HomeMy WebLinkAboutEnergy ReportGenerated by REScheck-Web Software Com pl ia nce Cett¡ficate Project Pena Residence Lot 43 Grass Mesa Ranch Energy Code: 2018 IECC Location: Rifle, Colorado Construction Type: Single-family Project Type: New Construction Conditioned Floor Area: L,948 ll2 Glazing Area L6Vo Climate Zone: 5 (6881 HDD) Permit Date: Permit Number: Designer/Contractor: Compliance: 2.270 BetterThan Code Maximum UA: 278 Your UA: 272 The 96 Better or Worse Than Code lndex reflects how close to compl¡ance the house is based on code trade-off rules. It DOES NOT provide an est¡mate of energy use or cost relative to a minimum-code home. Slab-on-grade tradeoffs are no longer considered in the UA or pedormance compliance path in REScheck. Each slab-on-grade assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements. Envelope Assemblies Construction Site: Lot 43 Grass Mesa Ranch Rifle, co 81650 Owner/Agent: Mario Pena PO Box 1904 Rifle, co 81650 970-355-0357 marioed ian 1975@icloud.com 1,948 398 81 78 461 43 51 289 24 293 16 t02 1,958 ù LL s :s 5sa ùr Ceiling: Raised or Energy Truss East Elevation: Wood Frame, 16" o.c, East Elevation Doors: Glass Door (over 50% glazing) East Wall Windows: Vinyl Frame WestWall Elevation: Wood Frame, L6" o.c. West Elevation Doors: Solid Door (under 50% glazing) West Wall Windows: Vinyl Frame North Elevation Wall: Wood Frame, 16" o.c. North Windows: Vinyl Frame South Elevation Wall: Wood Frame, 16" o.c, South Elevation Windows: Vinyl Frame Rim Board: Wood Frame, L6" o.c, Main Level Wood Framed Floor: All-Wood JoisVTruss 20.0 0.0 20.0 0,0 20.0 0.0 39 I4 26 25 22 L4 16 16 I 16 6 5 65 51 T4 24 23 22 13 15 16 7 L7 5 6 65 49.0 20.0 30,0 30.0 0.0 0.0 0.020 0.059 0.320 0,320 0.059 0.320 0,320 0.059 0,320 0.059 0.350 0.049 0.033 0.026 0.060 0.300 0,300 0.060 0.300 0.300 0,060 0,300 0.060 0.300 0.060 0.033 0.0 0.0 Compliance: Passes using UA trade-off Cav¡ty R-Value Cont. R-Value Prop. Reg. U-Factor U-Factor Prop UA Req UA Gross Area orAssembly Perimeter Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: LLl0Ll23 Page 1 of10 compllancë Starêménti The proposêd bulldlng de6lgn descrlbed here 16 conslstent wlth the bulldlng plans, speciflcatlons,.and other calcúlatlons submitted with the Èermit application, fhe proposed þuilding has been deslgnèd to mêþt thê 2018 lEcc requlrements in R[Schcck Version : RESchcck-Web and to comply with the mandatory requirements llsted in the REScåeck lnspectlon Checklist. Name - Title n Date ProJect Tltle: Pena Resldence Lot43 Grass Mesa Ranch Data filename: Report däte: LLlOLlz3 Page 2 of10 REScheck Software Version : REScheck-Web lnspect¡on Checklist Energy Code: 2018 IECC Requirements:7.Oo/o were addressed directly in the RESchecksoftware Text in the "Comments/Assumptions" column is provided bythe user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Additional Com ments/Assum ptions: Section # & Req.lD Pre-lnspectionlPlan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. !Complies nDoes Not nNot Observable nNot Applicable 103.1, 103.2 lPRllr .çJ Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. lComplies Requirement will be met. lDoes Not !Not Observable INot Applicable 103.1, 103,2, 403.7 lPR3ll 't¿j Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_ Cooling: Btu/hr Heating: Btu/hr_ Cooling: Btu/hr_ 302.L, 403.7 lPR2l2 ,{¿, nComplies lDoes Not nNot Observable !Not Applicable Requirement will be met. Location on plans/spec: re: mechanical subcontractor 3 Low lm ct (Tier 3)L ct (Tier 1.)Hi hlm 2 Medium I (Tier 2) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename; Report date: LLlOLl23 Page 3 of10 A proteetive covering iE inßtellad to protect exposed exterior lnsulation and extends a rninimum of 6 in. below iEcomplies iEDoes l,lot iElNot o¡servable iEruot Rnplica¡le grade. Snow-andice-melting.sy-stemeontrolsinCsmplles iinstalled. iEOoes ¡¡ot i itl¡*¡et ouservanb i itrt-rtot ¡Bplicable i Ex¡eptlonr Requirement is not applicable. Additlonal Comment¡/Aseumptlons: (Tier 1)Medium (Tler 2)ffier 3)Low ProJect Tltlê: Pênã Regldence Lot 43 Gråss Mësa Ranch Data fllenamê: Repórt dåtê: 1f/Oxl23 Page 4 of10 Section # & Req,lD Framing I Rough-ln Inspection PIans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1,.1, 402.3.4 lFR1l1 ,s,, Door U-factor U-U-nComplies nDoes Not nNot Observable nNot Applicable See the Envelope Assemb/ies table for values, 402.L.r, 402.3.L, 402.3.3, 402.5 lFR2lr 'Ur Glazing U-factor (area-weighted average). U-U-EComplies nDoes Not nNot Observable !tttot Applicable See the Envelope Assemblies teble for values. 303.1.3 lFR4l1 g/ U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. !Complies nDoes Not nNot Observable !Not Applicable 402.4.L.7 lFR23l1 9r Air barrier and thermal barrier installed per manufacturer's instructions. ncomplies nDoes Not nNot Observable !Not Applicable 402.4.3 lFR20lr u., Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 1 O1/I.S,2/4440 or has infiltration rates per NFRC 400 that do not exceed code limits. Dcomplies nDoes Not nNot Observable nNot Applicable 402.4.5 lFRL612 lC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate <2.0 cfm leakage at 75 Pa, LI Complies nDoes Not nNot Observable !Not Applicable 403,3.1 lFRl2lr u, Supply and return ducts in attics insulated >: R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. SupPlY and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4,2 for < 3 inches in diameter. !complles nDoes Not !Not Observable nruot Applicable 403.3.2 lFR13l1 'fu)r Ducts, air handlers and filter boxes are sealed with joints/seams compliant with lnternational Mechanical Code or lnternational Residential Code, as nComplies nDoes Not !Not Observable []Not Applicable a le 403.3,5 lFR15l3 &¡,, Building cavit¡es are not used as ducts or plenums. tes nDoes Not INot Observable nNot Applicable 403.3.6(1, 2) lFR26l3 ..t|, Ducts partially or completelY buried in ceiling insulation have an insulation R-value not less than R-8, the sum of the ceiling insulation R-value against and above the top of the duct, and against and below the bottom of the duct, is >= than R-19, excluding the R-value of the duct insulation. nComplies nDoes Not nNot observable ENot Applicable 1 High lmpact (Tier L)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: LLlOLl23 Page 5 of10 Section # & Rcq.lD Framing / Rough-ln lnspectlon Plans Verified Value Field Verified Valua Complies?Comments/Assumptlons .Drrrt,ì dcclðred to bc within the conditioned space are either 1) completely within the continuous rair barrier and wlthln the building thermal envelope, 2) buried within ceiling insulation in accordance with Section R403.3.6 and the air handler is llocated completely within the continuous air barrier and within :the building thermal envelope and the duct leakage is <= 1.5 cfm / 100 square feet of conditioned floor area served by the duct system, or 3) the ceiling insulation R-value installed against and above the insulated duct >= to the proposed ceiling insulation R-value, less the R- value of the insulation on the 403.i.7 lFR28l3 ,'a/ Ecomplies lDoes Not nNot Observable nruot Applicable 403.4 lFR1712 ,.s HVAC piping conveying fluids above 105 oF or chilled fluids below 55 sF are insulated to >R- 3. :!Complies nDoes Not !Not Observable !Not Applicable R-R- 403.4,1 lFR24l1 ,'9/ IComplies lDoes Not !Not Observable nNot Applicable Protection of insulation on HVAC piping. 403,5,3 IFR18I' .q/ .lcomplies lDocs Not rnNot Observable !Not Applicable R-R-Hot water pipes are insulated to >R-i. Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. nComplies lDoes Not lNot Observable !Not Applicable 403,6 lFR19l2 Additional Comments/Assum ptions: 1 (Tier 1)h 2 3Medium lm (Tier 2)Low lm (Iier 3) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: 1.1-107-123 Page 6 of10 Field Verified Value Complies?Comments/AssumptionsSection # & Reo,lD lnsulation Inspection Plans Verified Value See the Envelope AssembliesFloor insulation R-value table for values. R-R- All installed insulation is labeled or the installed R-values provided. 402.L.1, 402.2.6 llN 111 .Ër 303.1 ilN1312 o ncomplies lDoes Not !Not Observable nNot Applicable nComplies nDoes Not '!Not Observable nNot Applicable ! Wood ! Steel Wood Steel Floor insulation installed per manufacturer's instructions and in substantial contact with the underside ofthe subfloor, orfloor framing cavity insulation is in contact with the top side of sheathing, or continuous insulation is installed on the underside of floorframing and extends from the bottom to the top of all perimeter floor framing members. 303,2, 402.2.8 ltN2ll Sr nComplies nDoes Not []Not Observable nNot Applicable 402.r.r, 402.2.5, 402.2.6 ltN3ll .ç/ Wall insulation R-value. lf this is a mass wall with at least % of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_ ! Wood ! Mass ! Steel R-_ ! Wood fl Mass ! Steel !Complies lDoes Not nNot Observable nNot Applicable See the Envelope Assemblies table for values. nDoes Not nNot Observable nNot Applicable Complies303.2 llN4ll Wall insulation is installed per manufacturer's instructions. Additiona I Com ments/Assum ptions: 2 Medium lmpact (Tier 2)3 Low I (Tier 3)1 High lmpact (Tier L) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: Lll0Ll23 Page 7 ofL0 Section # & Req.lD 402,1,1, 4u2.2.1, 402.2.2, 402.2.6 lFt 111 Comments/Assumpt¡onsFinal Inspection Provisions Ceiling insulation R-value.R-_ ! Wood n Steel R-_ I Wood ! Steel !Complies DDoes Not !Not Observable INot Applicable See the Envelope Assemblies L¿l:le fo¡ v¿lues. 303.1.1.1, Ceiling insulation installed per303.2 manufacturer's instructions.lFl211 Blown insulation marked every 300 ft,. !Complies lDoes Not nNot observable nNot Applicable Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. nComplies nDoes Not !Not Observable nNot Applicable 402.2.3 lFt22l2 Attic access hatch and door insulation >R-value of the adjacent assembly. nComplies lDoes Not nNot Observable nNot Applicable R-R402.2.4 lFt3lr Blower door test @ 50 Pa. <:5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. nComplies lDoes Not !Not Observable nNot Applicable ACH 50 =ACH 50 =402.4.t.2 lFt 1711 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure ditferential of 0,1 inch w.g. across the system including the manufacturer's air handler enclosure if installed at time of LC>L. TU>LLU|t5ttULLtUil LesL. I ULdt leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer's air handler enclosure. cfm/100cfm/l00 ft2 ft2 403.3.3 lFl2Tlr nComplies nDoes Not nNot Observable nNut Applicable Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/]"00 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing lnspection. nComplies nDoes Not !Not Observable nNot Applicable cfm/100cfm/100 ft2 ft2 403.3.4 lFt4l1 Air handler leakage designated by manufacturer at <=2Vo of design air flow. nComplies IDoes Not nNot Observable nNot Applicable 403.3.2.r lFl24ll Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. 403.1.1 lFl9l2 !Not Observable nNot Applicable Complies Does Not nNot icable Complies403.1.2 lFr10l, Heat pump thermostat installed on heat pumps. 403,5.1 tFt 1112 Circulating service hot water systems have automatic or accessible manual controls. LlDoes Not lNot Observable flNot Applicable nComplies nDoes Not !Not Observable 1 ht (Tier L)2 3 Low lm ct (Tier 3)Medium I (Tier 2) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: L1.lOLl23 Page I ofL0 Complies?CommentslAssumptionsPlans Verified Value Field Verified Value Sect¡on # & Req.lD Final lnspection Provisions All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and airflow limits perTable R403.6.1. Hot water boilers supplying heat lies tem 403,6,1 lFt2512 403.2 lFt26l2 nComplies nDoes Not nNot Observable ENot Applicable lDoes Not !Not Observable !Not Applicable through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor Heated water circulation systems have a circulation pump. The system return pipe is a dedicated 'return pipe or a cold water supply pipe. Gravity and thermos- ,syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. plies 403.5.1,1 lFt2812 403.5,1,2 lFl2912 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping, nComplies lDoes Not nNot Observable INot Applicable nDoes Not nNot Observable !Not Applicable Demand recirculation water systems have controls that manage operation of the pump and limit the temperature of the water entering the cold water pipinq to <= 104qF. nComplies lDoes Not nNot Observable nNot Applicable 403.5,2 lFt3012 Drain water heat recovery units tested in accordance with CSA 855.1, Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers, Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. plies D Notoes 403.5.4 lFt3112 nNot Observable nNot Applicable nComplies nDoes Not nNot ObservabÍe !Not Applicable 404.t lFt6l1 gOYo or more of Permanent fixtures have high efficacy lamps. 404.L.t lFt23l3 &¡r nComplies nDoes Not nNot Observable nNot Applicable Fuel gas lighting systems have no continuous pilot light. nComplies nDoes Not nNot Observable nNot Applicable Com pliance certificate posted401.3 lFt712 3 Low lmpact (Tier 3)1 lm ct (Tier 1)H 2 Medium lm (Tier 2) Project Title: Pena Residence Lot 43 Grass Mesa Ranch Data filename: Report date: l1-l0Ll23 Page 9 of10 Manufacturor manuals for systetns Aüdlttona,l CommantÊlAÊ¡umptlon ¡ I Low lrnpäet flier 3) Projeet fiflel Pêna Residence Lot 43 Grass Mesa Ranch Data fflename: Report date: 11/0X/23 Page L0 of1.O 2018 IEGC Energy Efficiency Gertifi cate Above-Grade Wall Below-Grade Wall Floor Ceiling / Roof Ductwork (unconditioned spaces): Window Door Heating System Cooling System:_ Water Heater:_ Name: Comments 20.oo o.oo 30.oo 49.OO o.32 o,32 Date lnsulation Rating R-Value Glass & Door Rating U-Factor SHGC Heating & Cooling Equipment Efficiency