From: Donald Eggers <don.eggers@eggersarchitecture.com>
Sent Wednesday, April24, 2024 10:53 AM
To: Colleen Wirth; wes.gardner@bridgenetworkcolorado.com
Subject RE: BLRE-04 -24-8593 - Gardner Dynasty Trust - GAZEBQ is now under review
Attachments; ESR-24o1.pdf -$e,e ;*A"J1ed
^^,,(r"voed"stJe ptm - h';ii""-Efecs ;;**1 of-zr-z|
CoIteen,
The Mason-Lite fireptace specified is a pre-manufactured concrete fireptace kit. lt is intended for indoor and /
outdoor use. l've attached the ESR report regarding the unit and its compliance with buitding codes. Here is atso a
tink to their website: https://www.mason-tite.com. I have instatted these units both indoors and outdoors on
muttipte projects and haven't had any issues. They work extremely we[[ outdoors with the potentiaI to weather
exposure because they are a concrete product.
The unit witt be utitized as a wood burning fireplace
Ptease tet me know if you have any additionat questions regarding the fireptace. We are working to get you a
revised site ptan that shows the gazebo footprint at the location shown on the ptan as the "proposed gazebo".
Thanks,
CURRENT SCOPE REVIEWED AS A PRIVATE USE, OPEN AIR GAZEBO ACCESSORY TO THE
MAIN RESIDENCE. ANY FUTURE CHANGE TO BUILDING USE OR OCCUPANCY' SHALL BE
SUBJECT TO A NEW BUILDING PERMIT AND LAND USE CHANGE PERMIT IN ACCORDANCE
WITH ADOPTED CODES AND LAND USE REGULATIONS IN EFFECT AT TIME OF FUTURE
WORK.
970-409-9790
From: Co I leen Wi rth <cwirth @ga rfie ld-co u nty.com>
Sent: Tuesday, April 23,2024 L2:43 PM
To: wes.gardner@bridgenetworkcolorado.com; Donald Eggers <don.eggers@eggersarchitecture.com>
Subject: BLRE-04-24-8593 - Gardner Dynasty Trust - GAZEBO is now under review
BLRE-O4-24-8593 - Gardner Dynasty Trust - GAZEBO
Courtesy Message for Wes Gardner and Don Eggers
I am starting review for the timber frame gazebo project at 9171, Hwy 82 and have a few questions:
Please respond in writing for the permit records:
L l'm viewing a photo copy of C1 (grading & erosion control & site plan). While a "proposed gazebo"
label is found on the plan between the existing leach field and an {presumed) existing irrigation supply
pond, no graphic lines are found showing an actual location of the 22ftby 27 ft structure.
1
REQUESTED CORRECTION: Please remit to the Garfield County Community Development Dept front
desk (2) full size paper copies of an updated SITE PLAN showing the proposed gazebo structure on
it. While a 30 ft = inch scale is provided, we cannot clearly measure proximity to property lines,
water features and other built elements. Receiving such will allow me to finish the zoning review for
the project, thanks!
2. A1.1 main level plan lists a "pre-manufactured fireplace":
2.al Please verify / confirm the proposed manufactured fireplace model is currently tested / listed for
installation outdoors? (we're mildly concerned when placed in an unconditioned, open air'on four sides -
that it be deemed safe from exposure impacts such as corrosion, ignition failure, water moisture freeze
damage during times and periods of non-use.)
2.b) Viewing fireplace details on A1.1, A2.1 and 43.1, l'm unclear if the fireplace is to be fueled by
woodburning solid fuel, natural gas or liquid propane (LP) gas or other? Please confirm.
Questions ltems 2.a and 2.b can be responded to directly via email to Colleen Wirth, Plans Examiner, at
cwi rth @ ga rfi eld-cou ntv.com.
Wes and Don -- Thanks for your help on this next construction phase for Gardner Dynasty Trust. I look
forward to receiving clarification and seeing things move forward.
Best regards,
Colleen Wirth
Building Plans Examiner
Garfield County Community Development
108 8th Street, Suite 40L
(970) 945-1377 extL6LO
cwirth @ga rfie ld-cou ntv.com
2
lcc
EVALUATION
SIRVICE"
ICC-ES Evaluation Report
ESR-2401
Relssued January 2024 This repoft also contains:
- LABC Supplement
SubT'ect to renewal January 2026
ICC-ES Evatuation Repofts are not to be construed as representing aesthetics or any other aftibutes not specifically addressed, nor are they to be construed as an
endorsement of the subject of the report or a recommendation for its use. Therc is no wananty by ICC Evaluation Service, LLC, express or implied, as to any linding or
other matter in this report, or as to any product covercd by the repoft
@2024lCC Evaluation
1.0 EVALUATION SCOPE
Compliance with.the following codes:
t 2018,2015,2012,2009 and 2006 lnternational Buildins Code@ (IBC)
t 2018,2015,2012,2009 and 2006 International Residential Code@ ilRC)
t 2018,2015,2012,2009 and 2006 lnternational Mechanical Code@ (IMC)
t 2018,2015,2012,2009 and 2006 lnternational Fuel Gas Code@ IFGC\
For evaluation for compliance with codes adopted by Los Angeles Department of Building and Safety (LADBS),
see ESR-2401 LABC and LARC Supplement
Properties evaluated:
I Fire resistance
r Seismic resistance
2.0 USES
The Mason-LiterM modular concrete fireplaces, Models MFP-33, MFP-39, MFP-44, MFP-49 and MFP-63
[Burntech Fireplace Solutions Models TFS33, TFS39, TFS44, TFS49 and TFS63 and Capo Fireside Artisan
Series Models AS33, AS39, AS44, AS49 and 4563l, comply with UL 127 and are fireplaces constructed in the
field using prefabricated concrete firebox components with factory-built chimneys. The fireplaces are for use
only with solid wood logs, LPG or natural gas log lighters complying with CSA 8, and decorative gas appliances
complying with ANSI 221.60.
Mason-Lite modular concrete vented gas-fired fireplace models MGFP-39, MGFP-44, and MGFP-49
[Burntech Fireplace Solutions Models_GBVS3g, GBVS44 and GBVS49 and Capo Fireside Artisan Series
Models ASG39, ASG44 and ASG49I comply with ANSI 221.50, and are constructed in the field and vented
with a listed Type B gas vent.
M ^i^"lN! q:i!q!q
llil ^"-:-:jj'"
EVALUATION SUBJECT:
MASON.LITE MODULAR
CONCRETE
FIREPLACES
DIVISION: 10 00 00-
SPECIALTIES
Section: 10 31 00-
Manufactured Fireplaces
REPORT HOLDER:
MASONRY FIREPLACE
INDUSTRIES, LLC
ADDITIONAL LISTEES:
CAPO FIRESIDE
BURNTECH
FIREPLACE
SOLUTIONS
Page 1 of 16
Most Widely Amepl€d and Trustedlcc-Es'
ESR-2401 2of16
Mason-Lite modular concrete gas-fired vent free fireplace models MFP-39VF, MFP-44VF, and MFP49VF
[Burntech Fireplace Solutions Models_VFS3g, VFS44 and VFS49 and Capo Fireside Artisan Series Models
AS-39VF, AS44VF and AS-49VFIcomply with ANSI Z21,91and are constructed in the field.
3.0 DESGRIPTION
3.1 Fireplace Units:
The Mason-LiterM Masonry Fireplace is a modular refractory masonry unit designed for field assembly. The
firebox is constructed using precast, interlocking refractory blocks secured to each other using Mason-Lite
mortar. The system is supplied with all parts necessary for the assembly of a complete masonry firebox unit.
Fiqures 1 and ! illustrate the Mason-Lite system components. For combustible floor installations, the Mason-
Lite system includes a noncombustible raised platform designed to be placed beneath the field-assembled
firebox unit. High-temperature refractory brick, 1lls inches (28.6 mm) thick, is required to line the interior of the
firebox. See Table 1 for Masonry Fireplace lndustries (MFl), Capo Fireside and Burntech Fireplace Solutions
(Burntech) models, fireplace weights and floor areas.
The Mason-LiterM Models MFP-33, MFP-39, MFP44, MFP-49, and MFP-63 are also sold as Burntech
Fireplace Solutions models TFS-33, TFS-39, TFS-44, TFS-49, and TFS-63, respectively. The products are
also sold as Capo Fireside models AS33, AS39, AS44, AS49 and 4563.
3.2 Factory-built Ghimneys:
The wood-burning fireplaces may only be used in conjunction with listed factory-built specific chimney systems.
The MFP-33, MFP-39, MFP-44 (AS33, AS39,_AS44, TFS33, TFS39, TFS44) wood burning fireplaces require
the use of a Desa/FMl DM12 12-inch-diameter (305 mm) chimney or 12- or 14-inch-diameter (305 or 356 mm)
flue system listed by an approved agency as complying with UL103. The MFP-49 (AS49, TFS-49) fireplace
requires a 14-inch-diameter (356 mm) flue system listed by an approved agency as complying with UL103.
The MFP-63 (AS63, TFS63) fireplace requires the use of a Desa/FMl DM16 16-inch-diameter (406 mm) flue
system listed by an approved agency as complying with UL103 and labeled as "ResidentialType and Building
Heating Appliance Chimney". As an alternative, the MFP-63 (A563, TFS63) fireplace may use a dual Desa/FMl
DM1212-inch-diameter (305 mm) flue system. The chimneys are limited to a maximum height of 40 feet (12
192 mm) and a minimum height of 14 feet (4267 mm); except that, where offsets are used, the minimum height
is 17 feet (5181 mm). No more than two offsets are permitted.
3.3 Fireplaces Equipped with a Decorative Gas Appliance:
The fireplace systems described in Section 3.1 may be installed with a decorative gas appliance listed in
accordance with ANSI 221.60, provided the fireplace is terminated with a 1O-inch-diameler (254 mm) listed
Type B gas vent.
3.4 Vented Gas-fired Fireplaces:
Models MGFP-39, MGFP-44, and MGFP49 (GBVS39, GBVS44, GBVS49, ASG39, ASG44 and ASG49),
complying with ANSI 221.50, require the use of a listed 10-inch-diameter (254 mm) Type B gas vent and must
comply with Chapter 8 of the IMC and Chapter 5 of the IFGC. The models must be as specified in the report
holder's Mason-Lite published installation instructions.
3.5 Unvented (Vent Free) Gas-fired Fireplaces:
Unvented (vent free) gas-fired fireplace models MFP-39VF, MFP-44VF and MFP49VF (VFS39, VFS44,
VFS49, AS-39VF, AS-44VF and AS49VF) complying with ANSI 221.91, require the use of an unvented
decorative room heater complying with ANSI 221.11.2. See Table 1A for vent free fireplace weights and floor
areas.
3.6 Grout and Mortar:
The grout and mortar used to construct the fireplace is provided by Masonry Fireplace Industries, LLC.
4.0 DESIGN AND INSTALLATION
4.1 General:
The fireplace units must be installed in accordance with this report, the fireplace report holder's published
installation instructions, and the applicable code. A copy of the report holder's installation instructions must be
available at the jobsite at all times during installation. As applicable, the factory-built chimney or Type B gas
vent installation instructions must also be available at the jobsite at all times during installation.
Most Widely Accepled and Trusledtcc-EsESR-2401 Page 3 of 16
4.2 Design:
When installed in accordance with Section 4.3 of this report and the manufacturer's instructions, the fireplace
units may be installed in Seismic Design Categories A through F. ln Seismic Design Categories C, D, E and
F, the seismic design parameters are limited to the values noted in Table 2. The seismic design must be in
accordance with Sections 13.3, 13.4,13.5 and 13.6 of ASCE 7.
When installed in accordance with Fiqure 10 or Fiqure 11 of this report, the Mason-Lite modular concrete
fireplaces may be anchored to a concrete slab-on-grade, located in Seismic Design Categories A through F,
as determined from the seismic design parameters shown in Table 2 of this report.
When installation is on wood floor construction, the licensed design professional must determine the
requirements for support and anchorage for the combined gravity and seismic loading The applicability of the
seismic design parameters in Table 2 must be verified with due consideration of the flexibility of anchorage
and supports-. ln addition, the calculated long-term deflection of the wood members supporting the fireplace
must noi exceed the values shown in IBC Table 1604.3 for floor members. Under the lRC, an engineered
design must be provided in accordance with IRC Section R301.1'3.
4.3 lnstallation:
The Mason-LiterM masonry fireplace system may be installed directly on concrete slabs and footings or on
combustible floors, subject to the structural design limitations contained within this report. For concrete
foundations, the firebox base must be installed directly to the foundation. For combustible supporting systems,
instattation of a 1-inchthick (25.4 mm) ceramicfiber-board,6-inch-high (152 mm) or8.S-inch-high (216 mm)
(for MFP-63, A563, TFS63) metal support base and 1/z-inch-thick (12.7 mm) cement board is required before
placement of the firebox hearth components. The precast components are assembled following the Mason-
Lite published instructions and using ihe mortar described in Section 3.5. Minimum No. 4 reinforcing bar or1lz-
inch-diameter (12.7 mm) all-thread bar must be installed, and the cells of the precast components are grouted
with Mason-Lite grout. Anchorage of the fireplace unit to the foundation or supporting floor must be as
described in Section 4.2.
After completion of the construction of the lower firebox components, the precast lintel and firebox dome
components are installed. The chimney anchor plate must then be attached to the firebox dome as shown in
Fiquie 4. With the exception of the unvented (vent free) gas-fired fireplaces, once the installation of the chimney
anc,nor ptate is completed, the listed prefabricated chimney flue pipe or listed Type B gas vent must be installed.
See Fiqures 5, Q and 7..The clearances to combustibles must comply with Table 4 or Table 5. lnstallation of
tfre cnimsey or gas vent must be in accordance with the chimney or gas vent listing, the chimney or gas vent
report holder's instructions and the applicable code.
Firebrick lining having a minimum thickness of 11le inches (29 mm) and complying with ASTM C1261 must
be installed along with any required hearth extensions as shown in FiOure 8.
Combustion air must be provided in accordance with IBC Section 2111.14,1RC Section R1006.1, IRC Section
G2407 or IFGC Section 304, as applicable, and the report holder's published installation instructlons.
The wood-burning fireplace models specified in Table 7 may be installed with glass doors. Wood-burning
fireplace Models Mfp-Og, TFS-63 and 4563 are not recognized for use with doors. The vented gas-fired
fireplaces described in Section 3.4 may be installed with a Crown-Breckinridge glass door or a McKenzie-
Pendelton glass door. The unvented (vent free) gas-fired fireplaces described in Section 3.5 are not recognized
for use with doors.
5.0 CONDITIONS OF USE:
The Mason-Lite modular concrete fireplaces described in this report comply with, or are suitable alternatives to
what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions:
b.1 The fireplaces must be installed in accordance with this report and the report holder's published installation
instructions. ln the event of a conflict between this report and the report holder's instructions, the more
restrictive governs.
5.2 The fireplace units must be installed by contractors approved by Masonry Fireplace lndustries, LLC.
5.3 When installation is over framed floor construction, the supporting structure and the anchorage of the
fireplace unit to the supporting structure must be designed for all applicable loads, including gravity, wind
and earthquake loading, and must include applicable load combinations in accordance with IBC Section
1605. The weights of the various components and the footprint of the installed unit are included in Table 1.
Mosl Widely Accepted and Tustedtcc-ES'
ESR-2401 Page 4 of 16
The structural design and calculations must be prepared by a registered design professional and must be
provided to the code official for approval.
5.4 When installation is over a slab-on-grade concrete foundation, the installation nrust be as shown in
Figure 10 or Fiqure 11 of this report.
5.5 For fireplaces recognized for use with glass doors, see Section 4.3 and Table 7.
5.6 Compliance with the fireplace air leakage provisions found in 2018 and 2015 lnternational Energy
Conseruation Code@ (IECC) Section R402.4.2, 2012 IECC Section R4024.2 and Table R402/.1.1 , 2018
and 2015lRC Section N1102.4.2,2012|RC Section N1102.4.2 and Table N1102.4.1.1,20091ECC Section
402.4.3 and 2009 IRC Section N1 102.4.3 are outside the scope of this report.
5.7 Under the 2018 lRC, 2018 IMC and 2018 IFGC, where factory-built chimneys pass through insulated
assemblies, an insulation shield complying with 2018 IRC Section R1005.8, 2018 IMC Section 805.7 or
2018 IFGC Section 503.5.11, as applicable, must be installed.
5.8 The fireplace units are manufactured in Riverside, California, under a quality-control program with
inspections by ICC Evaluation Service, LLC.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria for Field-constructed Fireplace Systems
Using Prefabricated Blocks (AC375), dated February 2012 (editorially revised August 2019).
7.0 IDENTIFICATION
7.1 The components of the fireplace units, including mortar and grout, are supplied to the jobsite on a factory-
assembled, shrink-wrapped pallet bearing a labelwith the company name (Masonry Fireplace lndustries,
LLC; Capo Fireside; or Burntech Fireplace Solutions) and address; the product name; the address of the
manufacturing plant; and the evaluation report number (ESR-2401). A permanent label must be attached to
the installed fireplace by the contractor, identifying the report holder's or additional listee's name; the product
name; the manufacturing location; the date of manufacture and the serial number; the clearances to
combustibles; other information required by UL 127; and the evaluation report number (ESR-2401).
7.2 fhe report holder's contact information is the following:
MASONRY FIREPLACE INDUSTRIES, LLC
639{ JURUPA AVENUE
RIVERSIDE, CALIFORNIA 92504
(800) 345-7078
vnruw.masonJite.com
7.3 The Additional Listees' contact information is the following:
BURNTECH FIREPLACE SOLUTIONS
6250 PLATT AVENUE, NO. 577
WEST HILLS, CALIFORNIA 91307
vnrw.burntech.com
CAPO FIRESIDE
26401 VIA DE ANZA
SAN JUAN CAPISTRANO, CALIFORNIA 92675
(949) 364-5118
www.capofireside.com
MbslWdblyacceptedrciC-ESESR-2401 5of16
TABLE T_MASON.LITE FIREPLACE WEIGHTS AI{D FLOOR AREA
For Sl: 1 lb = 4.45N, 1 in. = 25.4 mm' 1 lb/lineal ft. = 0.0146 N/mm, 1 ft2 = 0 092 m m2
rMFp, AS and TFS designaies fireplace used with a UL 103 complying listed factory-built chimney. MGFP, ASG and GBVS designates fireplace used
with a listed Type B gas vent.
2AS49 fireplace requires the use of a 12-inch-diameter listed flue system. The MFP-63, ,4563 and TFS63 fireplaces require the use of a dual 12-inch-
diameter flue system or a single 16-inch-diameter flue system'
TABLE IA-MASON-LITE VENT FREE FIREPLACE TIUEIGHTS AND FLOORAREA
MFI MODEL MFP-3gVF MFP-44VF MFP-49VF
CAPO FIRESIDE MODEL ASVF.39 ASVF.44 ASVF49
BURNTECH vFs39 vFs44 VFS49
Fireplace 809 896 987
Mortar, Rebar & Ready Mix Concrete Weight (lbs)350 357 364
Firebrick Lini 333 345 356
Floor Area 43 in. x 28 in. (8. 12 ft2)48in.x28 in. (9,33fi2)53 in. x 28 in. ('10.33 ft2)
For Sl: 1 lb = 4,45 N, 1 in. = 25.4 mm, 1 ft2 = 0.092 mm2
TABLE 2-SEISIIIIC DESIGN PARAIWETERS
TABLE 3-DEFLECTION LIINTS
MFI MODEL MFP-33 MFP-39 MGFP-39 MFP-rl4 [/tGFP-44 MFP-49 MGFP-49 MFP.63
CAPO FIRESIDE MODEL AS33 AS39 ASG39 AS44 ASG44 AS49 ASG49 AS63
BURNTECH TFS33 TFS39 GBVS39 TFS44 GBVS44 TFS49 GBVS49 TFS63
Fireplace Weight (lbs)1.167 1,260 1,460 1,331 1.580 1,462 1,680 2,225
Damper/Anchor Plate,
Firebrick, Grout & Mortar
Weisht (lbs)
350 380 380 430 430 480 480 s50
Sieel Platform Weight
(tbs)51 61 61 65 65 80 80 90
Maximum Chimney
Weight
(lbs/lineal ft)
10 10 10 10 10 12 12 15
Chimney or Vent Size-|.D.
(inches)12 12 10 12 10 142 10 162
Floor Area 37 i^. x28
in. (7.2ft2)
42i^. x28 in.
@.12ft2)
48 in. x 28 in.
(9.33 ft2)
53 in. x 28 in
(10.30 ftr)
67 in. X 28 in.
(13.03 ft2)
VALUEPARAMETER
1.0factor, ap
1.smodification factor
0theofandtoatattachofmentstructuretnpointfireplacewithzlhumwherefactor:isz respect gradetheMaximheight
basethe elevationstructuofwithretothersroofrespectaverageheight
0.1 6period of the Tp
1.25response acceleration parameter, SDsum
CONSTRUCTION L S orW D +Lr
Floor members t/360 |/240
lFor wood structural members having a moisture content of less than 1 6 percent ai time of i
resultlng from L + O.5D is permitted to be substituied forthe deflection resulting from L + D
nstallation and used under dry conditions, the deflection
(Note: contents of this table are from IBC Table 1604.3).
ESR-2401 Fage 6 ol 16
mC'i:"(
TABLE4-[dNlll[u M CLEAMNC E TO COUBU STIE LES FO R
ilrFn TFSAND MM SERESnTOOD-FIRED
FIRFPI ACE SYSTF[&$ (inchee]
For Sl: 1 inch=25,4.mrn.
TAF$.g 5-TfiI'IiltJT CLEAR,ANCE TO COffiT'S"FL€5 F€R
trGFP,. ESg AND GBVS SERB SAS.FEEE
FIREPLACE SYSTEIF (inchesi
ForSI; 1 ihch=25.4 mm.
'rTop of lbuver openihg to ceiling.
23'inch wids nrarile.
TAELE 5-MilMUil[ CLEARANCE TO COilIETISTIELES FE'R
E[FP.VF", VFS.AIIITI AS-VF SERIES GAS-FTRED VE!6T FREE
flAEPtACE $YSTEiS {*ele}
For 3*: 1r ir',cH5.4 nr,r+r.
1 Maxjmum. mantla projaction.
TABLF ?..&&E}€[IRISIilI6 FIREPLACFS F$R {LS€ UTTSH GT.AS,S trCIAEst.
ForSl: 1 inch=25.4 mm.
Uhit front, sides, rear:2
Combustibie. Hoor {MFP-33 through nfFFAS)]o'
Combusiible Sheathing above opening tocp:.ta
gombustibie Floor (MFP-53):I
Sl'reatt{ing or trim to opening sides:I
Mantle above opening 12
Opening to sidewall:24
Hear'i.h'extension beyond f!:ont:t.
Head,h, exlansion heyond sida>-+t
lnsulation from firebox:2
Back/Side(s)0
Top 0
Vent '1
Frontl 46
Pe{pendicular Wa}{s q
l-loor 0
Ceiling 24
Mantle2 ?
Back/Side(s)0
Top 0
Combustible Floor
Opening to sidewall 3
Opening to ceiling
Opening to mantle (0 to 10 inches)Nbnel
Openingio mantle (>10 to 15 inches).1v;1
Opmringtn mantle (>16 to tB indres):31
,3pening, ?.o. rnantle (>1 8 to ?1 incheqi
npenin8trrr,nantle (>18 to ?? in6he-t 8.1
Opening,to mantle (>22 inct"ss.\.!a.1
rrason-
LFeffi
Fire*hce
ffi
r$ason-
Li{effi
Glass Door
ffi
Burntech
Firep*ace ffiode}
8urfiscft Glass
SoorlH*!
Capo FlresidB
Fireplace lf;a#}
gapo Firesidts
Ca$assEoorModgi
€iass
PdrEt
iltfritft
{incjtl
Orerali'gFass
hErUaidUE
(htclrl
gfass
DqoF
ireigkf
(ihah):
rutFP-3C,MFP-3S.4D,TE€iI "IF. S-33-6tr AS33 AS33^6,F 1.4%29 Ya ttl
li[FF-34'M,FP.3S-GD,TtrA€TFSAA,GD AS3S A,S-39-GD,1,7, th 34%?8,
MF.F.44 |I,TFF-44-GD r lo44 T:F5'44:GD AS44 AO-4S-UU t3 71 Ja /2 28
MFF49,MFP-4g-GD TFS49 TFS.49-GD AS49 AS-49-GD 22%.44%28
iThe v.enteid gss-fired.firepltzces d'€scriffi in ser:tiien 3',4 m€lr-be installed with a Crown-Eteckinridge giass dborora McKefae-Puireieibn gt{irsc dooc
Mosl Widely Accepted and Trustedtcc-E$ESR-2401 Page 5 of '16
TABLE 1-MASON-LITE FIREPLACE WEIGHTS AND FLOOR AREA1
For Sl: 1 lb = 4.45 N, 1 in. = 25.4 mm, 1 lb/lineal ft. = 0.0146 N/mm, 1 ft2 = 0 092 mm2.
1MFp, AS and TFS designates fireplace used with a UL 103 complying listed factory-built chimney. MGFP, ASG and GBVS designates fireplace used
with a listed Type B gas vent.
2AS49 fireplace requires the use of a 12-inch-diameter listed flue system. The MFP-63, A563 and TFS63 fireplaces require the use of a dual 12-inch-
diameter flue system or a single 1G-inch-diameter flue system.
TABLE 1A_MASON.LITE VENT FREE FIREPLACE WEIGHTS AND FLOOR AREA
MFI MODEL MFP-39VF MFP44VF MFP.49VF
CAPO FIRESIDE MODEL ASVF-39 ASVF-44 ASVF49
BURNTECH vFs39 VFS44 VFS49
Fireplace Weight (lbs)809 896 987
Mortar, Rebar & Ready Mix Concrete Weight (lbs)350 357 364
Firebrick Lining Weight (lbs)345 356
Floor Area 43in.x28 in. (8.12 ft2)48 in. x28 in. (9.33 ft2)53 in. x 28 in. (10.33 ft2)
For Sl: 1 lb = 4.45 N, 1 in. = 25.4 mm, 1 ft2 = 0.092 mm2
TABLE 2-SEISMIC DESIGN PARAMETERS
TABLE 3-DEFLECTION LIMITS
MFI MODEL MFP-33 MFP-39 MGFP.39 MFP44 MGFP.44 MFP-49 MGFP-49 MFP-63
CAPO FIRESIDE MODEL AS33 AS39 ASG39 AS44 ASGrt4 AS49 ASG49 AS63
BURNTECH TFS33 TFS39 GBVS39 TFS44 GBVS44 TF549 GBVS49 TFS63
Fireplace Weight (lbs)1,167 1,260 1,460 1,331 1,580 1,462 1,680 2,225
Damper/Anchor Plate,
Firebrick, Grout & Mortar
Weisht (lbs)
350 380 380 430 430 480 480 550
Steel Platform Weight
(lbs)51 61 61 65 65 80 80 90
Maximum Chimney
Weight
(lbs/lineal ft)
10 10 10 10 10 12 12 15
Chimney or Vent Size-l.D
(inches)12 12 10 12 10 142 10 162
Floor Area 37 in. x 28
in. (7.2 ft2)
42in.x28 in
(8.12ftz)
48 in. x 28 in
(9.33 ft2)
53 in. x 28 in.
(1 0.30 ft2)
67 in. X 28 in
(1 3.03 ftr)
PARAMETER VALUE
Amplification factor, ap 1.0
Component response modification factor, Rp.1.5
N/laximum zth faclot; where z is the height in structure with respect to grade at point of attachment of the fireplace and
h is the average roof height of structure with respect to the base elevation
0
Fundamental period of the fireplace, Tp 0.16
lvlaximum Spectral response acceleration parameter, So"1.25
CONSTRUCTION L S orW D +Lr
Floor members l/360 u240
lFor wood structural members having a moisture content of less than 16 percent at time of installation and used under dry conditions, the deflection
resulting from L + O.5D is permitted to be substituted for the deflection resulting from L + D. (Note: contents of this table are from IBC Table 1604.3)
Most Wldely Accepted and Trustedtcc-Es'
ESR-2401 Page 6 of 16
TABLE 4_MINIMUM CLEARANCE TO COMBUSTIBLES FOR
MFP, TFS AND MM SERIES WOOD.FIRED
FIREPLACE SYSTEMS (inches)
ForSl: 1 inch=25.4 mm
TABLE s-MINIMUM CLEARANCE TO COMBUSTIBLES FOR
MGFP, ASG AND GBVS SERIES GAS-FIRED
FIREPLACE SYSTEMS (inches)
ForSl: 1 inch=25.4 mm.
rTop of louver opening io ceiling.
23-inch wide mantle.
TABLE 6-MINIMUM CLEARANCE TO COMBUSTIBLES FOR
MFP-VF, VFS AND AS.VF SERIES GAS-FIRED VENT FREE
FIREPLAGE SYSTEMS (inches)
ForSl: 1 inch=25.4 mm.
lMaximum mantle projection.
TABLE 7-WOOD-BURNING FIREPLACES FOR USE wlTH GLASS DOORSI
For 1 inch=25.4 mm
Unit front, sides, rear:2
Combustible Floor (MFP-33 through MFP-49):6
Combustible Sheathing above opening top:18
Combustible Floor (MFP-63):a
Sheathing or trim to opening sides:8
Mantle above opening 12
Opening to sidewall:24
Hearth extension beyond front:20
Hearth e)dension beyond sides:12
lnsulation from fi rebox:2
BacUSide(s)0
Top 0
Vent 1
Frontl 48
Perpendrcular Walls 8
Floor 0
Ceiling 24
Mantle2 a
BacUSide(s)0
Top 0
Combustible Floor U
Opening to sidewall J
Opening to ceiling 42
Opening to mantle (0 to 10 inches)None 1
Opening to mantle (>10 to 16 inches)1Y"1
Opening to mantle (>16 to 18 inches)31
Opening to mantle (>18 to 20 inches)61
Opening to mantle (>18 to 22 inches)g1
Opening to mantle (>22 inches)101
Mason-
LiterM
Fireplace
Model
Mason-
LiterM
Glass Door
Model
Burntoch
Fireplace Model
Burntech Glass
Door Model
Capo Fireside
Fireplace Model
Capo Fireside
Glass Door Model
Glass
Panel
width
(inch)
Overall Glass
Door Width
(lnch)
Glass
Door
height
(inch)
MFP-33 MFP-33-GD TFS33 TFS-33-GD AS33 AS-33-GD 14%29%20
MFP-39 MFP-39-GD TFS39 TFS-39-GD AS39 AS-39-GD 17%34%28
Mt-P-44 MFP-44-GL)I FS44 tFs-44-GlJ AS44 AS-44-Gu 19%39%28
MFP.49 MFP-49.GD TFS49 TFS-49-GD AS49 AS-49-GD 22%44%28
lThe vented gas-fired fireplaces described in Section 3.4 may be installed with a Crown-Breckinridge glass doorora McKenzie-Pendelton glass door
Most Widely Accepted and iustedtcc-E$
ESR-2401 Page 7 of 16
Optional Outside 04"
Gombustion Air Kit
Model No.: MFP4-AK
MFPXXSHBL- Herringbone
MFPXXFRBL- Running Bond
FIREPLACE PARTS DIAGRAM
MODELS MFP33/39144149
Note: See MFI installation instructions for a complete description of the items shown.
@
&
il
/
FOR
COMBUSTIBLE
FLOORS
FIGURE 6 //
FIGURE 1
Most Wldely Acepted and Trustedtcc-Es'
ESR-2401 Page 8 of 16
Optional Outside 04"
Combustion Air Kit
Model No.: MFP4-AK
MFP63SHBL- Herringbone
MFP63FRBL- Running Bond
FIREPLACE PARTS DIAGRAM
MODEL MFP63
Note: See MFI installation instructions for a complete description of the items shown
,4L/
W
fr)
n
il
il
u
\
FIGURE 2
tcc-Es'
ESR-2401 Page 9 of 16
Most Widely Accepted and lrusted
trtoDEls tFP,63, 4563, TFS63
see Page 16 thru 18 for coltfiustible
floor and ffamin0 mcfiorim
illustralioats.
@
FIGURE 2 (Continued)
MFP33/39/44149 MFP63
Combustible Floo. Systems Non-combustlble Floor Systems
FIGURE 3_MASON-LITE ASSEMBLED FIREPLACE COMPONENTS
ESR-2401 Page 10 of tG
Most Wrdery Aoceptod and lrustddtcc-Es
Place 1" Oeramic Fiber
Blanket under Anchor
Plate and secure wlth
1/4{noh masonry
anchors.
FIGURE 4
Most Wldely Acepted and TrustedtGc-Es"
ESR-2401 Page 11 of 16
CLASS'A'
CHIMNEY
Firestop Spacer with Living Space
Above Ceiling
Existing
iling
Frame
Firestop
Spacer
eight #8 x
3/4 screws
FIGURE 6
Firestop Spacer with Attic Space
Above Geiling
eight #8 x 3/4
screwsNOTE:
NON-COMBUSTIBLE
ONLY WITHIN 18" OF
TOP OF OPENING
FIRESTOP
SPACER
1" THICK
CERAMIC FIBER
ANCHOR
PLATE
2"AIRSPACE
CLEARANCE TO
COMBUSTIBLES
ON REARAND
SIDES OF UNIT.
6" METAL
PLATFORM
Firestop
Spacer
Existing
Ceiling
Frame
{
o(O
FIGURE 7
1I2"THrcK
CONCRETE
BOARD
t{
d!\o
FIGURE 5
ESR-2401 Page 12 of 1.6
MostWdely Accepled and trusledtcc-Es'
MIN. FROM
REARAND
SIDES TO
COMBUSTIBLES
2
=
MIN
FIGURE 8
MAINTAIN THE 2" CLEARANCE
TO COMBUSTIBLESABOVE
THE DOME. DO NOTATTACH
COMBUSTIBLE MATERIALS
ON TOP OF THE DOME.
18" MIN*
8'MIN*
NON-COMBUSTIBLE
FACING (NOT SUPPLIED).
Condltlon Dlm. "H"**
with 6" platform 't0"
with S" platform 12"
without platform 3"
. MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS.. MEASUREtr FRCIM FLOOR TO T'JP '9F FIREBRICK LINER.
6
n
NON-COMBUSTIBLE
FACING MATERIAL
HEARTH EXTENSION
0P
8"
l'-0'
MIN MIN
FIGURE 9
STRUCTURAL NOTES
DLSCREPANCES SHALL FE tsROUGHT TQ IHE IMMEDIAIE ATEI]IIOI] OF THE
CANTRACTOR FgF CARRECTION; frErJ rF riOT coRReCtED, TO THE ENGINEER ANO
BUILD NC DEPARTMENT.
SPE.C.IAI*IN,AEFC]LAN__EFAuIEEL
.ANCHORS, AIJCHOR BOLTS, & ryELS
1. VERFY MAI]UF'ACTURERS IJSTALLATIOIi PEQUIREN1EIJTS (AIID TESTNG) OF EPAXIED
DOWELS [! CONCRETE AT (HOLDO\'ffS) (EXTST[]G FOOTTNGS) (CONCRETE REPATRS).
SOIL SUPPORTII]G FOONNGS IS TIATIVE SOL.
SOIL ALLOWABLE BEARINC PRESSUPE USED IIJ DESIGTJ IS 15OO PSF-
RE]I]FORCNG STEEL StsALL AOI]EARM TO ASTM 615, GRADE 50.
]'hREADEO RODS StsALL COI!FORtr4 TO ASru F 1554, GRADE 36.
ALL NlATERIALS AI{D WORKMAI!SHIP SHALL COIIFORM ]O THE REOUIREMEIJTS OF
GE 2OO9 AIJD 2O12 IIJERINATIOIiAL BUILDIIJG CODE & ].OCAL CITY OR COUIIT/ REOUIRE\1EI]8.
SPECIAL IIJSPECTIOIJ
1. SPECIAL IIJSPECTIOIJ SHALL MEET THE REOUIRENIENIS OF THE 2OO9 AIID 2012 IBC.
2- S6ECIAL JNSPECTOPS SLALL'
A) BE UNDEF THE SUPERVLS]ON OF A REGiSTERED DES]GIJ PRQFESSIOI]AL.
B) OBSERVE THE WORK ASSIGNED FOR CONFORMANCE WTII THE APPROVEO DRAWINGS
Aritr SPECIFTGAT Or!S.
C) FURNISH INSPECTION REPORTS TO THE ENG]NEER AtlD BUILDIIJG OEPARru€IiT.
D) SUSTJII IO THE EIJGIIiEER Ai]D BUII-DIIJG DEPAPIMENT A FIIJAL REPORT, SIGi]ED AY
A RECISTERED DESIGTJ PROFESSIOIiAL, STATIiJG TtsAI TE WORK WAS I[J
CANFAFMAIiCE W!fr THE APPRQVED DRAWIIG5 AND SPECIF]CATIONS AIJD THE
APPLICABLE WORKMAIJSh P FROVIS]QIN5 AF THE ZODg IBC.
INSPECTION IJOTES:
a) coNsiRucTroN msPECTrouS LTSTED ARE tN aDDrnoN ro THE CALLED NSPECIONS
RECU REO B\' BE 2OO9 JNERNATIONAL AUILDII{G CODE. SPEC]AL ]I]SPECI AN IS NOT
A SUBSTITU'E FOR TiSPECTIOI{ EY'A BUlLDING OFFICIAL. SPECIALLY II]SPEATED I{ORK
WHICH IS ]IISTALLED OR COVERED WfrOUT APPPOVAL OF THE BU LDING OFF]CIAL IS
SUBJTCT TO REMOVAL OR SXPOSURT.
B) CQNTINUOUS II]SPTCT]OII I5 ALWA6 REAU|RED DURII]G PERFORIiANCE OF frE
WARK UNLESS SPECIFCALLY IiOED.
c) spEctaL tNsFEcroRS MUST Be CERT|FTED Bl rHE BUil-DNc DEFARTMefJa To
PERFORM THE TYPES OF IIJSPECTIOI{S SPECIFIED.
D) rr ts THE RfsPor]slBr|fY oF rHE owlER Tc mFoRM THE SPEC|AL IilSPECTOP OP
NSPECTION AGEI]CY AT LEAST ONE IVORKIITG DAY BEFORE PERFORM]NG At]'/ WORK
NAA P€CU]RES SPECIAL II]SPECTIOI] ALL WORK PERFORMEO WTHOLIT FEOIJIRED
SPECIAL IIJSPEQTIQIJ IS SL'AJECT TQ FEMOVAL.
r.)
2.)
3,)
4.)
5.)
?"h'ffi@/! Er 9Eru TEroKd6ffi'a sT-F'iccrffi-tmrlEN,@ffid{ffirflF@
G)d
l,lAS('Irl.LITE INDOO]I FITIE PLAGE
trtsAN.LE
?,?r'rc @s. EA SOE
srss F-f 16!EK-rur'ilN.W9&ANwCT6Ed,
2ri're @D A9. A 9r
ffi9 S,F aECr*.?5D} '"
tsN B€fidAffiddM9.
5'MN.$€*-\
i
FRONT VIEW TLEVATION (FIG, 1)
2-l!'W @ lt^S, gE
FLL'Effid0ffi'0F-re(@.ER-M)r'frffiOaEd4[@td@.F6Frotr]M.L]E
-GJ5'MN. +A
/^*
PLAN VIEW (FiG, 3)
n
EASTILLI]
EN6INEgRING
FI
U'nIN5o
PROJECT:
aJ
JI 0
I
UFFE
ful
$lfiH
il>>
sls it_,__illo_or
3
sr
3
q
E.
oct
Im
vr.
TITLE
INDOOR
FIREPLACE
!!l
GIo
C'
o
CD
FIGURE 1O-MASON-LITE INSTALLATION DETAILS-20I2,2009 AND 2006 IBC AND IRC
ffiffiirrx.lffiaffiNffid4@ro r ffi arM)FSF rffit@iftT isnt,
STRUETURAL NOTES
q TEEffiMGEffiEIWreru@4ffidffiATlffGffiil'ffiffiNffiuT@@HrcmruwffisffiEqreruffittlgDlry
ffi4m
ru@6j@
I. NE4'mmMEEffi4z 4ffiffire@i*mB$*.a ffigEruffirc[ilFEreea. n@ErudwTomFg,ruii uu1Erupwruffitffiffic
ArenH&a ffiE*lErwresimDEe,,smES@ flarfiffiiloffiffi!,m ffi 6MA
ffiffiffiryArufmo#&!ruYffiEffircEruqre'1!ffMf,CEffiffiEffiEWA6ffi.I.ffiffiEA$EffiqffffitrffiffilJBffit@
G M*FISffi$EGrcWETMEffiFffiffifficffi@
t. ruffiruErEffirs&ffiGla$E2tErurelEroi-tJEffit.ffirG@mMr.ffiflffiffiuwffiEffiEruBNFffi.CffiffiH[EEffiADgUEffilEt.ffiBruEFffiroffiretrEAl]ExnGEffimffi;1€lFgffi,rcEffiSutmffiq ffiDEffiBAD4urerffiAruffi.*DryAruEilEGIEMffiSAilgBTEMWf,ffiffiffiffiM8mffi&EE
ffiffiPffiSffiAlCFAlt
MASON+ITE INDOOR FI REPI.ACE
ilTHEsil
F@
rffia4
lt-Nrcru4ffiJiEsF16lm4
aam4GEIIM
@ry?R5g.ffiS
/C\urExmf1/--
IEaftt
a
I
illllll
DCAtmFm
1&|flAE|ff*g,aEr(5r4ss
DC I*E
uE 1ffildtl ld
ffiru
NO1ES&DETALS
lETre
s1.0
FMre
,lot
f,tUIdtiilel
8la
ztE
Hl9
=t:
313dlI<lE
=l>
g
s
6t6tu
tI
FIGURE 11-IMASON.LITE INSTALLATION DETAILS 2018 AND 2015 IBC
AND IRC
m
@vIN5o
3
=
g
o
ct
c':l
Im
v2
!o
GIo
5
o
'6)
H l0c
IVi\I UATION
stRVl0t"
ICC-ES Evaluation Report ESR-2401 LABG and LARG Supplement
ReissuedJanuary 2024
This report is subject to renewal January 2026.
www.icc-es.ors | (800) 423-6587 | (562) 699-0543 A Subsidiary of the lnternational Code Council@
DIVISION: 10 00 OO-SPECIALTIES
Section: 10 31 O0-Manufactured Fireplaces
REPORT HOLDER:
MASONRY FIREPLACE INDUSTRIES, LLC
EVALUATION SUBJECT:
MASON-LITE MODULAR CONGRETE FIREPLACES
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that the Mason-Lite Modular Concrete Fireplaces described in
ICC-ES evaluation report ESR-2401, have also been evaluated for compliance with the codes noted below as adopted by the
Los Angeles Department of Building and Safety (LADBS).
Applicable code editions:
. 2020 City of Los Angeles Building Code (LABC)
. 2O2O City of Los Angeles Residential Code (LARC)
2.0 CONCLUSIONS
The Mason-Lite Modular Concrete Fireplaces, described in Sections 2.0 through 7.0 of the evaluation report
ESR-2401 , comply with LABC Chapters 1 3 and 28 and LARC Section Rl 004 (with the exception of LARC Section R1 004. 1 .1 ),
and are subjected to the conditions of use described in this supplement.
3.0 CONDITIONS OF USE
The Mason-Lite Modular Concrete Fireplaces, described in this evaluation report supplement must comply with all of the
following conditions:
. All applicable sections in the evaluation report ESR-2401.
. The design, installation, conditions of use and identification are in accordance with the 2018 lnternational Building Code@
(lBC) and 2018 lnternational Residential Code@ (lRC) provisions noted in the evaluation report
ESR-2401.
. The design, installation and inspection are in accordance with additional requirements of LABC Chapters 16 and '17, as
applicable.
. The Mason-Lite Modular Concrete Fireplaces are not approved for use with solid wood logs.
. The Mason-Lite Modular Concrete Fireplaces, vented gas-fired, comply with ANSI 221.50, and are constructed in the field
and vented with a 10-inch diameter listed Type B gas vent as described in the evaluation report ESR-2401.
. The Mason-Lite Modular Concrete Fireplaces, when installed with a decorative gas appliance listed in accordance with
ANSI 221.60, shall be terminated with a 10-inch diameter listed Type B gas vent as described in the evaluation report $ft
2401.
. The Mason-Lite Modular Concrete Fireplaces, unvented gas-fired, comply with ANSI 221 .91 and are constructed in the field
with an unvented decorative room heater complying with ANSI 221 .11.2 as described in the evaluation report
ESR-2401.
o When installed with doors, the Mason-Lite Modular Concrete Fireplaces must be installed with the doors specified in the
evaluation report ESR-2401, and when required by the California Energy Code (CEC), the combustible air intake specified
in the evaluation report ESR-2401.
ICC-ES Evqlwtion Reports qre not to be constmed os representing aesthetics or any olher attribules nol specifically addressed, nor qre they lo be conslmed
as an endorsement ofthe subiect of the report or a recommendation for ils use. There is no warranly by ICC Evaluation Sevice, LLC, exprcss or implied, as
to anyfinding or other mql,er in lhis report, or as to any producl covered by lhe report.
SS -$lre-;FFJ':m,*:
Copyright@2024 ICC Evaluation Service, LLC. All rights reserved.Page15of16
ESR-2401 LABC and LARG Supplement I Most Widelv and Trusted Paqe l6 ofJ6.
. The exterior air supply system to the fireplaces must comply with the requirements noted in 2020 LABC Section 2111.14.1
or 2020 LARC Section R1006, as applicable.
r The installation of the Mason-Lite Modular Concrete Fireplaces is limited to hase floor and seismic parameters noted in
Table 2 of the evaluation report $ft]!Q!.
. Use of the Mason-Lite Modular Concrete Fireplaces, when subject to the 2020 Los Angeles City Green Building Code, must
conform to the applicable section of 4.503.1 or 5.503.1 that requires the installation of a direct vent or sealed combustion
chamber.
. The Mason-Lite Modular Concrete Fireplace installations in new or existing construction must conform to the provisions of
South Coast Air Quality Management District Rule 445.
. The Mason-Lite Modular Concrete Fireplaces must be installed in accordance with the manufacturer's published installation
instructions, lhe202Q LABC or2020 LARC, and the evaluation report ESR-2401 . A copy of the manufacturer's published
installation instructions must be available at the jobsite.
This supplement expires concurrently with the evaluation report, reissued January 2024.