HomeMy WebLinkAboutEngineer's Design Plan129 Cerrus LANE CRReoNronLE, CO A1623 970.309.5259 CARLA.oSTBERG@GMAIL, coM sttl"l'I ( : ( :()Nst !I-'t.I i\('; March 4,2024 Project No. C1869 Whit Whitaker wrw3@hotmail.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design Barn 11454 CR 115 Garfield County, Colorado whit, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 4O-acre property is located outside of Glenwood Springs, in an area where OWTSs and wells are necessary. Legal Description: Section: 6 Township: 7 Range: 87 A TRACK lN THE SESE. 40 ACRES Parcel lD: 2391-064-00-146 SITE CONDITIONS The property is currently undeveloped. A S-bedroom residence is proposed on the eastern portion of the property. The OWTS that will serve the residence is described in a separate design (CBO lnc. Project No. C1716, dated April 27 , 2022). A Barn near the northern property boundary with a toilet and sink and a Recreational Vehicle (RV) dump (intended for limited use) is proposed. The structures will be served potable water from a well on the property. The well is located over 400-feet south of the Barn and is greater than SO-feet from the proposed septic tank and greater than 10O-feet from the proposed soil treatment area (STA). No water line will come within 2S-feet of any OWTS component. The proposed soil treatment area (STA) location has an approximate 7 to I percent slope to the east The proposed area is vegetated with native grasses. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE The subsurface was investigated on March 1,2024 by digging two soil profile test pit excavations (Test Pits) A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l I Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page2 The materials encountered in Test Pit #1 consisted of dark brown loamy topsoil with a reddish brown matrix to 4-feet, underlain by more dense, gray, clay loam to a maximum depth explored of 8.O-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit#2were similar to those encountered in Test Pit #1. Test Pit #2was excavated to a maximum depth explored of 8.O-feet. No bedrock or groundwater was encountered. A sample of the soilwas taken from Test Pit #1 at 3-feet below grade. Soil structure grade was moderate. The soilformed a balland a ribbon less than 1-inch in length before breaking. Soilstructure shape was blocky and consistence was firm. Soil texture was more both gritty and smooth. A sample of the soil was taken from Test Pit #1 at 6Jeet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon between 1 and 2-inches in length before breaking. Soil structure shape was blocky. With depth, soils had more clay content. The upper horizon of soil is consistent with Soil Type 2, Loam, with moderate structure grade. We are proposing a very shallow installation in the Soil Type 2 horizon. For the purpose of sizing the STA, we are using a more conservative long-term acceptance rate (LTAR) of 0.35 gallons per square foot. Soils contain more clay with depth. Test Pit #1 Page 3 Loamy topsoil (upper horizon)Backfill Soils below 4-feet become more clayey and dense Page 4 View of Test Pits #1 and#2 Test Pit #2 -.x?p",. Arrow indicates change in soiltype at approx. 4-feet Sieved sample Ribbon less than 1-inch (above 4-feet) Page 5 DESIGN SPECIFICATIONS Desion Calculations: Average Design Flow = 200 GPD LTAR = 0.35 GPD/SF 200 GPD / 0.35 GPD/SF = 656.25 SF The OWTS design an average daily wastewater flow of 200 GPD will be used. This is an estimated design flow based on use of a toilet and sink in the Barn and occasional use from the RV dump. No chemicals should be introduced into the OWTS. For the purposes of this OWTS design, Benchmark Elevation at grade 7186' has been established as 100' (Finished Floor). CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. Minimum grade refers to piping between components. The 4-inch SDR-35 sewer line exiting the residence must have a double-sweep clean out and a minimum 2o/o grade to the septic tank. The system installation must include a 1000-gallon, two-compartment lnfiltrator@ poly septic tank with an Orenco@ Biotube effluent filter on the outlet tee. Any state-approved concrete or poly septic tank may be substituted. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Effluent will gravity flow to a distribution box, and then to three gravelless chamber trenches. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each trench. Each trench will consist of '12 'Quick 4' Standard Plus Low Profile lnfiltrator@ chambers for a total of 36 chambers and 432 square feet of infiltrative area. We are recommending trenches be excavated no more than 1-foot below native grade and the backfill mounded over the trenches. Mounding may tie into the upgradient slope and there must be a minimum 3:1 slope downgradient. There must be at least 4-feet of undisturbed soil between each trench. lnspection ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. OWTS Component Minimum Elevation Primary Tank lnlet lnvert Approximate horizontal distance 14' I min. 2% fall I min. 3.5" fall Distribution Box Approximate horizontal distance 5'l min. 1%fall I min. 6.25" fall lnfiltrative Surface Approximate horizontal distance 16' to furthest trench / min. 1o/o fall lo STA / min. 2" fall Page 6 Construction must be according to the jurisdiction's adopted On-Site Wastewater Treatment System Regulations, the OWTS Permit, and this design. PERMIT APPLICATION INSTRUCTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department https://www.qarfield-countv.com/environmental-health/filesqcco/sites/16/OWTS-Application-Complete- Packet-Dec.-2019.pdf. lf the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-661 4 xBl 50. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. COMPONENT MANUFACTURER MODEL NO COMMENTS Septic Tank lnfiltrator@ tM-1060-2CP 1000-9allon, 2- compartment poly septic tank Effluent Filter Orenco@ 4-inch diameter, full size Tank Risers and Lids Orenco@ Double-walled PVC Rtsers and Lids (24" diameter) Distribution Box Polylok Distribution box, risers, lids, and flow equalizers (3) chambers lnfiltrator@ 'Quick 4' Plus Standard Low Profile 36 Low Profile Chambers Page 7 REVEG ETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Page 8 Please call with questions Sincerely, CBO lnc. Carla Ostberg, MPH, REHS (s"nb oxfu-,^'g DMWINGS MUST BE USED IN CONJUNCTION WITH DESIGN.. LETTER DATED O3IO4I2O24 CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.mm PROPERTY I ) (-- N{\ .TP TP2 +,-.\J'29^\ cba-STA EXISTING EXISTING RANCH AND WATER LINE (APPROX.) WELL LOCATED APPROX.400'SOUTH THE LOCATION OF PROPOSED IMPROVEMENTS SHOWN ARE NOT THE RESUL OF PROPERTY SURVEY THE LOCA TIONS.\ lT ls THE HOt\4EOWNERS' DUTY TO ENSURE ALL CONSTRUCTION AND IMPROVEMENT LOCATIONS ARE ACCURATE, PROPERry LINES AND SETBACK DISTANCES SHOULD BE CONFIRMED PRIOR TO EXCAVATION. SCALED FOR PRINTING ON 11'X 17'PAPER. l l I I Ili li ( lr I/r I Il,I, (\,ir i I ( ) \ 7 i,:r?. ------1x )ot XX glr Ir I l Whitaker Barn 1 1454 CR 115 Garfield County, Colorado ProjectNumber: C1869 Date: O3lO4l2O24 Designed by: CBO Drawn by: DD ----x -,x x ( _--.-X ' --/ 60' Access Ecsement Reception No. 556,556 w1 .0 Sheet 1 0F 4 c".J "+ "qV fv 1) ,L4 ^v ^n-4,J N -72N ,/,/scA{E:1 =r0.=0il ,/ /aslfE PLAN t'/''///// ,/ / CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.com Whitaker Barn 1 1454 CR 1 15 Garfield County, Colorado ProjectNumber: C1869 Date: 0310412024 Designed by: CBO Drawn by: DD Sheet 2 0F 4 w2.0 l \ ( X I \'- /,/ PROPERry LI I ( '\ ..... X 1" = 30L0' XX .i. tY ) 'QUICK.4' LOW PROFILE CHAMBER TRENCHES. 3 TRENCHES WITH 12 CHAMBERS PER TRENCH FOR A TOTAL OF 36 CHAMBERS AND 432 SF.\,r\ 4" DIA SDR.35 SEWER PIPE WITH CLEANOUT MIN 2OlO FALL TO TANK MtN. 10'TO LINE EXISTING BARN FF 7186'(BM 100') I ) \\\ TP 4' DIA SDR-35 INSPECTION PORT AT BEGINNING AND END OF EACH TRENCH + TP2\\r \ DISTRIBUTION BOX ..\ wtTH ACCESS AT \ GRADE (.. 4" DIA SDR-35 SEWER PIPE '.. MIN 1% FALL TO D-BOX\'.r\ \ \ 5'.( N l 1 OOO-GALLON, TWO-COMPARTMENT POLY SEPTIC TANK WITH EFFLUENT SCREEN \ tt\\ \.\ '\\\ \\ /APROPOSED OVTS - S-0' CBO lnc. 129 Cains Lane Carbondale, Colorado 8 1623 Phone 970.309.5259 mrla.ostberg@gmail.@m Whitaker Barn 1 1454 CR 1 15 Garfield County, Colorado ProjectNumber: C1869 03t04t2024 by: DD by: CBO Sheet 3 0F 4 w3.0 4' DIA SDR.35 SEWER LINE TO EACH TRENCH (MrN. 1%o SLOPE TO TRENCH)4' DIA SDR-35 EFFLUENT PIPE FROM SEPTIC TANKINFILTRATOR END PLATE GRAVELLESS'QUICK4' LOW PROFILE CHAMBER (4'xg) DISTRIBUTION BOX WITH ACCESS AT GMDE TIE GRADE INTO UPGRADIENT HILLSIDE FILL NEW GRADE MIN. '1' COVER OVER CHAMBERS FROI/I HOUSE EXCAVATION DIA SDR-35 INSPECTION PLACED IN NATIVE4'.TOP PORT OF CHAI/IBER END PLATES NOTE: MlN. 3:1 SLOPE TO TIE INTO DOWNGRAOIENT HILLSIDE1'max L sotL DIA SDR-35 INSPECTION height PORTAT BEGINNING AND END OF EACH TRENCH EXCAVATION SCARIFY 'ourcK4' Low PROFILE CHAMBER (4'x 3') /iSTA PLAN MEW\lr-rdndtr /iCHAMBER TRENCH SECTION\3r--rftffi SMIL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADE FINISHED GRADE CAP OR THREADED BOX AND COVER BROUGHT TO GRADE CLEANOUT ASSEMBLY 24'MtN.CONCRETE LID-\... COMPACT 4'DIA SDR-35 SEWER LINE (MtN 2olo SLOPE TO TANK, MrN. 1olo TO STA) .-GRAD- BASE TO SUPPORT BOX PVC PIPE CUTTO FIT USE HOLE SAW TO CUT THRU TOP OF SCREENED END OR SAND FOR AEDDING 3'MtN. 8" MIN BAFFLE OR ANGLED PIPE /iDISIRIBUTION BOX\gr-rffi TO BE USED AT INLET /AIRENCH DETAIL\9,-_-......ffffi /ADIS1RIBUNON BOX DET\9r-==-r6r-ffi AIL ,12 CHAMBERS PERTRENCH z OUTLETS oooo il: CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.com Whitaker Barn 1 1454 CR 1 15 Garfield County, Colorado ProiectNumber: C1869 Date: O3lO4l2O24 Drawn by: DD by: CBO w4.0 Sheet 4 0F 4 DESIGN OWTS COMPONENTS AND MINIMUM REOUIRED SETBACK APPROXIMATE PROPOSED EXISTING BARN WTH BATHROOM DESIGN FLOW = 200 cPD STA TO WATER COURSE 50'N/A STA TO WELL 100'477', STA TO BARN '10'21 SEPTIC TANK TO WATER COURSE 50'N/A SEPTIC TANK TO WELL 50'455' BARN TO SEPTIC TANK 5'10' TANK: MIN. lOOO GALLONS USE lOOO-GALLON, TWO.COMPARTMENT POLY SEPTIC TANK SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.35 GAU SF CALCULATED STA = Q|/LTAR = 200 / 0.35 = 571 SF GRAVlry, TRENCHES = 200 SF x 1.0 = 571 SF CHAMBERS = 571 SF X 0.7 = 4OO SF / 12 SF / CHAMBER = 34 CHAMBERS THREE GMVELLESS CHAMBER TRENCHES 12'QUICK 4'CHAMBERS IN EACH TRENCH TOTAL 36 'QUICK 4' CHAMBERS SOIL PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO.2 0 DARK BROWN LOAM WITH REDDISH BROWN MATRIX DARK BROWN LOAM WITH REDDISH BROWN MATRIX 3 FuUI IF 0-uo 4 6 7 8 9 10 GRAY CLAY LOAM GRAY CLAY LOAM SLIP.ON PVC DO NOT GLUE INSULATED LEGEND F loamy topsoil V ctay loam TMCERWIRE FINISHED GRADE 4'DIA NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION SEWER LINE TO TANK HOUSE /A SOILS LOG\3r--6r-16ffi /iCLEAN OUT DETAIL s/ Norbs4 Legend11454 cr 115 { t' j. 'p * ,.' '. 239.1064001 ll'& S'OPHIE R, GDqPublic.h€t''"' Garfield County, CO D eve ro pe d ou C) 9,"Xtpg',4 er Overview I Legend [---l Parcels Roads Parcel/Account Numbers Highways : Limited Access - Highway Major Road Local Road Minor Road Other Road Ramp Ferry Pedestrian Way Owner Name Lakes & Rivers - County Boundary Line $2,200 Last2sales Date Price 9/70/2020 $O 9/70/2O2O $O Account R7t752O Physical O 2ol9TotalActual Number Address Value Parcel Number 239tO64OOt46 CARBONDALE 81623 Acres 40 OwnerAddress WHITAKER,WALTERRIII&SOPHIE LandSqFt 0 R TaxArea 011 IOO9CATTLECREEKR|DGE ROAD 2019 Mill Levy 79.7760 CARBONDALE CO 87623 D ate cr e ate d: 4 / 28 / 2O22 Last Data Uploaded: 4/28/2022 2:73:49 AM 4128122,1:42 PM qPublic.net - Garfield County, CO - Property Record Card: R111520 G)qPublic.net'" Garfi eld County, CO Summary Account Parcel Property Address Legal Description Acres Land SqFt Tax Area Mill Levy Subdivision R111520 239!06400746 ,CARBONDALE,CO 87623 Section: 5 Township: 7 Range: 87 ATRACK lN THE SESE.40 ACRES 40 0 7t 79.7760 View Map Owner WHITAKER.WALTER R III&SOPHIE R 1OO9 CATTLE CREEK RIDGE ROAD CARBONDALE CO 81623 Land Unit Type Square Feet Actual Values Assessed Year Land Actual lmprovement Actual Total Actual Assessed Values Assessed Year Land Assessed lmprovement Assessed Total Assessed Tax History Tax Year Taxes Billed Sale Date 9/70/2020 9/lO/2020 9/70/2020 9/9/2020 9/9/2020 6/24/20tt 6/22/2017 9/4/2002 9/4/2002 9/4/2002 9/4/2002 4/t9/2002 GRAZING LAND-AGRICULTURAL. 4147 (AGRICULTURAL PROPERTY) 0 2027 $s1.04 2020 $46.08 2079 $46.48 202t $2,2OO.OO $0.00 $2,200.oo 2021 $640.00 $o.oo $640.00 2078 $44.60 2020 $2,110.00 $o.oo $2,r10.00 2020 $610.00 $o.oo $610.00 20t7 $42.64 Click here to view the tax information for this p=Eel-9!$S-G4ie!g!@v&agC-tg5ryS!gile. Transfers Deed Type Right Of Way Easement Right Of Way Easement Right Of Way Easement SPECIAL WARRANry DEED STATEMENT OF AUTHORITY WARRANTY DEED STATEMENTOFAUTHORIry QUITCLAIM DEED QUIT CLAIM DEED QUITCLAIM DEED WARRANry DEED AGREEMENT Reception Number ?4?746 948265 942556 947698 947697 804305 804306 6ro240 6ro239 670238 6ro237 6VZJ5J Book - Page Sale Prlce $o $o $o $s2s,000 $o $47s,000 $o $o $o $o $33s,000 $o 1384-110 1384-108 1"384-106 1384-702 1350-595 https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=566230598&KeyValue=R111520 112 4128122,1:42PM qPublic.net - Garfield County, CO - Property Record Card: R111520 4/70/2002 !t/77/1994 9/3/7993 2/28/7990 3/L5/7989 7/22/1984 4/L6/1984 7/3u1983 u37/7983 70/25/r977 9/6/t977 AGREEMENT WARRANWDEED WARMNTYDEED SPECIALWARRANTY DEED QUITCLAIM DEED COURT DECREE RESOLUTION DEED RESOLUTION QUITCLAIM DEED WARRANTY DEED 6023s! 47rr58 452774 4ro363 400692 355277 357445 337987 33797A 281482 280637 1350-598 0923-OO23 o874-0785 o773-0822 0752-0369 0655-0987 0647-0993 0619-0504 o6t9-0467 o502-0275 o500-0654 $o $1s8,000 $80,000 $2,0s0,000 $o $o $o $o $o $o $o Property Related Public Documents Click here to view Prop3l!y-@|4!g1zu!!q@$ Photos No data avallable for the following modules: Buildings, Sketches. Th-^ Garfrelcl County Assessor's Otfrce makes every effort to produce the mosl. accurate inforntation possible. No vrarrantit:s. expressed or implied are 1;rovided lor tlte data herein. iis use or interpretalicn. Daia is subject to conslant chang€ and its accur acy and comltleieness cannot be guaraniecrd. Llser Privacy.Pqliqy 9DP j-Pr-vesvIsIlrs LaslDataUpload:4/28/2Q22.21 ,49AV Version2.3.191 Developcd by (.)9."19p1,4fl https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=566230598&KeyValue=R111520 212