HomeMy WebLinkAboutEngineer's Design PlanHuddleston-Berry Engineering & Testing, LLC Monico Murillo 250 County Road 127 #2 Glenwood Springs, Colorado 81601 2789 Riverside Parkrval' Crand Junction. Colorado 8 1 50 I Phone: 970-255-8005 Inlo@huddlestonberry.com September 26,2023 Project#0263 I -000 I Subject: Reference OWTS Design Parcel 212728100386 Garfi eld County, Colorado Geotechnical Investigation, Parcel 212728100386, Garfield County, Colorado by Huddleston-Berry Engineering & Testing, LLC for Monico Murillo, May 2,2023. Dear Mr. Murillo, At your request, Huddleston-Berry Engineering & Testing, LLC completed design of an Onsite Wastewater Treatment System (OWTS) for a single-family residence at Parcel 212728100386 in Garfield County, Colorado. The site location is shown on Figure I - Site Location Map. A site plan is included as Figure 2. Site Description At the time of the investigation, an existing barn occupied the eastern portion of the investigated area. The remainder of the site was open and sloping down towards the west. Site topography is shown on Figure 2. Vegetation consisted of weeds, grasses, brush, bushes, and trees. The site was bordered to the north, south, west, and east by large vacant parcels. Subsu rface Investiqation As discussed in the referenced report, the subsurface conditions at the site were fairly consistent. Based upon visual-tactile soil classification methods, the soil profile consisted of 1.0 to 1.5 feet of topsoil above tan to brown, moist, loose to dense sandy loam soils to the bottoms of the excavations. A large boulder was encoLlntered at a depth of 6.0 feet in TP-3. Groundwater was not encountered at the time of the investigation. The locations of the test pits are shown on Figure 2. Copies of the test pit logs are included in Appendix A. Onsite Wastewater Treatment System In order to evaluate the site soils for onsite wastewater treatment, percolation testing was conducted at the site in accordance with Garfield County regulations. The percolation rate in the native soils ranged from 9 to 30 minutes-per-inch. The percolation testing data are included in Appendix B. Parcel 21278100386 #0263 l -000 r 09t26/23 Illddleston-Berry Engin.ctug&Icsin8, LLC In accordance with Garfield Cor-rnty regLrlations, a percolation rate of between 5 to 60 minlrtes- per-inch is required for soils to be deemed suitable for onsite wastewater treatment. Therefore. based upon the results of the percolation testing. HBET believes that the native soils are suitable for onsite wastewater treatment. In addition to the percolation rate of the subsr-rrface materials, the seasonal high groundwater elevation is an imporlant factor in determining the suitability of the site for Onsite Wastewater Treatment Systems. For OWTS suitability, the seasonal high groundwater elevation should be at least four feet below the bottom of the proposed absorption bed. As discussed previously, groundwater was not encountered at the tirne of the investigation. In general, based upon the results of the subsurface investigations, HBET believes thatthe seasonal high groundwater level is deeper than 10.0 feet'below the existing grade at this site. Seepage Bed Design The design of the absorption system generally follows the requirements of the Garfield County Department of Public Works as or,rtlined in the Garfield County On-Site Wastewater Treatment System Regulations, effective June 2018. The proposed construction at the site is anticipated to include a five-bedroom home. Based upon the soil percolation rate and visual-tactile classification, a Long-Term Acceptance Rate (LTAR) of 0.5 will be utilized for the absorption field design. Infiltrator Systems Quick4 Standard Chambers are proposed. The daily flow of the sewage disposal system is calculated below and a plan and profile of the absorption system are shown on Figure 3. Average Daily Flow: (8 persons)(75 GPD/person) :600 GPD Soil Treatment Area: (600 GPD / 0.5;: 1,200 Square Feet Adjusted Soil Treatment Area: (1,200 SFXl.2X0.7): 1,008 Square Feet # of Quick4 Chambers : ( I ,008 I 121 :84 Chambers System Instullation The installation of the septic tank, plumbing lines, Infiltrators, etc. should be completed in accordance with the Garfield County On-Site llastewater Treatment System Regulations and Infiltrator Systems, Inc. specifications. In addition, the following construction procedures are recommended:. The septic tank and distribution box should be placed level over native soils that have been scarified to a depth of 8 to l2 inches, moisture conditioned, and recompacted to a minimum of 95Yo of the standard Proctor maximum dry density, within +2o/o of optimum moisture content. However, up to 3-inches of washed rock or pipe bedding passingthe l-inch sieve may be used as a leveling course underthe septic tankand/or distribution box. ' The bottoms of trenches and backfill around the septic tank and distribution box which will support sewer or effluent lines should be compacted to at least 90 percent of the standard Proctor maxirnum dry density, within +2%o of optimum moisture content. Pipe bedding should have a maximum particle size of I -inch. Z:003ALl,PROJE('TSr0l6ll-llonico\lurrllo\026-ll'000lPaLcel:ll7lsl00lSo,l00-Ceo0l6il-000lLR09l6l-ldoc 2 Parcel 21278100386 #0263 l -000 r 09/26123 Iluddleston-Berry Enairaing&T$dnE, LLc Vehicular or heavy eqLripment traffic and placement of structures should not encroach within 10 feet of the septic tank or distribution box. Inspection Schedule Huddleston-Berry Engineering & Testing LLC should be retained to monitor the construction of the OWTS. The following schedule of observation and/or testing should be followed:. Observe the absorption bed excavation prior to placement of Infiltrator chambers.. Observe placement of the septic tank, distribution box, and all connecting sewer and effluent lines prior to backfill. Verify proper fall between inverts.. Observe and verify installation of the absorption bed prior to placement of cover and backfill. In conformance with Garfield County regulations, HBET will be required to provide the Garfield County Health Department with documentation certifying that the OWTS was placed in conformance to the plan and profile and Garfield County regulations. General Notes The OWTS design was based upon the results of the subsurface investigation and on our local experience. The design is valid only for the proposed construction. We are pleased to be of service to your project. Please contact us if you have any questions or comments regarding the contents of this report. Respectfully Submitted: Huddleston-Berry Engineering and Testing, LLC MichaelA. Berry, P.E. Vice President of Engineering Z \ 2008 ALt. PROJ ECTS\026j I - trlonico !l uril l0\016i I -000 I Parc.'l I I l713 I 001 36,100 - Ceo 0:b i I -000 I LR0ql6lj doc J FIGURES G)qPublic.net''' Garfie ld County, CO Date created: 3/3O/2023 Last Data Uploaded;3/30/2023 2:39:58 AM FIGURE 1 Site Location Map D e ve ro pe d tt Ct 9Flrgl""idF[ APPENDIX A Typed Test Pit Logs GEOTECH BH COLUI\iINS 02631-0001 PARCEL 212728100386.GPJ GINT US LAB.GDT 9/26/23 !noL mo -.1z L =(D mv oN OJ oo otrmzI of. oo c =.o o-{+'OPr=lJ^u:-Y,-F= I'O =oo @;O a D E av o cda a adfq!. :. oqk-la =.=qo Il--a !noL mo-{ 1-oo -{ o-z og)3o o c s o 1'aoLmo-{z 3 m !o oo N N\t N @ OO(j @ O) {ma{ ! -{zc =TEmv {! I -o o m oTI zo -.1mo t-ooo mg I! --l m mxc) Ioz 3m{Ioo -l o-f F o)oxfoo mxc, Ioz oo2-{n o{on oJ o -{m 6-{ n+ m0 (j(, N@ o+ moxmo @ @ oo3!t-m-{mo (, o No ono>>>5 ilq*E5H9S ixilHeiEh r96,22 o7oczo mrm { 6z oa o? -{mo-{ ! -laNm O DEPTH (ft) GRAPHIC LOG --l m7 r- o m CNon -u --l Oz SAMPLE TYPE NIJMBER RECOVERY % (ROD) BLOW COUNTS (N VALUE) POCKET PEN (ts0 DRY UNIT WT (pcft MOISTURE coNTENr (%) --l 1 --{ =lilSiU -lEamn FINES CONTENT (o/") LIQUID LIMIT PLASTIC LIMIT PLASTICITY INDEX -_t 'll-. l\-t-t': a 0)f,o r- s 3 €. J o eof,. o --lo-oa a') F o(! :i f- 0)oo oa @ =oo ecn^tofi =<o_ sBe3o- CO o o€J 3o6 @o o 3oec 3oo = -o eo 0)x -otI] (t NG ol (o s6 @o o 3 o o ='D Io o^of+ E @N ts o ai J a l Fzo Iq @ oo NN N)Uou o oo o @No az)Jo (_) I-[uddleston-Berry Engineering & Testing. LLC 2789 Riverside Parkrvav Grand .lunction. CO 8 t 50 I 970-255-8005 TEST PIT NUMBER TP.z PAGE 1 OF 1 CLIENT Monico Murillo PROJECT NAME Parcel 212728100386 PROJECT NUMBER 02631-OOO1 PROJECT LOCATION Garfield County, CO DATE STARTED 3131123 COMPLETED 3/31/23 GROUND ELEVATION TEST PIT SIZE EXCAVATION CONTMCTOR C|ieni GROUND WATER LEVELS: AT TIME OF EXCAVATION AT END OF EXCAVATION AFTER EXCAVATION --- EXCAVATION METHOD LOGGED BY TEC Trackh/Backhoe Dry CHECKED BY MAB Drv NOTES =F TL uJo 0.0 O Irn +qu-o MATERIAL DESCRIPTION UJ TL>EFul sgo-l>z a s iio5oar (fd- uJtr (/)O =F=<zJ dd>oz z Lr.l(I FC LU 13 (Jo rL I 70 =euo Lll o-t- -F aP -rOz>o O ATTERBERG LIMITS Fz uJFz a') C)a uJz tr so,:)= )- trF 3=(L Fx><:: rr 6el= o_ 25 !1..! : .:' t1). I ., i;. l Sandy Loam with Organics (TOPSOIL) %, Sandy Loam, tan to brown, moist, loose to medium dense, weak granular structure I MC 1 88 '13 5.0 7.5 10 0 Bottom of test pit at 10.0 feet. G EOTECH BH COLU IV] NS 0263 1.OOO1 P ARCEL 2127 2A1 9t26t23 -It 7oL mo{zc =@mv oN OJ oo otrmz-l of. o c =. \o{O la aOO = =.o .)o 6 O !m.o Ao p =- D oo- a o o a rn f0:. @ f. oq ts-lo =.: qa--- -ovoL mo-{t-ooD{ o-z o A) _f,o a oocf, s c)o I'noL mo-{z 3m -o o oo N N{N @ oo(r) @o {rfl cn{ !+zc -o [Dxm i''i n-{ 9P -G) zo-{ma t-ooomg @ --l mo mxo Joz =m-{-o E' -l ooxJ F o)oxf o mXo -.16z ooz-{7 o{ov o of o -lma-{ u+ m0 o (,) N6 () I moxm0 (D m oo =!t-m-{mo O O NO ono>>>5 #++;5H9S38xudlifi r9o-t-z onoczo mt- m Ioz o:o e -{ma-{!-{ aNm IO DEPTH (ft) GRAPHIC LOG -l mntF o m6ont --l z SAMPLE TYPE NUMBER RECOVERY % (ROD) BLOW COUNTS (N VALUE) POCKET PEN. (tsf) DRY UNIT WT (pcD MOISTURE coNrENr (%) --1r! = [t<n -l t!amn FINES CONTENT (Yo) LIOUID LIMIT PLASTIC LIMIT PLASTICITY INDEX L.. .lr- ri ..lr_ . ri. l._y-:;t.': . O. l: . l.: ..lsl @o:o. r-onif E. f o (o o)J. --lo!a . T- o) Go IEocoo c' @o eoo. o) bfloo 9AoiP o_ e.8e3 Co oJ o 6 =af lo6'f,+ 3og C 3oofao ooof, -o{oox t! 3 o o p. D 90 O o'o APPENDIX B Percolation Testing Results PERCOLATION TESTING STP322Iluddleston-Berry Etrgilrrcri[g.( Tcitiig, LI-C Project Name: Parcel 212728100386 Location: Garfield County, CO Testing Conducted By: Supervising Engineer: TEST PIT DIMENSIONS SOIL PROFILE T. Collins M. Be o. TP.3 313112023 Test Pit No. Date: Water Level Depth (ft)Length (ft) width (ft) Depth (ft)Depth (ft)Not Encountered 8.0 XI Depth (ft)Description Remarks 0-1 Sandv Loam with Orqanics (TOPSOIL) 1-8 Sandy Loam, tan to brown, moist, medium dense to dense, weak qranular structure Test Number: 1 Top of Hole Depth: e tttl Diameter of Hole: 3 (in) Depth of Hole: 18 (in) Time (min.) Water Depth fin.) Change (in.) 0 1.625 10 2.125 0.5 20 2.375 o.25 30 2.875 0.5 40 3.375 0.5 50 3.625 0.25 60 4.'t25 0.5 70 4.375 o.25 80 4.625 0.25 90 4.875 0.25 100 5.375 0.5 110 5.625 0.25 120 5.875 o.25 30 Rate (min/in):Rate (min/in) 20 Test Number: 1 Top of Hole Depth: S ftl Diameter of Hole: 3 (in) Depth of Hole: 17 (in) Test Number: Top of Hole Depth: - (ft) Diameter of Hole: (in) Depth of Hole: (in) Time (min.) Water Depth (in.) Change (in.) 0 1.875 10 6.625 4.75 20 9.125 2.5 30 11.125 2 40 12.625 1.5 50 14j25 '1.5 60 15j25 I 7A 16.125 1 80 17j25 1 90 17.625 0.5 100 Drv 110 1 120 3 2 o Time (min.) Water Depth (in.) Change (in.) Average Percolation Rate (min/in) Rate (min/in) Project No.: 0263 1-0001 Date: 09/21123 By: MAB Huddlest0n-Berry Engineering & Testing, LLC 2 789 Riverside Parku'a,v Grand Junction. CO 81501 PARCEL#212728100386 FIGURE2-SITEPLAN NEW HOME STA ,, , a ,, WELL , WELL TER LINE __t SITE PLAN ENLARGED VIEW tnF\Ri9<funr.ev ?la J 20' PRIVATE DRIVE AND EMERGENCY ACCESS EASEMENT ( \ REPAIR AREA-'Y \ A TP-3 TP.1 TER LINE 1O'UTILITY EASEMENT SCALE: l":40' '-NOTE: TANK AND BEO LOCATIoNS APPROXIIVIATE AND l\,lAY SHIFT SOI\IE DURING CONSTRUCTION BASED UPON SITE TOPOGRAPHY, OWNER PREFERENCE. AND/OR OTHER FACTORS AS LONG AS APPLICABLE SETBACKS ARE MET. ACTUAT IOCATION OF TANK AND BED WILt BE INDICATED ON AS.BUILT DRAWINGS,* SCALE: l":200' C.I. : 1 FT A TEST PIT NEW HOME SEPTTC TANK(S) WITH MINIMUM 1,500 GALLON CAPACITY POLE N t( GENERALIZED SYSTEM PROFILE NNT TO SCALE RESIDENTIAL STRUCTURE RISERS (AS NECESSARY) UCH THAT LIDS ARE AT OR INFlLTRATER OUICK4 STANDARD CHAMBERSCLEUTVE FINISHED GRADE 1.0 FT MIN. CNVER ON EFFLUENT EST 6,0T[ 8.0 FT EST, 2,0 FT 4,0 FT MAX, 1.0 FT MIN, CI]VER DISTRIBUTIDN BOX TIC TANK GENERALI ZED BED PROFILE NET TB SCALE COVER SOIL; NATIVE SOILS OR OTHER SU]TABLE TOPSOIL. GRADE TO CARRY SURFACE WATER AWAY FROM BED. INFILTRATOR SYSTEMS QUICK4 STANDARD CHAMBERS NON\A/OVEN. NEEDLE PUNCHED. GEOTEXTILE FABRIC IMIVIED]ATEL\' ABOVE CHAMBERS MINIMIJM SETBACKS (UNITS: FT) VELLS VJATER LINE ORY 6ULCH, CU] BANK, AND FILL LINED DITCH FLEODED FIELDS LAKE, STREAM, UNLINED DITCH DVELLING UNOCCUPIED BUILDlNG PRT]PERTY LINE SEPTIC TANK 50 10 10 10 t0 50 5 10 AA\URI- I lUN BEI)100 e5 e5 10 a5 50 20 5 10 LT I. LULN I I TNFS 50 10 10 10 10 50 10 ffic'(# \7.MIN,O,5Z FALL MIN. \NZ '(r,\\ *xOTllER SETIIACKS NO'f l".lSTED IJEI{E SIJOUI-D IIE IN ACC'ORDANUE \\'11-11(;.ARFTIrl-D COUNTY O\\-TS ILEGLILATIONS DETAIL AREA **USE S\\'EEP 9O'S OR TWO 45',S AT 90 i]EGREE BENDSs"SCALE: l":20' N INSPECTION PORTS INFILTRATOR SYSTEMS QUICK4 STANDARD C]JAMBERS INSPECTION PORTS DISTR]BUTION BOX THAT ENSURES EVEN DISTRIBUTION OF EFFLUENT MI SEPTIC TANK WJTH 4-]NCH DIA]\,{ETER SEWER AND r\4lNIMUNI 1,500 EFFLUENT P]PE MEETING AS GA]-I-ON CAPAC]TY Dr785. SCHEDULE40 OR SDRA \ IATER LINE----\ NEW HOME Project No.: 0263 1-0001 Date: 09126123 BY: MAB Huddleston-Berry Engineering & Testing, LLC 2789 Riverside Parku'ay Grand Junction. CO 81501 PARCEL#212728I 00386 FIGURE3-SEPTICSYSTEM DETAILS