HomeMy WebLinkAboutOriginal- Engineer's OWTS DesignK.CROTfI(P.O. Box 4o Mat:k, C() g7o.25a.o 5Z 2 f kachayln.cronkq tnttlook;r.ttnt Onsite Wastewater Treaftnent System Desrgn February 16,2024 Sedota Project 2255 -CR- 226 Rifle, CO 31650 Parcel No. 2127 -024-OO-I3I Prepared By: K-Cronk Engineering, Inc. P.O. Box I40 Mack, CO 81525 970-250-0572 Site History There is an existing residence on the site that is served by an existing onsite wastewater treatment system (OWTS). The existing system is experiencing slow drainage and signs of failure, and the owner would like to replace it. The owrs will be designed for a five-bedroom residential loading. The site consists of approxim ately 43 .83 acres of uncultivated native soil. Drainage is approxim ately 3%o to the southeast. A percolation (trterc) test/soils evaluation and site study were conducted on the property of reference on0ll31l2024by Kachayla R. Cronk, registered professional engineer (R.P.E.). The perc excavation trench was located approximately 400' south of the norlh property line and approximately 720' east of the west property line. This OWTS design has been prepared for the project based on information disclosed during the site studies mentioned above. A discussion of the engineered OWTS design follows. The perc test/soils evaluation are attached for reference as Appendix A. The location of the perc excavation trench is shown on the plot plan included in this report. Development of Desiqn Parameters The perc excavation trench was extended to a depth of 108" below ground surface (BGS). There was no evidence of ground water or high seasonal water table in the open excavation to a depth of 108" BGS. The soils evaluation indicates one distinct soil horizon underlies the site. A lithological description follows. depth (in.) 0"- 108" description highly weathered shale, grey (Soil Type 3, USDA - clay loam, granular, strong structure) Based on the results from the 0ll3ll24 perc test/soils evaluation (Appendix A), an LTAR of 0.35 is chosen for overall system sizing for a pressurized infiltrator trench soil treatment area designed to discharge to subsoils below the 36" depth. Svstem Design An INFILTRATOR trench soil treatment system is proposed for discharge of septic effluent at the site. Construction of the system will consist of excavating level trenches in the area comprising the soil treatment area. Grading during construction may affect slope. therefore contractor shall verifv slope at time of insfallafion^Soil treatment area orientation mav he adiusted ner site vari to facilitate consistent trench depth running parallel to final contours. The initial excavation shall be continued to a level depth of 36" BGS (see Soil Treatment Area Cross Section). If consistent trench depth cannot be maintained. INFIZZRIZOR chambers may be installed level at 24" minimum and 48" maximum BGS. A lift station discharging into pressurized effluent distribution laterals will be employed to discharge septic effluent into the soil treatment area. Following completion of the initial excavation, INFILTRAZORS (QUICK4 STANDARD or equivalent) will be used to construct a septic effluent distribution system. The INFILTRAZOR effluent distribution system will be installed in accordance with the "Infiltrator Technical Manual", available from Infiltrator Systems 1nc.,723 Elm Street, Suite 12, Old Saybrook, Connecticut 0647 5. Adjacent INFILTRATORS shall be fastened with a minimum of three (3) %" self-tapping screws to prevent movement and separation during backfilling. After the INFILTRATORS are installed, synthetic filter fabric (140-200 mesh) will be placed over the INFILTRATORS and the system will be covered with a soil cap. The soil cap will consist of approximately 24" minimum of native soil backfill. The soil cap will be mounded 5%o above the existing ground surface to promote surface run off away from the soil treatment area. Septic effluent will be introduced into the soil treatment area through pressurized distribution laterals installed in each row of INFILTRATORS as shown in the included graphics. The injection laterals will consist of l-112" Schd 40 PVC pipe with 5132" holes equally spaced 48tr o.c. along each row of INFILTRATORS. Holes in the injection laterals will be drilled at 12:00 o'clock to direct effluent up for dispersal against the top of the chamber. Injection laterals shall be suspended from the top of the chamber with all-weather plastic pipe strapping (min. 120 lbs tensile strength) at every chamber joint connection. There is an existing tank on the site that has been used for sewage storage. The tank will be removed or abandoned in place and replaced with a new tank described below. Abandonment shall consist of pumping the tank of all solids and crushing the top and sides in before filling all void space with structural fill. A 1,OO0-gallon, single compartment septic tank is required with a non-corrodible Orenco filter (model # FTW0436-28) installed at the final outlet tee of the septic tank to limit the size of solids and sludge passing into the second tank. The filter must be accessible for cleaning and replacement from the ground surface. A second, 1,000-gallon, two-compartment septic tank will be placed down-gradient of the single compartment tank. A screened effluent pump will be placed in the second compartment of the down- gradient tank. The effluent pump system will employ an OSI high head, non-clog (3/4" solids handling capability), effluent pump (OSI model no. PF50051 l) and screened pumping vault (OSI model no. PVU57- 1819-L). A 2" Schd 40 PVC pressure transport line will be used to transfer septic effluent from the pumping system to the STA. The pressure main will be self-draining or be buried a minimum of 36" below ground surface to prevent freezing. All pressure piping and construction shall be completed in accordance with the attached graphics. 2 As shown in the included graphics, the trench soil treatment system will consist of four (4) trenches 3'wide x 36" deep x 80' long with twenty Q0) INFILTRATOR (or equivalent) units each for a total of eighty (80) units. The soil treatment area will encompass an effective area of 1714.29 sq. ft. DESIGN CALCULATIONS DESIGN LOADING RATE oF 3 BEDROOMS @ rs} GAL./BEDROOM-DAY :4s0 gat.tday PLUS 4h & 5h BEDROOMs @75 GAL./BEDROOM-DAY :600 gat.tday DESIGN LONG TERM ACCEPTANCE RATE (LTAR) = 0.35 GAL./Se.FT./DAY A= Q .WHERE. A = SOIL TREATMENT AREA (Se. FT.) Q= DESIGN FLOW (cAL./DAy) LTAR = LONG TERM ACCEPTANCE RATE (GAL./Se.FT./DAY) A=# = 1714'29sQ'FT' SOIL TREATMENT AREA ADJUSTMENT FACTOR FOR PRESSURE TRENCH DESIGN = 0.8 SOIL TREATMENT AREA ADJUSTMENT FACTOR FOR USE OF CHAMBERS : 0.7 ADJUSTED soIL TREATMENTAREA = 1200 se.FT. x 0.8 x 0.7 =960 se. FT. LENGTH OF 3', WIDE TRENCH REQ'D : 960 SQ.FT. / 3 FT. :320FT. USE 4 TRENCHES WITH 20 QUICK4 STANDARD INFILTRATORS (or equivalent) EACH, FOR A TOTAL OF 80 LTNITS soIL TREATMENT AREA SIZED AT 4 TRENCHES 3 FT. WIDE X 80 FT LONG:960 SQ. FT. aJ Installation - Setbacks" Notifications" and Inspections The owner and installer shall be aware of and comply with the following installation and system operation requirements. a o The installer must be approved and licensed by Garfield County for installation of onsite wastewater treatment systems. All installation activities shall be conducted in accordance with current Garfield County OZZ,S Regzlafions. If at any time during construction. subsurface site conditions are encountered which differ from the design parameters previously described. construction activities will stog and the design engineer and Garfield County will be contacted to address any necessary design modifications. The final cover shall not be placed on sewer lines, septic tank, or the soil treatment area until the system has been inspected and approved by the design engineer and Garfield County. The installer shall provide 48-hour notice for all required inspections. Installation procedures including grade, location, setbacks, septic tank size, and soil treatment size shall conform with the attached graphic details. Construction activities and system components will not encroach upon existing easements or utility corridors. A minimum of 5 ft of undisturbed soil shall be maintained between individual absorption elements and the septic tank. A minimum of 4'of undisturbed soil shall be maintained between adjacent absorption elements. The installer must maintain all setbacks to utility lines, easements, property lines, or other adverse conditions, whether they are known and shown on the attached graphics or have been disclosed during construction. Vehicle traffic and parking is to be prevented over the soil treatment and repair area. Minimum setbacks for system components are: a a a a Source domestic water line domestic well domestic water cistern property lines structure w/crawl space structure w/o crawl space irigation ditch open intermittent irrigation gated solid pipe/lined Soil Treatment Area 25', 100' 1 00' l0' 20' 10' Septic Tank l0' 50' 50' l0' 5' 5' 50' 10' l0' l0' 50' 2s', 25', l0' All gravity flow sewer lines and effluent distribution piping shall be 4 inches in diameter and have glued joints. All lines discharging sewage from the residence to the septic tank shall maintain a minimum fall of 1/8 in. per foot and shall employ sweep 90's or 2-45's at all turns. Sewer lines from the dwelling to the septic tank and at least 6 ft from the septic tank outlet must meet minimum standard ASTM-3034. Lines discharging from the septic tank to the soil treatment area shall maintain a minimum fall of 1/8 in. per foot. Sewer lines under driveways shall meet the minimum Schedule 40 PVC standards. Additionally, effluent piping in traffic areas with less than 24" of cover shall be encased in 6" CMP or flow fill and covered with minimum 2" high density blue board insulation. 4 a a a a o a a Sewer lines or domestic water lines shall be encased in minimum SCHD 40 with water-tight end caps or aminimum of 6" of flow fill at all points with less than 5' separation between sewer and domestic water lines. Four-inch clean outs shall be installed at maximum 100' intervals in all gravity flow effluent lines exceeding 100'in length. A minimum of 72" of soil cover (18" recommended) shall be maintained over all gravity draining OWTS components to prevent freezingof septic effluent (excepting septic tank access ports which must be extended to the ground surface). A minimum of 36" of soil cover shall be maintained over all non-draining pressure effluent line. The septic effluent pumping system shall consist of OSI components (OSI, non-clog (314" solids handling capability) effluent pump model no. PF50051 1 and OSI screened pumping vault model no. PVU57-1819-L) as detailed in the attached effluent pumping system detail. The effluent pump control panel shall be Orenco model no. S1ETM. Electrical wiring shall be continuous cable with all connections made in a weatherproof box. Limit switching shall consist of: 1) low level/pump off,2) high level/pump on, and 3) high level alarm/system failure. The high-level alarm shall be both audible and visual and shall be easily detectable by occupants. Emergency notification information (e.g., telephone numbers of owner, Garfield County, service personnel) shall be posted near the high-level alarm. The effluent pump shall be configured with a minimum dose volume of 100 gal (4.80" float differential for two-compartment, 1,000 gal. tank). Storage capacity in excess of the high-level alarm shall be 6" above the pump-on float level. All access manholes on septic tanks and dosing chambers will be child proof and contain appropriate warning labels if accessible to the public. Confined space entry precautions should be observed by maintenance personnel. The system contractor shall be aware of the potential for construction activities to reduce soil permeabilities at the site through compaction, smearing, and shearing. The following precautions and construction procedures should be employed during installation to minimize disturbance to native soils: i. Excavation should proceed only when the moisture content of the soil is below the plastic limit. If a sample of soil forms a rope instead of crumbling when rolled between the hands it is too wet and should be allowed to dry before excavation continues. ii. Excavation and backfill equipment should work from the surface where at all practical to avoid compaction of the soils at depth. iii. The bottom and sidewalls of the excavation should be left with a rough, open surface. The appearance should be that ofbroken or ripped soil as opposed to a sheared, smeared, or troweled surface. Any smoothed or smeared surfaces should be removed with a toothed rake or shallow ripper, taking care to remove loose residues from the bottom of the excavation by hand if necessary. iv. Care should be taken in placing fill materials in the excavation to avoid damaging the exposed soil surfaces. 5 Operation - Maintenance and Inspections The owner shall install a structural barrier ifnecessary and take precautions to prevent vehicular traffic, excessive surface watering, accidental flooding, or other activities in the vicinity of the soil treatment area which may compact, saturate, or otherwise alter the subsurface soil parameters used in designing the septic system. The owner will plant and maintain grass or other shallow rooted cover crop to prevent erosion and promote evapotranspiration over the soil treatment area. The owner will inspect and maintain the required mounding and drainage away from the soil treatment area to prevent saturation from precipitation and surface flows. To mitigate the generation of preferential flow channels which may compromise the operation of the system, the owner will inspect and prevent intrusion of burrowing animals and deep- rooted plants into the soil treatment area. The septic effluent pump and the effluent pump filter shall be inspected and cleaned as necessary every six (6) months. The owner will conduct periodic maintenance of the septic system by removing accumulated sludge from the septic tank every 3-4 years to prevent clogging ofthe soil treatment area. a a a a a 6 Limitations This report is a site-specific design for installation of an onsite wastewater treatment system and is applicable only for the client for whom our work was performed. Use of this report under other circumstances is not an appropriate application of this document. This report is a product of K-Cronk Engineering, Inc. and is to be taken in its entirety. Excerpts from this report may be taken out of context and may not convey the true intent of the report. It is the owner's and owner's agent's responsibility to read this report and become familiar with the recommendations and design guidelines contained herein. The recommendations and design guidelines outlined in this report are based on: 1) the proposed site development and plot plan as furnished to K-Cronk Engineering, Inc. by the client, and 2) the site conditions disclosed at the specific time of the site investigation of reference. K-Cronk Engineering, Inc. assumes no liability for the accuracy or completeness of information furnished by the client. Site conditions are subject to external environmental effects and may change over time. Use of this plan under different site conditions is inappropriate. Ifit becomes apparent that current site conditions vary from those anticipated, the design engineer and Garfield County should be contacted to develop any required design modifications. K-Cronk Engineering, Inc. is not responsible and accepts no liability for any variation in assumed design parameters. K-Cronk Engineering, Inc. represents this report has been prepared within the limits prescribed by the owner and in accordance with the current accepted practice of professional engineering in the area. No warranty or representation, either expressed or implied, is included or intended in this report or in any of our contracts. SEAL A O-r,Z Kachayla { Cronk, P.E. Date NOTE: This OWTS design is meant to include the following seven pages: 1) plot plan 2) septic layout plan 3) notes for your installer 4) soil treatment area plan view 5) soil treatment area cross section 6) pump vault detail 7) pump curve The plan is not to be implemented in the absence of these sheets. In addition, results from the percolation test and soils evaluation are included for reference as Appendix A. 7 t- 0! oa/d/ o"/\ perc excovo 43,83 acres I L__ resldence locotion of exlstlng cteon out te locatlon exlstlng EVTS --- Coa^t, 'oqc/ee6 exlstlng shed SEDOTA PREJECT 2255 -CR- a26 ?127-O24-OO-L3L PLOT PLAN FEBRUARY 16, ?024 SCALET 1'=200'NERTH perc exco,vo,tion )!t NOTE PROVIDE MIN. 12' COVER (18' RECOMMENDED) OVER ALL GRAVITY DRAINING EFFLUENT LINES AND MIN, 36' FROST PRETECTIEN COVER OVER ALL NON-DRAINING PRESSURE oneo solt treotnent oreo(STA) conslstlng of 4 rows of 20 Oulck4 Stondord In€lttrqtors(on equlvotent) fon ototol of 80 unlts wlth pressune dlstrlbutlon os shown 1,,000 9o(ton, two NETE CALL 811 FOR UTILITY LECATES SEDDTA PROJECT 22ss -cR- 266 ?r27-024-00-131 PLET PLAN-EBRUARY 16, 2O?4 SCALET 1'=40'NERTH NOTE EXISTING SEPTIC TANK TE BE ABANDONED IN PLACE OR REMOVED, IF THE TANK IS TE BE ABANDONED, IT MUST BE PUMPED OUT PRIDR TN CRUSHING, ANI) THE REMAINING VO]D IS TO BE FILLED V]TH GRAVEL, SAND, ER COMPACTED SOIL 1,,000 gotton, slngte conportment septlc tonk w/ effluent fll.ten (0SI Mode( FTV0436-28) O5, oF t/ or. e5, k7 compontnnent septlctonk w/ screenedeffluent purnp ln second chomber obqndon exlstlng DVTS ln ptoce exlstlhg resldenc€ 43,83 ocnes at3/t4/ 'l note o.ddressing cover) 2' SCHD 40 pnessure tnonspont noln (see Nt]TE THE FOLLOVING SETBACKS MUST BE MAINTAINEDI SEPTICTANK STA LAKE/STREAM,/IRR16, DITCH - 50/ INTERMITTENT IRRIG, DITCH-iO, 100' 50' 25', ?s'. 10' r00' 25' 20' 10' 10' SELID PIPEILINED DITCH DDMESTIC VATER CISTERN - 50i DT]MESTIC \./ATER LINE STRUCTURE V,/ CRAVLSPACE-5' STRUCTURE V,/[ CRAVLSPACE_5' 50' 10' 10' SPRINGS/VELLS GATED PIPE PROPERTY LINE K-CROAII(P.O. Box 4o Ivlat:k, CO Bt g Zo. 25o. o jZ 2 f ka ch ay la. cr on k @ ou tlaok. t-t nt NOTES F'OR YOUR INSTALLER o Please veri$/ slope at the time of system installation - the orientation of the STA shown in this design has been determined based on existing site conditions at the time of the original site investigation, but that may have changed during construction and pre-construction grading of the site. o The depth of the trenches is determined by percolation rates and soil conditions relative to the existing ground surface at the time of the soils investigation. If the site slope or grading of the ground surface at the time of installation differs significantly from what was initially observed, the trench depths may have to be adjusted to make sure the infiltrative surface remains in the desired soil layer, and portions of the trenches don't end up too deep or too shallow.The denth soil can relative to finished sradins is not oartofthe of the OWTS design criteria. o Please provide K-Cronh Engineering with a copy of the septic tank manufacturer's specification sheet veri$'ing maximum backfill depth. Tanks must be backfilled according to manufacturer's specification. Pressurized System Notes o Please provide K-Cronk Engineering a copy of the sand sieve analysis, if relevant, dated within 30 DAYS of installation before purchasing/installing the sand so we can check that it meets Garfield County OWTS standards. o Pump floats do not come pre-set from the factory. Please refer to the Pump Vault Detail for the distance needed between the on/off floats. Please reach out at any time during the installation process ifyou have any questions! Ka"iz'/e E. C,*nZ / Kachayla Cronk - (970) 250-0572 solt tneotr4eht oreo (STA) conslstlng of 4 nows of 20 Oulck4 Stqndord Inflltnatons(on equlvolent) for o totoLof 80 unlts wlth pnessure dlstrlbutlon systen os shown fosten odJo w/ (9 3/4' 1-112' SCHD 40 PVC pnessure lqterqts wlth 5/32' hotes spoced48' o,c, Ilnltt hotes ot 1?100 o'ctockto dlrect dlschonge up to dlspense ogolnst top oF chornben, typ. two(2) of elsht (8) \ I I I 85' w,/ endcops, of chonbens, septlc lnftuent fnon tift stqtlon pnovlde ventlng ond observatlon/botonclngports ot eqch end of Inflltnoton trenches o.s shown (see detoll on Sol[ Treotment Aneo - Cnoss Sectlon) ! 0,t-( oq o,( o- nr\t I I \ \ I I I I I SEIL TREATMENT AREA - PLAN VIE\^/ SCALET 1'=10' SEI}OTA PRDJECT 2255 -CR- 2e6 21?7-024-00-t3t SOIL TREATMENT AREA-PLAN VIEV FEBRUARY 16, 2OE4 SCALET 1'=10' cent In€lttrotors scnews qt SCRE\r' DETAIL NTS opproxlnotety 10 o'ctock, 12 o'ctock, ond 2 o'ctock posltlon, typ, aL \_ o o J__ o o \., (10' reconmended) o + \o(,48', typ, H 4' nin, a' scHD 40 no.ln pressure tnonspont2' SCHD 40 pnessune nonlfold INFILTRATDR (OUICK 4 STANDARD [R EOUIVALENT), ]NSTALL IN ACCI]RDANCE VITH'INFILTRATOR TECHNICAL MANUAL, INFILTRATDR SYSTEMS INC,, 1A3 ELM STREET, SUITE 1E, ILD SAYBRIEK, CONNECTICUT 06475 SYNTHET]C FILTER FABRIC (140-EOO MESH) IVER TNFILTRATERS, TYP, 2' SCHD 40 PVC 1-1,/?' SCHD 40 pressure loterots wlth 5/32' hotes spoced 48' o.c, qt 12100 o'clock to dlnect dlschorge up for dlspenslon ogolnsttop of chomben (typ. 1 of 8) PROVIDE VENTING/INSPECTION PtrRTS AT EACH END AS SHOVN PRI]VIDE NATVIE SNIL CAP (MNUND 5Z), TYPICAL EXISTING GREUND SURFACE DISK OR NETEI IF CDNSISTENT TRENCH IEPTH CANNET 3E MAINTAINEI, INFILTRATOR CHAMBERS MAY 3E INSTALLEI LEVEL AT 24' MIN. AND 48' MAX. BGS PRESSURE MANIFOLD, INSTALLATINN DII4ENSIONS TYPICAL [F ALL TRENCHES (10' pnefenred) PROVIDE MIN, 1/8' FALL PER 12' RUN FOR DRAIN BACK T[ LIFT STATION FOR ALL LINES ViTH LESS THAN 36' OF CEVER, TYPICAL -108', SEILS LEG (SEE NITES) E' SCHD 40 PVC PRESSURE TRANSPERT LINE FRIM LIFT STATIEN SEIL TREATMENT AREA - CROSS SECTIEN (TYPICAL 4 trF 4> SCALET 1'=10' SOILS LDG NOTES #1 - HIGHLY VEATHERED SHALE, GRAY (USDA-CLAY LOAI"I, GRANULAR, STRONG STRUCTURE) NE GROUNDVATER OR H]GH SEASONAL VATER TABLE OBSERVED TN A DEPTH OF 108' BELEV GREUND SURFACE (BGS) SEDETA PRIJECT 2255 -CR- 226 2127-024-OO-13r SOIL TREATMENT AREA - CRESS SECTIEN iEBRUARY 16, EO?4 SCALEI AS SHIVN 4' SCHD 40 PVC VENT/INSPECTIEN Pt]RT SOIL CAP 3/4' THREAD CAP ELEVATIEN DESIGN SPECIFICATIDNS DESIGN DISTANCE FRDi4 SEPTIC TANK T[ S[]L TREATMENT AREA = 260' ASSUMED ELEVATIEN tF GRTUND SURFACE AT ENTRY T0 SIIL TREATMENT AREA = 100.00' ELEVATIIN OF INFILTRATIVE SURFACE EF SIIL TREATMENT AREA = 97'OO, ASSUMED INVERT ELEVATION DF SEVAGE LINE AT EXIT FRIM SEPTIC TANK = 91.80, INVERT ELEVATIIN !F SEVAGE LINE AT ENTRY T[ SEPTIC TANK = 92,50' 3/4' THREAD TEEPRESSURE MAIN, TYP. SUSPEND PRESSURE LATERAL VITH ALL WEATHER PLASTIC PIPE STRAP VITH 120 LBS TENSILE STRENGTH AT EVERY CHAMBER CONNECTIEN, TYP, 1-1lA' SCHD 40 PVC PRESSURE LATERAL VITH 5/34' HOLES SPACED 48' E.C, DRILL HELES AT 12100 E'CLBCK TE IIIRECT DISCHARGE UP FER DISPERSAL AGAINST TEP OF INFILTRATER lUT AND PRESSURE BALANCING (END EF LATERAL ONLY) 3,/4' THREAD NIPPLE TE SURFACE FER CLEAN PREVIDE MIN. 1/8' FALL PERlE' RUN FIR DRAIN BACK TO =4-# - __+1+_-ttf-+---ti---_ilt-= PRESSURE I.ATERAL CONSTRUCTION DETAIL SCALE: 1"='l ' Effluent Pumping System - 2nd Compartment Drawdown Effluent Pumping System for Cold Weather Applications (cw style) tu *tr Orenco Systems lncorporated Conduit Seol Slope Ground Awoy from Riser PVC Splice Box with Cord Grips lnsuloted Gosketed Lid with Stoinless Steel Bolts @ 814 AIRWAY AVENUE SUTHERUN, OREGON 97479-9012 TELEPHONE: (541) 4s9-444e FACSIMILE: (s41) 45e-2884 EDW_TD-18 Rev. 1 .0 (2/s8) lnspection Access Riser ond Lid (ot ground surfoce) l5'*utY PVC Riser with Grommets (bond to tonk odopter with recommended odhesive) Peo Grovel Bockfill Provide 1/4' Droin Hole Efflueni Dischorge Below Frost Line (2" schd 40) Tonk Adopter (.0 st or bolted) lnlet T Potents # 4,439,323 & 5,492,635 Foreign Potents Pending @ 1997, 0renco Systems, lnc. Tonk Adopter (cost or bolted) Level Control Floot Assembly lnducer Check Volve Voult lnlet Ports Filter Cortridge Effluent Pum (trlooet ersoost t roin Port * Peo Grovel Bockfill Recommended to Help Prevent Frost Heove p ) SEDNTA PREJECT 2255 -CR- 226 ?r27-0?4-00-r3r PUMP VAULT DETAIL FEBRUARY T6, ?O?4 conduit to * Control Ponel (uoaet srnu) high level olorm set to trigger mox. 6" obove pump-on floot level pump-on/pump-off floot differeniiol set to provide dose volume of 100 gollons (4.80' floot differentiol for 1,000 gol. tonk) ONE PIECE, TWO COMPARTMENT, I,OOO GALLON SEPTIC TANK Liouid Level 17 T olorm b,mox l / 4.80 l FLOAT DITAIL not to scole Biotube@ Pumo Voult (uoaer evusz-1819-L) Pump Selection for a Pressurized System - Singte Famity Residence Project SEDOTA -2255 CR 226 / RTFLE, CO 8'1650 Parameters 160Discharge Assembly Size Transport Length Transport Pipe Class Transport Line Size Distributing Valve Model Max Elevation Lift l\4anifold Length Manifold Pipe Class Manifold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter Add-on' Friction Losses Galculations 2.00 300 40 2.00 None 30 21 40 1.00 JO 40 1.50 5132 4 2 None 0 inches feet feet feet inches inches feet inches inches feet feet inches feet 140 120 100 80 60 40 20 PumpData 0 10 20 30 40 50 Net Discharge (Spm) 60 70 80 gpm gpm ool! !oF dooI .c E(tt o (E o? Minimum Flow Rate per Orifice 0.43 Number of Orifices per Zone 80 Total Flow Rate perZone 34.2 Number of Laterals per Zone 8 % Flow Drfferential lsvlast Orifice 0.4 Transport Velocity 3.3 Frictional Head Losses o/o fps Loss through Discharge Loss in Transport Loss through Valve Loss in Manifold Loss in Laterals Loss through Flowmeter 'Add-on' Friction Losses Pipe Volumes 5.9 0.0 3.1 0.0 0.0 0.0 feet feet feet feet feet feet feet 0 Vol of Transport Line 52.3 0.9 5U.5 83.7 gals gals gals gals Vol of Manifold Vol of Laterals per Zone Total Volume Minimum Pump Requirements PF5005 High Head Effluent Pump 50 GPM, 1/2HP 1151230V 1A 60H2,2001230Y 3@ 6AHz PF5007 High Head Effluent Pump 50 GPM, 3/4HP 230V 1@ 60H2,20012301460V 3A 60Hz PF5010 High Head Effluent Pump 50 GPIVI, 1HP 230V 1@ 60Hz'2001460V 30 60Hz PF5015 High Head Effluent Pump 50 GPM, 1-1l2HP 230V 1A 60H2,200V 3g 60Hz Design Flow Rate Total Dynamic Head 34.2 43.4 gpm feet @OreneoSYSTCMS System Curve: - Pump Curve: * PUmp upomal Kange: Operating Point: o Design Point: r Appendix A Soils and Percolation Report K-CROI/I(P.O. Box r4o Mach, CO g7o.2ro.o i4z f l<achayla.cronkqoutloolLrcm Soils and Percolation Report January 3I,2024 Sedota Proiect 2255 -CR- 226 Rifle, CO 81650 P"t..l No. 2127 -024-OO-I3I Prepared By: K-Cronk Engineering, Inc. P.O. Box I40 Mack, CO 81525 970-250-0572 Soils Evaluation The site consists of approximately 43.83 acres of uncultivated native soil. Drainage is approximately3Yoto the south east. A percolationQterc)test/soils evaluation and site study were conducted on the property of reference on 01/3112024 by Kachayla R. Cronk, registered professional engineer (R.P.E.). The perc excavation trench was located approximately 400' south of the north property line and approximately 720' east of the west property line. The perc excavation trench was extended to a depth of 108" below ground surface (BGS). There was no evidence of ground water or high seasonal water table in the open excavation to a depth of 108" BGS. The soils evaluation indicates one distinct soil horizon underlies the site. A lithological description follows. depth (in.) description 0" - 108"highly weathered shale, grey (Soil Type 3, USDA - clay loam, granular, strong structure) Perc holeswere constructed atthe surface andat adepth of approximately 36" . The holes appeared to be well saturated at the time of the test. Results of the percolation test are shown in Table 1. TABLE 1 Percolation Test Results 2255 -CR-226 Depth Time on 0113112024 Time Drop Perc Rate min/in1l:03 ll:12 11:30 ll:45 12:03 0"-72"2.5 2.75 3.312s 3.75 4.125 60/1.625 37 36--48"5 6 6.875 7.5 8 6013 20 -1- Limitations This document is representative of the site conditions disclosed at the specific time of the site investigation. Site conditions are subjectto change from external events both manmade (irrigation or water feature construction) and naturally occurring (flooding or excessive precipitation). K-Cronk Engineering, Inc. is not responsible and accepts no liability for any future variation in site conditions. K-Cronk Engineering, Inc. represents this report has been prepared within the limits prescribed by the owner and in accordance with the current accepted practice of professional engineering in the area. No warranty or representation, either expressed or implied, is included or intended in this report or in any of our contracts. SEAL Kachayl(R. Cronk, P.E. o//J//L1 Date ,| -L-