HomeMy WebLinkAboutTABB Report JEDI Balancing, Inc. 568 Briggs Street (physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Certified Test, Adjust & Balance Report Project Battlement Mesa Golf Course Restaurant Kitchen Addition Address 3030 North Battlement Pkwy Parachute, CO 81635 Architect Terri Montoya Architects Mechanical Engineer SGM Inc. Contractor Rapid Creek Mechanical Company Date 6/25/2024 Job Number 2024-10243 Donald W. Pittser TABB Certified Supervisor TABB Firm Certification #BB009003C Stamp Expires 9/30/2024 Warranty Information: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB International Standards for Environmental Systems Balance. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed TABB tolerances, are noted in the TAB report project summary. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Instrumentation: Instrument Manufacturer Model Serial Number Calibrated On Calibration Due Tachometer Shimpo MT-200 B175B5016P 03-12-2024 03-12-2025 Air Temperature Probe Evergreen Telemetry PR-T-1 1700353 07-14-2023 07-14-2024 Immersion Temperature Probe Evergreen Telemetry PR-T-4-6 1700204 07-14-2023 07-14-2024 Humidity Evergreen Telemetry S-H-3-5 1700295 07-14-2023 07-14-2024 Volt-Amp Meter Fluke 323 49251381WS 04-24-2024 04-24-2025 Air Pressure Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025 Air Velocity / Airfoil Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025 Flowhood Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025 Hydronic Pressure TSI HM-675 71646134 07-25-2023 07-25-2024 Hydronic Differential Pressure TSI HM-675 71646134 07-25-2023 07-25-2024 Abbreviation Index TAB: Testing, Adjusting & Balancing Cx: Commissioning OD: Outside Diameter AHU: Air Handling Unit Motor FLA: Full Load Amperage T1: Terminal 1 RTU: Roof Top Unit S.F.: Service Factor T2: Terminal 2 PACU: Packaged Air Conditioning Unit RPM: Revolutions per Minute T3: Terminal 3 MAU: Make Up Air Unit P.F.: Power Factor CS: Circuit Setter FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency BV: Balance Valve VAV: Variable Air Volume TDH: Total Dynamic Head K Factor: Correction Factor FPB: Fan Powered Box AK: Area Correction PSI: Pounds per Square Inch CUH: Cabinet Unit Heater Valve D.P.: Discharge Pressure UH: Unit Heater Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit EF: Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan SF: Supply Fan RF: Return Fan TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan DX: Direct Expansion SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure in. wc: Inches Water Column ESP: External Static Pressure HW: Heating Water VP: Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA: Return Air HX: Heat Exchanger OSA: Outside Air SWD: Sidewall Diffuser MA: Mixed Air EAT: Entering Air Temperature OA: Outside Air CD: Ceiling Diffuser EWT: Entering Water Temperature SD: Supply Diffuser ER: Exhaust Register LAT: Leaving Air Temperature MVD: Manual Volume Damper RG: Return Grille LWT: Leaving Water Temperature OBD: Opposed Blade Damper NAC: No Access CFM: Cubic Feet Per Minute CMH: Cubic Meters per Hour NG: Not Given FPM: Feet Per Minute SSD: Square Supply Diffuser NIC: Not in Contract SRD: Square Return Diffuser E: Existing M: Meter TG: Transfer Grille cm: Centimeter Pa: Pascal l/s: Liters per Second mm: Millimeter kPa: Kilopascal ADM: Air Data Meter (manometer) SPF: Stairwell Pressurization Fan N/A: Not Applicable Design D.P.: Design Differential Pressure Actual D.P.: Recorded Differential Pressure Ind.Imp.Dia. Indicated Impeller Diameter CRAC: Computer Room Air Conditioning Unit Table of ContentsPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser 1 2024 10243 Battlement Mesa Golf Course Restaurant Kitchen Addition Report Summary.pdf...............................1 2 Air Handling Unit......................................................................................................................................................2 2.1 F-01....................................................................................................................................................................2 2.2 F-01/SPP-01.......................................................................................................................................................3 2.3 F-02....................................................................................................................................................................4 2.4 F-02/SPP-01.......................................................................................................................................................5 2.5 MAU-01..............................................................................................................................................................6 2.6 MAU-01/SPP-01.................................................................................................................................................7 3 Energy Recovery Unit..............................................................................................................................................8 3.1 ERV-01...............................................................................................................................................................8 3.2 ERV-01/SPP-EXHAUST.....................................................................................................................................9 3.3 ERV-01/SPP-SUPPLY........................................................................................................................................10 4 Fan Unit....................................................................................................................................................................11 4.1 KEF-01...............................................................................................................................................................11 5 BATTLEMENT MESA GOLF COURSE RESTAURANT AND KITCHEN TAB DRAWINGS.pdf...............................12 6 TAB Equipment Calibrations 2024b.pdf...................................................................................................................26 JEDI Balancing, Inc. Page 1 of 26 JEDI Balancing, Inc. 568 Briggs Street (physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Report Summary and Remarks Project: Battlement Mesa Golf Course Restaurant Kitchen Addition Project: 2024 10243 Scope: The Test and Balance (TAB) scope of work consisted of Air Handling Unit (F)-2, (MAU)-1, Exhaust Fan (EF)-1 Procedures: F, MAU - Constant Volume Each unit has a constant volume fan that was set for design airflow and the associated supply outlets were balanced in full cooling demand. The total Supply Air CFM was measured as individually listed under each unit. The Outside Air CFM was measured as individually listed under each unit. The Return Air CFM was measured as individually listed under each unit. All final TAB settings and performance measurements were completed, and data was recorded on to the appropriate test report forms. Exhaust Fans with Grilles and Hoods The exhaust fans were energized, measured and set for total airflow. The associated inlets were balanced as noted in this report. The Exhaust Air CFM was measured as individually listed under each unit. Final settings and performance measurements were completed, and data recorded on to the appropriate test report forms. Motor Tag Data Not Accessible (Embedded) Embedded Motor – Limited motor nameplate information provided. Motor nameplate information is obscured by the motor mounting bracket and not visible without disassembly of the motor from the unit. The motor is accessible for service and maintenance. No Access Between Coils Some unit arrangement prevents access to obtain a complete static pressure profile for all the components. Static pressure test ports could not be safely drilled between the heating and cooling coils without risking damage to the coils and are recorded as “Not Accessible” in the Report. Schematic Line Diagrams Report includes reduced mechanical drawings used for the test and balance work. These “Keyed Drawing” were used in place of single line schematic diagrams and include the unique designations for the tested items in the final TAB report. Submittals: Submittals were not provided for the project. to +/-10% of design flow rates Any values outside the specified tolerances are noted on the Equipment Comment Log and the individual test report pages. Previously Forwarded / Accepted As-Is Equipment Comment Log Project Summary The following page(s) lists all project comments and issues. All items described and listed on the following Equipment Comment Log have been previously forwarded for resolution and have been accepted as reported. Page 2 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: F-01 Unit Data Unit Manufacturer TRANE Unit Model Number S9V2C100U4VSADA Unit Serial Number 23321PEJKG Starter Data F-01/Supply Fan Starter Manufacturer Thermally Protected Design Data Total Flow Design 1770 Supply Fan Design ESP 0.62 in. wc Supply Fan Design TSP Not Given in. wc Supply Fan Design RPM Not Given Supply Fan Motor Design HP Not Given Supply Fan Motor Design RPM Not Given Supply Fan Motor Design Volts 120 Supply Fan Motor Design Phase 1 Design Filter MERV Rating Not Given Test Data Connected Actual Supply Airflow 1920 1815 Outside Airflow 725 680 Return Airflow 1135 Electrical Test Data F-01/Supply Fan Motor Volts 1 121 Motor Amps 1 9.90 Corrected Nameplate Amps 12.79 Volts/Amps Measured By RMS Clamp Meter Motor Data F-01/Supply Fan Motor Manufacturer Embedded Motor HP Not Given Motor RPM Not Given Motor Frame Not Given Motor Phase 1 Motor Rated Volts 120 Motor FL Amps 12.9 (Unit Amps) Motor Service Factor 1.0 Sheave Data F-01/Supply Fan Drive Type Direct Drive Final Data Fan Flow Test Method Flowhood Summation OA Damper Pos Not Applicable % OA Flow Test Method Airfoil Traverse Measured Data F-01/Supply Fan Fan RPM Actual Direct Drive Fan Speed / Setpoint Tested on cooling speed Operating Hertz 60 Filter Data F-01/SF Filter Bank Filter Type RETURN / OSA AIR MERV Rating MERV 11 Filter Quantity (set 1)1 Filter Size (set 1)20X25X4 JEDI Balancing, Inc. Page 3 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: F-01/SPP-01 Test Data Actual TSP 0.84 in. w.c. External SP 0.50 in. w.c. Test Pressures Filter SP In -0.20 in. w.c. Filter SP Out -0.36 in. w.c. DX Coil SP In 0.46 in. w.c. DX Coil SP Out 0.30 in. w.c. Gas Heat Exchanger In 0.48 in. w.c. Gas Heat Exchanger Out 0.46 in. w.c. Supply Fan SP In -0.36 in. w.c. Supply Fan SP Out 0.48 in. w.c. Static Pressure Profile System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM Outlet-01 DINING SD 8"165 225 155 94 Flow Hood Outlet-02 DINING SD 8"180 250 170 94 Flow Hood Outlet-03 DINING SD 8"180 225 165 92 Flow Hood Outlet-04 DINING SD 8"180 65 165 92 Flow Hood Outlet-05 DINING SD 8"180 140 170 94 Flow Hood Outlet-06 DINING SD 8"180 280 180 100 Flow Hood Outlet-07 DINING SD 8"165 110 155 94 Flow Hood Outlet-08 DINING SD 8"180 120 170 94 Flow Hood Outlet-09 DINING SD 8"180 100 165 92 Flow Hood Outlet-10 BAR SD 8"180 120 170 94 Flow Hood Outlet-11 WOMENS LOCKER CD 6"75 110 80 107 Flow Hood Outlet-12 WOMENS LOCKER CD 6"75 55 70 93 Flow Hood Totals:---1920 1800 1815 95 ---- F-01 Supply Outlet Summary JEDI Balancing, Inc. Page 4 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: F-02 Unit Data Unit Manufacturer TRANE Unit Model Number S9V2C100U4VSADA Unit Serial Number 23326PEJKG Starter Data F-02/Supply Fan Starter Manufacturer Thermally Protected Design Data Total Flow Design 1770 Supply Fan Design ESP 0.62 in. wc Supply Fan Design TSP Not Given in. wc Supply Fan Design RPM Not Given Supply Fan Motor Design HP Not Given Supply Fan Motor Design RPM Not Given Supply Fan Motor Design Volts 120 Supply Fan Motor Design Phase 1 Design Filter MERV Rating Not Given Test Data Connected Actual Supply Airflow 1620 1715 Outside Airflow 0 0 Return Airflow 1715 Electrical Test Data F-02/Supply Fan Motor Volts 1 123 Motor Amps 1 10.40 Corrected Nameplate Amps 12.59 Volts/Amps Measured By RMS Clamp Meter Motor Data F-02/Supply Fan Motor Manufacturer Embedded Motor HP Not Given Motor RPM Not Given Motor Frame Not Given Motor Phase 1 Motor Rated Volts 120 Motor FL Amps 12.9 (Unit Amps) Motor Service Factor 1.0 Sheave Data F-02/Supply Fan Drive Type Direct Drive Final Data Fan Flow Test Method Flowhood Summation Measured Data F-02/Supply Fan Fan RPM Actual Direct Drive Fan Speed / Setpoint Tested on cooling speed Operating Hertz 60 Filter Data F-02/SF Filter Bank Filter Type RETURN AIR MERV Rating MERV 11 Filter Quantity (set 1)1 Filter Size (set 1)20X25X4 JEDI Balancing, Inc. Page 5 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: F-02/SPP-01 Test Data Actual TSP 0.87 in. w.c. External SP 0.46 in. w.c. Test Pressures Filter SP In -0.17 in. w.c. Filter SP Out -0.33 in. w.c. DX Coil SP In 0.50 in. w.c. DX Coil SP Out 0.29 in. w.c. Gas Heat Exchanger In 0.54 in. w.c. Gas Heat Exchanger Out 0.50 in. w.c. Supply Fan SP In -0.33 in. w.c. Supply Fan SP Out 0.54 in. w.c. Static Pressure Profile System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM Outlet-01 KITCHEN SD 10"295 280 320 108 Flow Hood Outlet-02 KITCHEN SD 10"295 230 310 105 Flow Hood Outlet-03 BOH SD 10"295 390 310 105 Flow Hood Outlet-04 BOH SD 10"245 340 270 110 Flow Hood Outlet-05 BOH SD 10"295 320 300 102 Flow Hood Outlet-06 BOH SD 8"195 190 205 105 Flow Hood Totals:---1620 1750 1715 106 ---- F-02 Supply Outlet Summary JEDI Balancing, Inc. Page 6 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: MAU-01 Unit Data Unit Manufacturer CAPTIVE AIRE Unit Model Number A2-D.250-20D-MPU Unit Serial Number 6476229 MAU-01 Starter Data MAU-01/Supply Fan Starter Manufacturer LENZE (VFD) Design Data Total Flow Design 2500/2000 Supply Fan Design ESP 0.5 in. wc Supply Fan Design TSP Not Given in. wc Supply Fan Design RPM 1391 Supply Fan Motor Design HP 1.5 Supply Fan Motor Design RPM 1391 Supply Fan Motor Design Volts 208 Supply Fan Motor Design Phase 3 Design Filter MERV Rating Not Given Test Data Connected Actual Supply Airflow 2500 2400 Outside Airflow 2500 2400 Electrical Test Data MAU-01/Supply Fan Motor Volts 1 247 Motor Volts 2 246 Motor Volts 3 246 Motor Amps 1 5.40 Motor Amps 2 5.35 Motor Amps 3 5.40 Corrected Nameplate Amps 5.57 Actual BHP 1.45 Volts/Amps Measured By RMS Clamp Meter Motor Data MAU-01/Supply Fan Motor Manufacturer TECO Motor HP 1.5 Motor RPM 1170 Motor Frame 182T Motor Phase 3 Motor Rated Volts 208-230/460 Motor FL Amps 6.6-6.01/3.0 Motor Service Factor 1.15 Sheave Data MAU-01/Supply Fan Drive Type Direct Drive Final Data Fan Flow Test Method Velgrid Traverse Measured Data MAU-01/Supply Fan Fan RPM Actual Direct Drive Fan Speed / Setpoint 72 hz Operating Hertz 72 hz Filter Data MAU-01/SF Filter Bank Filter Type Washable Metal Filter Quantity (set 1)Built into unit JEDI Balancing, Inc. Page 7 of 26 Air Handling UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: MAU-01/SPP-01 Test Data Actual TSP 0.78 in. w.c. External SP 0.35 in. w.c. Test Pressures Filter SP In Atmosphere in. w.c. Filter SP Out -0.10 in. w.c. DX Coil SP In 0.48 in. w.c. DX Coil SP Out 0.35 in. w.c. Gas Heat Exchanger In -0.10 in. w.c. Gas Heat Exchanger Out -0.30 in. w.c. Supply Fan SP In -0.30 in. w.c. Supply Fan SP Out 0.48 in. w.c. Static Pressure Profile System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM Outlet-01 KITCHEN HOOD 12/28 835 830 830 99 Velgrid 5.20 5.20 160 Outlet-02 KITCHEN HOOD 12/28 830 770 770 93 Velgrid 5.20 5.20 148 Outlet-03 KITCHEN HOOD 12/28 835 800 800 96 Velgrid 5.20 5.20 154 Totals:---2500 2400 2400 96 ---- MAU-01 Supply Outlet Summary JEDI Balancing, Inc. Page 8 of 26 Energy Recovery UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: ERV-01 Unit Data Unit Manufacturer RENEWAIRE Unit Model Number HE10IN Unit Serial Number C24101755C Starter Data ERV-01/Exhaust Fan Starter Manufacturer Thermally Protected ERV-01/Supply Fan Starter Manufacturer Thermally Protected Design Data Supply OA Flow Design 725 Supply Fan Design ESP 0.5 in. wc Supply Fan Design TSP Not Given in. wc Supply Fan Design RPM Not Given Supply Fan Motor Design HP (2) 0.5 Supply Fan Motor Design RPM Not Given Supply Fan Motor Design Volts 120 Supply Fan Motor Design Phase 1 Design Filter MERV Rating Not Given Exhaust Fan Flow Design 725 Exhaust Fan Design SP 0.5 in. wc Test Data Connected Actual Supply Airflow 725 680 Exhaust Airflow 725 650 Electrical Test Data ERV-01/Exhaust Fan Motor Volts 1 123 Motor Amps 1 5.40 Corrected Nameplate Amps 6.34 Actual BHP 0.55 Volts/Amps Measured By RMS Clamp Meter ERV-01/Supply Fan Motor Volts 1 123 Motor Amps 1 5.70 Corrected Nameplate Amps 6.34 Actual BHP 0.58 Volts/Amps Measured By RMS Clamp Meter Motor Data ERV-01/Exhaust Fan Motor Manufacturer Embedded Motor HP 480 watts Motor RPM Not Given Motor Frame Not Given Motor Phase 1 Motor Rated Volts 115 Motor FL Amps 6.50 Motor Service Factor 1.0 ERV-01/Supply Fan Motor Manufacturer Embedded Motor HP 480 watts Motor RPM Not Given Motor Frame Not Given Motor Phase 1 Motor Rated Volts 115 Motor FL Amps 6.50 Motor Service Factor 1.0 Sheave Data ERV-01/Exhaust Fan Drive Type Direct Drive ERV-01/Supply Fan Drive Type Direct Drive Final Data Supply OA Flow Test Method Airfoil Traverse Exhaust Flow Test Method Flowhood Summation Measured Data ERV-01/Exhaust Fan Fan RPM Actual Direct Drive Fan Speed / Setpoint Speed control on highest setting Operating Hertz 60 ERV-01/Supply Fan Fan RPM Actual Direct Drive Fan Speed / Setpoint Speed control on highest setting Operating Hertz 60 Filter Data ERV-01/EF Filter Filter Type EXHAUST AIR MERV Rating MERV 8 Filter Quantity (set 1)1 Filter Size (set 1)20X20X2 ERV-01/SF Filter Filter Type OSA AIR MERV Rating MERV 8 Filter Quantity (set 1)1 Filter Size (set 1)20X20X2 JEDI Balancing, Inc. Page 9 of 26 Energy Recovery UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: ERV-01 Filter Data Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: ERV-01/SPP-EXHAUST Test Data Actual TSP 0.69 in. w.c. External SP 0.39 in. w.c. Test Pressures Filter SP In -0.20 in. w.c. Filter SP Out -0.29 in. w.c. EF HEX SP In -0.29 in. w.c. EF HEX SP Out -0.50 in. w.c. Exhaust Fan SP In -0.50 in. w.c. Exhaust Fan SP Out 0.19 in. w.c. Static Pressure Profile JEDI Balancing, Inc. Page 10 of 26 Energy Recovery UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: ERV-01/SPP-SUPPLY Test Data Actual TSP 0.76 in. w.c. External SP 0.36 in. w.c. Test Pressures Filter SP In -0.20 in. w.c. Filter SP Out -0.36 in. w.c. Supply Fan SP In -0.60 in. w.c. Supply Fan SP Out 0.16 in. w.c. Heat Exchanger SP In -0.36 in. w.c. Heat Exchanger SP Out -0.60 in. w.c. Static Pressure Profile System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM F-01 F-01 OA 14"725 680 680 94 Airfoil 1.07 1.07 636 Totals:---725 680 680 94 ---- ERV-01 Supply Outlet Summary System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM Inlet-01 KITCHEN ER 14"725 650 650 90 Flow Hood Totals:---725 650 650 90 ---- ERV-01 Exhaust Inlet Summary JEDI Balancing, Inc. Page 11 of 26 Fan UnitPROJECT: LOCATION: BATTLEMENT MESA GOLF COURSE RESTAURANT AND PARACHUTE, CO 2024-10243PROJECT #: DATE: CONTACT: AUTHOR: 6/25/2024 Josh Cota Donald Pittser Tested By:Bryan Hund Date:6/24/2024 SYSTEM/UNIT: KEF-01 Unit Data Fan Manufacturer CAPTIVE AIRE Fan Model Number DU200HFA Fan Serial Number 6476229 KEF-01 Type of Service EXHAUST Starter Data Starter Manufacturer LENZE (VFD) Design Data Total Flow Design 3125 Total Connected Design Flow 3125 Design ESP 1.75 in. wc Design TSP Not Given in. wc Fan Design RPM 1320 Fan Motor Design HP 5 Fan Motor Design RPM 1320 Fan Motor Design Voltage 208 Fan Motor Design Phase 3 Electrical Test Data Motor Volts 1 Actual 158 Motor Volts 2 Actual 157 Motor Volts 3 Actual 157 Motor Amps 1 Actual 11.30 Motor Amps 2 Actual 11.70 Motor Amps 3 Actual 11.88 Corrected Nameplate Amps 19.83 Actual BHP 2.93 Volts/Amps Measured By RMS Clamp Meter Motor Data Motor Manufacturer TECO Motor HP 5 Motor RPM 1750 Motor Frame 184T Motor Phase 3 Motor Rated Volts 208-230/460 Motor FL Amps 15-13.6/6.8 Motor Service Factor 1.15 Sheave Data Drive Type Direct Drive Final Data Total Fan Flow Actual 2990 Fan Flow Test Method Velgrid Traverse Measured Data Fan RPM Actual Direct Drive Fan Speed / Setpoint 45 hz Operating Hertz 45 Test Pressures Fan SP In Actual -0.48 in. wc Fan SP Out Actual Atmosphere in. wc System/Unit Area Served Outlet Type Size inch Design Airflow CFM Prelim Airflow CFM Final Airflow CFM % Final Instrument Open Area (sq ft) Ak (sq ft)Final Velocity FPM Inlet-01 KITCHEN HOOD 14/20 3125 2990 2990 96 Velgrid 14.2 14.2 211 Totals:---3125 2990 2990 96 ---- KEF-01 Exhaust Inlet Summary JEDI Balancing, Inc. Page 12 of 26 Page 13 of 26 T T M T/P P/T F MOUNTING HEIGHTS: 1. MOUNT ALL THERMOSTATS AT 54 INCHESS AFF, UNLESS NOTED OTHERWISE. CONTROL WIRING: 1. PROTECT ALL EXPOSED CONTROL AND LOW VOLTAGE WIRING BY INSTALLING WITHIN EMT CONDUIT. SUBMITTALS: 1. REFER TO GENERAL NOTES FOR SUBMITTAL REQUIREMENTS. 2. PROVIDE SEPARATE SUBMITTAL FOR EACH CATEGORY GROUP OR SCHEDULE OF ITEMS. 3. AT MINIMUM, PROVIDE SUBMITTALS FOR THE FOLLOWING: a. FANS. b. PUMPS. c. FURNACES, COILS. d. ROOF TOP UNITS. e. PACKAGED EQUIPMENT. f. GRILLES, REGISTERS, DIFFUSERS, AND DUCT ACCESSORIES. g. CONTROLS PACKAGES. h. DUCT AND DUCT INSULATION MATERIALS AND METHODS i. PIPE AND PIPE INSULATION MATERIALS AND METHODS. j. TEST AND BALANCE REPORTS. k. TERMINAL UNITS. l. CONDENSING UNITS. MECHANICAL COMMISSIONING: 1.MECHANICAL COMMISSIONING SHALL BE PERFORMED IN COMPLIANCE WITH SECTION C408 OF THE ADOPTED IECC. 2.COMMISSIONING SHALL INCLUDE ALL SCHEDULED EQUIPMENT AND WORK INDICATED AS NEW WITHIN THE PLANS AND SPECIFICATIONS. SUCH COMMISSIONING SHALL BE SUFFICIENT TO DEMONSTRATE INTENDED OPERATING CONDITIONS AND FUNCTIONS. 3.COMMISSIONING AGENTS SHALL INCLUDE BUT ARE NOT LIMITED TO: THE MECHANICAL CONTRACTOR, TAB CONTRACTOR, RELATED SUB CONTRACTORS. 4.PRELIMINARY AND FINAL COMMISSIONING REPORTS SHALL BE FURNISHED TO THE ENGINEER FOR APPROVAL. REPORTS SHALL INCLUDE ITEMIZATION OF DEFICIENCIES, DEFERRED TESTS, AND CLIMATIC CONDITIONS, AT A MINIMUM. TEST AND BALANCE: 1. PERFORM TESTING, ADJUSTING AND BALANCING (TAB) BY AN AABC, NEBB, OR TABB AGENCY WITH CURRENT CERTIFICATION. 2. TAB INCLUDES BUT IS NOT LIMITED TO (WHEN PRESENT): ADJUSTING AND RESHEAVING FANS, AIR HANDLING EQUIPMENT, PUMPS, AIR TERMINAL UNITS AND DEVICES, CALIBRATING THERMOSTATS, BALANCING VALVES, PRESSURE RELATIONSHIPS, OUTSIDE AIR DAMPERS, AND MEASURING MOTOR ELECTRICAL CHARACTERISTICS. 3. AIRSIDE TOLERANCES: a. SUPPLY, RETURN, AND EXHAUST FANS AND EQUIPMENT WITH FANS: MINUS 5 TO PLUS 10 PERCENT. b. AIR OUTLETS AND INLETS: 0 TO MINUS 10 PERCENT. 4.INDICATE % DISCREPANCY BETWEEN ACTUAL AND DESIGN VALUES FOR EACH OF THE FOLLOWING (WHEN PRESENT WITH A SPECIFIED VALUE/SETTING), AT MINIMUM: a. DIFFUSER/REGISTER/GRILLE/LOUVER. b. FAN. 5. BALANCE AIR AND WATER FLOWS TO VALUE SHOWN AT THE TERMINAL DEVICE UNLESS NOTED OTHERWISE. TERMINAL VALUES MAY DIFFER FROM CENTRAL EQUIPMENT VALUES OR CAPACITIES. PENETRATIONS AND RATED ASSEMBLIES: 1. INSTALL COMBINATION FIRE/SMOKE DAMPERS AT ALL REQUIRED RATED WALL PENETRATIONS AND BE WIRED INTO THE FIRE ALARM PANEL BY THE ELECTRICAL AND/OR FIRE ALARM PANEL CONTRACTOR. COORDINATE TO PROVIDE MOTOR VOLTAGE TO MATCH THAT OF THE FIRE ALARM PANEL. INSTALL PER THE MANUFACTURER'S INSTRUCTIONS AND THE ADOPTED CODE. 2. FIRE DAMPERS AND FIRE SMOKE DAMPERS SHALL BE UL LISTED AND INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS AND THE ADOPTED CODE. 3. PROVIDE FIRE STOP MATERIAL TO SEAL AROUND DUCT AND PIPE PENETRATIONS THROUGH RATED PARTITIONS AND ASSEMBLIES, IN ACCORDANCE WITH THE ADOPTED CODE. 4. THE SPACE ABOVE THE CEILING MAY BE USED AS A RETURN AIR PLENUM. AS SUCH, ALL MATERIALS USED ABOVE THE CEILING SHALL BE PLENUM RATED WITH A FLAME SPREAD INDEX NOT EXCEEDING 25 AND A SMOKE- DEVELOPED INDEX NOT EXCEEDING 50. MECHANICAL SPECIFICATIONS DUCTWORK: 1. CONSTRUCT ALL DUCTWORK IN ACCORDANCE WITH THE MATERIAL, PRESSURE, AND SEAL CLASS, AS INDICATED WITHIN THE PROJECT DOCUMENTS. 2. ALL DUCT SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS. ACTUAL SHEET METAL SIZE MAY VARY DEPENDING ON LINER AND WRAP SPECIFICATIONS DEFINED WITHIN THE PROJECT DOCUMENTS. 3. MATCH RUNOUT DUCTS TO SUPPLY DIFFUSERS WITH DIFFUSER NECK SIZE. 4. LIMIT LENGTH OF FLEXIBLE DUCWORK TO NO MORE THAN 8'-0". 5. AIR SYSTEMS WITH CAPACITIES GREATER THAN 2000 CFM MAY REQUIRE DUCT DETECTORS. PROVIDE DUCT DETECTORS AS PRESCRIBED BY THE ADOPTED CODE, AT THE LOCATIONS REQUIRED. DUCT DETECTORS SHALL BE INSTALLED AS FOLLOWS: MOUNTED BY MECHANICAL CONTRACTOR, POWER WIRING BY ELECTRICAL CONTRACTOR, CONTROL WIRING BY THE CONTROLS CONTRACTOR. 6. ALL AIR HANDLING EQUIPMENT IS TO HAVE VIBRATION ISOLATION. SPLIT DX SYSTEMS: 1. CONSTRUCT ALL PIPING IN ACCORDANCE WITH THE MATERIALS, FITTINGS, METHODS, AND INSULATION REQUIREMENTS, AS INDICATED ELSEWHERE WITHIN THE PROJECT DOCUMENTS. 2. INSTALL REFRIGERATION SPECIALTIES IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. 3. PIPING INSTALLATION SHALL NOT EXCEED EQUIPMENT MANUFACTURER MAXIMUM VERTICAL AND HORIZONTAL LENGTHS. CONTRACTOR TO VERIFY FINAL LENGTHS ARE IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS PRIOR TO PURCHASING AND INSTALLATION. 4. PROVIDE FACTORY STARTUP ON COMPLETE SYSTEM. ELECTRICAL ROOMS: 1. ONLY PIPING DEDICATED TO EQUIPMENT SERVING OR CONDITIONING AN ELECTRICAL ROOM MAY BE INSTALLED IN THE ELECTRICAL ROOM. IN SUCH CASES, PROVIDE SECONDARY CONTAINMENT TO PREVENT LEAKS AND/OR CONDENSATION, VIA SECONDARY CONTAINMENT BENEATH THE PIPE, WITH AUDIBLE ALARM UPON LEAK DETECTION OR VISUAL "TELL TALE" DRAIN TERMINATION LOCATION. REFERENCE NEC 110. IN NO CASE MAY PIPING OR DUCTWORK BE INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT WITHIN THE SPACE. KEYNOTE TAG REVISION TAG EQUIPMENT TAG REFER TO EQUIPMENT SCHEDULE REFERENCE EQUIPMENT TAG SPECIFIED BY ANOTHER DISCIPLINE GRILLE, REGISTER, DIFFUSER TAG AA-#-### ? ## AA-#-### NEW, OR OTHER ACTION ITEMS (Solid dark lines) ITEMS TO BE DEMOLISHED (Dashed dark lines on demo plans) EXISTING ITEMS TO REMAIN (Solid light lines and text) CONNECT NEW TO EXISTING ## Type CFM Size reference info ANNOTATION SYMBOLS LINETYPES / PHASING MECHANICAL SYMBOL LEGEND TEMPERATURE SENSOR THERMOSTAT MOTORIZED DAMPER DEVICE SYMBOLS SUPPLY / DRAIN RETURN BELOW GRADE PIPING LINE TYPES SYSTEM TYPE SYSTEM TYPE SYSTEM TYPE C CONDENSATE CA COMPRESSED AIR CD GRAVITY FLOW CONDENSATE DRAIN PCD PUMPED CONDENSATE DRAIN CH CHILLED WATER CW CONDENSATE WATER HW HEATING WATER RL/RS REFRIGERANT LINESET RS REFRIGERANT SUCTION RL REFRIGERANT LIQUID SM SNOWMELT HR HEAT RECOVERY HPS HIGH PRESSURE STEAM MPS MEDIUM PRESSURE STEAM LPS LOW PRESSURE STEAM HGBP HOT GAS BYPASS PIPE SYSTEM TYPE ABBREVIATIONS 2-WAY VALVE 3-WAY VALVE ISOLATION VALVE BALANCING VALVE TEMP. AND PRESSURE RELIEF VALVE CHECK VALVE VALVE SYMBOLS FLOW SWITCH PRESSURE GAUGE PRESSURE AND TEMPERATURE TAP THERMOMETER CONTROL & INSTRUMENTATION SYMBOLS HYDRONIC SPECIALTIES SYMBOLS AIR VENT STRAINER COUPLING & CONNECTOR SYMBOLS FLANGED CONNECTION UNION EQUIPMENT SYMBOLS PUMP DUCT SYSTEM TYPE ABBREVIATIONS FV FLUE VENT CA COMBUSTION AIR OA OUTSIDE AIR (UNCONDITIONED) FA FRESH AIR (CONDITIONED) SA SUPPLY AIR RA RETURN AIR EA EXHAUST (GENERAL) GE GREASE EXHAUST TA TRANSFER AIR DEFINITIONS: 1. CONTRACTOR: THE ENTITY BINDED BY THE PRIME AGREEMENT WITH THE CLIENT TO PERFORM THE TASKS INDICATED IN THE CONTRACT DOCUMENTS. THE TERM CONTRACTOR INCLUDES AND IMPLIES ANY RELEVANT SUB-CONTRACTOR THAT MAY BE PERFORMING THE ACTUAL TASK UNDER THE CONTRACTOR’S DIRECTION. 2. CONTRACT DOCUMENTS: THE COMPLIMENTARY COLLECTION OF DRAWINGS, SPECIFICATIONS, AND PROJECT MANUAL, WHICH ARE DIRECTED TO THE CONTRACTOR, UNDER THE PRIME AGREEMENT. 3. FURNISH: TO SUPPLY, DELIVER, UNLOAD, AND INSPECT FOR DAMAGE. 4. INSTALL: TO UNPACK, ASSEMBLE, ERECT, APPLY, PLACE, FINISH, CURE, PROTECT, CLEAN, START UP, AND MAKE READY FOR USE. 5. PROVIDE: TO FURNISH AND INSTALL. 6. SUPPLY: SAME AS FURNISH. 7. PRODUCT: MATERIAL, MACHINERY, COMPONENTS, EQUIPMENT, FIXTURES, AND SYSTEMS FORMING THE WORK RESULT. NOT MATERIALS OR EQUIPMENT USED FOR PREPARATION, FABRICATION, CONVEYING, OR ERECTION AND NOT INCORPORATED INTO THE WORK RESULT. PRODUCTS MAY BE NEW, NEVER BEFORE USED, OR RE-USED MATERIALS OR EQUIPMENT. 8. PROJECT MANUAL: THE BOOK-SIZED VOLUME THAT INCLUDES THE PROCUREMENT REQUIREMENTS (IF ANY), THE CONTRACTING REQUIREMENTS, AND THE SPECIFICATIONS. NATURE AND USE OF CONTRACT DOCUMENTS: 1. IF ANY DISCREPANCY IS FOUND WITHIN THE CONTRACT DOCUMENTS DURING CONSTRUCTION, SUBMIT AN RFI TO THE ENGINEER FOR DIRECTION BEFORE PROCEEDING. IF A DISCREPANCY IS FOUND DURING BIDDING, AND THE DESIGN TEAM DOES NOT PROVIDE A RESOLUTION BY THE FINAL ADDENDUM, BASE THE BID ON THE MORE COSTLY INTERPRETATION. FAILING TO DO SO WILL NOT BE CONSIDERED A VALID BASIS FOR CHANGE ORDERS DURING CONSTRUCTION. 2. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE CONTRACT DOCUMENTS TO ALL TRADES, AND FOR COORDINATING BETWEEN ALL TRADES TO ENSURE PROPER INSTALLATION OF COMPLETE AND FUNCTIONAL SYSTEMS AS SHOWN ON THE CONTRACT DOCUMENTS. 3. THE CONTRACTOR IS RESPONSIBLE FOR ALL SCOPES OF WORK, COMPLETENESS OF BIDS, AND PRICING EXERCISES. FURTHER, COORDINATION AND DIVISION OF SCOPE AMONGST SUB- CONTRACTORS IS THE RESPONSIBILITY OF THE CONTRACTOR. 4. DO NOT SCALE DRAWINGS FOR ROUGH-IN MEASUREMENTS OR USE AS SHOP DRAWINGS. WHERE DRAWINGS ARE REQUIRED FOR THESE PURPOSES OR HAVE TO BE MADE FROM FIELD MEASUREMENTS, TAKE THE NECESSARY MEASUREMENTS AND PREPARE THE DRAWINGS. 5. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW EVERY SYSTEM OFFSET REQUIRED. COORDINATE WITH THE EXISTING AND NEW STRUCTURE, ELECTRICAL, PLUMBING, FIRE PROTECTION AND CEILING TO PROVIDE OFFSETS AS REQUIRED AND APPROPRIATE. CODES, INSPECTIONS, AND PERMITS: 1. PERFORM ALL WORK IN ACCORDANCE WITH THE CODES, REGULATIONS, AND LOCAL AMENDMENTS, AS CURRENTLY ADOPTED BY THE AUTHORITY HAVING JURISDICTION (AHJ). 2. IF ANY DISCREPANCIES ARE FOUND BETWEEN CONTRACT DOCUMENTS AND ANY APPLICABLE CODE OR LEGAL REQUIREMENT, SUBMIT AN RFI TO ENGINEER FOR DIRECTION BEFORE PROCEEDING. 3. OBTAIN ALL PERMITS AND INSPECTIONS, AND PAY FOR ALL UTILITY METERS AND UTILITY CONNECTIONS, REQUIRED BY THE AHJ FOR PROJECT COMPLETION. WARRANTY: 1. UNCONDITIONALLY GUARANTEE ALL LABOR AND MATERIAL ON ALL WORK AGAINST DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR, FOLLOWING FINAL ACCEPTANCE, EXCEPT AS EXTENDED BY STANDARD MANUFACTURER WARRANTY AND/OR BY REQUIRED EXTENSION STATED IN THE CONTRACT DOCUMENTS. SUBMITTALS AND SUBSTITUTIONS: 1. MEET THE CRITERIA DESCRIBED HEREIN, PRIOR TO ENGINEER'S REVIEW OF THE SUBMITTAL. 2. REFERENCE EQUIPMENT TAGS PROVIDED IN THE CONTRACT DOCUMENTS. 3. CLEARLY INDICATE THE INTENDED PRODUCT TYPE, MODE, OPTIONS, ACCESSORIES (FACTORY AND FIELD INSTALLED), AND ANY OTHER OPTIONS OF ANY KIND. 4. INDICATE THE PLAN ISSUANCE AND DATE ON WHICH SUBMITTAL IS BASED. 5. IF PROPOSING A SUBSTITUTION IN PLACE OF THE BASIS OF DESIGN EQUIPMENT, THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SPATIAL REQUIREMENTS, ACOUSTICAL, THERMAL, PHOTOMETRIC, AND ELECTRICAL PERFORMANCE CHARACTERISTICS, AND COORDINATION OF ALL INSTALLATION REQUIREMENTS. REVIEW AND APPROVAL BY THE DESIGN TEAM DOES NOT ALTER OR MITIGATE THIS RESPONSIBILITY. CLEARLY MARK SUBSTITUTIONS AS SUCH. 6. DESCRIBE ANY IMPACT TO OTHER DIVISIONS CREATED BY A PRODUCT SUBSTITUTION ON THE SUBSTITUTION REQUEST FOR CONSIDERATION BY THE DESIGN TEAM. PROVIDE AN ESTIMATE OF ASSOCIATED COST IMPACT TO OTHER DIVISIONS WHERE APPLICABLE. 7. INDICATE WHERE PRODUCTS REQUIRE A PERFORMANCE DE-RATE DUE TO ALTITUDE EFFECTS. 8. RE-SUBMITTALS MUST CONTAIN MARKUPS THAT CLEARLY DELINEATE THE CHANGED ITEMS. ENGINEER WILL NOT RE-REVIEW THE ENTIRE SUBMITTAL PACKAGE IN ORDER TO FIND THE CHANGES. 9. ALL DATA REQUIRED FOR REVIEW MUST BE CONTAINED IN THE FILES PROVIDED TO THE ENGINEER. LINKS TO MANUFACTURER’S WEBSITES WILL NOT BE ACCEPTED. 10. ROOM SCHEDULES ARE ACCEPTABLE TO INDICATE QUANTITIES. PROJECT CLOSEOUT REQUIREMENTS: 1. COMPLETE ALL REQUIRED AHJ INSPECTIONS. MAKE COPIES OF PERMITS AND INSPECTION REPORTS AVAILABLE. 2. PROVIDE A COMPLETE SET OF AS-BUILT PLANS AT THE COMPLETION OF THE PROJECT WITH ALL CHANGES NOTED. 3. CONDUCT A TRAINING SESSION FOR OWNER’S DESIGNATED STAFF FOR ALL CONTROLS SYSTEMS AND MAJOR EQUIPMENT. PRODUCE A SIGN IN SHEET FOR THIS SESSION SHOWING ATTENDEES, DATE, LIST OF EQUIPMENT AND SYSTEMS COVERED. 4. CLEAN JOB SITE OF ALL CONSTRUCTION DEBRIS, REPAIR ALL DAMAGED FINISHES. REMOVE ALL EXISTING EQUIPMENT LABELS THAT ARE NO LONGER ACCURATE, AND INSTALL NEW LABELING FOR NEW EQUIPMENT AND SYSTEMS. 5. DELIVER EQUIPMENT MANUALS AND ANY REQUIRED SPARE PARTS TO OWNER. ACCESS AND CLEARANCES: 1. MAINTAIN ALL SERVICE AND ACCESS CLEARANCES REQUIRED BY CODE OR MANUFACTURER FOR ALL EQUIPMENT. 2. PROVIDE ACCESS FOR ALL EQUIPMENT, ETC. LOCATED ABOVE NON- ACCESSIBLE CEILINGS OR IN CONCEALED AREAS. PROVIDE SUFFICIENT ACCESS FOR SERVICING AND MAINTENANCE. 3. UTILIZE APPROPRIATELY RATED ACCESS PANELS WHEN PENETRATING A RATED ASSEMBLY. PENETRATIONS AND RATED ASSEMBLIES: 1. THE ARCHITECTURAL PLANS SERVE AS THE REFERENCE FOR LOCATIONS OF RATED WALLS, PARTITIONS, AND ASSEMBLIES. COORDINATE ALL PENETRATIONS PRIOR TO ROUGH IN. FOR ALL PENETRATIONS OF FIRE RATED ASSEMBLIES, UTILIZE AN ASSEMBLY UL LISTED TO MAINTAIN THE RATING AND APPROVED BY ALL APPLICABLE CODES. STRUCTURAL MODIFICATIONS: 1. DO NOT DRILL, NOTCH, CUT, OR ALTER STRUCTURAL MEMBERS IN ANY MANNER EXCEPT AS PERMITTED BY THE MATERIAL SPECIFIC SECTIONS OF THE BUILDING CODE, MANUFACTURER’S GUIDELINES FOR ENGINEERED PRODUCTS, OR THE RECOMMENDATION OF THE STRUCTURAL ENGINEER OF RECORD. EXISTING CONDITIONS AND DEMOLITION: 1. VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS TO THE EXTENT POSSIBLE BEFORE BEGINNING WORK. IF DISCREPANCIES ARE FOUND BETWEEN THE CONTRACT DOCUMENTS AND ACTUAL SITE CONDITIONS, SUBMIT AN RFI TO THE ARCHITECT OR ENGINEER FOR DIRECTION BEFORE PROCEEDING. 2. COORDINATE IN ADVANCE ALL WORK THAT AFFECTS EXISTING SYSTEMS OR OPERATIONS (SUCH AS SHUT DOWNS, TIE-INS, OR DEMOLITION), WITH THE BUILDING OWNER IN ADVANCE. 3. RETURN EXISTING EQUIPMENT NOTED AS TO BE REMOVED TO OWNER IN THE SAME CONDITION AS FOUND (EXCEPT WHERE CONTRACT DOCUMENTS CALL FOR DISPOSAL BY CONTRACTOR). COORDINATE DELIVERY AND STORAGE LOCATION WITH CONTRACTOR. 4. COORDINATE REPAIR OF ADJACENT CONSTRUCTION AND FINISHES DAMAGED OR EXPOSED DURING DEMOLITION WORK. MATCH EXISTING FINISHES, AND INCLUDE PAINT ON ENTIRE WALL OR ROOM IF REQUIRED TO MATCH COLOR. 5. X-RAY ANY SLAB PENETRATIONS PRIOR TO CORE DRILLING. 6. PRIOR TO TRENCHING OR EXCAVATION, CONTACT UTILITY COMPANIES TO IDENTIFY UNDERGROUND UTILITIES AND LOCATE SECONDARY SERVICE FEEDERS, UNDERGROUND BRANCH CIRCUITS, GAS LINES, SPRINKLER LINES, ETC. ANY CUT OR DAMAGED UNDERGROUND SYSTEMS TO BE REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE. 7. PROVIDE MEANS OF TRACING TO ALL UNDGROUND UTILITIES OUTSIDE THE BUILDING PERIMETER, IN COMPLIANCE WITH SUBSURFACE UTILITY ENGINEERING REGULATIONS. GENERAL NOTES Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 1 5 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB MECHANICAL LEGEND AND SPECIFICATIONS M001 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t MECHANICAL SHEET LIST Sheet Number Sheet Name M001 MECHANICAL LEGEND AND SPECIFICATIONS M002 SPECIFICATIONS M101 MAIN LEVEL MECHANICAL DEMO PLAN M102 MAIN LEVEL MECHANICAL PROPOSED PLAN M103 ROOF LEVEL MECHANICAL DEMO PLAN M104 ROOF LEVEL MECHANICAL PROPOSED PLAN M201 ELEVATIONS M401 ENLARGED PLANS M501 DETAILS M601 SCHEDULES M901 AXONOMETRICS ADOPTED CODES AHJ GARFIELD COUNTY LOCAL AMENDMENTS EXHIBIT A NEC 2020 IECC 2018 IBC 2015 IMC 2015 IFGC 2015 IPC 2015 SITE CONDITIONS ELEVATION AIR DENSITY RATIO CLIMATE ZONE WINTER DESIGN SUMMER DESIGN 5240' - 0" 0.81 5B -2 °F 95 °F # R e v i s i o n : D a t e : B y : 10/23/2023 Page 14 of 26 GRILLE, REGISTER, AND DIFFUSER SCHEDULE SYMBOL SERVICE MFR. & MODEL FACE TYPE MOUNTING MATERIAL FINISH DEVICE MOUNTED DAMPER ACCESSORIES / OPTIONS DESCRIPTION FACE SIZE / NECK SIZE (INCHES)NOTES S1 SUPPLY PRICE SPD SQUARE PLAQUE LAY IN STEEL FACTORY WHITE NA NA REMOVABLE SINGLE INNER CONE, MAXIMUM 1/4 INCH DROP BELOW FACE. 24X24 / 8 Ø ALL S2 SUPPLY PRICE SPD SQUARE PLAQUE LAY IN STEEL FACTORY WHITE NA NA REMOVABLE SINGLE INNER CONE, MAXIMUM 1/4 INCH DROP BELOW FACE. 24X24 / 10 Ø ALL R1 RETURN PRICE PDDR PERFORATED FACE LAY IN STEEL FACTORY WHITE NA NA SQUARE FACE, STEEL, CEILING GRILLE WITH ROUND NECK AND PERFORATED ALUMINUM FACE. 24X24 / 14X14 ALL E1 EXHAUST PRICE PDDR PERFORATED FACE LAY IN STEEL FACTORY WHITE YES TYPE SPF RAPID MOUNT FRAME SQUARE FACE, STEEL, CEILING GRILLE WITH ROUND NECK AND PERFORATED ALUMINUM FACE. 24X24 / 14Ø ALL NOTES: 1. GENERAL: VERIFY CEILING, WALL AND FLOOR CONSTRUCTION MATERIALS AND FINISHES ON THE ARCHITECTURAL DRAWINGS, AND COORDINATE BORDER TYPES/FRAMES FOR THE GRILLES, REGISTERS AND DIFFUSERS ACCORDINGLY. 2. MILL FINISH AND FACTORY WHITE FINISH SHALL BE PAINTABLE. REFER TO ARCHITECTURAL FOR PAINT COLOR (IF APPLICABLE). LOUVER SCHEDULE UNIT TAG MFR. MODEL SERVICE LOCATION AIRFLOW (CFM) AIRFLOW DIRECTION SIZE (IN)FACE VELOCITY (FPM) NET VELOCITY (FPM) WATER PENETRATION VELOCITY (FPM) PRESSURE DROP @ S.L. (IN W.G.) FREE AREA (SQ.FT.) FRAME DEPTH (IN.) FINISH NOTES WIDTH HEIGHT L-1 GREENHECK ESD-435 F-1, F-2 N WALL, ATTIC 725 INTAKE 16 24 272 642 >1100 0.067 1.13 4 MILL 1, 2 L-2 GREENHECK ESD-435 F-1, F-2 N WALL, ATTIC 725 EXHAUST 16 24 272 642 >1100 0.067 1.13 4 MILL 1, 2 NOTES: 1. LOUVER SHALL BE AMCA CERTIFIED, WITH DRAINABLE STATIONARY BLADE. 2. PROVIDE THE FOLLOWING OPTIONS AND ACCESSORIES: BIRD SCREEN. FURNACE SCHEDULE UNIT TAG MFR. MODEL CONFIG.THERMOSTAT SERVICE FAN COOLING HEATING ELECTRICAL DATA DIMENSIONS WEIGHT (LBS)NOTES SUPPLY AIRFLOW @ PROJECT ALTITUDE (CFM) MIN. OUTSIDE AIR (CFM) FAN SPEED FILTER (L X W X D) ESP @ S.L. WITH ACCESSORIES (IN.WC.) ESP @ PROJECT ALTITUDE (IN.WC.) TOTAL CAPACITY (MBH) EVAPORATOR EAT EVAPORATOR LAT EVAP. MODEL OUTDOOR COMPANION UNIT FUEL FIRED HEAT EXCHANGER VOLTS / PHASE FLA MOCP (A) LENGTH (IN) WIDTH (IN) HEIGHT (IN)DB (˚F) WB (˚F) DB (˚F) EFFICIENCY (AFUE) FUEL TYPE (NG/P) TURNDOWN OR STAGES TEMP. RISE @ ALTITUDE (˚F) INPUT CAPACITY @ S.L. (MBH) OUTPUT CAPACITY @ ALTITUDE (MBH) F-1 TRANE S9V2C100U4VSAC/D UPFLOW, RIGHT INLET T1 DINING ROOM / FOH 1770 650 H 20" X 25" X 1" (HI VEL)0.5 0.62 60.0 77 55 40.0 4TXCC009 DS3HCB CU-1 97 NG 2 STAGE 53.6 100.0 83.5 120/1 12.90 15 34 21 34 (+31 W/ EVAP) 154 (+70 W/ EVAP)ALL F-2 TRANE S9V2C100U4VSAC/D UPFLOW, RIGHT INLET T2 KITCHEN / BOH 1770 75 H 20" X 25" X 1" (HI VEL)0.5 0.62 42.0 77 55 51.1 4TXCC007 DS3HCB CU-2 97 NG 2 STAGE 53.6 100.0 83.5 120/1 12.90 15 34 21 34 (+27 W/ EVAP) 154 (+61 W/ EVAP)ALL NOTES: 1. REFER TO CONDENSER SCHEDULE FOR AMBIENT TEMPERATURES AND ADDITIONAL INFORMATION. 2. FURNISH WITH THE FOLLOWING ACCCESSORIES: DISCONNECT, CONDENSATE OVERFLOW SWITCH, AND STAINLESS STEEL DRAIN PAN. 3. UNIT SHALL INCLUDE FACTORY STARTUP. 4. FILTER NOT FURNISHED WITH UNIT. 5. PROVIDE TRANE XR203 THERMOSTAT OR APPROVED EQUAL, CAPABLE OF 2 STAGE HEATING AND SINGLE STAGE COOLING, WITH 7 DAY PROGRAMMABLE SCHEDULE. AIR COOLED CONDENSING UNIT OUTDOOR UNIT SCHEDULE UNIT TAG INDOOR UNIT TAG MFR. MODEL REFRIGERANT TYPE SOUND PRESSURE (DBA) FAN VOLUME (CFM) AMBIENT TEMP.NOMINAL CAPACITY EFFICIENCY @ AHRI UNIT ELECTRICAL DATA DIMENSIONS WEIGHT (LBS)NOTES SUMMER (F) WINTER (F) COOLING (MBH) COOLING (SEER)V / PH / HZ MCA (AMPS) MOCP (AMPS) W X H X D (IN) CU-1 F-1 TRANE 4TTR4060N1000A R410A 72 5,230 95 -2 60 14 208-230 / 1 / 60 28 50 36 X 51 X 39 302 ALL CU-2 F-2 TRANE 4TTR4042N1000A R410A 72 4,513 95 -2 42 14 208-230 / 1 / 60 20 35 36 X 42 X 39 246 ALL NOTES: 1. ALL PERFORMANCE VALUES AT PROJECT ALTITUDE UNLESS NOTED OTHERWISE. 2. FURNISH WITH OPTIONS AND ACCCESSORIES: DISCONNECT. 3. REFRIGERANT PIPING AS SPECIFIED BY PROJECT SPECIFIC LAYOUT AND COMPUTER GENERATED BILL OF MATERIALS FROM MANUFACTURER. REFER TO PLANS AND RELATED SCHEDULES FOR ADDITIONAL INFORMATION. ENERGY RECOVERY VENTILATOR SCHEDULE UNIT TAG MANUFACTURER MODEL NUMBER SUPPLY FAN EXHAUST FAN WINTER AIRSTREAM SUMMER AIRSTREAM LEAVING AIR TEMPERATURE CORE PERFORMANCE ELECTRICAL DIMENSIONS UNIT WEIGHT (LBS) NOTESALTITUDE VOLUME (CFM) MOTOR TYPE ALTITUDE ESP (IN.WG) ALTITUDE VOLUME (CFM) MOTOR TYPE ALTITUDE ESP (IN.WG) INDOOR OUTDOOR INDOOR OUTDOOR WINTER (F) SUMMER (F)TEMP. EFF% HVI TOTAL EFFICIENCY V PH HZ FAN POWER MCA MOCP HEIGHT (IN) LENGTH (IN) WIDTH (IN)DRY BULB (F) WET BULB (F) DRY BULB (F) WET BULB (F) DRY BULB (F) WET BULB (F) DRY BULB (F) WET BULB (F) SUMMER (%) WINTER (%)HP ERV-1 RENEWAIRE HE1XINH 725 ECM 0.5 725 ECM 0.5 70 48 -2 NA 75 52 95 65 48.8 80.9 70.5 45.5 68.6 120 1 60 2 @ 0.5 18.2 25 35 53.75 21.75 275 ALL NOTES: 1. AIR CONDITIONS ARE BASED ON A PROJECT ALTITUDE OF 5300 FEET ABOVE SEA LEVEL. 2. FURNISH WITH THE FOLLOWING FACTORY OPTIONS AND ACCESSORIES: TWO MERV 8 FILTERS, MOTORIZED DAMPER (INTAKE), FUSED DISCONNECT AND POTENTIOMETER SPEED CONTROL. SEQUENCES OF OPERATION: PROVIDE ALL THE NECESSARY CONTROLS, WIRING, RELAYS, SENSORS, SOFTWARE, CONTROL VALVES, AND HARDWARE TO ACHIEVE THE FOLLOWING SEQUENCES HEREIN, AND IN CONJUNCTION WITH THE PROJECT DOCUMENTS. SETPOINTS: ALL SETPOINTS ARE INDICATED VIA UNDERLINE.ADJUSTABLE INDICATES VALUE IS USER ADJUSTABLE VIA FACTORY INTERFACE OR DDC INTERFACE (NOT HARD WIRED/CODED). SPACE, ZONE, AND SLAB SETPOINTS: SPACE HEATING TEMPERATURE = 70F (ADJUSTABLE) SPACE COOLING TEMPERATURE = 75F (ADJUSTABLE) INDIVIDUAL ZONE CONTROL PROGRAMMABLE ZONE CONTROL PROVIDE A 7-DAY PROGRAMABLE THERMOSTAT SPECIFICALLY DESIGNED TO SUPPORT A FURNACE APPLICATION WITH DX COOLING, CAPABLE OF COMMUNICATING WITH AN ERV INTERLOCK. HEATING F-1 AND F-2: UPON A CALL FOR HEATING, THE FURNACE SHALL UTILIZE INTERNAL FACTORY CONTROL TO MAINTAIN SPACE HEATING TEMPERATURE. COOLING F-1/CU-1 AND F-2/CU-2: UPON A CALL FOR COOLING, THE FURNACE AND CORRESPONDING CU SHALL UTILIZE INTERNAL FACTORY CONTROL TO MAINTAIN SPACE COOLING TEMPERATURE. VENTILATION ERV-1: THE ERV SERVES AS OUTSIDE AIR VENTILATION FOR THE KITCHEN AND RESTAURANT VIA F-1 AND F-2. PROVIDE AN INTERLOCK WITH F-1 AND F-2. THE UNIT SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. UPON A CALL FOR VENTILATION THE MOTORIZED DAMPER SHALL OPEN AND ERV-1 SHALL UTILIZE INTERNAL FACTORY CONTROL TO SUPPLY OUTSIDE AIR TO THE F-1 AND F-2. THE DAMPER SHALL CLOSE WHEN THE CALL FOR VENTILATION ENDS. MAU-1: THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS. KEF-1: THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS. CU-K1: THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS. Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 2 2 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB SCHEDULES M601 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t # R e v i s i o n : D a t e : B y : 10/23/2023 Page 15 of 26 EXHAUST FAN INFORMATION - JOB#6145305 1 1 DU200HFA CAPTIVEAIRE 3125 1.750 1320 ODP,PREMIUM 5.000 2.0380 3 208 15.0 760 FPM 219 27.7 FAN UNIT NO TAG QTY FAN UNIT MODEL #MANUFACTURER CFM ESP RPM MOTOR ENCL HP BHP PHASE VOLT FLA DISCHARGE VELOCITY WEIGHT (LBS) SONES CONDENSER DETAILS 2 A2-D.250-20D-MPU 1 5 208-230 3 PHASE 60 HZ 21.4 AMPS 17.4 AMPS 30 AMPS 10 AWG 14 FAN UNIT NO TAG FAN UNIT MODEL # CONDENSER NO TONNAGE VOLTAGE PHASE FREQUENCY MCA RLA MAX FUSE SIZE MIN WIRE SIZE SEER MUA FAN INFORMATION - JOB#6145305 2 1 A2-D.250-20D-MPU 20MF-2-MOD A2-D.250 2000 2500 0.500 1391 ODP,PREMIUM 1.500 1.1520 3 208 6.6 8.3A 15A 1366 12.3 FAN UNIT NO TAG QTY FAN UNIT MODEL #BLOWER HOUSING MIN CFM DESIGN CFM ESP RPM MOTOR ENCL HP BHP PHASE VOLT FLA MCA MOCP WEIGHT (LBS) SONES COILS - JOB#6145305 2 DX 2500 93.0°F 60.0°F 64.7°F 50.0°F ------------60.0 MBH 60.0 MBH 0.0 MBH --------------------------- FAN UNIT NO TAG COIL TYPE DESIGN CFM COOLING ENTERING DB TEMP ENTERING WB TEMP LEAVING DB TEMP LEAVING WB TEMP ENTERING FLUID TEMP LEAVING FLUID TEMP FLUID FLOW RATE PERCENT GLYCOL TOTAL CAPACITY SENSIBLE CAPACITY LATENT CAPACITY HEATING ENTERING DB TEMP LEAVING DB TEMP ENTERING FLUID TEMP LEAVING FLUID TEMP FLUID FLOW RATE PERCENT GLYCOL TOTAL CAPACITY SENSIBLE CAPACITY GAS FIRED MAKE-UP AIR UNIT(S) 2 158275 145613 67°F 7 IN. W.C. - 14 IN. W.C.NATURAL 92 FAN UNIT NO TAG INPUT BTUs OUTPUT BTUs TEMP RISE REQUIRED INPUT GAS PRESSURE GAS TYPE BURNER EFFICIENCY(%) FAN OPTIONS 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 GREASE BOX FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS 2 YEAR PARTS WARRANTY INLET PRESSURE GAUGE, 0-35" MANIFOLD PRESSURE GAUGE, -5 TO 15" WC BUTTERFLY MOD VALVE OPTION FOR MOD SIZE 2 (1" MOD VALVE) SHIP LOOSE GAS STRAINER 1" CASLINK BUILDING MONITORING SYSTEM - INTERNET OR CELLULAR CONNECTION REQUIRED MOTORIZED BACKDRAFT DAMPER FOR A2-D HOUSING - MEETS AMCA CLASS 1A RATING 5 TON SINGLE CIRCUIT MODULAR PACKAGED AC COOLING OPTION FOR SIZE 2 DF/EH MUA (1000 TO 2750 CFM), 208V/230V, 3 PHASE. COOLING THERMOSTAT OR PROGRAMMABLE STAT REQUIRED FOR PROPER OPERATION SHIP CONDENSER LOOSE - SINGLE CONDENSER, THREE PHASE - CONDENSER DISCONNECT SHIPPED LOOSE. ALL PIPING AND WIRING BETWEEN INDOOR AND OUTDOOR UNITS BY OTHERS DOWNTURN PLENUM FOR SIZE 2 DX COIL MODULE SEPARATE 120V WIRING PACKAGE (REQUIRED AND USED ONLY FOR DCV OR PREWIRE WITH VFD) - THREE PHASE ONLY SIZE 2 DIRECT FIRED HEATER LOW CFM PROFILE PACKAGE - USED ON HEATERS UNDER 2500 CFM 2 YEAR PARTS WARRANTY FAN UNIT NO TAG QTY DESCRIPTION FAN ACCESSORIES 1 2 YES YES FAN UNIT NO TAG EXHAUST GREASE CUP GRAVITY DAMPER WALL MOUNT SUPPLY SIDE DISCHARGE GRAVITY DAMPER MOTORIZED DAMPER WALL MOUNT CURB ASSEMBLIES 1 2 # 1 # 2 34 LBS 92 LBS CURB CURB 26.500"W X 26.500"L X 26.000"H 4.000:12.000 PITCH ALONG LENGTH, RIGHT VENTED HINGED. 31.000"W X 145.000"L X 20.000"H INSULATED. NO ON FAN WEIGHT ITEM SIZE - VARIABLE SPEED CONTROL. - THERMAL OVERLOAD PROTECTION (SINGLE PHASE). - HIGH HEAT OPERATION 300°F (149°C). EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 300°F (149°C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. NORMAL TEMPERATURE TEST 26" 28" 37 3/8" 18" 2" 29 1/2" - INTERNAL WIRING. - ROOF MOUNTED FANS. - RESTAURANT MODEL. FEATURES: - DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS). TOP VIEW 37 3/8" 28" - NEMA 3R SAFETY DISCONNECT SWITCH. DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS). 33 3/8" GREASE DRAIN. - GREASE CLASSIFICATION TESTING. - UL705 AND UL762 AND ULC-S645 ABNORMAL FLARE-UP TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 600°F (316°C) FOR A PERIOD OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION. 26" 26" ROOF OPENING DIMENSIONS. 26" 26 1/2" 20 GAUGE CONSTRUCTION. STEEL 3" FLANGE. 26 1/2" HINGE KIT VENTED CURB. EXAMPLE: 7/12 PITCH = 30° SLOPE. PITCHED CURBS ARE AVAILABLE FOR PITCHED ROOFS. SPECIFY PITCH: 4" 18° 12" FAN #1 DU200HFA - EXHAUST FAN OPTIONS - GREASE BOX. - FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS. - 2 YEAR PARTS WARRANTY. SHEET NO. SCALE: DWG.#: DRAWN DATE: BY: REVISIONS DESCRIPTION ww w . c a p t i v e a i r e . c o m DATE: AC C O R D A N C E No . 9 6 BU I L T NF P A WI T H IN S LI D TE R C U S 6145305 MASTER DRAWING tom.oates 3 10/11/2023 Th e R o u g h B a r 3/4" = 1'-0" PA R A C H U T E , C O , 8 1 6 3 5 De n v e r O f f i c e 73 0 0 S A l t o n W a y B u i l d i n g 5 , S u i t e B , C e n t e n n i a l , C O , 8 0 1 1 2 P H O N E : ( 7 2 0 ) 5 7 0 - 0 9 8 1 F A X : 9 1 9 2 2 7 5 9 9 9 E M A I L : r e g 4 2 @ c a p t i v e a i r e . c o m Page 16 of 26 1 2 3 4 5 6 7 8 9 B C D E F CURB 26.5"X26.5". MAX ROOF OPENING 26" X 26" CENTERED AS INDICATED. 14"X20" GE AT 20"X26" O.D. ROOF CURB, 31"x145" OD. M201 1 MAU-1 R 1 0 ' - 0 " (EX) INTAKE GRAV. HOOD KEF-1 14"x20" GE 3' - 0" 3' - 0 " (EX) EF-1 3"ø FV 3"ø FV 3"ø FV 3"ø FV 2' - 4 " 1 1 1 1 2 3 4 5 AA ROOF ACCESS LADDER. RE: ARCH. LADDER OVER PARAPET WALL. RE: ARCH. Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 1 9 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB ROOF LEVEL MECHANICAL PROPOSED PLAN M104 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t NORTH SCALE: 1/4" = 1'-0"1 ROOF LEVEL PROPOSED PLAN - MECHANICAL KEYNOTES 1 FLUE VENT THROUGH ROOF. TERMINATE PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. 2 NEW LOCATION OF AHU-2 (EX) FLUE. MATCH MATERIALS AND EXTEND FLUE IN ATTIC AS NEEDED. 3 KEF-1 OUTLET SHALL BE MIN 40" ABOVE ROOF SURFACE AND 10' FROM ANY PART OF THE BUILDING IN COMPLIANCE WITH IMC SECTION 506.3.13.3. 4 MAU-1 INLET SHALL HAVE NO EXHAUST DISCHARGE WITHIN 10' PER IMC SECTION 401.4. 5 MAU-1 SUPPLY DUCT DOWN THROUGH CURB INTO BUILDING. GENERAL MECHANICAL NOTES 1 REFER TO CAPTIVEAIRE SHEETS FOR ALL SPECIFICATIONS, SEQUENCES AND DIMENSIONAL DRAWINGS IN RELATION TO KEF-1, MAU-1 AND HD-1. # R e v i s i o n : D a t e : B y : 10/23/2023 KEF-01 MAU-01 Page 17 of 26 5-TIER(86) 4-TIER(74) 3621 18 T2 T1 GMS ENTRY FOYER COVERED PATIO PRO SHOP BAG STORAGE STORAGE OFFICE REPAIR MECH. MENS RESTROOM / LOCKER WOMENS RESTROOM / LOCKER REFRIG. ROOM KITCHEN BAR RESTAURANT 1 2 3 4 5 6 7 8 9 B C D E F HD-1 10X8 EA UP TO EF-1 (EX) (EX) GRILLE, 100 CFM (EX) GRILLE, 100 CFM S4 (EX)6"ø 75 CFM S4 (EX)6"ø 75 CFM L1 16"x24" 725 CFM M M201 1 F-2 F-1 CU-1 CU-2 CU-K1 ERV-1 S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 165 CFM 14"x14" SA PROPOSED ROOF ACCESS LADDER SHALL HAVE 30" CLEAR LANDING. RE: ARCH 3"ø FV IWH-1 14" X 20" GE UP TO KEF-1 10"x10" OA 8"ø OA 24"x8" RA 1 2 3 4 26"x14" SA A M401 1 14"x26" SA L2 16"x24" 725 CFM 3"ø FV 3"ø FV 3"ø FV 3"ø FV 14 " x 1 4 " S A Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 1 9 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB MAIN LEVEL MECHANICAL PROPOSED PLAN M102 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t NORTH SCALE: 1/4" = 1'-0"1 MAIN LEVEL PROPOSED PLAN - MECHANICAL KEYNOTES 1 GE WITH UL LISTED 2-HR FIRE RATED WRAP CENTERED BETWEEN EXISTING TRUSSES. ALL GE SHALL SLOPE TO HOOD CONNECTION AT MIN 1/4" / 12". PROVIDE CLEANOUTS PER IMC SECTION 506.3.9. 2 REQUIRED SERVICE CLEARANCE OF CONDENSING UNITS. 3 PROVIDE CAP AT EXISTING. 4 SA FROM MAU-1 ON ROOF. GENERAL MECHANICAL NOTES 1 REFER TO CAPTIVEAIRE SHEETS FOR ALL SPECIFICATIONS, SEQUENCES AND DIMENSIONAL DRAWINGS IN RELATION TO KEF-1, MAU-1 AND HD-1. # R e v i s i o n : D a t e : B y : 10/23/2023 F-01 56 7 1 2 3 48 9 10 Page 18 of 26 5-TIER(86) 4-TIER(74) 3621 18 T2 T1 GMS 1 1 2 2 3 3 4 4 B B C C D D ENTRY FOYER WOMENS RESTROOM / LOCKER KITCHEN BAR RESTAURANT HD-1 12"x28" SA 12"x28" SA 12"x28" SA 14"x26" SA 10X8 EA UP TO EF-1 (EX) (EX) GRILLE, 100 CFM (EX) GRILLE, 100 CFM 8"x6" EA 6" x 6 " E A S4 (EX)6"ø 75 CFM S4 (EX)6"ø 75 CFM L1 16"x24" 725 CFM M 14 " x 1 0 " O A F-2 F-1 L2 16"x24" 725 CFM ERV-1 12 " ø E A 14"ø EA 14"ø FA 12"ø EA 14 " ø F A 14"x24" RA 16"x18" SA 16"x18" SA S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 180 CFM S1 8"ø 165 CFM S1 8"ø 195 CFM S2 10"ø 245 CFM S2 10"ø 295 CFM S2 10"ø 295 CFM S2 10"ø 295 CFM S2 10"ø 295 CFM 16 " x 1 8 " S A 16 " x 1 8 " S A 14 " x 1 4 " S A 1/ 4 " / 1 ' -0" 650 CFM 75 CFM 1 1 8"ø SA 21/4" / 1'-0"3"ø FV 3"ø FV 3"ø FV 3"ø FV 3"ø CA 3"ø CA 3"ø CA 3"ø CA E1 14"ø 725 CFM 18"x18" RA 14"x24" RA R1 14"x14" R1 14"x14" R1 14"x14" IWH-1 14 " x 1 4 " R A R1 14"x14"R1 14"x14"1/4" / 1'-0"14"x20" GE 14"x20" GE 14" X 20" GE UP TO KEF-1 18 " x 1 8 " R A 14 " x 1 4 " R A 6"ø FA 14"x14" RA 14"x14" RA 14"x14" RA 12"ø EA 14"ø FA 14"ø FA 3 4 5 5 55 6 6 7 7 7 8 9 7 10 14 " x 2 0 " G E 14"x26" SA CU-2 CU-1 Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 2 1 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB ENLARGED PLANS M401 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t NORTH SCALE: 1/2" = 1'-0"1 ENLARGED MECHANICAL PLAN KEYNOTES 1 BALANCE TO VOLUME INDICATED. 2 CONNECT TO EXISTING DUCT SERVING WOMEN'S RESTROOM. 3 GE WITH UL LISTED 2-HR FIRE RATED WRAP CENTERED BETWEEN EXISTING TRUSSES. ALL GE SHALL SLOPE TO HOOD CONNECTION AT MIN 1/4" / 12". PROVIDE CLEANOUTS PER IMC SECTION 506.3.9. 4 MOTORIZED DAMPER INTERLOCKED WITH ERV-1. 5 PROVIDE WALL INLET PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. 6 BALANCING DAMPER ABOVE ACCESSIBLE CEILING. TYPICAL. 7 3" FV UP THROUGH ROOF. 8 PROVIDE LONG RADIUS ELBOWS WITH NO TURNING VANES ON GREASE DUCT. 9 PROVIDE WRAPPED INSULATION IN COMPLIANCE WITH IMC SECTION 506.3.6(3). REFER TO DUCT INSULATION SPECIFICATION. 10 GE UP TO KEF-1. # R e v i s i o n : D a t e : B y : 10/23/2023 F-01 F-02 ERV-01 1 2 3 48 9 10 KEF-01 MAU-01 12 11 2 1 34 56 123 1 1 Page 19 of 26 DUCT CONSTRUCTION SPECIFICATION SYSTEM SUB-SYSTEM PRESSURIZATION APPLICATION PRESSURE CLASS (IN. W.C.) SEAL CLASS MATERIAL EXHAUST ALL U.N.O NEGATIVE NON-RECIRCULATED AIR FROM INTERIOR TERMINAL INLET DEVICE TO OUTDOOR TERMINATION DEVICE.-1 C GALVANIZED EXHAUST ALL U.N.O POSITIVE NON-RECIRCULATED AIR FROM INTERIOR TERMINAL INLET DEVICE TO OUTDOOR TERMINATION DEVICE.+1 A GALVANIZED OUTSIDE AIR SUPPLY (FRESH AIR) ALL U.N.O POSITIVE CONDITIONED OUTSIDE AIR FROM THE CONDITIONING EQUIPMENT OUTLET TO THE TERMINAL DEVICE OR MIXING POINT WITH OTHER SYSTEM. +1 C GALVANIZED RAW OUTSIDE AIR INTAKE ALL U.N.O. NEGATIVE UNCONDITIONED OUTSIDE AIR FROM THE INLET DEVICE TO THE CONDITIONING EQUIPMENT INLET.-1 C GALVANIZED SUPPLY ALL U.N.O POSITIVE CONDITIONED AIR DOWN STREAM OF CONDITIONING EQUIPMENT.+1 B GALVANIZED RETURN ALL U.N.O NEGATIVE RECIRCULATED AIR FROM TERMINAL INLET DEVICE TO CONDITIONING EQUIPMENT.-1 C GALVANIZED TRANSFER ALL U.N.O. POSITIVE INTERIOR AIR TRANSFERRED BETWEEN SPACES. +1/2 C GALVANIZED GREASE EXHAUST ALL U.N.O. NEGATIVE ALL GREASE EXHAUST DUCTWORK -4 A STEEL FULLY WELDED NOTES FOR ALL DUCTWORK: 1. ALL DUCT SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA. GALVANIZED SHEET METAL CONSTRUCTION: 1. GAUGES SHALL BE PER SMACNA LOW PRESSURE SYSTEMS. 2. SHEET METAL DUCT SHALL BE CONSTRUCTED OF LOCK FORMING QUALITY GALVANIZED STEEL SHEET, WITH A G90 ZINC COATED FINISH, AND IN COMPLIANCE WITH ASTM-A653. STEEL GREASE EXHAUST CONSTRUCTION: 1. GAGES SHALL BE MINIMUM NO.16 (0.0575 INCH) PER IMC SECTION 506.3.1.1. 2. SHEET METAL DUCT SHALL BE CONSTRUCTED OF A CONTINUOUS LIQUID-TIGHT WELD OR BRAZE MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM. 3. ALL JOINTS, FITTINGS, AND FASTENING HARDWARE SHALL BE OF THE SAME GRADE STEEL. 4. INTERNAL WELDING OR BRAZING SHALL NOT BE PROHIBITED PROVIDED THAT THE JOINT IS FORMED OR GROUND SMOOTH AND IS PROVIDED WITH READY ACCESS FOR INSPECTION. 5. PRIOR TO USE OR CONCEALMENT OF ANY PORTION OF THE GREASE DUCT SYSTEM, A LEAK TEST MUST BE PERFORMED IN ACCORDANCE WITH IMC SECTION 506.3.2.5. MECHANICAL DUCT INSULATION SPECIFICATION SYSTEM TYPE DUCT TYPE LOCATION SUB-SYSTEM AIR STREAM DESCRIPTION INTERNAL LINER (IN.) EXTERNAL WRAP (IN.) REQUIRED R-VALUE (INSTALLED) NOTES SUPPLY ROUND INTERIOR ALL U.N.O. CONDITIONED AIR DOWN STREAM OF CONDITIONING EQUIPMENT IN UN-INSULATED ATTIC. NA 2.5 R-6 SUPPLY RECTANGULAR INTERIOR ALL U.N.O. CONDITIONED AIR DOWN STREAM OF CONDITIONING EQUIPMENT IN UN-INSULATED ATTIC. NA 2.5 R-6 SUPPLY FLEX INTERIOR ALL U.N.O. CONDITIONED AIR DOWN STREAM OF CONDITIONING EQUIPMENT IN UN-INSULATED ATTIC. PRE- INSULATED PRE- INSULATED R-6 RETURN RECTANGULAR INTERIOR ALL U.N.O. RECIRCULATED AIR FROM TERMINAL INLET DEVICE TO CONDITIONING EQUIPMENT IN UN- INSULATED ATTIC. NA 2.5 R-6 RETURN ROUND INTERIOR ALL U.N.O. RECIRCULATED AIR FROM TERMINAL INLET DEVICE TO CONDITIONING EQUIPMENT IN UN- INSULATED ATTIC. NA 2.5 R-6 RAW OUTSIDE AIR INTAKE RECTANGULAR INTERIOR ALL U.N.O. UNCONDITIONED OUTSIDE AIR FROM THE INLET DEVICE TO THE CONDITIONING EQUIPMENT INLET.NA (2) LAYERS @2.5 R-12 OUTSIDE AIR SUPPLY (FRESH AIR) RECTANGULAR INTERIOR ALL U.N.O. CONDITIONED OUTSIDE AIR FROM THE CONDITIONING EQUIPMENT INLET TO THE TERMINAL DEVICE OR MIXING POINT WITH OTHER SYSTEM IN UN-INSULATED ATTIC. NA 2.5 R-6 GREASE EXHAUST ROUND, RECTANGULAR INTERIOR ALL U.N.O. ALL KITCHEN HOOD EXHAUST FROM HOOD TO ROOF CURB NA (2) LAYERS 1.5" FIRE BARRIER NA 2-FIRE RATED BARRIER WRAP, NOTE 3 EXHAUST ROUND INTERIOR ALL U.N.O. NON-RECIRCULATED AIR FROM INTERIOR TERMINAL INLET DEVICE TO OUTDOOR TERMINATION DEVICE. NA NA NA NOTES: 1. INSULATION IS NOT REQUIRED VIA THE FOLLOWING: ALL DUCT IS LOCATED IN A CONDITIONED SPACE. AN INDIRECTLY HEATED SPACE SEPERATED BY UNINSULATED CEILINGS MAY BE CONSIDERED A CONDITIONED SPACE PER IECC CHAPTER 2 DEFINITION. PER IECC SECTION C403.2.9 INSULATION IS ONLY REQUIRED FOR UNCONDITIONED SPACES. 2. INSULATION IS NOT REQUIED VIA IECC C403.2.9 EXCEPTION 2. THE DESIGN TEMPERATURE DIFFERENCE FOR THIS SYSTEM IS LESS THAN 15 DEGREES. SPECIFICATION: ALL INSTALLATION METHODS, INCLUDING APPLICATION, SEALING, JOINTS, ETC. SHALL BE PER THE MANUFACTURER'S RECOMMENDATIONS. ALL INTERIOR INSULATION SHALL BE PLENUM RATED. ALL PRODUCTS SHALL BE LABELED FOR NFPA 90A AND 90B COMPLIANCE. LINER: 1. JM LINEACOUSTIC RC. WRAP: 1. INTERIOR A. JM MICROLITE FSK 0.75 LB DENSITY. B. COMPOSITE FHC 25/50 2. EXTERIOR A. JM 800 SERIES SPIN GLASS 3 LB DENSITY. B. FLEXCLAD 250 ALUMINUM JACKET APPLIED OVER INSULATION, SUITABLE FOR EXPOSED EXTERIOR INSTALLATIONS. C. COMPOSITE FHC 25/50 3. 2-HOUR FIRE RATED BARRIER: A. 3M FIRE BARRIER DUCT WRAP 615+, 1.5 INCH, 6 PCF DENSITY RATED FOR CONTINUOUS USE AT 1832F. B. 3M FIRE BARRIER SEALANT. C. ASTM E2336. D. 3M FIRE BARRIER DUCT WRAP 615+. E. ZERO CLEARANCE TO COMBUSTIBLES. F. FOIL SCRIM BACKING. OUTDOOR AIR VENTILATION CALCULATION PER IMC ZONE EQUIPMENT TAG SYSTEM TYPE (EQUATION FOR VOT) SPACE ZONE FLOOR AREA (AZ) (SQ. FT.) OCCUPANT DENSITY (PEOPLE PER 1,000 SQ. FT.) ZONE POPULATION - PER ARCHITECTURA L LAYOUT OA FLOW RATE PER PERSON (RP) (CFM/PERSON) OA FLOW RATE PER UNIT AREA - TABLE 6-1 (RA) CFM/SF ZONE POPULATION (PZ) SYSTEM POPULATION (PS) BREATHING ZONE OA FLOW (VBZ) (CFM) ZONE AIR DISTRIBUTION EFFECTIVENESS (EZ) ZONE OUTDOOR AIRFLOW (VOZ) (CFM) ZONE PRIMARY OA FRACTION (ZP) SYSTEM VENTILATION EFFICIENCY - TABLE 6-3 OR APPENDIX A (EVZ) UNCORRECTED OUTDOOR AIR INTAKE (VOU) (CFM) SYSTEM VENTILATION EFFICIENCY - TABLE 6-3 OR APPENDIX A (EV = MIN(EVZ)) OA REQUIRED (VOT) (CFM) OA PROVIDED (ZRTU) (CFM) COMPLIES WITH CODE (ZRTU>VOT) F-1 / ERV-1 SINGLE ZONE FRONT OF HOUSE 937 NA 63 7.5 0.18 63 63 641 1.0 641 NA NA NA NA 641 650 YES F-2 / ERV-1 SINGLE ZONE BACK OF HOUSE 373 NA 2 7.5 0.12 2 63 60 1.0 60 NA NA NA NA 60 75 YES REMARKS: 1. IMC CHAPTER 4 IS BASED ON THE ASHRAE 62.1. OCCUPANT DIVERSITY MAY BE IMPLIED IN SOME ZONES. REFER TO SECTION 403, EQUATION 4-7. 2. SOME HEATED SPACES WILL BE IN COOLING MODE DURING FULL OCCUPANCY; THEREFORE EV VALUES REFLECT ACTUAL OPERATING CONDITION AT TIME OF DESIGN OCCUPANCY. 3. BACK OF HOUSE VENTILATED VIA KITCHEN EXHAUST FAN AND MAKE-UP AIR UNIT. COMBUSTION AIR AND FLUE SPECIFICATION SYSTEM DESCRIPTION MAX. OPERATING GAS TEMPERATURE NOMINAL SIZE MANUFACTURER & MATERIAL FITTINGS TERMINATION AND ADAPTERS LISTING FURNACES F-1, F-2 HIGH EFFICEINCY FURNACE COMBUSTION AIR INTAKE AND VENTING FOR CATEGORY IV FURNACES 230F 3" CENTROTHERM INNOFLUE SINGLE-WALL RIGID POLYPROPYLENE SINGLE-WALL RIGID POLYPROPYLENE AS SPECIFIED BY THE PIPE MANUFACTURER. UL 1738 LISTED VENTING FOR CATEGORY IV GAS- BURNING APPLIANCES. WATER HEATER IWH-1 HIGH EFFICEINCY WATER HEATER COMBUSTION AIR INTAKE AND VENTING FOR CATEGORY IV FURNACES 230F 3" CENTROTHERM INNOFLUE SINGLE-WALL RIGID POLYPROPYLENE SINGLE-WALL RIGID POLYPROPYLENE AS SPECIFIED BY THE PIPE MANUFACTURER. UL 1738 LISTED VENTING FOR CATEGORY IV GAS- BURNING APPLIANCES. NOTE: ALL CA AND FV SYSTEMS SHALL BE INSULATED WITH 1/2" THICK ARMAFLEX-TYPE INSULATION OR APPROVED EQUAL PER MANUFACTURER'S REQUIREMENTS. APPLIANCE FLUE AND COMBUSTION AIR VENT CALCULATIONS F-1 (FV) FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) FLUE VENT DUCT NA NA 37.3 3" DIA 45 SHORT ELBOW 0 5 0 3" DIA 90 SHORT ELBOW 3 10 30 TERMINATION 1 0 0 TOTAL (NOTE 2) 67.3 F1 (CA) FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) COMBUSTION AIR DUCT NA NA 28 3" DIA 45 SHORT ELBOW 2 5 10 3" DIA 90 SHORT ELBOW 1 10 10 BIRD SCREEN 1 0 0 TOTAL (NOTE 2) 48 F-2 (FV) FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) FLUE VENT DUCT NA NA 27 3" DIA 45 SHORT ELBOW 1 5 5 3" DIA 90 SHORT ELBOW 2 10 20 TERMINATION 1 0 0 TOTAL (NOTE 2) 52 F2 (CA) FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) COMBUSTION AIR DUCT NA NA 24 3" DIA 45 ELBOW 2 5 10 3" DIA 90 ELBOW 1 10 10 BIRD SCREEN 1 0 0 TOTAL (NOTE 2) 44 WATER HEATER FLUE VENT FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) 3" 45-ELBOW 2 2.5 5 3" 90-ELBOW 1 0 0 3" FLUE VENT DUCT NA NA 32 TOTAL (NOTE 3) 37 WATER HEATER COMBUSTION AIR FITTING QUANTITY EQUIVALENT LENGTH (FT) LENGTH (FT) 3" 45-ELBOW 2 0 0 3" 90-ELBOW 2 0 0 3" COMBUSTION AIR DUCT NA NA 31 TOTAL (NOTE 4) 31 NOTES: 1.CALCULATION PER MANUFACTURER'S IOM AND LAYOUT INDICATED ON THE PLANS. 2. FURNACE (TRANE S9V2C100U4VS...) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE 150' IN 3" SIZE OR AT ELEVATIONS UP TO 5400'. 3. WATER HEATER (RHEEM RTR-WM220DVLN) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE 38' IN 3" SIZE OR 94' IN 4" SIZE (WITH 0 OR 1 90 DEGREE ELBOWS) PER MANUFACTURER'S SPECIFICATIONS. 4. WATER HEATER (RHEEM RTR-WM220DVLN) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE 36.5' IN 3" SIZE WITH (2) 90 DEGREE ELBOWS PER MANUFACURER'S SPECIFICATIONS. Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 1 6 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB SPECIFICATIONS M002 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t # R e v i s i o n : D a t e : B y : 10/23/2023 Page 20 of 26 MAIN LEVEL 0' -0" 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 EXIST T.O. PLATE 10' -10" L1 16"x24" 725 CFM L2 16"x24" 725 CFM MAU-1 KEF-1 CU-K1 CU-1 CU-2 CA INTAKES Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 2 0 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB ELEVATIONS M201 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t SCALE: 1/4" = 1'-0"1 MECHANICAL - NORTH ELEVATION # R e v i s i o n : D a t e : B y : 10/23/2023 Page 21 of 26 EQUIPMENT 4" M I N EXTEND PAD 4" BEYOND EQUIPMENT PERIMETER ON ALL SIDES 4" 4" ROOF MOUNTED UNIT REQUIRING CURB BASE RAIL UNIT OVERHANGS CURB TOP OF CURB WOOD NAILER STRIP GALVANIZED METAL CURB. REFER TO PLANS FOR CURB HEIGHT. BATTING TO MATCH ROOF INSULATION R-VALUE CURB SUPPORTED DIRECTLY ON STRUCTURAL DECK, STRUCTURAL SUPPORT, OR SHIM. DO NOT REST ON ROOF INSULATION. COUNTER FLASHING RIGID INSULATION FLASHING CANTILEVER STRIP SEALED ROOFING LAYER ROOFING INSULATION ROOF DECK R 4 - 1 / 2 " LOCKING LUG 26 GAUGE MIN. FRAME DUCT VANED ELBOW TURNING VANE NOTES: 1. PROVIDE LOCKING LUGS INTEGRAL WITH VANE. 2. VANES SHALL BE 4" WIDE. 3. LIMIT VANE BANK HEIGHT TO 36". 4. FRAMES SHALL BE BOLTED OR RIVETED TO ELBOW. 5. VANES SHALL BE SAME GAUGE AS ELBOW. NO TRAILING EDGE3-1/2"AIRFLOW DIRECTION SPIN-IN FITTING WITH MANUAL VOLUME DAMPER ROUND RIGID DUCT 2" 24 GA. STRAP SUPPORT TO STRUCTURE WITH WIRE HANGER FLEXIBLE DUCT CEILING DIFFUSER LAY -IN CEILING LOW PRESSURE SUPPLY SCREW DRIVER OPERATED BAND FLEXIBLE CONNECTION SUPPLY AIR DUCT CONDENSATE PIPE FROM EVAPORATOR COIL AND HEAT EXCHANGER CONDENSATE NEUTRALIZER. TERMINATE ABOVE FLOOR SINK VIA AIR GAP (6" MIN.) VIBRATION ISOLATION MOUNTING PADS FLEXIBLE CONNECTION RETURN AIR DUCT GAS SUPPLY PIPE WITH SEDIMENT TRAP COMBUSTION AIR INTAKE AND VENT PIPE EVAPORATOR COIL 3-VANDAL PROOF SET SCREWS WATER PROOF PERMASEAL STEEL REINFORCING BOOT STRUCTURAL MEMBER SECURE TO STRUCTURE ANGLE IRON 1/2" U-BOLT ROOFING LEAD FLASHING COUNTERFLASHING CAP CAULK WITH ROOF MASTIC Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 2 2 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB DETAILS M501 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t NO SCALE1CONCRETE EQUIPMENT PAD NO SCALE2ROOF CURB NO SCALE3DUCT ELBOW TURNING VANE - SINGLE THICKNESS NO SCALE5LAY-IN MOUNTED CEILING DIFFUSER CONNECTION DETAIL NO SCALE6UPFLOW GAS FURNACE NO SCALE4PIPE THROUGH ROOF DETAIL # R e v i s i o n : D a t e : B y : 10/23/2023 Page 22 of 26 MAU-1 KEF-1 HD-1 CU-K1 CU-1 CU-2 1 4 " x 2 0 " G E 26 " x 1 4 " S A 3 "ø C A 3 "ø C A 3 "ø C A 3 "ø C A 3"ø FV 3"ø FV 3"ø FV 3"ø FV ERV-1 F-1 F-2L116"x24" 725 CFM L2 16"x24" 725 CFM IWH-1 MAU-1 KEF-1 L2 16"x24" 725 CFM 14"x20" GE 26 " x 1 4 " S A 14"x26" SA ERV-1 Title: Dwg No. Job No. Drawn by: Print Date: PE:QC: Pr o j e c t M i l e s t o n e : 11 8 W e s t S i x t h S t r e e t , S u i t e 2 0 0 Gl e n w o o d S p r i n g s , C O 8 1 6 0 1 97 0 . 9 4 5 . 1 0 0 4 ww w . s g m - i n c . c o m File: Ce n t r a l M o d e l : C: \ U s e r s \ p g o r r a \ D o c u m e n t s \ R B G _ M E P _ R 2 3 _ p a b l o g R Y F V F . r vt 1 0 / 2 3 / 2 0 2 3 1 1 : 2 6 : 2 4 A M BA T T L E M E N T M E S A GO L F C O U R S E PE R M I T S E T 2023-316 PG 10/23/23 THIB AXONOMETRICS M901 RE S T A U R A N T / K I T C H E N AD D I T I O N RBG_MEP_R23 I: \ 2 0 2 3 \ 2 0 2 3 - 3 1 6 - T h e R o u g h B a r G r i l l e \ 0 0 1 - M E P \ H - D w g s \ M ep \ R e v i t \ R B G _ M E P _ R 2 3 . r v t NO SCALE1MECHANICAL AXONOMETRIC - NORTHWEST NO SCALE2MECHANICAL AXONOMETRIC - SOUTHEAST # R e v i s i o n : D a t e : B y : 10/23/2023 Page 23 of 26 Denver Office REGION 42 PHONE: (720) 570 - 0981 EMAIL: reg42@captiveaire.com FOR QUESTIONS, CALL THE HOOD INFORMATION - JOB#6145305 1 6624 ND-2-PSP-F CAPTIVEAIRE 12' 6" 600 DEG I HEAVY 250 3125 4"18"3125 1768 -1.032"2500 430 SS WHERE EXPOSED ALONE ALONE HOOD NO TAG MODEL MANUFACTURER LENGTH MAX COOKING TEMP TYPE APPLIANCE DUTY DESIGN CFM/FT TOTAL EXH CFM EXHAUST PLENUM RISER(S) WIDTH LENG HEIGHT DIA CFM VEL SP TOTAL SUPPLY CFM HOOD CONSTRUCTION HOOD CONFIG END TO END ROW HOOD INFORMATION 1 CAPTRATE SOLO FILTER 9 20"16" 85% SEE FILTER SPEC 5 RECESSED ROUND NO LEFT 12"x66"x24"TANK FS 4.0/4.0 DCV-1111 1 LIGHT 1 FAN YES 1290 LBS HOOD NO TAG FILTER(S) TYPE QTY HEIGHT LENGTH EFFICIENCY @ 7 MICRONS LIGHT(S) QTY TYPE WIRE GUARD UTILITY CABINET(S) LOCATION SIZE FIRE SYSTEM TYPE SIZE ELECTRICAL MODEL # SWITCHES QUANTITY FIRE SYSTEM PIPING HOOD HANGING WEIGHT HOOD OPTIONS 1 FIELD WRAPPER 18.00" HIGH FRONT, LEFT. BACKSPLASH 122.00" HIGH X 181.00" LONG 430 SS VERTICAL. RIGHT SIDESPLASH 122.00" HIGH X 84.00" LONG 430 SS VERTICAL. RIGHT END STANDOFF (FINISHED) 1" WIDE 66" LONG INSULATED. INSULATION FOR TOP OF HOOD. INSULATION FOR BACK OF HOOD. LEFT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430 SS. RIGHT WALL AS END PANEL. HOOD NO TAG OPTION PERFORATED SUPPLY PLENUM(S) 1 Front 163"16"6" MUA MUA MUA 12" 12" 12" 28" 28" 28" 833 833 833 0.222" 0.222" 0.222" HOOD NO TAG POS LENGTH WIDTH HEIGHT TYPE RISER(S) WIDTH LENG DIA CFM SP FIRE SYSTEM INFORMATION - JOB#6145305 1 TANK FS 4.0/4.0 40 37 FIRE CABINET LEFT LEFT, HOOD 1 FIRE SYSTEM NO TAG TYPE SIZE MAX FP DESIGN FP INSTALLATION SYSTEM LOCATION ON HOOD GAS VALVE(S) 1 SC ELECTRICAL 2.000 CAPTIVEAIRE SYSTEMS FIRE SYSTEM NO TAG TYPE SIZE SUPPLIED BY System Design Verification (SDV) If ordered, CAS Service will perform a System Design Verification (SDV) once all equipment has had a complete start up per the Operation and Installation Manual. Typically, the SDV will be performed after all inspections are complete. Any field related discrepancies that are discovered during the SDV will be brought to the attention of the general contractor and corresponding trades on site. These issues will be documented and forwarded to the appropriate sales office. If CAS Service has to resolve a discrepancy that is a field issue, the general contractor will be notified and billed for the work. Should a return trip be required due to any field related discrepancy that cannot be resolved during the SDV, there will be additional trip charges. During the SDV, CAS Service will address any discrepancy that is the fault of the manufacturer. Should a return trip be required, the general contractor and appropriate sales office will be notified. There will be no additional charges for manufacturer discrepancies. *** NOTE *** ALL WALLS AND STRUCTURES THAT COME WITHIN 18" OF HOOD MUST BE METAL STUDS AND SHEETROCK. WOOD STUDS OR ANY OTHER COMBUSTIBLE MATERIAL WITHIN 18" OF HOOD NOT ALLOWED *** NOTE *** HOOD MANUFACTURER RECOMMENDS NO RETURNS OR 4-WAY DIFFUSERS WITHIN 10 FEET OF HOOD IN ALL DIRECTIONS. *** NOTE *** MAKE-UP AIR SHALL BE DELIVERED INTO SPACE IN MANNER THAT WILL NOT DISRUPT HOODS ABILITY TO CAPTURE AND CONTAIN. HOOD CORNER HANGING ANGLE (WEIGHT BEARING ANCHOR POINT FOR HOOD) 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUTS 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL ALL-THREAD 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUT ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS. 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUTS 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER HOOD CORNER HANGING ANGLE (HARDWARE BY INSTALLER) 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUT 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER FULL LENGTH HANGING ANGLE (WEIGHT BEARING ANCHOR POINT FOR HOOD) 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUTS 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL ALL-THREAD 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUT 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR FULL LENGTH HANGING ANGLES. MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS. FULL LENGTH HANGING ANGLE (HARDWARE BY INSTALLER) SUPPLY PLENUM HANGING ANGLE (WEIGHT BEARING ANCHOR POINT FOR SUPPLY PLENUM) 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUT 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUTS 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL ALL-THREAD 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHER 1/2" - 13 TPI GRADE 5 (MINIMUM) STEEL HEX NUT ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS. SUPPLY PLENUM HANGING ANGLE (HARDWARE BY INSTALLER) Hoods are ETL Listed And Complies with UL710, ULC710, and ULC-S646 Standards. Fire Systems ETL Listed and Complies With Ul300 and Meets requirements of NFPA 96 and NFPA 17A SHEET NO. SCALE: DWG.#: DRAWN DATE: BY: REVISIONS DESCRIPTION ww w . c a p t i v e a i r e . c o m DATE: AC C O R D A N C E No . 9 6 BU I L T NF P A WI T H IN S LI D TE R C U S 6145305 MASTER DRAWING tom.oates 1 10/11/2023 Th e R o u g h B a r 3/4" = 1'-0" PA R A C H U T E , C O , 8 1 6 3 5 De n v e r O f f i c e 73 0 0 S A l t o n W a y B u i l d i n g 5 , S u i t e B , C e n t e n n i a l , C O , 8 0 1 1 2 P H O N E : ( 7 2 0 ) 5 7 0 - 0 9 8 1 F A X : 9 1 9 2 2 7 5 9 9 9 E M A I L : r e g 4 2 @ c a p t i v e a i r e . c o m Page 24 of 26 12' 6"NOM./12' 6.00"OD. 13'-7.00" OVERALL LENGTH 66" 12" UTILITY CABINET. SC - 2 4 X 1 8 X 8 . 6 2 B O X 16" 44" 8" 12" 28" 37 1/2" 8" 12" 28" 54 1/4" 8" 12" 28" 1" LAYER OF INSULATION FACTORY INSTALLED IN 1.00" END STANDOFF MEETS 0" REQUIREMENTS CLEARANCE TO COMBUSTIBLE SURFACES. 1" 1" LAYER OF INSULATION FACTORY INSTALLED IN INTERNAL BACK STANDOFF. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. 3" § 75"75" 12" ∅18" U.L. LISTED RECESSED ROUND LED FIXTURE AND LED LIGHT. INSTALLER MUST CONFIRM HOOD IS INSTALLED SUCH THAT THE SPECIFIED WALL, ACTING AS AN END PANEL, IS MATED TIGHT TO THE CORRECT END OF HOOD TO ACHIEVE A REDUCED MINIMUM EXHAUST CFM LISTING. NON-COMPLIANCE WILL NULLIFY THE ETL LISTING, VOID THE MANUFACTURER'S WARRANTY, AND HOLD THE CONTRACTOR LIABLE FOR ANY AND ALL LOSSES, COSTS, AND EXPENSES RELATED TO THE NON-CONFORMANCE OF THE MANUFACTURER'S SPECIFIED INSTRUCTION. THE WALL ACTING AS AN END PANEL MUST EXTEND NO LESS THAN 20" FROM THE INTERSECTING WALL ON WHICH HOOD IS MOUNTED AND MUST EXTEND NO LESS THAN 20" UNDER BOTTOM OF HOOD TO BE ELIGIBLE FOR REDUCED MINIMUM EXHAUST CFM LISTING. PLAN VIEW - HOOD #1 12' 6.00" LONG 6624ND-2-PSP-F NOTE: ADDITIONAL HANGING ANGLES PROVIDED FOR HOODS 12' AND LONGER. 1" LAYER OF INSULATION FACTORY INSTALLED IN 3" INTERNAL STANDOFF. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. GREASE DRAIN WITH REMOVABLE CUP. SEE HOOD TABLE. § EXHAUST RISER. HANGING ANGLE. RECESSED ROUND LED FIXTURE AND LED LIGHT, 3500 K WARM OUTPUT. 23.5% OPEN STAINLESS STEEL PERFORATED PANEL. ATTACHING PLATES. SUPPLY RISER WITH VOLUME DAMPER. 6" 2 3/4" 16" 18" BACKSPLASH 122.00" HIGH X 181.00" LONG. FIELD WRAPPER 18.00" HIGH (SEE HOOD OPTIONS TABLE). 1" LAYER OF INSULATION FACTORY INSTALLED ON TOP OF HOOD. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. RIGHT WALL AS END PANEL. 20" 4" 4 1/2" 21" 27" 80" LEFT VERTICAL END PANEL WITH ADJUSTABLE LEGS. GAS CHASE CUTOUT (FOR GAS AND POWER LINES). EQUIPMENT BY OTHERS. 48.0" MAX. 80" 24" NOM. 66" SECTION VIEW - MODEL 6624ND-2-PSP-F HOOD - #1 IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TO ENSURE THAT THE HOOD CLEARANCE FROM LIMITED-COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. 20" CAPTRATE SOLO FILTER WITH HOOK. SHEET NO. SCALE: DWG.#: DRAWN DATE: BY: REVISIONS DESCRIPTION ww w . c a p t i v e a i r e . c o m DATE: AC C O R D A N C E No . 9 6 BU I L T NF P A WI T H IN S LI D TE R C U S 6145305 MASTER DRAWING tom.oates 2 10/11/2023 Th e R o u g h B a r 3/4" = 1'-0" PA R A C H U T E , C O , 8 1 6 3 5 De n v e r O f f i c e 73 0 0 S A l t o n W a y B u i l d i n g 5 , S u i t e B , C e n t e n n i a l , C O , 8 0 1 1 2 P H O N E : ( 7 2 0 ) 5 7 0 - 0 9 8 1 F A X : 9 1 9 2 2 7 5 9 9 9 E M A I L : r e g 4 2 @ c a p t i v e a i r e . c o m Page 25 of 26 6" 24" SERVICE. 24" SERVICE. 24" SERVICE. 24" SERVICE. 18"18" CONDENSER CLEARANCES 48" CLEARANCE REQUIRED ABOVE CONDENSERS. (NOTE: **CONDENSERS SHOWN HERE ARE NOT DRAWN AT SCALE). 6" 12" 12" 12" 12" 18" 145" 1 9/16"18" 4 5/16" 22 3/8" AIRFLOW. LIFTING LUG. 3 3/4" AIRFLOW. COOLING COIL MODULE. 1" MPT CONNECTION FOR SS PITCHED DRAIN PAN. COIL ACCESS DOOR. FLEX CONDUIT FOR FIELD WIRING. AIRFLOW. BLOWER/MOTOR ACCESS DOOR 24" SERVICE CLEARANCE REQ. SERVICE DISCONNECT SWITCH. AIRFLOW. 1" NPT. 7 13/16" 39 9/16" DIRECT FIRED MODULE. AIRFLOW. 49 3/8" 16 1/4" 20" 31" 20" EQUIPMENT CURB. CURB OUTER WALL. DISCHARGE OPENING. 24 1/4" 36 3/4" 42 1/8" 47 3/4" 40 1/8"42 1/8" 202 1/4" MIN. 20" MINIMUM STRAIGHT DUCT PER AMCA* FAN #2 A2-D.250-20D-MPU - HEATER 1. DIRECT GAS FIRED HEATED MAKE UP AIR UNIT WITH 20" MIXED FLOW DIRECT DRIVE FAN. 2. INTAKE HOOD WITH EZ FILTERS. 3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT. 4. GAS PRESSURE GAUGE, 0-35", 2.5" DIAMETER, 1/4" THREAD SIZE. 5. GAS PRESSURE GAUGE, -5 TO +15 INCHES WC., 2.5" DIAMETER, 1/4" THREAD SIZE. 6. BUTTERFLY MOD VALVE OPTION FOR MOD SIZE 2 (1" MOD VALVE). 7. SHIP LOOSE GAS STRAINER. TO BE INSTALLED UPSTREAM OF UNIT CONNECTION. 1" CONNECTION. 8. CASLINK BUILDING MONITORING SYSTEM COMMUNICATIONS MODULE. REQUIRES INTERNET & FIELD WIRED ETHERNET CONNECTION OR 3G CELLULAR SERVICE. INCLUDES REV 3 COMM MODULE, RJ45 TO MODBUS CONVERTER, 3 FT CAT5 CABLE, AND 1 FT OF SHIELDED TWISTED PAIR. 9. MOTORIZED BACK DRAFT DAMPER 22.75" X 24" FOR SIZE 2 STANDARD & MODULAR HEATER UNITS W/EXTENDED SHAFT, STANDARD GALVANIZED CONSTRUCTION, 3/4" REAR FLANGE, LOW LEAKAGE, LF120S ACTUATOR INCLUDED. 10. 5 TON, SINGLE CIRCUIT MODULAR PACKAGED AC COOLING OPTION FOR SIZE 2 DF/EH MODULAR PACKAGED UNIT. INCLUDES CONDENSER, DX COIL, FILTER/DRYER KIT, THERMAL EXPANSION VALVE. (1,000 TO 2,750 CFM) WHEN ORDERED WITH OPPOSITE AIRFLOW CONDENSERS ACCESS AND COIL PIPING WILL REMAIN IN STANDARD POSITION. DRAIN AND SLEDS WILL MOVE TO THE OPPOSITE SIDE. ANY OTHER CHANGE WILL REQUIRE CLI. CONDENSERS REQUIRE SEPARATE 208V, 3 PHASE POWER SUPPLY UNLESS ORDERED WITH SINGLE POINT CONNECTION. COIL = 3EY1102. 11. SHIP CONDENSER LOOSE. THE REFRIGERATION LINES WILL NEED TO BE STUBBED OUT 12 INCHES. THE SUCTION LINE NEEDS TO BE INSULATED INSIDE THE COIL MODULE. ROTARY DISCONNECT SHOULD NOT BE INSTALLED ON THE POST, BLANK POST SHOULD BE USED IN PLACE. ALL PIPING AND WIRING BETWEEN INDOOR AND OUTDOOR UNITS BY OTHERS. 12. DOWNTURN PLENUM FOR SIZE 2 COOLING COIL MODULE - REQUIRED FOR DOWN DISCHARGE COOLING COIL APPLICATIONS. 13. SEPARATE 120VAC WIRING PACKAGE FOR MAKE-UP AIR UNITS. OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE PANEL OR WITH DCV PACKAGE. PROVIDES SEPARATE 120VAC INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY ELECTRICIAN FROM DCV TO MUA SWITCH. 14. PROFILE PLATE CONFIGURATION FOR SIZE 2 DIRECT FIRED UNIT FOR LOW CFM APPLICATIONS. 15. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER/MPU SECTION). 16. 2 YEAR PARTS WARRANTY. *NOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT. SUGGESTED STRAIGHT DUCT SIZE IS 20" x 20". **NOTE: CONDENSERS SHIPPED LOOSE FOR REMOTE MOUNTING. ALL WIRING AND PIPING BETWEEN INDOOR AND OUTDOOR UNIT TO BE COMPLETED BY OTHERS. SUPPLY SIDE HEATER INFORMATION: WINTER TEMPERATURE = 8°F. TEMP. RISE = 67°F. BTUs CALCULATED OFF ACTUAL AIR DENSITY. OUTPUT BTUs AT ALTITUDE OF 0.0 FT. = 178947. INPUT BTUs AT ALTITUDE OF 0.0 FT. = 194508. OUTPUT BTUs AT ALTITUDE OF 5594 FT. = 145613. INPUT BTUs AT ALTITUDE OF 5594 FT. = 158275. L ETS DI R 6" 6" 3" FLANGE. 20 GAUGE CONSTRUCTION. STEEL 20" 31" 145" OPTIONS: - FULL BOTTOM CORNERS. CURB. SHEET NO. SCALE: DWG.#: DRAWN DATE: BY: REVISIONS DESCRIPTION ww w . c a p t i v e a i r e . c o m DATE: AC C O R D A N C E No . 9 6 BU I L T NF P A WI T H IN S LI D TE R C U S 6145305 MASTER DRAWING tom.oates 4 10/11/2023 Th e R o u g h B a r 1/2" = 1'-0" PA R A C H U T E , C O , 8 1 6 3 5 De n v e r O f f i c e 73 0 0 S A l t o n W a y B u i l d i n g 5 , S u i t e B , C e n t e n n i a l , C O , 8 0 1 1 2 P H O N E : ( 7 2 0 ) 5 7 0 - 0 9 8 1 F A X : 9 1 9 2 2 7 5 9 9 9 E M A I L : r e g 4 2 @ c a p t i v e a i r e . c o m Page 26 of 26 For Asset: Calibrated Int. MTh's 12-Mar-2024 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. 5756 5/2026 Serial Number Description Re-CalManufacturerModel NEBB Procedure Shimpo MT-200 1) As-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. As-Received Physical Condition(s) Calibration Event: C-Procedure Environmental 73.4°F ±9°F, 40 to 65%RH Jedi Balancing Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing 568 Briggs St. PO Box 525 Erie, CO 80516 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). 221576.5299Certificate Number: Customer Purchase Order: B175B5016P Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. Calibration Type:CAL-2 NEBB : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. Projected Re- Cal. CALIBRATION LOCATION:Laerie Inc. Laboratory NDH Laboratory Altitude: 5,063.25 Ft. Description Procedure Executed by: Primary References Traceability Number Used in Calibration REF Description Strobe Certificate of Accredited and Traceable Calibration B175B5016P Pocket Tachometer, contact non contact 12-Mar-2025 56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 www.laerie.com TCC 2023-8A Comments: Veridical Review By: L. E. Armfield CEO/President REF Projected Re- Cal.LA E R I E Ca l i b r a t i o n & M e t r o l o g y S e r v i c e s Ca l i b r a t i o n E v e n t : FO U ND- L E F T Ma n u f a c t u r e r : Mo d e l : De s c r i p t i o n : S/ N: B1 7 5 B 5 0 1 6 P ID : B1 7 5 B 5 0 1 6 P Ca l T y p e Ca l - 2 N E B B CA L - D A T E : 3/ 1 2 / 2 0 2 4 CA L - D U E : 3/ 1 2 / 2 0 2 5 En v i r o m e n t a l : Te c h n i c i a n : ND H St o b e 1, 0 0 0 . 0 1, 0 0 0 . 0 99 5 . 0 10 0 5 . 0 PA S S 2, 2 5 0 . 0 2, 2 4 9 . 9 2, 2 4 5 . 0 22 5 5 . 0 PA S S 3, 5 0 0 . 0 3, 4 9 9 . 9 3, 4 9 5 . 0 35 0 5 . 0 PA S S 4, 0 0 0 . 0 3, 9 9 9 . 9 3, 9 9 5 . 0 40 0 5 . 0 PA S S 5, 0 0 0 . 0 5, 0 0 0 . 0 4, 9 9 5 . 0 50 0 5 . 0 PA S S RE F 5 7 5 6 S t o b e Cu s t o m e r : Sh i m p o MT - 2 0 0 La s e r T a c h o m e t e r 68 ° F ± ( 2 ° F ) / ( 1 0 - 4 5 ) % R H Li g h t n i n g Sy s t e m s Ca l i b r a t i o n & M e t r o l o g y S e r v i c e s 56 G a t e w a y C i r c l e Th i s r e p o r t s h a l l n o t b e m o d i f i e d o r r e p r o d u c e d e x c e p t i n f u l l a n d w i t h t h e w r i t t e n a p p r o v a l o f L a e r i e I n c . ww w . l a e r i e . c o m TF : 1 - 8 7 7 - 5 3 2 - 7 9 9 0 Of f i c e : 9 7 0 - 5 3 2 - 7 9 9 0 Be r t h o u d , C o l o r a d o 8 0 5 1 3 Ca l i b r a t i o n D e s c r i p t i o n ST D I n d . R P M UU T I n d . R P M Ma x Co m p i l a t i o n Mi n La b o r a t o r y A l t i t u d e : 5 , 0 4 4 f t Ve r i d i c a l R e v i e w C o n t a c t : v r @ l a e r i e . c o m Pa g e 1 o f 1 For Asset: Calibrated Int. MTh's 14-Jul-2023 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. 5467 5/2024 www.laerie.com Certificate of Accredited and Traceable Calibration 1700353 Insertion Temperature Probe 14-Jul-2024 56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 TCC 2021-18C Comments: Veridical Review By: L. E. Armfield CEO/President REF Projected Re- Cal. Procedure Executed by: Primary References Traceability Number Used in Calibration REF Description Dry Dual Block Calibrator Projected Re- Cal. CALIBRATION LOCATION:Laerie Inc. Laboratory JRN Laboratory Altitude: 5,063.25 Ft. Description Jedi Balancing Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing 568 Briggs St. PO Box 525 Erie, CO 80516 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). 187606.4885Certificate Number: Customer Purchase Order: 1700353 Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. Calibration Type:CAL-2 NEBB : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. Serial Number Description Re-CalManufacturerModel MPS/LAP Evergreen Telemetry PR-T-1 1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. As-Received Physical Condition(s) Calibration Event: C-Procedure Environmental 73.4°F ±9°F, 40 to 65%RH NEBB 2023 LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% UUT Manufacturer: Model:Description: S/N:ID: CAL-DATE:CAL-DUE: REF NOMINAL REF Min UUC Ind Max Compilation 40.0 °F 39.83404 °F 37.6 °F 39.8 °F 42.0 °F Calibrated 100.0 °F 99.98052 °F 97.5 °F 100.0 °F 102.5 °F Calibrated 160.0 °F 160.00263 °F 157.2 °F 159.7 °F 162.8 °F Calibrated TF: 1-877-532-7990 Fax: 970-532-7992 www.laerie.com This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc. LAERIE Calibration & Metrology Services 56 Gateway Circle Berthoud, Colorado 80513 Office: 970-532-7990 FOUND-LEFT Temperature ±.5% R ± 2 °F Range 0-200 °F Evergreen Telemetry Calibration Event:FOUND-LEFT Calibration Performance Report for: Temperature Probe JEDI Balancing17003531700353Eng. / Metrologist: 7/14/2023 7/14/2024 JRN Calibration Performed: Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1 For Asset: Calibrated Int. MTh's 14-Jul-2023 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. 5467 5/2024 www.laerie.com TCC 2021-18C Certificate of Accredited and Traceable Calibration Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing 568 Briggs St. PO Box 525 Erie, CO 80516 Jedi Balancing Calibration Type: : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. 180173.4803Certificate Number: Customer Purchase Order: 1700204 CAL-2 NEBB CALIBRATION LOCATION:Laerie Inc. Laboratory Projected Re- Cal.REF Projected Re- Cal. Procedure Executed by:56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). Dry Dual Block Calibrator Primary References Traceability Number Used in Calibration 73.4°F ±9°F, 40 to 65%RH Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. 1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. Comments: JRN DescriptionREF Laboratory Altitude: 5,063.25 Ft.Veridical Review By: L. E. Armfield CEO/President MPS/LAP Description Calibration Event: Evergreen Telemetry PR-T-4-6"1700204 Water Insertion Probe Environmental As-Received Physical Condition(s) 14-Jul-2024 C-Procedure Manufacturer Model Serial Number Description Re-Cal NEBB 2023 LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% UUT Manufacturer: Model:Description: S/N:ID: CAL-DATE:CAL-DUE: REF NOMINAL REF Min UUC Ind Max Compilation 40.0 °F 40.01068 °F 40.1 °F 40.2 °F 42.2 °F Calibrated 100.0 °F 99.98815 °F 97.5 °F 100.0 °F 102.5 °F Calibrated 160.0 °F 160.07153 °F 157.3 °F 160.0 °F 162.9 °F Calibrated Temperature ±.5% R ± 2 °F Range 0-200 °F Evergreen Telemetry Calibration Event:FOUND-LEFT Calibration Performance Report for: Temperature Probe Jedi Balancing17002041700204Eng. / Metrologist: 7/14/2023 7/14/2024 JRN Calibration Performed: TF: 1-877-532-7990 Fax: 970-532-7992 www.laerie.com This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc. LAERIE Calibration & Metrology Services 56 Gateway Circle Berthoud, Colorado 80513 Office: 970-532-7990 Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1 For Asset: Calibrated Int. MTh's 14-Jul-2023 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. 4272 4/2024 4273 4/2024 A727 8/2023 www.laerie.com TCC 2021-18C Certificate of Accredited and Traceable Calibration Veridical Review By: Procedure Executed by: MPS/LAP Laboratory Altitude: 5,063.25 Ft. 73.4°F ±9°F, 40 to 65%RH Description Humidity/Thermometer L. E. Armfield CEO/President JRN Environmental Calibration Event: Calibration Salt Temperature Kit Sensor As-Received Physical Condition(s) 1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. Primary References Traceability Number Used in Calibration Comments: 56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 Projected Re- Cal. Projected Re- Cal. Customer Purchase Order: 1700295 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. S-H-3-5"1700295 Humidity Sensor Calibration Type:568 Briggs St. PO Box 525 Erie, CO 80516 14-Jul-2024 Re-Cal Jedi Balancing CALIBRATION LOCATION:Laerie Inc. Laboratory CAL-2 NEBB REF Description REF Manufacturer Model Serial Number Description : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. Certificate Number:111978.9285 C-Procedure Evergreen Telemetry Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing NEBB 2022 LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% UUT Manufacturer: Model:Description: S/N:ID: CAL-DATE:CAL-DUE: REF RH Min RH UUC Ind RH Max Compilation 33.07 % RH 30.1 % RH 36.0 % RH 36.1 % RH Calibrated 42.34 % RH 39.3 % RH 44.1 % RH 45.3 % RH Calibrated 75.47 % RH 72.5 % RH 73.1 % RH 78.5 % RH Calibrated HUMIDITY Extech Calibration Event:FOUND-LEFT Calibration Performance Report For: RH390 Psychrometer JEDI Balancing17002951700295Eng. / Metrologist: 14-Jul-2023 14-Jul-2024 JRN Calibration Performed: TF: 1-877-532-7990 Fax: 970-532-7992 www.laerie.com This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc. LAERIE Calibration & Metrology Services 56 Gateway Circle Berthoud, Colorado 80513 Office: 970-532-7990 Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1 For Asset: Calibrated Int. MTh's 24-Apr-2024 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. TOC22 4/2025 9707 5/2024 Serial Number Description Re-CalManufacturerModel LAP: NEBB 2024 Fluke 323 1) As-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. As-Received Physical Condition(s) Calibration Event: C-Procedure Environmental 73.4°F ±9°F, 40 to 65%RH Jedi Balancing Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing 568 Briggs St. PO Box 525 Erie, CO 80516 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). 96164.1511Certificate Number: Customer Purchase Order: 49251381WS Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. Calibration Type:CAL-2 NEBB : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. Projected Re- Cal. CALIBRATION LOCATION:Laerie Inc. Laboratory JRN Laboratory Altitude: 5,063.25 Ft. Description Procedure Executed by: Primary References Traceability Number Used in Calibration REF Description Calibrator 50 Turn Coil Certificate of Accredited and Traceable Calibration 49251381WS True RMS Clamp Meter 24-Apr-2025 56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 www.laerie.com TCC 2023-8A Comments: Veridical Review By: L. E. Armfield CEO/President REF Projected Re- Cal. NEBB 2024 LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% UUC Manufacturer: Model:Description: S/N:ID: CAL-DATE:CAL-DUE: Range REF Min UUC Ind Max Compilation 20.0 %120 VAC 117.1 VAC 119.9 VAC 122.9 VAC Calibrated 50.0 %300 VAC 293.5 VAC 299.7 VAC 306.5 VAC Calibrated 80.0 %480 VAC 469.9 VAC 479.5 VAC 490.1 VAC Calibrated Range REF AAC Min AAC UUC Ind AAC Max AAC Compilation Calibrator Setting for 50 Turn Coil 20.0 %20.000 AAC 19.1 AAC 20.2 AAC 20.9 AAC Calibrated 0.4000 AAC 50.0 %50.000 AAC 48.5 AAC 50.1 AAC 51.5 AAC Calibrated 1.0000 AAC 80.0 %80.000 AAC 77.9 AAC 80.1 AAC 82.1 AAC Calibrated 1.6000 AAC Calibration Performed: That is All. Thank you for using LAERIE Calibration & Metrology Service 56 Gateway Circle Berthoud, Colorado 80513 Office: 970-532-7990 www.laerie.com TF: 1-877-532-7990 Fax: 970-532-7992 This report shall not be reproduced except in full and with the written approval of Laerie Inc. AS-FOUND AC Volts Accuracy 60 Hz RANGE 0-600 VAC Calibration Performed: AS-FOUND AC Current Accuracy 60 Hz RANGE 0-100 AMPS FLUKE Calibration Event:FOUND-LEFT Calibration Performance Report for: 322 DMM Jedi Balancing49251381WS49251381WSEng. / Metrologist: 24-Apr-2024 24-Apr-2025 JRN Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1 For Asset: Calibrated Int. MTh's 25-Jul-2023 12 2FL: NEBB Compliant Calibration performed published data no adjustments required or performed. 10014 9/2023 www.laerie.com Serial Number Description Re-CalManufacturerModel NEBB 2023 / LAP TSI HM675 1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible, initial inspection PASS. As-Received Physical Condition(s) Calibration Event: C-Procedure Environmental 73.4°F ±9°F, 40 to 65%RH Jedi Balancing Laerie, Inc. Issues this Certificate of Calibration to: Jedi Balancing 568 Briggs St. PO Box 525 Erie, CO 80516 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST). 169394.6759Certificate Number: Customer Purchase Order: 71646134 Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2. Calibration Type:CAL-2 NEBB : accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration. Projected Re- Cal. CALIBRATION LOCATION:Laerie Inc. Laboratory JRN Laboratory Altitude: 5,063.25 Ft. Description Procedure Executed by: Primary References Traceability Number Used in Calibration REF Description Pressure Calibrator Certificate of Accredited and Traceable Calibration 71646134 Hydronic Manometer 25-Jul-2024 56 Gateway Circle Berthoud, Colorado 80513 877-532-7990 970-532-7990 TCC 2021-18C Comments: Veridical Review By: L. E. Armfield CEO/President REF Projected Re- Cal. NEBB 2023 LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% UUC Manufacturer: Model:Description: S/N:ID: CAL-DATE:CAL-DUE: REF Min UUC Ind.Max Compilation 0.000 PSI -1.000 PSI 0.000 PSI 1.000 PSI Calibrated 60.000 PSI 57.800 PSI 60.03 PSI 62.200 PSI Calibrated 150.000 PSI 146.000 PSI 150.1 PSI 154.000 PSI Calibrated 200.000 PSI 195.000 PSI 200.2 PSI 205.000 PSI Calibrated NOM REF Min UUC Ind.Max Compilation 18.0 °F -2.000 °F N/A 2.000 °F N/A 105.0 °F -2.000 °F N/A 2.000 °F N/A 192.0 °F -2.000 °F N/A 2.000 °F N/A TSI Calibration Event:FOUND-LEFT Calibration Performance Report For: HM675/801290 Hydronic Manometer & Probe Jedi Balancing7164613471646134Eng. / Metrologist: 56 Gateway Circle 7/25/2023 7/25/2024 JRN Calibration Performed: Pressure ±2% R +1 PSI RANGE 0.4 TO 200 PSI Calibration Performed: Temperature ±.5% R + 2 °F RANGE -40 TO 200 °F Temperature probe not provided for calibration LAERIE Calibration & Metrology Services Berthoud, Colorado 80513 Office: 970-532-7990 TF: 1-877-532-7990 Fax: 970-532-7992 www.laerie.com This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc. Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1