMdçr 2t2 David Youn From: Sent: lo: Subject: Ashly Ditlow <ashlyditlow@gmail.com> Sunday, November 5,2023 3:28 PM David Young Fwd: Blue lines Sent from my iPhone Begin forwa rded message: From: Carla Ostberg <carla.ostberg@gmail.com> Date: November 5,2023 at9:28:22 AM MST To: ash lyd itlow@gma il.com Subject: Blue lines Sent from my iPhone Item # It.l530-2CP l53O Gallon Two Gompartment lnflltrator@ Poly Tank 61 7" TANKTOP HALF CONTINUOUS EI-ASTOMETRIC 175.6 TANK INTERIOR SEAM CLIP TOPVIEW (86) ruGilIÆNT DOTYEL (1E)TANKBOTTOM HALF 2/l¡ ACCESSPORT TarÚchdußffi wrrH LocKtNG LrD (Ð O MID-HEIGHT sEAM sEcroN DETATL OUTLET TEE 2/3TOTALVOL 1I3 TOTAL VOL SIDEVIEW SEAM CLIP ¡ Compliont with CSA ond IAPMO Stondords¡ PVC risers ovoiloble¡ Secondory sofety screen ovoiloble wíth PVC riser r Moximum buriol depth !s 48" ¡ Minumum buriol depth is 6"¡ Tonk is not roted for vehiculor troffic looding¡ Exterior of monhole cover includes the following worning: "DANGER DO NOT ENTER: POISON GASES" LIFTINGSTRAP (ÍYPIGAL) END VIEW ffir,rr$fl,*n' It¡rAIq$lülr€. rLtïru il, o o èoê o a-o :Þ o o <E Eà o FIBERGLASS SUPPORT Digging Specs lnvert Dimensions Net Weight Net Workin 16' Long x 7' Wide 43" below inlet lnlet 47" Outlet 44" Length 175.6" width 61.7" Height 54.5"501 lbs.1006 gol 503 9ol 1509 gol Wabr & Wa¡tewür r System ¡ Pmduc'ts InG. r SeMce rr9) 3g5s7o4 zf,XEOo ru'fi7 P.O. Bo(m5 Fu: (/1g) g%srzt Hm\flsb' æ81ã1 Webrlb: mrrv.valleyprcætæm Enulft fronüesk@allqprccast æmM,