Mechanical Gompl iance Gertificate
' Project lnformation
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
545 Bald Eagle Way
Carbondale, CO 81623
2015IECC
Aspen Glen Club-Fitness Center Renovation
Carbondale, Colorado
5b
Addition
Owner/Agent:
Aspen Glen Club
Designer/Contractor:
B&H Engineers
511 E John Carpenter Fwy Suite 250
lrving, TX 75062
(2r4) 496-7670
Mechanical Systems List
Quantity System Type & Description
HVAC System 1 (Single Zone):
VRF Condensing Unit, Air Cooled Heat Pump
Heating Mode: Capacity = 58 kBtuih,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 72kBlulh,
No minimum efficiency requirement applies
Fan System: None
HVAC System 2 (Single Zone):
Cooling:1 each -VRFZone Fan Unit, Capacity= 12 kBtu/h, No Economizer, Economizerexception: None
No minimum efficiency requirement applies
Fan System: FAN SYSTEM 1 | FCU-1 , FCU-2, FCU-3 - Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Single-Zone VAV, 511 CFM, 0.1 motor nameplate hp, 80.0 fan efficiency grade
HVAC System 3 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 7 kBtu/h, Unknown Economizer
No minimum efficiency requirement applies
Fan System: FAN SYSTEM 2IFCU-4 - Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Single-Zone VAV, 317 CFM, 0.1 motor nameplate hp, 80.0 fan efficiency grade
Mechanical Gompliance Statement
Compliance Statementj The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory
requirements listed in the lnspection Checklist,
Nevena Parsons - Sen. Mechanical Engineer N.Parsons 101272023
me Signature Date
3
Project Title:
Data filename
Aspen Glen Club-Fitness Center Renovation Report date
Z:\Projects\05066 - Club Corp\o5066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
L0t27 t23
lof 10
COMcfi eck Software Versicn 4,L. 5.5
Inspection Checklist
Energy Code: 201-5 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to thattable is provided.
Additional Comments/Assumptions:
Project Title: Aspen Glen Club-Fitness Center Renovation Report date: LOl27 123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 2 of I0
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
€omplies?CommentslAssumptions
Section
#
& Req.lD
Plan Review
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
c103.2
lPR2l1
,nComplies
:nooes Not
]ENot observable
jflNot Applicable
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
res
efficien e ons
c406
lPR9l1 ;lDoes Not
Not Observable
Not Applicable
ct (Tier 1)H h 2 Medium ct (Tier 2)3 Low lmpact (Tier 3)1
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Does Not
Not Observable
Not Applicable
plies
Add itional Comments/Assum ptions :
Project Title: Aspen Glen Club-Fitness Center Renovation Report date: L0127123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 3 of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
ct (Tier 3)LowL(Tier 1)Hi Medium I (Tier 2)
Comments/Assumptions
Section
#
& Reo.lD
Plumbing Rough-ln lnspection Complies?
C404.5, ,Heated water supply piping conforms
C4O4.5.1, .to pipe length and volume
C404.5.2 :requirements. Refer to section details
:nrtr
ln
ln
Complies
Does Not
Not Observable
Not ApplicablelPL6l3
c404.5,
c404.5.1,
c404.5.2
lPL6l3
,Heated water supply plping conforms
,to pipe length and volume
:requirements. Refer to section details
Complies
Does Not
Not Observable
Not Applicable
tn
itr
c404.5,
c404.5.1,
c404.5.2
lPL6l3
to pipe length and volume llOoes lrlot
requirements. Refer to section details. ENot Observable
:ENot Applicable
Heated water supply piping conforms Complies
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
Does Not
mpliesc404.6.3
lPL7l3
;ENot Observable
jEruot npplicaole
heater and storage
that limit operation
m ESUrcwaterlateabetweenPumclthatplips
nta hk VCa ntrolco s Does Not,E
from tostartup otN bseo btrva e:!tihea n5tnmafterutesofend s c bleaotN:!Applcycle
c404.6.3
lPL7l3
'Pumps that circulate water between a
, heater and storage tank have controls
lljtr
mplies
lDoes Not
cycle
c404.6.3
lPL7l3
Not Observable
Not Applicable
,that limit operation from startup to
r<= 5 minutes after end of heating
;Water distribution system that pumps
'water from a heated-water supply
: pipe back to the heated-water source
,through a cold-water supply pipe is a
: demand recirculation water system.
:Pumps within this system have
, controls that start the pump upon
,receiving a signal from the action of a
.user of a fixture or appliance and
,limits the temperature of the water
entering the cold-water piping to
:104'F.
mpliesc404.7
lPL8l3 lDoes Not
nNot Observable
ENot Applicable
, Water distribution system that pumps
,water from a heated-water supply
: pipe back to the heated-water source
,through a cold-water supply pipe is a
, demand recirculation water system.
,Pumps within this system have
controls that start the pump upon
:receiving a signal from the action of a
:user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
:104'F.
mpliesc404.7
IPL8]3 EDoes Not
ENot Observable
ENot Applicable
31lm(Tier 1)Hi 2 Medium lmpact (Tier 2)Low I (Tier 3)
Project Title:
Data filename
Aspen Glen Club-Fitness Center Renovation Report datei lll27 123
Z:\Projects\05066 - Club Corp\05066,65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 4 of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop,cck
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
l-04'F.
;tr
t;tr
;tr
plies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions :
Medium lm 2)(Tier 3)LowIlmpact (Tier 1)H
Project Title:
Data filename:
Aspen Glen Club-Fitness Center Renovation Report datei IOl27l23
Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 5 of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
Section
s
& Reo.lD
Mechanical Rough-ln lnspectaon Complies?Cornments/Assumptions
Thermally ineffective panel surfaces
sensible heating panels have
insulation >= R-3.5.
EComplies
EDoes Not
ENot Observable
ENot Applicable
c402.2.6
lME41l3
C403.2.12 HVAC fan systems at design.l conditions do not exceed allowable
[ME65]3 fan system motor nameplate hp or fan
See the Mechanical Systems list for values
system bhp.
lDoes Not
Complies
lENot Observable;
iEtrtot Applicable
,Fans have efficiency grade (FEG) >=
,67. The total efficiency of the fan at
:the design point of operation <: l5o/o
of maximum total efficiency of the
, fan.
c403.2.12
.3
lME1L7l2
,tr
;l
:a
Complies
Does Not
Not Observable
Not Applicable
C403.2.13 Unenclosed spaces that are heated
lME7l,l2 use only radiant heat.
;nir
,EComplies
,EDoes Not
Not Observable
Not Applicable
HVAC equipment efficiency verified. :lComplies :See the Mechanicat Systems list for vatues.
[Does Not
ENot Observable
Eruot applicable .
c403.2.3
lME55l2
: Demand control ventilation provided
,for spaces >500 ft2 and >25
: people/1000 ft2 occupant density and
,served by systems with air side
:economizer, auto modulating outside
:air damper control, or design air"flow
, >3,000 cfm.
:EComplies
:lDoes Not
.!lVot Observable
:nNot Applicable
c403.2.6.
1
lME59l1
c403.2.6.
2
lME115l3
, Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 5oo/o or less of design capacity
nComplies
EDoes Not
INot observable
ENot Applicable :
: Exhaust air energy recovery on
i systems meeting Table C403.2.7(1)
:and C403.2.7(2).
EComplies
EDoes Not
!Not Observable
ENot le
c403.2.7
lME57l1
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
EComplies
nDoes Not
!Not observable
nNot Applicableexhaust rate criteria.
c403.2.8
lM€11613
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
:in or under a slab, verification may
need to occur during Foundation
lnspection,
inNot Observable
iEruot applicable
EComplies
lDoes Not
c403.2.9
lME60l2
, Ducts and plenums sealed based on
, static pressure and location.
Ewot licable
resc403,2.9
lME10l2 EDoes Not
nNot Observable
c403.2.9
1.3
tMc11l3
Ductwork operating >3 in. water
column requires air leakage testing.
!Complies
lDoes Not
nNot Observable
nruot Rpplicable
1 Hi ct (Tier 1)I 2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: Aspen Glen Club-Fitness Center Renovation Report date: 10127/23
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 6 of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
CcmmentslAssumptions
Section
#
& Reo.lD
I{echanical Rough-ln lnspection Complies?
c403.2.9.
1.3
lMf 1113
,Ductwork operating >3 in. water
, column requires air leakage testing
Complies
Does Not
Not Observable
Not Applicable
1tr
.tr
:fl
:n
c403.2.9-
1.3
lME11l3
,Ductwork operating >3 in. water
,column requires air leakage testing
Complies
Does Not
Not Observable
Not Applicable
'tr
isolate the cooling tower from the
, heat pump loop, and heat loss is
,controlled by shutting down the
:circulation pump on the cooling towe
,Open- or closed circuit cooling towers Complies
, have a separate heat exchanger to Does Not
lnNot Observable
.nruot Rpplicable
f:
loo
c403.4.2.
3.2.2
lMEL2213
, Multiple zone VAV systems with DDC
,of individual zone boxes have static
: pressure setpoint reset controls,
Complies :see the Mechanical Systems list for values
Does Not :
Not Observable;
c403.4.4.
in
iltrtot Rpplicaole
6
lME11013
C403.4.4. ,Multiple zone VAV systems with DDC6 of individual zone boxes have static
:tr
;tr
See the Mechanical Systems list far values.
pressure setpoint reset controls.
Complies
Does Not
lME1l"013 :nNot Observable,
:ENot Applicable ;
c403.4.4.
6
lME11013
Multiple zone VAV systems with DDC
,of individual zone boxes have static
: pressure setpoint reset controls.
See the Mechanical Systems list for values.
,tr
in
:!Complies
:EDoes Not
Not Observable
Not Applicable
C408.2.2. Air outlets and zone terminal devices1 :have means for air balancing.
tME53l3 .rfl
:tr
ilcomplies
iEooes t',tot
Not Observable
Not Applicable
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
:EComplies
,f]ooes Not
,!Not Observable
:!Not Applicable
c403.5,
c403.5.1,
c403.5.2
lMEt 2313
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
Project Title: Aspen Glen Club-Fitness Center Renovation Report dafe: !0127123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 7 of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
3 Low lm (Tier 3)1 (Tier 1)Hi hlm 2 Medium ct (Tier 2)
Complies?Comments/Assumptions
Section
#
& Req.lD
Final lnspe€tion
c303.3,
c408.2.5
3
lFt8l3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
flComplies
EDoes Not
ENot Observable
ENot Applicable
HVAC systems and equipment
capacity does not exceed calculated
loads.
EComplies
EDoes Not
ENot Observable
ENot Applicable
c403.2.2
lFt2713
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
h u m idification/deh umidification
system.
EComplies
EDoes Not
!Not Observable
nNot Applicable
c403.2.4.
1
lFt47l3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
lDoes Not
nNot Observable
ENot Applicable
pliesc403.2.4.
1
lFt47l3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
, humidification/dehumidification
EComplies
EDoes Not
INot Observable
INot Applicable
c403.2.4.
1
lFr47l3
c403.2.4.
1,1
lFt42l3
:Heat pump controls prevent
supplemental electric resistance heat
,from coming on when not needed.
EComplies
EDoes Not
ENot Observable
Etrtot ble
Thermostatic controls have a 5 'F
,deadband.
c403.2.4.
L.2
lFt3813
lEcompties
iDooes ltot
ENot Observable
ENot Applicable
c403.2.4.
1.3
lFt20l3
: Temperature controls have setpoint
overlap restrictions.
iEComplies
,EDoes Not
nNot Observable
!Not Applicable
lElComplies
inooes trtot
inNot observable
iEruot Rpplicable
c403.2.4.
2
lFt39l3
: Each zone equipped with setback
controls using automatic time clock or
programmable control system.
!Complies
nDoes Not
ENot Observable
Eruot Applicable
c443.2.4.
2.1,
c403.2.4.
2.2
lFt40l3
:Automatic Controls: Setback to 55'F
, (heat) and 85"F (cool); 7-day clock, 2-
: hour occupant override, 10-hour
, backup
.
:
iEComplies
:IDoes Not
;LNot Observable
jLruot Applicable
c403.2.4
2.3
IF141]3
:Systems include optimum start
, controls.
;tr
;tr
:tr
C403.2.4. .systems include optimum start2.3 ,controls.
IFt4].13
:EComplies
Does Not
Not Observable,
Not Applicable .
2 Medium lm ct (Tier 2)3 Low I (Tier 3)1 High lmpact (Tier 1
Project Title:
Data filename
Aspen Glen Club-Fitness Center Renovation Report date: 10/27 123
Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page I of 10
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
Complies?Ccmments/Assumptions
Section
#
& Req.lD
Final lnspection
Commissioning plan developed by
registered design professional or
approved agency.
;nComplies i
iEooes ltot :
iEtttot observable i
iEruot Applicable :
c408.2.1
lFt28l1
c408.2.3.
1
lFt31l1
HVAC equipment has been tested to
ensure proper operation.itr
;tr
iEruot applicable :
mplies
Does Not
Not Observable
c408.2.3.
2
lFr10l1
HVAC control systems have been i[Complies :
tested to ensure proper operation, :EDoes Not .
caribration and adjustment of contrors. ENot observabrel
ENot Applicable ,
,Preli
i com
: desi
minary commissioning report
pleted and certified by registered
gn professional or approved
iu
,a
tn Not Applicable ;
agency
iEcompliesc408.2.4
lFt29l1 Does Not
Not Observable
C408.2.5. Furnished HVAC as-built drawings1 submitted within 90 days of system
lFl7l3 acceptance,
:!Does Not
.!Not Observable
Etttot Applicable
mplies
c408.2.5.
3
lFt43l1
An air and/or hydronic syste
balancing report is provided
systems.
EComplies
EDoes Not
!Not Observable
ENot Applicable
m
for HVAC
c408.2.s
4
lFt3oll
,Final commissioning report due to
,building owner within 90 days of
: receipt of certificate of occupancy
nComplies
nDoes Not
ENot Observable
!wot Rpplicable
Additional Comments/Assumptions:
2 Medium lm (Tier 2)3 Low I (Tier 3)1 High lmpact (Tier 1)
Project Title:
Data filename
Aspen Glen Club-Fitness Center Renovation Report date
Z:\Projects\05066 - Club Corp\O5066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
10127 t23
9of 10
Project Title: Aspen Glen Club-Fitness Center Renovation Report date
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page
ComCheck\Phase 2\Pro Shop\ComCheck-Mechanical-Aspen Glen-Pro shop.cck
L0t27 t23
L0 of 10
COMcheck Software Version 4.1.5.5
lnterior Lighting Gompliance Gertificate
Project lnformation
Energy Code:
Project Title:
Project Type:
2015 |ECC
ASpen Glen Club-Pro shop
Addition
Owner/Agent:
Aspen Glen Club
Construction Site:
545 Bald Eagle
Carbondale, CO
way
81623
Designer/Contractor:
Larry Garrett
B&H engineers
511 E John Carpenter Fwy Suite 250
lrving, TX 75062
2L4-496-L670
lgarrett@bandhengi neers.com
Allowed lnterior Lighting Power
A
Area Gategory
B
Floor Area
(ft2)
c
Allowed
Watts /ft2
D
Allowed Watts
(Bxc)
'l-Country club (Dining: Bar Lounge/Leisure)4478 1.01 4523
Total Allowed Watts = 4523
Proposed Interior Lighting Power
A
Fixture lD : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
c
#of
Fixtures
D
Fixture
Watt.
E
(cxD)
Fixture
1-Countrv club (Dinino: Bar Lounoe/Leisure)
LED 1: B: 4" downlight: LED A Lamp 25W:
LED 2: C: 2" spot light LED A Lamp 13W:
LED 3: D: semi flush light LED A Lamp 13W:
LED 4: F: semi flush light: LED A Lamp 3.2W:
LED 5: H: 8" pendant light LED A Lamp 6W:
LED 6: J: wall sconce light LED A Lamp 13W:
LED 7: K: wall sconce lighfi LED Linear 33W:
LED 8: L: chandelier: LED Linear 33W:
LED 9: M: wall sconce light LED Linear 33W:
LED 10: N: track light: LED Linear 33W:
LED 11: T: tape lineat light: LED Linear 33W:
LED 12'. 52: existing wall sconce: LED Linear 33W:
68
26
3
4
4
4
4
3
I
16
194
4
22
13
30
4
6
15
10
210
40
10
4
10
1496
338
90
16
24
60
40
630
360
160
776
40
Total Proposed Watts = 4030
lnterior Lighting Gompliance Statement
Compliance Statementj The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory
requirements listed in the lnspection Checklist.
Project Title: ASpen Glen Club-Pro shop
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspe
ComCheck\Phase 2\Pro Shop\ComCheck-Lighti
Report datet 06102123
n Glen Pool & Fitness Country Club Renovations\ Page 1 of 9
ng-Aspen Glen-Pro shop.cck
lnterior Lighting PASSES: Desig,n 11% be.tter than code
Larry Garrett - Electrical Engineer PE 06t0212023
Name - Title Signature Date
Project Title: ASpen Glen Club-Pro shop Report date: 06/02123
Data filename: Z:\Projects\05066 - Club Corp\05066,65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 2 of 9
ComCheck\Phase 2\Pro Shop\ComCheck-Li ghting-Aspen Glen-Pro shop.cck
COMcheck Software Version 4.1.5.5
Exterior Lighting Gompliance Certificate
Project lnformation
Energy Code:
Project Title:
Project Type:
Exterior Lighting Zone
Construction Site:
545 Bald Eagle Way
Carbondale, CO 81623
Allowed Exterior Lighting Power
A
Area/Surface Gategory
2015 IECC
ASpen Glen Club-Pro shop
Addition
1 (Developed rural area (LZ1))
Owner/Agent:
Aspen Glen Club
Designer/Contractor:
Larry Garrett
B&H engineers
511 E John Carpenter Fwy Suite 250
lrving, TX 75062
214-496-t670
I garrett@bandhengi neers.com
BC
Quantity Allowed
Watts / Unit
E
Allowed Watts
(BXc)
D
Tradable
Wattage
entry to building (Entry canopy)
Canopy around bldg. (Plaza area\
54ft2
1136 ft2
0.25
0.14
Yes
Yes
14
159
Total Tradable Watts (a) - 173
Total Allowed Watts = 173
fotal Allowed Supplemental Watts (b) = 500
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 500 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A
Fixture lD : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
c
#oI
Fixtures
D
Fixture
Watt.
E
(cxD)
entry to building ( Entry canooy 54 ft2): Tradable Wattage
LED 1: B: Pendant mounted: LED PAR 20W:
LED 2: T: Tape light: LED MR 4W:
LED 3: 52: Ceiling fan: LED A Lamp 6W:
Canopy around bldg. ( Plaza area 1 136 ft2): Tradable Wattage
1
1
1
22
88
24
90
22
4
6
6
1
22
4
151LED 4: 32: Ceiling fan: LED A Lamp 6W:
Total Tradable Proposed Watts = 224
Exterior Lighting Compliance Statement
Compliance Statementj The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 20L5 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory
requirements listed in the lnspection Checklist.
Project Title: ASpen Glen Club-Pro shop Report date: O6lO2123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 3 of 9
ComCheck\Phase 2\Pro Shop\ComCheck-Lighting-Aspen Glen-Pro shop.cck
Lighting PASSES: Design 67% better than code
Larry Garrett - Electrical Engineer PE 06t02t2023
Name - Title Signature Date
Project Title: ASpen Glen Club-Pro shop Report datet 06102123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 4 ot 9
ComCheck\Phase 2\Pro Shop\ComCheck-Lighting-Aspen Glen-Pro shop,cck
€OMcheck Software Version 4.1,5.5
lnspection Checklist
Energy Code: 20L5 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Additional Comments/Assumptions:
Project Title: ASpen Glen Club-Pro shop Report date: 06/02i23
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 5 of 9
ComCheck\Phase 2\Pro Shop\ComCheck-Lighting-Aspen GIen-Pro shop.cck
Section
#
& Res.lD
Plan Review €omplies?
c103.2
lPR4l1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. lnformation
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices,
EComplies
flDoes Not
!Not Observable
!Not Applicable
c103.2
lPR8l1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. lnformation
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
DComplies
[Does Not
ENot Observable
ENot Applicable
c406
lPR9l1
, Plans, specifications, and/or
: calculations provide all information
:with which compliance can be
:determined for the additional energy
, efficiency package options.
nComplies
EDoes Not
ENot Observable
nNot Applicable ,
3 Low lm (Tier 3)1 Hi lmpact (Tier 1)2 Medium lm ct (Tier 2)
Section
& Reo.lD
Rough-ln Electrical lnspection Comp!ies?€osr! ments/Ass umptions
Lighting controls installed to uniformly lEComplies
reduce the lighting load by at least jEooes Not
.tr
:l
50o/o.
c405.2.1
lELl5l1
Not Observable
Not Applicable
,!Complies
:!Does ruot
.Etttot Observable
:nruot Applicable
c405.2.L
lELlBll
Occupancy sensors installed in
required spaces.
c405.2.1,
c4a5.2.2.
3
lEL23l2
, lndependent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
EComplies
EDoes Not
INot Observable
nNot Applicable
C4A5.2.2. ,Automatic controls to shut off all1 building lighting installed in all
lEL2212 , buildings.
lComplies
lDoes Not
nNot Observable
ENot Applicable
lights independent of general area
lighting.
EComplies
EDoes Not
!Not Observable
nNot Applicable
c405.2.3
lEL16l2
Daylight zones provided with
individual controls that control the
c405.2.3,
c405.2.3.
1,
c40s.2.3.
2
lEL20l1
Primary sidelighted areas are
equipped with required lighting
controls.Not Observable ;
Not Applicable :
Complies
Does Not
c405.2.3,
c40s.2.3.
1,
c40s.2.3.
3
lEL21l1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
itr
lEjl
i"
.
Complies
Does Not
Not Observable
Not Applicable
c405.2.4
lEL4l1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
.EComplies
'Eooes
t"tot
;Etrtot Observable
j!ruot npplicable
c405.2.4
lEL8l1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
1lComplies .
;Eooes Not
,nNot Observable ,
:nruot applicable .
c405.2.5
lEL251n"tt
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
EComplies
lDoes Not
ENot Observable
DNot Applicable
flComplies
!Does Not
nNot Observable
!Not Applicable
c405,3
lEL6l1
Exit signs do not exceed 5 watts per
face.
Additional Comments/Assumptions:
1 lm (Tier 1)Hi 2 Medium lm (Tier 2)3 Low lm (Tier 3)
Project Title:
Data filename
ASpen Glen Club-Pro shop Report date: 06102123
Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 6 of I
ComCheck\Phase 2\Pro Shop\ComCheck-Lighting-Aspen Glen-Pro shop.cck
Medium ct Low I (Tier 3LHigh lmpact (Tier L)
Project Title:
Data filename
ASpen Glen Club-Pro shop Report date: 06102123
Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 7 of 9
ComCheck\Phase 2\Pro Shop\ComCheck-Lighting-Aspen Glen-Pro shop.cck
Section
#
& Reo.lD
Final lnspe€tion Complies?Comments/Assumptions
c303.3,
c408.2.5
2
lFt1713
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
EComplies
EDoes Not
ENot Observable
Eruot Applicable
c405.4.1
lFtlSli
lnterior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
EComplies
EDoes Not
!Not Observable
Ellot Applicable
See the lnterior Lighting fixture schedule for values.
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
!Complies
EDoes Not
ENot Observable
DNot Applicable
See fhe Exterior Lighting fixture schedule for values.c405.5.1
lFt19l1
c408.2.5
1
lFn 613
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
nComplies
EDoes Not
nNot Observable
lNot Applicable
Lighting systems have been tested to ;EComplies
ensure proper calibration, adjustment, :EOoes trtot
programming, and operation. ;ENot Observable
lENot Rpplicable
c408.3
lFI33l1
Additional Com ments/Assum ptions:
1 hlm (Tier 1)H 2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: ASpen Glen Club-Pro shop
Data filename: Z:\Projects\05066 - Club Corp\O5066.65 - As
ComCheck\Phase 2\Pro Shop\ComCheck-Li g
Report date: 06/02123
Glen Pool & Fitness Country Club Renovations\ Page 8 of 9
g-Aspen Glen-Pro shop.cck
pen
htin
Project Title: ASpen Glen Club-Pro shop Report date: 06/02123
Data filename: Z:\Projects\05066 - Club Corp\05066.65 - Aspen Glen Pool & Fitness Country Club Renovations\ Page 9 of 9
ComCheck\Phase 2\Pro Shop\ComCheck-Li ghting-Aspen Glen-Pro shop.cck