HomeMy WebLinkAboutTABB Report
JEDI Balancing, Inc.
568 Briggs Street (physical)
P.O. Box 525 (mail)
Erie, CO. 80516
Phone (720) 839-5333
www.jedibalancing.com
Certified Test, Adjust & Balance Report
Project Battlement Mesa Golf Course Restaurant Kitchen
Addition
Address 3030 North Battlement Pkwy Parachute, CO 81635
Architect Terri Montoya Architects
Mechanical Engineer SGM Inc.
Contractor Rapid Creek Mechanical Company
Date 6/25/2024
Job Number 2024-10243
Donald W. Pittser
TABB Certified Supervisor
TABB Firm Certification #BB009003C
Stamp Expires 9/30/2024
Warranty Information:
The data presented in this report is a record of system measurements and final adjustments
that have been obtained in accordance with the current edition of the TABB International
Standards for Environmental Systems Balance. The measurements shown, and the
information given, in this report are certified to be accurate and complete, at the time and
date information was gathered. Any variances from design quantities, which exceed TABB
tolerances, are noted in the TAB report project summary.
This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date
listed on this cover page.
Instrumentation:
Instrument Manufacturer Model Serial Number Calibrated On Calibration Due
Tachometer Shimpo MT-200 B175B5016P 03-12-2024 03-12-2025
Air Temperature Probe Evergreen Telemetry PR-T-1 1700353 07-14-2023 07-14-2024
Immersion Temperature Probe Evergreen Telemetry PR-T-4-6 1700204 07-14-2023 07-14-2024
Humidity Evergreen Telemetry S-H-3-5 1700295 07-14-2023 07-14-2024
Volt-Amp Meter Fluke 323 49251381WS 04-24-2024 04-24-2025
Air Pressure Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025
Air Velocity / Airfoil Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025
Flowhood Evergreen Telemetry S-PVF-1 2000250 02-23-2024 02-23-2025
Hydronic Pressure TSI HM-675 71646134 07-25-2023 07-25-2024
Hydronic Differential Pressure TSI HM-675 71646134 07-25-2023 07-25-2024
Abbreviation Index
TAB: Testing, Adjusting & Balancing Cx: Commissioning OD: Outside Diameter
AHU: Air Handling Unit Motor FLA: Full Load Amperage T1: Terminal 1
RTU: Roof Top Unit S.F.: Service Factor T2: Terminal 2
PACU: Packaged Air Conditioning Unit RPM: Revolutions per Minute T3: Terminal 3
MAU: Make Up Air Unit P.F.: Power Factor CS: Circuit Setter
FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency BV: Balance Valve
VAV: Variable Air Volume TDH: Total Dynamic Head K Factor: Correction Factor
FPB: Fan Powered Box AK: Area Correction PSI: Pounds per Square Inch
CUH: Cabinet Unit Heater Valve D.P.: Discharge Pressure UH: Unit Heater
Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit
EF: Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan
SF: Supply Fan RF: Return Fan TF: Transfer Fan
Diff.: Differential SEF: Smoke Exhaust Fan DX: Direct Expansion
SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure
in. wc: Inches Water Column ESP: External Static Pressure HW: Heating Water
VP: Velocity Pressure CHW: Cooling Water SA: Supply Air
CW: Condenser Water RA: Return Air HX: Heat Exchanger
OSA: Outside Air SWD: Sidewall Diffuser MA: Mixed Air
EAT: Entering Air Temperature OA: Outside Air CD: Ceiling Diffuser
EWT: Entering Water Temperature SD: Supply Diffuser ER: Exhaust Register
LAT: Leaving Air Temperature MVD: Manual Volume Damper RG: Return Grille
LWT: Leaving Water Temperature OBD: Opposed Blade Damper NAC: No Access
CFM: Cubic Feet Per Minute CMH: Cubic Meters per Hour NG: Not Given
FPM: Feet Per Minute SSD: Square Supply Diffuser NIC: Not in Contract
SRD: Square Return Diffuser E: Existing M: Meter
TG: Transfer Grille cm: Centimeter Pa: Pascal
l/s: Liters per Second mm: Millimeter kPa: Kilopascal
ADM: Air Data Meter (manometer) SPF: Stairwell Pressurization Fan N/A: Not Applicable
Design D.P.: Design Differential Pressure Actual D.P.: Recorded Differential Pressure
Ind.Imp.Dia. Indicated Impeller Diameter CRAC: Computer Room Air Conditioning Unit
Table of ContentsPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
1 2024 10243 Battlement Mesa Golf Course Restaurant Kitchen Addition Report Summary.pdf...............................1
2 Air Handling Unit......................................................................................................................................................2
2.1 F-01....................................................................................................................................................................2
2.2 F-01/SPP-01.......................................................................................................................................................3
2.3 F-02....................................................................................................................................................................4
2.4 F-02/SPP-01.......................................................................................................................................................5
2.5 MAU-01..............................................................................................................................................................6
2.6 MAU-01/SPP-01.................................................................................................................................................7
3 Energy Recovery Unit..............................................................................................................................................8
3.1 ERV-01...............................................................................................................................................................8
3.2 ERV-01/SPP-EXHAUST.....................................................................................................................................9
3.3 ERV-01/SPP-SUPPLY........................................................................................................................................10
4 Fan Unit....................................................................................................................................................................11
4.1 KEF-01...............................................................................................................................................................11
5 BATTLEMENT MESA GOLF COURSE RESTAURANT AND KITCHEN TAB DRAWINGS.pdf...............................12
6 TAB Equipment Calibrations 2024b.pdf...................................................................................................................26
JEDI Balancing, Inc.
Page 1 of 26
JEDI Balancing, Inc.
568 Briggs Street (physical)
P.O. Box 525 (mail)
Erie, CO. 80516
Phone (720) 839-5333
www.jedibalancing.com
Report Summary and Remarks
Project: Battlement Mesa Golf Course Restaurant Kitchen Addition
Project: 2024 10243
Scope: The Test and Balance (TAB) scope of work consisted of Air Handling Unit (F)-2, (MAU)-1,
Exhaust Fan (EF)-1
Procedures:
F, MAU - Constant Volume
Each unit has a constant volume fan that was set for design airflow and the associated supply outlets were
balanced in full cooling demand. The total Supply Air CFM was measured as individually listed under
each unit. The Outside Air CFM was measured as individually listed under each unit. The Return Air
CFM was measured as individually listed under each unit. All final TAB settings and performance
measurements were completed, and data was recorded on to the appropriate test report forms.
Exhaust Fans with Grilles and Hoods
The exhaust fans were energized, measured and set for total airflow. The associated inlets were balanced
as noted in this report. The Exhaust Air CFM was measured as individually listed under each unit. Final
settings and performance measurements were completed, and data recorded on to the appropriate test
report forms.
Motor Tag Data Not Accessible (Embedded)
Embedded Motor – Limited motor nameplate information provided. Motor nameplate information is
obscured by the motor mounting bracket and not visible without disassembly of the motor from the unit.
The motor is accessible for service and maintenance.
No Access Between Coils
Some unit arrangement prevents access to obtain a complete static pressure profile for all the components.
Static pressure test ports could not be safely drilled between the heating and cooling coils without risking
damage to the coils and are recorded as “Not Accessible” in the Report.
Schematic Line Diagrams
Report includes reduced mechanical drawings used for the test and balance work. These “Keyed
Drawing” were used in place of single line schematic diagrams and include the unique designations for
the tested items in the final TAB report.
Submittals: Submittals were not provided for the project.
to +/-10% of design flow rates
Any values outside the specified tolerances are noted on the Equipment Comment Log and the individual
test report pages.
Previously Forwarded / Accepted As-Is
Equipment Comment Log Project Summary
The following page(s) lists all project comments and issues. All items described and listed on the
following Equipment Comment Log have been previously forwarded for resolution and have been
accepted as reported.
Page 2 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: F-01
Unit Data
Unit Manufacturer TRANE
Unit Model Number S9V2C100U4VSADA
Unit Serial Number 23321PEJKG
Starter Data
F-01/Supply Fan
Starter Manufacturer Thermally Protected
Design Data
Total Flow Design 1770
Supply Fan Design ESP 0.62 in. wc
Supply Fan Design TSP Not Given in. wc
Supply Fan Design RPM Not Given
Supply Fan Motor Design HP Not Given
Supply Fan Motor Design RPM Not Given
Supply Fan Motor Design Volts 120
Supply Fan Motor Design Phase 1
Design Filter MERV Rating Not Given
Test Data
Connected Actual
Supply Airflow 1920 1815
Outside Airflow 725 680
Return Airflow 1135
Electrical Test Data
F-01/Supply Fan
Motor Volts 1 121
Motor Amps 1 9.90
Corrected Nameplate Amps 12.79
Volts/Amps Measured By RMS Clamp Meter
Motor Data
F-01/Supply Fan
Motor Manufacturer Embedded
Motor HP Not Given
Motor RPM Not Given
Motor Frame Not Given
Motor Phase 1
Motor Rated Volts 120
Motor FL Amps 12.9 (Unit Amps)
Motor Service Factor 1.0
Sheave Data
F-01/Supply Fan
Drive Type Direct Drive
Final Data
Fan Flow Test Method Flowhood Summation
OA Damper Pos Not Applicable %
OA Flow Test Method Airfoil Traverse
Measured Data
F-01/Supply Fan
Fan RPM Actual Direct Drive
Fan Speed / Setpoint Tested on cooling speed
Operating Hertz 60
Filter Data
F-01/SF Filter Bank
Filter Type RETURN / OSA AIR
MERV Rating MERV 11
Filter Quantity (set 1)1
Filter Size (set 1)20X25X4
JEDI Balancing, Inc.
Page 3 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: F-01/SPP-01
Test Data
Actual TSP 0.84 in. w.c.
External SP 0.50 in. w.c.
Test Pressures
Filter SP In -0.20 in. w.c.
Filter SP Out -0.36 in. w.c.
DX Coil SP In 0.46 in. w.c.
DX Coil SP Out 0.30 in. w.c.
Gas Heat Exchanger In 0.48 in. w.c.
Gas Heat Exchanger Out 0.46 in. w.c.
Supply Fan SP In -0.36 in. w.c.
Supply Fan SP Out 0.48 in. w.c.
Static Pressure Profile
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
Outlet-01 DINING SD 8"165 225 155 94 Flow Hood
Outlet-02 DINING SD 8"180 250 170 94 Flow Hood
Outlet-03 DINING SD 8"180 225 165 92 Flow Hood
Outlet-04 DINING SD 8"180 65 165 92 Flow Hood
Outlet-05 DINING SD 8"180 140 170 94 Flow Hood
Outlet-06 DINING SD 8"180 280 180 100 Flow Hood
Outlet-07 DINING SD 8"165 110 155 94 Flow Hood
Outlet-08 DINING SD 8"180 120 170 94 Flow Hood
Outlet-09 DINING SD 8"180 100 165 92 Flow Hood
Outlet-10 BAR SD 8"180 120 170 94 Flow Hood
Outlet-11 WOMENS
LOCKER
CD 6"75 110 80 107 Flow Hood
Outlet-12 WOMENS
LOCKER
CD 6"75 55 70 93 Flow Hood
Totals:---1920 1800 1815 95 ----
F-01 Supply Outlet Summary
JEDI Balancing, Inc.
Page 4 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: F-02
Unit Data
Unit Manufacturer TRANE
Unit Model Number S9V2C100U4VSADA
Unit Serial Number 23326PEJKG
Starter Data
F-02/Supply Fan
Starter Manufacturer Thermally Protected
Design Data
Total Flow Design 1770
Supply Fan Design ESP 0.62 in. wc
Supply Fan Design TSP Not Given in. wc
Supply Fan Design RPM Not Given
Supply Fan Motor Design HP Not Given
Supply Fan Motor Design RPM Not Given
Supply Fan Motor Design Volts 120
Supply Fan Motor Design Phase 1
Design Filter MERV Rating Not Given
Test Data
Connected Actual
Supply Airflow 1620 1715
Outside Airflow 0 0
Return Airflow 1715
Electrical Test Data
F-02/Supply Fan
Motor Volts 1 123
Motor Amps 1 10.40
Corrected Nameplate Amps 12.59
Volts/Amps Measured By RMS Clamp Meter
Motor Data
F-02/Supply Fan
Motor Manufacturer Embedded
Motor HP Not Given
Motor RPM Not Given
Motor Frame Not Given
Motor Phase 1
Motor Rated Volts 120
Motor FL Amps 12.9 (Unit Amps)
Motor Service Factor 1.0
Sheave Data
F-02/Supply Fan
Drive Type Direct Drive
Final Data
Fan Flow Test Method Flowhood Summation
Measured Data
F-02/Supply Fan
Fan RPM Actual Direct Drive
Fan Speed / Setpoint Tested on cooling speed
Operating Hertz 60
Filter Data
F-02/SF Filter Bank
Filter Type RETURN AIR
MERV Rating MERV 11
Filter Quantity (set 1)1
Filter Size (set 1)20X25X4
JEDI Balancing, Inc.
Page 5 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: F-02/SPP-01
Test Data
Actual TSP 0.87 in. w.c.
External SP 0.46 in. w.c.
Test Pressures
Filter SP In -0.17 in. w.c.
Filter SP Out -0.33 in. w.c.
DX Coil SP In 0.50 in. w.c.
DX Coil SP Out 0.29 in. w.c.
Gas Heat Exchanger In 0.54 in. w.c.
Gas Heat Exchanger Out 0.50 in. w.c.
Supply Fan SP In -0.33 in. w.c.
Supply Fan SP Out 0.54 in. w.c.
Static Pressure Profile
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
Outlet-01 KITCHEN SD 10"295 280 320 108 Flow Hood
Outlet-02 KITCHEN SD 10"295 230 310 105 Flow Hood
Outlet-03 BOH SD 10"295 390 310 105 Flow Hood
Outlet-04 BOH SD 10"245 340 270 110 Flow Hood
Outlet-05 BOH SD 10"295 320 300 102 Flow Hood
Outlet-06 BOH SD 8"195 190 205 105 Flow Hood
Totals:---1620 1750 1715 106 ----
F-02 Supply Outlet Summary
JEDI Balancing, Inc.
Page 6 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: MAU-01
Unit Data
Unit Manufacturer CAPTIVE AIRE
Unit Model Number A2-D.250-20D-MPU
Unit Serial Number 6476229 MAU-01
Starter Data
MAU-01/Supply Fan
Starter Manufacturer LENZE (VFD)
Design Data
Total Flow Design 2500/2000
Supply Fan Design ESP 0.5 in. wc
Supply Fan Design TSP Not Given in. wc
Supply Fan Design RPM 1391
Supply Fan Motor Design HP 1.5
Supply Fan Motor Design RPM 1391
Supply Fan Motor Design Volts 208
Supply Fan Motor Design Phase 3
Design Filter MERV Rating Not Given
Test Data
Connected Actual
Supply Airflow 2500 2400
Outside Airflow 2500 2400
Electrical Test Data
MAU-01/Supply Fan
Motor Volts 1 247
Motor Volts 2 246
Motor Volts 3 246
Motor Amps 1 5.40
Motor Amps 2 5.35
Motor Amps 3 5.40
Corrected Nameplate Amps 5.57
Actual BHP 1.45
Volts/Amps Measured By RMS Clamp Meter
Motor Data
MAU-01/Supply Fan
Motor Manufacturer TECO
Motor HP 1.5
Motor RPM 1170
Motor Frame 182T
Motor Phase 3
Motor Rated Volts 208-230/460
Motor FL Amps 6.6-6.01/3.0
Motor Service Factor 1.15
Sheave Data
MAU-01/Supply Fan
Drive Type Direct Drive
Final Data
Fan Flow Test Method Velgrid Traverse
Measured Data
MAU-01/Supply Fan
Fan RPM Actual Direct Drive
Fan Speed / Setpoint 72 hz
Operating Hertz 72 hz
Filter Data
MAU-01/SF Filter Bank
Filter Type Washable Metal
Filter Quantity (set 1)Built into unit
JEDI Balancing, Inc.
Page 7 of 26
Air Handling UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: MAU-01/SPP-01
Test Data
Actual TSP 0.78 in. w.c.
External SP 0.35 in. w.c.
Test Pressures
Filter SP In Atmosphere in. w.c.
Filter SP Out -0.10 in. w.c.
DX Coil SP In 0.48 in. w.c.
DX Coil SP Out 0.35 in. w.c.
Gas Heat Exchanger In -0.10 in. w.c.
Gas Heat Exchanger Out -0.30 in. w.c.
Supply Fan SP In -0.30 in. w.c.
Supply Fan SP Out 0.48 in. w.c.
Static Pressure Profile
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
Outlet-01 KITCHEN HOOD 12/28 835 830 830 99 Velgrid 5.20 5.20 160
Outlet-02 KITCHEN HOOD 12/28 830 770 770 93 Velgrid 5.20 5.20 148
Outlet-03 KITCHEN HOOD 12/28 835 800 800 96 Velgrid 5.20 5.20 154
Totals:---2500 2400 2400 96 ----
MAU-01 Supply Outlet Summary
JEDI Balancing, Inc.
Page 8 of 26
Energy Recovery UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: ERV-01
Unit Data
Unit Manufacturer RENEWAIRE
Unit Model Number HE10IN
Unit Serial Number C24101755C
Starter Data
ERV-01/Exhaust Fan
Starter Manufacturer Thermally Protected
ERV-01/Supply Fan
Starter Manufacturer Thermally Protected
Design Data
Supply OA Flow Design 725
Supply Fan Design ESP 0.5 in. wc
Supply Fan Design TSP Not Given in. wc
Supply Fan Design RPM Not Given
Supply Fan Motor Design HP (2) 0.5
Supply Fan Motor Design RPM Not Given
Supply Fan Motor Design Volts 120
Supply Fan Motor Design Phase 1
Design Filter MERV Rating Not Given
Exhaust Fan Flow Design 725
Exhaust Fan Design SP 0.5 in. wc
Test Data
Connected Actual
Supply Airflow 725 680
Exhaust Airflow 725 650
Electrical Test Data
ERV-01/Exhaust Fan
Motor Volts 1 123
Motor Amps 1 5.40
Corrected Nameplate Amps 6.34
Actual BHP 0.55
Volts/Amps Measured By RMS Clamp Meter
ERV-01/Supply Fan
Motor Volts 1 123
Motor Amps 1 5.70
Corrected Nameplate Amps 6.34
Actual BHP 0.58
Volts/Amps Measured By RMS Clamp Meter
Motor Data
ERV-01/Exhaust Fan
Motor Manufacturer Embedded
Motor HP 480 watts
Motor RPM Not Given
Motor Frame Not Given
Motor Phase 1
Motor Rated Volts 115
Motor FL Amps 6.50
Motor Service Factor 1.0
ERV-01/Supply Fan
Motor Manufacturer Embedded
Motor HP 480 watts
Motor RPM Not Given
Motor Frame Not Given
Motor Phase 1
Motor Rated Volts 115
Motor FL Amps 6.50
Motor Service Factor 1.0
Sheave Data
ERV-01/Exhaust Fan
Drive Type Direct Drive
ERV-01/Supply Fan
Drive Type Direct Drive
Final Data
Supply OA Flow Test Method Airfoil Traverse
Exhaust Flow Test Method Flowhood Summation
Measured Data
ERV-01/Exhaust Fan
Fan RPM Actual Direct Drive
Fan Speed / Setpoint Speed control on highest
setting
Operating Hertz 60
ERV-01/Supply Fan
Fan RPM Actual Direct Drive
Fan Speed / Setpoint Speed control on highest
setting
Operating Hertz 60
Filter Data
ERV-01/EF Filter
Filter Type EXHAUST AIR
MERV Rating MERV 8
Filter Quantity (set 1)1
Filter Size (set 1)20X20X2
ERV-01/SF Filter
Filter Type OSA AIR
MERV Rating MERV 8
Filter Quantity (set 1)1
Filter Size (set 1)20X20X2
JEDI Balancing, Inc.
Page 9 of 26
Energy Recovery UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: ERV-01
Filter Data
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: ERV-01/SPP-EXHAUST
Test Data
Actual TSP 0.69 in. w.c.
External SP 0.39 in. w.c.
Test Pressures
Filter SP In -0.20 in. w.c.
Filter SP Out -0.29 in. w.c.
EF HEX SP In -0.29 in. w.c.
EF HEX SP Out -0.50 in. w.c.
Exhaust Fan SP In -0.50 in. w.c.
Exhaust Fan SP Out 0.19 in. w.c.
Static Pressure Profile
JEDI Balancing, Inc.
Page 10 of 26
Energy Recovery UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: ERV-01/SPP-SUPPLY
Test Data
Actual TSP 0.76 in. w.c.
External SP 0.36 in. w.c.
Test Pressures
Filter SP In -0.20 in. w.c.
Filter SP Out -0.36 in. w.c.
Supply Fan SP In -0.60 in. w.c.
Supply Fan SP Out 0.16 in. w.c.
Heat Exchanger SP In -0.36 in. w.c.
Heat Exchanger SP Out -0.60 in. w.c.
Static Pressure Profile
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
F-01 F-01 OA 14"725 680 680 94 Airfoil 1.07 1.07 636
Totals:---725 680 680 94 ----
ERV-01 Supply Outlet Summary
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
Inlet-01 KITCHEN ER 14"725 650 650 90 Flow Hood
Totals:---725 650 650 90 ----
ERV-01 Exhaust Inlet Summary
JEDI Balancing, Inc.
Page 11 of 26
Fan UnitPROJECT:
LOCATION:
BATTLEMENT MESA GOLF COURSE RESTAURANT AND
PARACHUTE, CO
2024-10243PROJECT #:
DATE:
CONTACT:
AUTHOR:
6/25/2024
Josh Cota
Donald Pittser
Tested By:Bryan Hund
Date:6/24/2024
SYSTEM/UNIT: KEF-01
Unit Data
Fan Manufacturer CAPTIVE AIRE
Fan Model Number DU200HFA
Fan Serial Number 6476229 KEF-01
Type of Service EXHAUST
Starter Data
Starter Manufacturer LENZE (VFD)
Design Data
Total Flow Design 3125
Total Connected Design Flow 3125
Design ESP 1.75 in. wc
Design TSP Not Given in. wc
Fan Design RPM 1320
Fan Motor Design HP 5
Fan Motor Design RPM 1320
Fan Motor Design Voltage 208
Fan Motor Design Phase 3
Electrical Test Data
Motor Volts 1 Actual 158
Motor Volts 2 Actual 157
Motor Volts 3 Actual 157
Motor Amps 1 Actual 11.30
Motor Amps 2 Actual 11.70
Motor Amps 3 Actual 11.88
Corrected Nameplate Amps 19.83
Actual BHP 2.93
Volts/Amps Measured By RMS Clamp Meter
Motor Data
Motor Manufacturer TECO
Motor HP 5
Motor RPM 1750
Motor Frame 184T
Motor Phase 3
Motor Rated Volts 208-230/460
Motor FL Amps 15-13.6/6.8
Motor Service Factor 1.15
Sheave Data
Drive Type Direct Drive
Final Data
Total Fan Flow Actual 2990
Fan Flow Test Method Velgrid Traverse
Measured Data
Fan RPM Actual Direct Drive
Fan Speed / Setpoint 45 hz
Operating Hertz 45
Test Pressures
Fan SP In Actual -0.48 in. wc
Fan SP Out Actual Atmosphere in. wc
System/Unit Area Served Outlet
Type
Size inch Design
Airflow
CFM
Prelim
Airflow
CFM
Final
Airflow
CFM
%
Final
Instrument Open Area
(sq ft)
Ak (sq ft)Final
Velocity
FPM
Inlet-01 KITCHEN HOOD 14/20 3125 2990 2990 96 Velgrid 14.2 14.2 211
Totals:---3125 2990 2990 96 ----
KEF-01 Exhaust Inlet Summary
JEDI Balancing, Inc.
Page 12 of 26
Page 13 of 26
T
T
M
T/P
P/T
F
MOUNTING HEIGHTS:
1. MOUNT ALL THERMOSTATS AT 54 INCHESS AFF, UNLESS NOTED
OTHERWISE.
CONTROL WIRING:
1. PROTECT ALL EXPOSED CONTROL AND LOW VOLTAGE WIRING BY
INSTALLING WITHIN EMT CONDUIT.
SUBMITTALS:
1. REFER TO GENERAL NOTES FOR SUBMITTAL REQUIREMENTS.
2. PROVIDE SEPARATE SUBMITTAL FOR EACH CATEGORY GROUP OR
SCHEDULE OF ITEMS.
3. AT MINIMUM, PROVIDE SUBMITTALS FOR THE FOLLOWING:
a. FANS.
b. PUMPS.
c. FURNACES, COILS.
d. ROOF TOP UNITS.
e. PACKAGED EQUIPMENT.
f. GRILLES, REGISTERS, DIFFUSERS, AND DUCT ACCESSORIES.
g. CONTROLS PACKAGES.
h. DUCT AND DUCT INSULATION MATERIALS AND METHODS
i. PIPE AND PIPE INSULATION MATERIALS AND METHODS.
j. TEST AND BALANCE REPORTS.
k. TERMINAL UNITS.
l. CONDENSING UNITS.
MECHANICAL COMMISSIONING:
1.MECHANICAL COMMISSIONING SHALL BE PERFORMED IN COMPLIANCE WITH
SECTION C408 OF THE ADOPTED IECC.
2.COMMISSIONING SHALL INCLUDE ALL SCHEDULED EQUIPMENT AND WORK
INDICATED AS NEW WITHIN THE PLANS AND SPECIFICATIONS. SUCH
COMMISSIONING SHALL BE SUFFICIENT TO DEMONSTRATE INTENDED
OPERATING CONDITIONS AND FUNCTIONS.
3.COMMISSIONING AGENTS SHALL INCLUDE BUT ARE NOT LIMITED TO: THE
MECHANICAL CONTRACTOR, TAB CONTRACTOR, RELATED SUB
CONTRACTORS.
4.PRELIMINARY AND FINAL COMMISSIONING REPORTS SHALL BE FURNISHED
TO THE ENGINEER FOR APPROVAL. REPORTS SHALL INCLUDE ITEMIZATION OF
DEFICIENCIES, DEFERRED TESTS, AND CLIMATIC CONDITIONS, AT A MINIMUM.
TEST AND BALANCE:
1. PERFORM TESTING, ADJUSTING AND BALANCING (TAB) BY AN AABC, NEBB,
OR TABB AGENCY WITH CURRENT CERTIFICATION.
2. TAB INCLUDES BUT IS NOT LIMITED TO (WHEN PRESENT): ADJUSTING AND
RESHEAVING FANS, AIR HANDLING EQUIPMENT, PUMPS, AIR TERMINAL UNITS
AND DEVICES, CALIBRATING THERMOSTATS, BALANCING VALVES, PRESSURE
RELATIONSHIPS, OUTSIDE AIR DAMPERS, AND MEASURING MOTOR
ELECTRICAL CHARACTERISTICS.
3. AIRSIDE TOLERANCES:
a. SUPPLY, RETURN, AND EXHAUST FANS AND EQUIPMENT WITH FANS:
MINUS 5 TO PLUS 10 PERCENT.
b. AIR OUTLETS AND INLETS: 0 TO MINUS 10 PERCENT.
4.INDICATE % DISCREPANCY BETWEEN ACTUAL AND DESIGN VALUES FOR
EACH OF THE FOLLOWING (WHEN PRESENT WITH A SPECIFIED
VALUE/SETTING), AT MINIMUM:
a. DIFFUSER/REGISTER/GRILLE/LOUVER.
b. FAN.
5. BALANCE AIR AND WATER FLOWS TO VALUE SHOWN AT THE TERMINAL
DEVICE UNLESS NOTED OTHERWISE. TERMINAL VALUES MAY DIFFER FROM
CENTRAL EQUIPMENT VALUES OR CAPACITIES.
PENETRATIONS AND RATED ASSEMBLIES:
1. INSTALL COMBINATION FIRE/SMOKE DAMPERS AT ALL REQUIRED RATED
WALL PENETRATIONS AND BE WIRED INTO THE FIRE ALARM PANEL BY THE
ELECTRICAL AND/OR FIRE ALARM PANEL CONTRACTOR. COORDINATE TO
PROVIDE MOTOR VOLTAGE TO MATCH THAT OF THE FIRE ALARM PANEL.
INSTALL PER THE MANUFACTURER'S INSTRUCTIONS AND THE ADOPTED
CODE.
2. FIRE DAMPERS AND FIRE SMOKE DAMPERS SHALL BE UL LISTED AND
INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS AND THE ADOPTED
CODE.
3. PROVIDE FIRE STOP MATERIAL TO SEAL AROUND DUCT AND PIPE
PENETRATIONS THROUGH RATED PARTITIONS AND ASSEMBLIES, IN
ACCORDANCE WITH THE ADOPTED CODE.
4. THE SPACE ABOVE THE CEILING MAY BE USED AS A RETURN AIR PLENUM.
AS SUCH, ALL MATERIALS USED ABOVE THE CEILING SHALL BE PLENUM
RATED WITH A FLAME SPREAD INDEX NOT EXCEEDING 25 AND A SMOKE-
DEVELOPED INDEX NOT EXCEEDING 50.
MECHANICAL SPECIFICATIONS
DUCTWORK:
1. CONSTRUCT ALL DUCTWORK IN ACCORDANCE WITH THE MATERIAL,
PRESSURE, AND SEAL CLASS, AS INDICATED WITHIN THE PROJECT
DOCUMENTS.
2. ALL DUCT SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS. ACTUAL
SHEET METAL SIZE MAY VARY DEPENDING ON LINER AND WRAP
SPECIFICATIONS DEFINED WITHIN THE PROJECT DOCUMENTS.
3. MATCH RUNOUT DUCTS TO SUPPLY DIFFUSERS WITH DIFFUSER
NECK SIZE.
4. LIMIT LENGTH OF FLEXIBLE DUCWORK TO NO MORE THAN 8'-0".
5. AIR SYSTEMS WITH CAPACITIES GREATER THAN 2000 CFM MAY
REQUIRE DUCT DETECTORS. PROVIDE DUCT DETECTORS AS
PRESCRIBED BY THE ADOPTED CODE, AT THE LOCATIONS REQUIRED.
DUCT DETECTORS SHALL BE INSTALLED AS FOLLOWS: MOUNTED BY
MECHANICAL CONTRACTOR, POWER WIRING BY ELECTRICAL
CONTRACTOR, CONTROL WIRING BY THE CONTROLS CONTRACTOR.
6. ALL AIR HANDLING EQUIPMENT IS TO HAVE VIBRATION ISOLATION.
SPLIT DX SYSTEMS:
1. CONSTRUCT ALL PIPING IN ACCORDANCE WITH THE MATERIALS,
FITTINGS, METHODS, AND INSULATION REQUIREMENTS, AS
INDICATED ELSEWHERE WITHIN THE PROJECT DOCUMENTS.
2. INSTALL REFRIGERATION SPECIALTIES IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
3. PIPING INSTALLATION SHALL NOT EXCEED EQUIPMENT
MANUFACTURER MAXIMUM VERTICAL AND HORIZONTAL LENGTHS.
CONTRACTOR TO VERIFY FINAL LENGTHS ARE IN ACCORDANCE WITH
MANUFACTURER SPECIFICATIONS PRIOR TO PURCHASING AND
INSTALLATION.
4. PROVIDE FACTORY STARTUP ON COMPLETE SYSTEM.
ELECTRICAL ROOMS:
1. ONLY PIPING DEDICATED TO EQUIPMENT SERVING OR
CONDITIONING AN ELECTRICAL ROOM MAY BE INSTALLED IN THE
ELECTRICAL ROOM. IN SUCH CASES, PROVIDE SECONDARY
CONTAINMENT TO PREVENT LEAKS AND/OR CONDENSATION, VIA
SECONDARY CONTAINMENT BENEATH THE PIPE, WITH AUDIBLE
ALARM UPON LEAK DETECTION OR VISUAL "TELL TALE" DRAIN
TERMINATION LOCATION. REFERENCE NEC 110. IN NO CASE MAY
PIPING OR DUCTWORK BE INSTALLED DIRECTLY ABOVE ELECTRICAL
EQUIPMENT WITHIN THE SPACE.
KEYNOTE TAG
REVISION TAG
EQUIPMENT TAG
REFER TO EQUIPMENT SCHEDULE
REFERENCE EQUIPMENT TAG
SPECIFIED BY ANOTHER DISCIPLINE
GRILLE, REGISTER, DIFFUSER TAG
AA-#-###
?
##
AA-#-###
NEW, OR OTHER ACTION ITEMS
(Solid dark lines)
ITEMS TO BE DEMOLISHED
(Dashed dark lines on demo plans)
EXISTING ITEMS TO REMAIN
(Solid light lines and text)
CONNECT NEW TO EXISTING
##
Type CFM
Size
reference info
ANNOTATION SYMBOLS
LINETYPES / PHASING
MECHANICAL SYMBOL LEGEND
TEMPERATURE SENSOR
THERMOSTAT
MOTORIZED DAMPER
DEVICE SYMBOLS
SUPPLY / DRAIN
RETURN
BELOW GRADE
PIPING LINE TYPES
SYSTEM TYPE
SYSTEM TYPE
SYSTEM TYPE
C CONDENSATE
CA COMPRESSED AIR
CD GRAVITY FLOW CONDENSATE DRAIN
PCD PUMPED CONDENSATE DRAIN
CH CHILLED WATER
CW CONDENSATE WATER
HW HEATING WATER
RL/RS REFRIGERANT LINESET
RS REFRIGERANT SUCTION
RL REFRIGERANT LIQUID
SM SNOWMELT
HR HEAT RECOVERY
HPS HIGH PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
LPS LOW PRESSURE STEAM
HGBP HOT GAS BYPASS
PIPE SYSTEM TYPE ABBREVIATIONS
2-WAY VALVE
3-WAY VALVE
ISOLATION VALVE
BALANCING VALVE
TEMP. AND PRESSURE RELIEF VALVE
CHECK VALVE
VALVE SYMBOLS
FLOW SWITCH
PRESSURE GAUGE
PRESSURE AND TEMPERATURE TAP
THERMOMETER
CONTROL & INSTRUMENTATION SYMBOLS
HYDRONIC SPECIALTIES SYMBOLS
AIR VENT
STRAINER
COUPLING & CONNECTOR SYMBOLS
FLANGED CONNECTION
UNION
EQUIPMENT SYMBOLS
PUMP
DUCT SYSTEM TYPE ABBREVIATIONS
FV FLUE VENT
CA COMBUSTION AIR
OA OUTSIDE AIR (UNCONDITIONED)
FA FRESH AIR (CONDITIONED)
SA SUPPLY AIR
RA RETURN AIR
EA EXHAUST (GENERAL)
GE GREASE EXHAUST
TA TRANSFER AIR
DEFINITIONS:
1. CONTRACTOR: THE ENTITY BINDED BY THE PRIME AGREEMENT WITH
THE CLIENT TO PERFORM THE TASKS INDICATED IN THE CONTRACT
DOCUMENTS. THE TERM CONTRACTOR INCLUDES AND IMPLIES ANY
RELEVANT SUB-CONTRACTOR THAT MAY BE PERFORMING THE
ACTUAL TASK UNDER THE CONTRACTOR’S DIRECTION.
2. CONTRACT DOCUMENTS: THE COMPLIMENTARY COLLECTION OF
DRAWINGS, SPECIFICATIONS, AND PROJECT MANUAL, WHICH ARE
DIRECTED TO THE CONTRACTOR, UNDER THE PRIME AGREEMENT.
3. FURNISH: TO SUPPLY, DELIVER, UNLOAD, AND INSPECT FOR DAMAGE.
4. INSTALL: TO UNPACK, ASSEMBLE, ERECT, APPLY, PLACE, FINISH,
CURE, PROTECT, CLEAN, START UP, AND MAKE READY FOR USE.
5. PROVIDE: TO FURNISH AND INSTALL.
6. SUPPLY: SAME AS FURNISH.
7. PRODUCT: MATERIAL, MACHINERY, COMPONENTS, EQUIPMENT,
FIXTURES, AND SYSTEMS FORMING THE WORK RESULT. NOT
MATERIALS OR EQUIPMENT USED FOR PREPARATION, FABRICATION,
CONVEYING, OR ERECTION AND NOT INCORPORATED INTO THE WORK
RESULT. PRODUCTS MAY BE NEW, NEVER BEFORE USED, OR RE-USED
MATERIALS OR EQUIPMENT.
8. PROJECT MANUAL: THE BOOK-SIZED VOLUME THAT INCLUDES THE
PROCUREMENT REQUIREMENTS (IF ANY), THE CONTRACTING
REQUIREMENTS, AND THE SPECIFICATIONS.
NATURE AND USE OF CONTRACT DOCUMENTS:
1. IF ANY DISCREPANCY IS FOUND WITHIN THE CONTRACT DOCUMENTS
DURING CONSTRUCTION, SUBMIT AN RFI TO THE ENGINEER FOR
DIRECTION BEFORE PROCEEDING. IF A DISCREPANCY IS FOUND
DURING BIDDING, AND THE DESIGN TEAM DOES NOT PROVIDE A
RESOLUTION BY THE FINAL ADDENDUM, BASE THE BID ON THE MORE
COSTLY INTERPRETATION. FAILING TO DO SO WILL NOT BE
CONSIDERED A VALID BASIS FOR CHANGE ORDERS DURING
CONSTRUCTION.
2. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
CONTRACT DOCUMENTS TO ALL TRADES, AND FOR COORDINATING
BETWEEN ALL TRADES TO ENSURE PROPER INSTALLATION OF
COMPLETE AND FUNCTIONAL SYSTEMS AS SHOWN ON THE CONTRACT
DOCUMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL SCOPES OF WORK,
COMPLETENESS OF BIDS, AND PRICING EXERCISES. FURTHER,
COORDINATION AND DIVISION OF SCOPE AMONGST SUB-
CONTRACTORS IS THE RESPONSIBILITY OF THE CONTRACTOR.
4. DO NOT SCALE DRAWINGS FOR ROUGH-IN MEASUREMENTS OR USE
AS SHOP DRAWINGS. WHERE DRAWINGS ARE REQUIRED FOR THESE
PURPOSES OR HAVE TO BE MADE FROM FIELD MEASUREMENTS, TAKE
THE NECESSARY MEASUREMENTS AND PREPARE THE DRAWINGS.
5. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW
EVERY SYSTEM OFFSET REQUIRED. COORDINATE WITH THE EXISTING
AND NEW STRUCTURE, ELECTRICAL, PLUMBING, FIRE PROTECTION
AND CEILING TO PROVIDE OFFSETS AS REQUIRED AND APPROPRIATE.
CODES, INSPECTIONS, AND PERMITS:
1. PERFORM ALL WORK IN ACCORDANCE WITH THE CODES,
REGULATIONS, AND LOCAL AMENDMENTS, AS CURRENTLY ADOPTED
BY THE AUTHORITY HAVING JURISDICTION (AHJ).
2. IF ANY DISCREPANCIES ARE FOUND BETWEEN CONTRACT
DOCUMENTS AND ANY APPLICABLE CODE OR LEGAL REQUIREMENT,
SUBMIT AN RFI TO ENGINEER FOR DIRECTION BEFORE PROCEEDING.
3. OBTAIN ALL PERMITS AND INSPECTIONS, AND PAY FOR ALL UTILITY
METERS AND UTILITY CONNECTIONS, REQUIRED BY THE AHJ FOR
PROJECT COMPLETION.
WARRANTY:
1. UNCONDITIONALLY GUARANTEE ALL LABOR AND MATERIAL ON ALL
WORK AGAINST DEFECTS IN WORKMANSHIP AND MATERIALS FOR A
PERIOD OF ONE YEAR, FOLLOWING FINAL ACCEPTANCE, EXCEPT AS
EXTENDED BY STANDARD MANUFACTURER WARRANTY AND/OR BY
REQUIRED EXTENSION STATED IN THE CONTRACT DOCUMENTS.
SUBMITTALS AND SUBSTITUTIONS:
1. MEET THE CRITERIA DESCRIBED HEREIN, PRIOR TO ENGINEER'S
REVIEW OF THE SUBMITTAL.
2. REFERENCE EQUIPMENT TAGS PROVIDED IN THE CONTRACT
DOCUMENTS.
3. CLEARLY INDICATE THE INTENDED PRODUCT TYPE, MODE, OPTIONS,
ACCESSORIES (FACTORY AND FIELD INSTALLED), AND ANY OTHER
OPTIONS OF ANY KIND.
4. INDICATE THE PLAN ISSUANCE AND DATE ON WHICH SUBMITTAL IS
BASED.
5. IF PROPOSING A SUBSTITUTION IN PLACE OF THE BASIS OF DESIGN
EQUIPMENT, THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
SPATIAL REQUIREMENTS, ACOUSTICAL, THERMAL, PHOTOMETRIC, AND
ELECTRICAL PERFORMANCE CHARACTERISTICS, AND COORDINATION
OF ALL INSTALLATION REQUIREMENTS. REVIEW AND APPROVAL BY
THE DESIGN TEAM DOES NOT ALTER OR MITIGATE THIS
RESPONSIBILITY. CLEARLY MARK SUBSTITUTIONS AS SUCH.
6. DESCRIBE ANY IMPACT TO OTHER DIVISIONS CREATED BY A
PRODUCT SUBSTITUTION ON THE SUBSTITUTION REQUEST FOR
CONSIDERATION BY THE DESIGN TEAM. PROVIDE AN ESTIMATE OF
ASSOCIATED COST IMPACT TO OTHER DIVISIONS WHERE APPLICABLE.
7. INDICATE WHERE PRODUCTS REQUIRE A PERFORMANCE DE-RATE
DUE TO ALTITUDE EFFECTS.
8. RE-SUBMITTALS MUST CONTAIN MARKUPS THAT CLEARLY DELINEATE
THE CHANGED ITEMS. ENGINEER WILL NOT RE-REVIEW THE ENTIRE
SUBMITTAL PACKAGE IN ORDER TO FIND THE CHANGES.
9. ALL DATA REQUIRED FOR REVIEW MUST BE CONTAINED IN THE FILES
PROVIDED TO THE ENGINEER. LINKS TO MANUFACTURER’S WEBSITES
WILL NOT BE ACCEPTED.
10. ROOM SCHEDULES ARE ACCEPTABLE TO INDICATE QUANTITIES.
PROJECT CLOSEOUT REQUIREMENTS:
1. COMPLETE ALL REQUIRED AHJ INSPECTIONS. MAKE COPIES OF
PERMITS AND INSPECTION REPORTS AVAILABLE.
2. PROVIDE A COMPLETE SET OF AS-BUILT PLANS AT THE COMPLETION
OF THE PROJECT WITH ALL CHANGES NOTED.
3. CONDUCT A TRAINING SESSION FOR OWNER’S DESIGNATED STAFF
FOR ALL CONTROLS SYSTEMS AND MAJOR EQUIPMENT. PRODUCE A
SIGN IN SHEET FOR THIS SESSION SHOWING ATTENDEES, DATE, LIST
OF EQUIPMENT AND SYSTEMS COVERED.
4. CLEAN JOB SITE OF ALL CONSTRUCTION DEBRIS, REPAIR ALL
DAMAGED FINISHES. REMOVE ALL EXISTING EQUIPMENT LABELS THAT
ARE NO LONGER ACCURATE, AND INSTALL NEW LABELING FOR NEW
EQUIPMENT AND SYSTEMS.
5. DELIVER EQUIPMENT MANUALS AND ANY REQUIRED SPARE PARTS TO
OWNER.
ACCESS AND CLEARANCES:
1. MAINTAIN ALL SERVICE AND ACCESS CLEARANCES REQUIRED BY
CODE OR MANUFACTURER FOR ALL EQUIPMENT.
2. PROVIDE ACCESS FOR ALL EQUIPMENT, ETC. LOCATED ABOVE NON-
ACCESSIBLE CEILINGS OR IN CONCEALED AREAS. PROVIDE
SUFFICIENT ACCESS FOR SERVICING AND MAINTENANCE.
3. UTILIZE APPROPRIATELY RATED ACCESS PANELS WHEN
PENETRATING A RATED ASSEMBLY.
PENETRATIONS AND RATED ASSEMBLIES:
1. THE ARCHITECTURAL PLANS SERVE AS THE REFERENCE FOR
LOCATIONS OF RATED WALLS, PARTITIONS, AND ASSEMBLIES.
COORDINATE ALL PENETRATIONS PRIOR TO ROUGH IN. FOR ALL
PENETRATIONS OF FIRE RATED ASSEMBLIES, UTILIZE AN ASSEMBLY UL
LISTED TO MAINTAIN THE RATING AND APPROVED BY ALL APPLICABLE
CODES.
STRUCTURAL MODIFICATIONS:
1. DO NOT DRILL, NOTCH, CUT, OR ALTER STRUCTURAL MEMBERS IN
ANY MANNER EXCEPT AS PERMITTED BY THE MATERIAL SPECIFIC
SECTIONS OF THE BUILDING CODE, MANUFACTURER’S GUIDELINES
FOR ENGINEERED PRODUCTS, OR THE RECOMMENDATION OF THE
STRUCTURAL ENGINEER OF RECORD.
EXISTING CONDITIONS AND DEMOLITION:
1. VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS
TO THE EXTENT POSSIBLE BEFORE BEGINNING WORK. IF
DISCREPANCIES ARE FOUND BETWEEN THE CONTRACT DOCUMENTS
AND ACTUAL SITE CONDITIONS, SUBMIT AN RFI TO THE ARCHITECT OR
ENGINEER FOR DIRECTION BEFORE PROCEEDING.
2. COORDINATE IN ADVANCE ALL WORK THAT AFFECTS EXISTING
SYSTEMS OR OPERATIONS (SUCH AS SHUT DOWNS, TIE-INS, OR
DEMOLITION), WITH THE BUILDING OWNER IN ADVANCE.
3. RETURN EXISTING EQUIPMENT NOTED AS TO BE REMOVED TO
OWNER IN THE SAME CONDITION AS FOUND (EXCEPT WHERE
CONTRACT DOCUMENTS CALL FOR DISPOSAL BY CONTRACTOR).
COORDINATE DELIVERY AND STORAGE LOCATION WITH CONTRACTOR.
4. COORDINATE REPAIR OF ADJACENT CONSTRUCTION AND FINISHES
DAMAGED OR EXPOSED DURING DEMOLITION WORK. MATCH EXISTING
FINISHES, AND INCLUDE PAINT ON ENTIRE WALL OR ROOM IF
REQUIRED TO MATCH COLOR.
5. X-RAY ANY SLAB PENETRATIONS PRIOR TO CORE DRILLING.
6. PRIOR TO TRENCHING OR EXCAVATION, CONTACT UTILITY
COMPANIES TO IDENTIFY UNDERGROUND UTILITIES AND LOCATE
SECONDARY SERVICE FEEDERS, UNDERGROUND BRANCH CIRCUITS,
GAS LINES, SPRINKLER LINES, ETC. ANY CUT OR DAMAGED
UNDERGROUND SYSTEMS TO BE REPAIRED OR REPLACED AT
CONTRACTOR'S EXPENSE.
7. PROVIDE MEANS OF TRACING TO ALL UNDGROUND UTILITIES OUTSIDE
THE BUILDING PERIMETER, IN COMPLIANCE WITH SUBSURFACE UTILITY
ENGINEERING REGULATIONS.
GENERAL NOTES
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
1
5
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
MECHANICAL
LEGEND AND
SPECIFICATIONS
M001
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
MECHANICAL SHEET LIST
Sheet Number Sheet Name
M001 MECHANICAL LEGEND AND
SPECIFICATIONS
M002 SPECIFICATIONS
M101 MAIN LEVEL MECHANICAL DEMO PLAN
M102 MAIN LEVEL MECHANICAL PROPOSED
PLAN
M103 ROOF LEVEL MECHANICAL DEMO PLAN
M104 ROOF LEVEL MECHANICAL PROPOSED
PLAN
M201 ELEVATIONS
M401 ENLARGED PLANS
M501 DETAILS
M601 SCHEDULES
M901 AXONOMETRICS
ADOPTED CODES
AHJ GARFIELD COUNTY
LOCAL AMENDMENTS EXHIBIT A
NEC 2020
IECC 2018
IBC 2015
IMC 2015
IFGC 2015
IPC 2015
SITE CONDITIONS
ELEVATION AIR DENSITY
RATIO
CLIMATE
ZONE
WINTER
DESIGN
SUMMER
DESIGN
5240' - 0" 0.81 5B -2 °F 95 °F
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 14 of 26
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
SYMBOL SERVICE
MFR. &
MODEL FACE TYPE MOUNTING MATERIAL FINISH
DEVICE
MOUNTED
DAMPER
ACCESSORIES / OPTIONS DESCRIPTION
FACE SIZE / NECK SIZE
(INCHES)NOTES
S1 SUPPLY
PRICE
SPD SQUARE PLAQUE LAY IN STEEL FACTORY WHITE NA NA
REMOVABLE SINGLE INNER CONE,
MAXIMUM 1/4 INCH DROP BELOW
FACE.
24X24 / 8 Ø ALL
S2 SUPPLY
PRICE
SPD SQUARE PLAQUE LAY IN STEEL FACTORY WHITE NA NA
REMOVABLE SINGLE INNER CONE,
MAXIMUM 1/4 INCH DROP BELOW
FACE.
24X24 / 10 Ø ALL
R1 RETURN
PRICE
PDDR PERFORATED FACE LAY IN STEEL FACTORY WHITE NA NA
SQUARE FACE, STEEL, CEILING GRILLE
WITH ROUND NECK AND PERFORATED
ALUMINUM FACE.
24X24 / 14X14 ALL
E1 EXHAUST
PRICE
PDDR PERFORATED FACE LAY IN STEEL FACTORY WHITE YES
TYPE SPF RAPID MOUNT
FRAME
SQUARE FACE, STEEL, CEILING GRILLE
WITH ROUND NECK AND PERFORATED
ALUMINUM FACE.
24X24 / 14Ø ALL
NOTES:
1. GENERAL: VERIFY CEILING, WALL AND FLOOR CONSTRUCTION MATERIALS AND FINISHES ON THE ARCHITECTURAL DRAWINGS, AND COORDINATE BORDER TYPES/FRAMES FOR THE GRILLES, REGISTERS AND DIFFUSERS ACCORDINGLY.
2. MILL FINISH AND FACTORY WHITE FINISH SHALL BE PAINTABLE. REFER TO ARCHITECTURAL FOR PAINT COLOR (IF APPLICABLE).
LOUVER SCHEDULE
UNIT
TAG MFR. MODEL SERVICE LOCATION
AIRFLOW
(CFM)
AIRFLOW
DIRECTION
SIZE
(IN)FACE
VELOCITY
(FPM)
NET
VELOCITY
(FPM)
WATER
PENETRATION
VELOCITY
(FPM)
PRESSURE
DROP
@ S.L.
(IN W.G.)
FREE
AREA
(SQ.FT.)
FRAME
DEPTH
(IN.)
FINISH NOTES
WIDTH HEIGHT
L-1 GREENHECK ESD-435 F-1, F-2 N WALL, ATTIC 725 INTAKE 16 24 272 642 >1100 0.067 1.13 4 MILL 1, 2
L-2 GREENHECK ESD-435 F-1, F-2 N WALL, ATTIC 725 EXHAUST 16 24 272 642 >1100 0.067 1.13 4 MILL 1, 2
NOTES:
1. LOUVER SHALL BE AMCA CERTIFIED, WITH DRAINABLE STATIONARY BLADE.
2. PROVIDE THE FOLLOWING OPTIONS AND ACCESSORIES: BIRD SCREEN.
FURNACE SCHEDULE
UNIT
TAG MFR. MODEL CONFIG.THERMOSTAT SERVICE
FAN COOLING HEATING ELECTRICAL DATA DIMENSIONS
WEIGHT
(LBS)NOTES
SUPPLY
AIRFLOW @
PROJECT
ALTITUDE
(CFM)
MIN.
OUTSIDE AIR
(CFM)
FAN SPEED FILTER
(L X W X D)
ESP
@ S.L. WITH
ACCESSORIES
(IN.WC.)
ESP
@
PROJECT
ALTITUDE
(IN.WC.)
TOTAL
CAPACITY
(MBH)
EVAPORATOR
EAT
EVAPORATOR
LAT
EVAP.
MODEL
OUTDOOR
COMPANION
UNIT
FUEL FIRED HEAT EXCHANGER
VOLTS /
PHASE FLA MOCP
(A)
LENGTH
(IN)
WIDTH
(IN)
HEIGHT
(IN)DB
(˚F)
WB
(˚F)
DB
(˚F)
EFFICIENCY
(AFUE)
FUEL
TYPE
(NG/P)
TURNDOWN
OR STAGES
TEMP. RISE
@ ALTITUDE
(˚F)
INPUT
CAPACITY @
S.L.
(MBH)
OUTPUT
CAPACITY @
ALTITUDE
(MBH)
F-1 TRANE S9V2C100U4VSAC/D
UPFLOW,
RIGHT INLET T1 DINING ROOM /
FOH 1770 650 H
20" X 25" X 1"
(HI VEL)0.5 0.62 60.0 77 55 40.0
4TXCC009
DS3HCB CU-1 97 NG 2 STAGE 53.6 100.0 83.5 120/1 12.90 15 34 21
34
(+31 W/ EVAP)
154
(+70 W/ EVAP)ALL
F-2 TRANE S9V2C100U4VSAC/D
UPFLOW,
RIGHT INLET T2 KITCHEN / BOH 1770 75 H
20" X 25" X 1"
(HI VEL)0.5 0.62 42.0 77 55 51.1
4TXCC007
DS3HCB CU-2 97 NG 2 STAGE 53.6 100.0 83.5 120/1 12.90 15 34 21
34
(+27 W/ EVAP)
154
(+61 W/ EVAP)ALL
NOTES:
1. REFER TO CONDENSER SCHEDULE FOR AMBIENT TEMPERATURES AND ADDITIONAL INFORMATION.
2. FURNISH WITH THE FOLLOWING ACCCESSORIES: DISCONNECT, CONDENSATE OVERFLOW SWITCH, AND STAINLESS STEEL DRAIN PAN.
3. UNIT SHALL INCLUDE FACTORY STARTUP.
4. FILTER NOT FURNISHED WITH UNIT.
5. PROVIDE TRANE XR203 THERMOSTAT OR APPROVED EQUAL, CAPABLE OF 2 STAGE HEATING AND SINGLE STAGE COOLING, WITH 7 DAY PROGRAMMABLE SCHEDULE.
AIR COOLED CONDENSING UNIT OUTDOOR UNIT SCHEDULE
UNIT TAG INDOOR UNIT
TAG MFR. MODEL
REFRIGERANT
TYPE
SOUND
PRESSURE
(DBA)
FAN VOLUME
(CFM)
AMBIENT TEMP.NOMINAL
CAPACITY EFFICIENCY @ AHRI UNIT ELECTRICAL DATA DIMENSIONS
WEIGHT
(LBS)NOTES
SUMMER
(F)
WINTER
(F)
COOLING
(MBH)
COOLING
(SEER)V / PH / HZ MCA
(AMPS)
MOCP
(AMPS)
W X H X D
(IN)
CU-1 F-1 TRANE 4TTR4060N1000A R410A 72 5,230 95 -2 60 14 208-230 / 1 / 60 28 50 36 X 51 X 39 302 ALL
CU-2 F-2 TRANE 4TTR4042N1000A R410A 72 4,513 95 -2 42 14 208-230 / 1 / 60 20 35 36 X 42 X 39 246 ALL
NOTES:
1. ALL PERFORMANCE VALUES AT PROJECT ALTITUDE UNLESS NOTED OTHERWISE.
2. FURNISH WITH OPTIONS AND ACCCESSORIES: DISCONNECT.
3. REFRIGERANT PIPING AS SPECIFIED BY PROJECT SPECIFIC LAYOUT AND COMPUTER GENERATED BILL OF MATERIALS FROM MANUFACTURER. REFER TO PLANS AND RELATED SCHEDULES FOR ADDITIONAL INFORMATION.
ENERGY RECOVERY VENTILATOR SCHEDULE
UNIT
TAG MANUFACTURER MODEL
NUMBER
SUPPLY FAN EXHAUST FAN WINTER AIRSTREAM SUMMER AIRSTREAM LEAVING AIR
TEMPERATURE CORE PERFORMANCE ELECTRICAL DIMENSIONS
UNIT
WEIGHT
(LBS)
NOTESALTITUDE
VOLUME
(CFM)
MOTOR
TYPE
ALTITUDE
ESP
(IN.WG)
ALTITUDE
VOLUME
(CFM)
MOTOR
TYPE
ALTITUDE
ESP
(IN.WG)
INDOOR OUTDOOR INDOOR OUTDOOR
WINTER
(F)
SUMMER
(F)TEMP. EFF%
HVI
TOTAL EFFICIENCY
V PH HZ
FAN
POWER
MCA MOCP
HEIGHT
(IN)
LENGTH
(IN)
WIDTH
(IN)DRY
BULB
(F)
WET
BULB
(F)
DRY
BULB
(F)
WET
BULB
(F)
DRY
BULB
(F)
WET
BULB
(F)
DRY
BULB
(F)
WET
BULB
(F)
SUMMER
(%)
WINTER
(%)HP
ERV-1 RENEWAIRE HE1XINH 725 ECM 0.5 725 ECM 0.5 70 48 -2 NA 75 52 95 65 48.8 80.9 70.5 45.5 68.6 120 1 60 2 @ 0.5 18.2 25 35 53.75 21.75 275 ALL
NOTES:
1. AIR CONDITIONS ARE BASED ON A PROJECT ALTITUDE OF 5300 FEET ABOVE SEA LEVEL.
2. FURNISH WITH THE FOLLOWING FACTORY OPTIONS AND ACCESSORIES: TWO MERV 8 FILTERS, MOTORIZED DAMPER (INTAKE), FUSED DISCONNECT AND POTENTIOMETER SPEED CONTROL.
SEQUENCES OF OPERATION:
PROVIDE ALL THE NECESSARY CONTROLS, WIRING, RELAYS, SENSORS, SOFTWARE, CONTROL
VALVES, AND HARDWARE TO ACHIEVE THE FOLLOWING SEQUENCES HEREIN, AND IN CONJUNCTION
WITH THE PROJECT DOCUMENTS.
SETPOINTS:
ALL SETPOINTS ARE INDICATED VIA UNDERLINE.ADJUSTABLE INDICATES VALUE IS USER
ADJUSTABLE VIA FACTORY INTERFACE OR DDC INTERFACE (NOT HARD WIRED/CODED).
SPACE, ZONE, AND SLAB SETPOINTS:
SPACE HEATING TEMPERATURE = 70F (ADJUSTABLE)
SPACE COOLING TEMPERATURE = 75F (ADJUSTABLE)
INDIVIDUAL ZONE CONTROL
PROGRAMMABLE ZONE CONTROL
PROVIDE A 7-DAY PROGRAMABLE THERMOSTAT SPECIFICALLY DESIGNED TO SUPPORT A
FURNACE APPLICATION WITH DX COOLING, CAPABLE OF COMMUNICATING WITH AN ERV
INTERLOCK.
HEATING F-1 AND F-2:
UPON A CALL FOR HEATING, THE FURNACE SHALL UTILIZE INTERNAL FACTORY CONTROL TO
MAINTAIN SPACE HEATING TEMPERATURE.
COOLING F-1/CU-1 AND F-2/CU-2:
UPON A CALL FOR COOLING, THE FURNACE AND CORRESPONDING CU SHALL UTILIZE INTERNAL
FACTORY CONTROL TO MAINTAIN SPACE COOLING TEMPERATURE.
VENTILATION ERV-1:
THE ERV SERVES AS OUTSIDE AIR VENTILATION FOR THE KITCHEN AND RESTAURANT VIA F-1 AND
F-2. PROVIDE AN INTERLOCK WITH F-1 AND F-2.
THE UNIT SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS.
UPON A CALL FOR VENTILATION THE MOTORIZED DAMPER SHALL OPEN AND ERV-1 SHALL UTILIZE
INTERNAL FACTORY CONTROL TO SUPPLY OUTSIDE AIR TO THE F-1 AND F-2. THE DAMPER SHALL
CLOSE WHEN THE CALL FOR VENTILATION ENDS.
MAU-1:
THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE
CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS.
KEF-1:
THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE
CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS.
CU-K1:
THE UNIT IS SUPPLIED BY CAPTIVEAIRE AS PART OF A COMPLETE SYSTEM PACKAGE. REFER TO THE
CAPTIVEAIRE DOCUMENTS FOR THE SEQUENCE OF OPERATIONS.
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
2
2
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
SCHEDULES
M601
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 15 of 26
EXHAUST FAN INFORMATION - JOB#6145305
1 1 DU200HFA CAPTIVEAIRE 3125 1.750 1320 ODP,PREMIUM 5.000 2.0380 3 208 15.0 760 FPM 219 27.7
FAN
UNIT
NO
TAG QTY FAN UNIT MODEL #MANUFACTURER CFM ESP RPM
MOTOR
ENCL
HP BHP PHASE VOLT FLA
DISCHARGE
VELOCITY
WEIGHT
(LBS)
SONES
CONDENSER DETAILS
2 A2-D.250-20D-MPU 1 5 208-230 3 PHASE 60 HZ 21.4 AMPS 17.4 AMPS 30 AMPS 10 AWG 14
FAN
UNIT
NO
TAG FAN UNIT MODEL #
CONDENSER
NO
TONNAGE VOLTAGE PHASE FREQUENCY MCA RLA
MAX FUSE
SIZE
MIN WIRE
SIZE
SEER
MUA FAN INFORMATION - JOB#6145305
2 1 A2-D.250-20D-MPU 20MF-2-MOD A2-D.250 2000 2500 0.500 1391 ODP,PREMIUM 1.500 1.1520 3 208 6.6 8.3A 15A 1366 12.3
FAN
UNIT
NO
TAG QTY FAN UNIT MODEL #BLOWER HOUSING
MIN
CFM
DESIGN
CFM
ESP RPM
MOTOR
ENCL
HP BHP PHASE VOLT FLA MCA MOCP
WEIGHT
(LBS)
SONES
COILS - JOB#6145305
2 DX 2500 93.0°F 60.0°F 64.7°F 50.0°F ------------60.0 MBH 60.0 MBH 0.0 MBH ---------------------------
FAN
UNIT
NO
TAG
COIL
TYPE
DESIGN
CFM
COOLING
ENTERING DB
TEMP
ENTERING WB
TEMP
LEAVING DB
TEMP
LEAVING WB
TEMP
ENTERING
FLUID TEMP
LEAVING
FLUID TEMP
FLUID FLOW
RATE
PERCENT
GLYCOL
TOTAL
CAPACITY
SENSIBLE
CAPACITY
LATENT
CAPACITY
HEATING
ENTERING DB
TEMP
LEAVING DB
TEMP
ENTERING
FLUID TEMP
LEAVING
FLUID TEMP
FLUID FLOW
RATE
PERCENT
GLYCOL
TOTAL
CAPACITY
SENSIBLE
CAPACITY
GAS FIRED MAKE-UP AIR UNIT(S)
2 158275 145613 67°F 7 IN. W.C. - 14 IN. W.C.NATURAL 92
FAN
UNIT
NO
TAG
INPUT
BTUs
OUTPUT
BTUs
TEMP RISE REQUIRED INPUT GAS PRESSURE GAS TYPE
BURNER
EFFICIENCY(%)
FAN OPTIONS
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GREASE BOX
FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS
2 YEAR PARTS WARRANTY
INLET PRESSURE GAUGE, 0-35"
MANIFOLD PRESSURE GAUGE, -5 TO 15" WC
BUTTERFLY MOD VALVE OPTION FOR MOD SIZE 2 (1" MOD VALVE)
SHIP LOOSE GAS STRAINER 1"
CASLINK BUILDING MONITORING SYSTEM - INTERNET OR CELLULAR CONNECTION REQUIRED
MOTORIZED BACKDRAFT DAMPER FOR A2-D HOUSING - MEETS AMCA CLASS 1A RATING
5 TON SINGLE CIRCUIT MODULAR PACKAGED AC COOLING OPTION FOR SIZE 2 DF/EH MUA
(1000 TO 2750 CFM), 208V/230V, 3 PHASE. COOLING THERMOSTAT OR PROGRAMMABLE STAT
REQUIRED FOR PROPER OPERATION
SHIP CONDENSER LOOSE - SINGLE CONDENSER, THREE PHASE - CONDENSER DISCONNECT
SHIPPED LOOSE. ALL PIPING AND WIRING BETWEEN INDOOR AND OUTDOOR UNITS BY OTHERS
DOWNTURN PLENUM FOR SIZE 2 DX COIL MODULE
SEPARATE 120V WIRING PACKAGE (REQUIRED AND USED ONLY FOR DCV OR PREWIRE WITH
VFD) - THREE PHASE ONLY
SIZE 2 DIRECT FIRED HEATER LOW CFM PROFILE PACKAGE - USED ON HEATERS UNDER 2500
CFM
2 YEAR PARTS WARRANTY
FAN
UNIT
NO
TAG QTY DESCRIPTION
FAN ACCESSORIES
1
2
YES
YES
FAN
UNIT
NO
TAG
EXHAUST
GREASE
CUP
GRAVITY
DAMPER
WALL
MOUNT
SUPPLY
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
WALL
MOUNT
CURB ASSEMBLIES
1
2
# 1
# 2
34 LBS
92 LBS
CURB
CURB
26.500"W X 26.500"L X 26.000"H 4.000:12.000 PITCH ALONG LENGTH, RIGHT VENTED
HINGED.
31.000"W X 145.000"L X 20.000"H INSULATED.
NO
ON
FAN
WEIGHT ITEM SIZE
- VARIABLE SPEED CONTROL.
- THERMAL OVERLOAD PROTECTION (SINGLE PHASE).
- HIGH HEAT OPERATION 300°F (149°C).
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING AIR AT 300°F (149°C)
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
NORMAL TEMPERATURE TEST
26"
28"
37 3/8"
18"
2"
29 1/2"
- INTERNAL WIRING.
- ROOF MOUNTED FANS.
- RESTAURANT MODEL.
FEATURES:
- DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS).
TOP VIEW
37 3/8"
28"
- NEMA 3R SAFETY DISCONNECT SWITCH.
DUCTWORK BETWEEN
EXHAUST RISER ON HOOD
AND FAN (BY OTHERS).
33 3/8"
GREASE DRAIN.
- GREASE CLASSIFICATION TESTING.
- UL705 AND UL762 AND ULC-S645
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
AT 600°F (316°C) FOR A PERIOD OF
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
26"
26"
ROOF OPENING
DIMENSIONS.
26"
26 1/2"
20 GAUGE
CONSTRUCTION.
STEEL
3" FLANGE.
26 1/2"
HINGE KIT
VENTED
CURB.
EXAMPLE: 7/12 PITCH = 30° SLOPE.
PITCHED CURBS ARE AVAILABLE
FOR PITCHED ROOFS.
SPECIFY PITCH:
4"
18°
12"
FAN #1 DU200HFA - EXHAUST FAN
OPTIONS
- GREASE BOX.
- FAN BASE CERAMIC SEAL - INSTALLED
AT PLANT - FOR GREASE DUCTS.
- 2 YEAR PARTS WARRANTY.
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
DESCRIPTION
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
DATE:
AC
C
O
R
D
A
N
C
E
No
.
9
6
BU
I
L
T
NF
P
A
WI
T
H
IN
S
LI
D
TE
R
C
U
S
6145305
MASTER DRAWING
tom.oates
3
10/11/2023
Th
e
R
o
u
g
h
B
a
r
3/4" = 1'-0"
PA
R
A
C
H
U
T
E
,
C
O
,
8
1
6
3
5
De
n
v
e
r
O
f
f
i
c
e
73
0
0
S
A
l
t
o
n
W
a
y
B
u
i
l
d
i
n
g
5
,
S
u
i
t
e
B
,
C
e
n
t
e
n
n
i
a
l
,
C
O
,
8
0
1
1
2
P
H
O
N
E
:
(
7
2
0
)
5
7
0
-
0
9
8
1
F
A
X
:
9
1
9
2
2
7
5
9
9
9
E
M
A
I
L
:
r
e
g
4
2
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
Page 16 of 26
1 2 3 4 5 6
7 8 9
B
C
D
E
F
CURB 26.5"X26.5".
MAX ROOF OPENING 26" X 26"
CENTERED AS INDICATED.
14"X20" GE AT 20"X26" O.D.
ROOF CURB,
31"x145" OD.
M201
1
MAU-1
R 1 0 ' - 0 "
(EX) INTAKE GRAV. HOOD
KEF-1
14"x20" GE
3' - 0"
3'
-
0
"
(EX) EF-1
3"ø FV
3"ø FV 3"ø FV
3"ø FV
2'
-
4
"
1
1
1
1
2
3
4
5
AA
ROOF ACCESS LADDER.
RE: ARCH.
LADDER OVER PARAPET WALL.
RE: ARCH.
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
1
9
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
ROOF LEVEL
MECHANICAL
PROPOSED PLAN
M104
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
NORTH
SCALE: 1/4" = 1'-0"1 ROOF LEVEL PROPOSED PLAN - MECHANICAL
KEYNOTES
1 FLUE VENT THROUGH ROOF. TERMINATE PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
2 NEW LOCATION OF AHU-2 (EX) FLUE. MATCH MATERIALS AND EXTEND FLUE
IN ATTIC AS NEEDED.
3 KEF-1 OUTLET SHALL BE MIN 40" ABOVE ROOF SURFACE AND 10' FROM ANY
PART OF THE BUILDING IN COMPLIANCE WITH IMC SECTION 506.3.13.3.
4 MAU-1 INLET SHALL HAVE NO EXHAUST DISCHARGE WITHIN 10' PER IMC
SECTION 401.4.
5 MAU-1 SUPPLY DUCT DOWN THROUGH CURB INTO BUILDING.
GENERAL MECHANICAL NOTES
1 REFER TO CAPTIVEAIRE SHEETS FOR ALL SPECIFICATIONS, SEQUENCES AND
DIMENSIONAL DRAWINGS IN RELATION TO KEF-1, MAU-1 AND HD-1.
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
KEF-01
MAU-01
Page 17 of 26
5-TIER(86)
4-TIER(74)
3621
18
T2
T1
GMS
ENTRY
FOYER
COVERED PATIO
PRO SHOP
BAG STORAGE
STORAGE
OFFICE
REPAIR
MECH.
MENS RESTROOM /
LOCKER
WOMENS RESTROOM /
LOCKER
REFRIG. ROOM
KITCHEN
BAR
RESTAURANT
1 2 3 4 5 6 7 8 9
B
C
D
E
F
HD-1
10X8 EA UP TO EF-1 (EX)
(EX) GRILLE, 100 CFM
(EX) GRILLE, 100 CFM
S4
(EX)6"ø
75 CFM
S4
(EX)6"ø
75 CFM
L1 16"x24"
725 CFM
M
M201
1
F-2
F-1
CU-1
CU-2
CU-K1
ERV-1
S1 8"ø
180 CFM
S1 8"ø
180 CFM
S1 8"ø
165 CFM
14"x14" SA
PROPOSED ROOF ACCESS
LADDER SHALL HAVE 30"
CLEAR LANDING.
RE: ARCH
3"ø FV
IWH-1
14" X 20" GE
UP TO KEF-1
10"x10" OA
8"ø OA
24"x8" RA
1
2
3
4
26"x14" SA
A
M401
1
14"x26" SA
L2 16"x24"
725 CFM
3"ø FV
3"ø FV
3"ø FV
3"ø FV
14
"
x
1
4
"
S
A
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
1
9
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
MAIN LEVEL
MECHANICAL
PROPOSED PLAN
M102
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
NORTH
SCALE: 1/4" = 1'-0"1 MAIN LEVEL PROPOSED PLAN - MECHANICAL
KEYNOTES
1 GE WITH UL LISTED 2-HR FIRE RATED WRAP CENTERED BETWEEN EXISTING
TRUSSES. ALL GE SHALL SLOPE TO HOOD CONNECTION AT MIN 1/4" / 12".
PROVIDE CLEANOUTS PER IMC SECTION 506.3.9.
2 REQUIRED SERVICE CLEARANCE OF CONDENSING UNITS.
3 PROVIDE CAP AT EXISTING.
4 SA FROM MAU-1 ON ROOF.
GENERAL MECHANICAL NOTES
1 REFER TO CAPTIVEAIRE SHEETS FOR ALL SPECIFICATIONS, SEQUENCES AND
DIMENSIONAL DRAWINGS IN RELATION TO KEF-1, MAU-1 AND HD-1.
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
F-01
56
7
1
2 3 48
9
10
Page 18 of 26
5-TIER(86)
4-TIER(74)
3621
18
T2
T1
GMS
1
1
2
2
3
3
4
4
B B
C C
D D
ENTRY
FOYER
WOMENS RESTROOM /
LOCKER
KITCHEN
BAR
RESTAURANT
HD-1
12"x28" SA 12"x28" SA 12"x28" SA
14"x26" SA
10X8 EA
UP TO EF-1 (EX)
(EX) GRILLE, 100 CFM
(EX) GRILLE, 100 CFM
8"x6" EA
6"
x
6
"
E
A
S4
(EX)6"ø
75 CFM
S4
(EX)6"ø
75 CFM
L1 16"x24"
725 CFM
M
14
"
x
1
0
"
O
A
F-2
F-1
L2 16"x24"
725 CFM
ERV-1
12
"
ø
E
A
14"ø EA
14"ø FA
12"ø EA
14
"
ø
F
A
14"x24" RA
16"x18" SA
16"x18" SA
S1 8"ø
180 CFM
S1 8"ø
180 CFM
S1 8"ø
180 CFM S1 8"ø
180 CFM S1 8"ø
180 CFM
S1 8"ø
180 CFM
S1 8"ø
165 CFM
S1 8"ø
195 CFM
S2 10"ø
245 CFM
S2 10"ø
295 CFM
S2 10"ø
295 CFM
S2 10"ø
295 CFM
S2 10"ø
295 CFM
16
"
x
1
8
"
S
A
16
"
x
1
8
"
S
A
14
"
x
1
4
"
S
A
1/
4
"
/
1
'
-0"
650 CFM
75 CFM
1
1
8"ø SA
21/4" / 1'-0"3"ø FV
3"ø FV
3"ø FV
3"ø FV
3"ø CA
3"ø CA
3"ø CA
3"ø CA
E1 14"ø
725 CFM
18"x18" RA
14"x24" RA
R1 14"x14"
R1 14"x14"
R1 14"x14"
IWH-1
14
"
x
1
4
"
R
A
R1 14"x14"R1 14"x14"1/4" / 1'-0"14"x20" GE
14"x20" GE
14" X 20" GE
UP TO KEF-1
18
"
x
1
8
"
R
A
14
"
x
1
4
"
R
A
6"ø FA
14"x14" RA
14"x14" RA
14"x14" RA
12"ø EA
14"ø FA
14"ø FA
3
4
5
5
55
6
6
7
7
7
8
9
7
10
14
"
x
2
0
"
G
E
14"x26" SA
CU-2 CU-1
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
2
1
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
ENLARGED PLANS
M401
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
NORTH
SCALE: 1/2" = 1'-0"1 ENLARGED MECHANICAL PLAN
KEYNOTES
1 BALANCE TO VOLUME INDICATED.
2 CONNECT TO EXISTING DUCT SERVING WOMEN'S RESTROOM.
3 GE WITH UL LISTED 2-HR FIRE RATED WRAP CENTERED BETWEEN
EXISTING TRUSSES. ALL GE SHALL SLOPE TO HOOD CONNECTION
AT MIN 1/4" / 12". PROVIDE CLEANOUTS PER IMC SECTION 506.3.9.
4 MOTORIZED DAMPER INTERLOCKED WITH ERV-1.
5 PROVIDE WALL INLET PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
6 BALANCING DAMPER ABOVE ACCESSIBLE CEILING. TYPICAL.
7 3" FV UP THROUGH ROOF.
8 PROVIDE LONG RADIUS ELBOWS WITH NO TURNING VANES ON
GREASE DUCT.
9 PROVIDE WRAPPED INSULATION IN COMPLIANCE WITH IMC SECTION
506.3.6(3). REFER TO DUCT INSULATION SPECIFICATION.
10 GE UP TO KEF-1.
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
F-01
F-02
ERV-01
1
2 3 48
9
10
KEF-01
MAU-01
12
11
2
1
34
56
123
1
1
Page 19 of 26
DUCT CONSTRUCTION SPECIFICATION
SYSTEM SUB-SYSTEM PRESSURIZATION APPLICATION
PRESSURE
CLASS
(IN. W.C.)
SEAL
CLASS MATERIAL
EXHAUST ALL U.N.O NEGATIVE NON-RECIRCULATED AIR FROM INTERIOR TERMINAL
INLET DEVICE TO OUTDOOR TERMINATION DEVICE.-1 C GALVANIZED
EXHAUST ALL U.N.O POSITIVE
NON-RECIRCULATED AIR FROM INTERIOR TERMINAL
INLET DEVICE TO OUTDOOR TERMINATION DEVICE.+1 A GALVANIZED
OUTSIDE AIR
SUPPLY
(FRESH AIR)
ALL U.N.O POSITIVE
CONDITIONED OUTSIDE AIR FROM THE CONDITIONING
EQUIPMENT OUTLET TO THE TERMINAL DEVICE OR
MIXING POINT WITH OTHER SYSTEM.
+1 C GALVANIZED
RAW OUTSIDE AIR
INTAKE ALL U.N.O. NEGATIVE
UNCONDITIONED OUTSIDE AIR FROM THE INLET DEVICE
TO THE CONDITIONING EQUIPMENT INLET.-1 C GALVANIZED
SUPPLY ALL U.N.O POSITIVE
CONDITIONED AIR DOWN STREAM OF CONDITIONING
EQUIPMENT.+1 B GALVANIZED
RETURN ALL U.N.O NEGATIVE
RECIRCULATED AIR FROM TERMINAL INLET DEVICE TO
CONDITIONING EQUIPMENT.-1 C GALVANIZED
TRANSFER ALL U.N.O. POSITIVE INTERIOR AIR TRANSFERRED BETWEEN SPACES. +1/2 C GALVANIZED
GREASE EXHAUST ALL U.N.O. NEGATIVE ALL GREASE EXHAUST DUCTWORK -4 A
STEEL FULLY
WELDED
NOTES FOR ALL DUCTWORK:
1. ALL DUCT SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA.
GALVANIZED SHEET METAL CONSTRUCTION:
1. GAUGES SHALL BE PER SMACNA LOW PRESSURE SYSTEMS.
2. SHEET METAL DUCT SHALL BE CONSTRUCTED OF LOCK FORMING QUALITY GALVANIZED STEEL SHEET, WITH A G90 ZINC COATED FINISH, AND IN COMPLIANCE
WITH ASTM-A653.
STEEL GREASE EXHAUST CONSTRUCTION:
1. GAGES SHALL BE MINIMUM NO.16 (0.0575 INCH) PER IMC SECTION 506.3.1.1.
2. SHEET METAL DUCT SHALL BE CONSTRUCTED OF A CONTINUOUS LIQUID-TIGHT WELD OR BRAZE MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM.
3. ALL JOINTS, FITTINGS, AND FASTENING HARDWARE SHALL BE OF THE SAME GRADE STEEL.
4. INTERNAL WELDING OR BRAZING SHALL NOT BE PROHIBITED PROVIDED THAT THE JOINT IS FORMED OR GROUND SMOOTH AND IS PROVIDED WITH READY
ACCESS FOR INSPECTION.
5. PRIOR TO USE OR CONCEALMENT OF ANY PORTION OF THE GREASE DUCT SYSTEM, A LEAK TEST MUST BE PERFORMED IN ACCORDANCE WITH IMC SECTION
506.3.2.5.
MECHANICAL DUCT INSULATION SPECIFICATION
SYSTEM TYPE DUCT TYPE LOCATION SUB-SYSTEM AIR STREAM DESCRIPTION
INTERNAL
LINER
(IN.)
EXTERNAL
WRAP
(IN.)
REQUIRED
R-VALUE
(INSTALLED)
NOTES
SUPPLY ROUND INTERIOR ALL U.N.O.
CONDITIONED AIR DOWN STREAM OF
CONDITIONING EQUIPMENT IN UN-INSULATED
ATTIC.
NA 2.5 R-6
SUPPLY RECTANGULAR INTERIOR ALL U.N.O.
CONDITIONED AIR DOWN STREAM OF
CONDITIONING EQUIPMENT IN UN-INSULATED
ATTIC.
NA 2.5 R-6
SUPPLY FLEX INTERIOR ALL U.N.O.
CONDITIONED AIR DOWN STREAM OF
CONDITIONING EQUIPMENT IN UN-INSULATED
ATTIC.
PRE-
INSULATED
PRE-
INSULATED R-6
RETURN RECTANGULAR INTERIOR ALL U.N.O.
RECIRCULATED AIR FROM TERMINAL INLET
DEVICE TO CONDITIONING EQUIPMENT IN UN-
INSULATED ATTIC.
NA 2.5 R-6
RETURN ROUND INTERIOR ALL U.N.O.
RECIRCULATED AIR FROM TERMINAL INLET
DEVICE TO CONDITIONING EQUIPMENT IN UN-
INSULATED ATTIC.
NA 2.5 R-6
RAW OUTSIDE
AIR INTAKE RECTANGULAR INTERIOR ALL U.N.O.
UNCONDITIONED OUTSIDE AIR FROM THE INLET
DEVICE TO THE CONDITIONING EQUIPMENT INLET.NA (2) LAYERS
@2.5 R-12
OUTSIDE AIR
SUPPLY
(FRESH AIR)
RECTANGULAR INTERIOR ALL U.N.O.
CONDITIONED OUTSIDE AIR FROM THE
CONDITIONING EQUIPMENT INLET TO THE
TERMINAL DEVICE OR MIXING POINT WITH OTHER
SYSTEM IN UN-INSULATED ATTIC.
NA 2.5 R-6
GREASE
EXHAUST
ROUND,
RECTANGULAR INTERIOR ALL U.N.O.
ALL KITCHEN HOOD EXHAUST FROM HOOD TO
ROOF CURB NA
(2) LAYERS
1.5" FIRE
BARRIER
NA
2-FIRE RATED
BARRIER
WRAP, NOTE
3
EXHAUST ROUND INTERIOR ALL U.N.O.
NON-RECIRCULATED AIR FROM INTERIOR
TERMINAL INLET DEVICE TO OUTDOOR
TERMINATION DEVICE.
NA NA NA
NOTES:
1. INSULATION IS NOT REQUIRED VIA THE FOLLOWING: ALL DUCT IS LOCATED IN A CONDITIONED SPACE. AN INDIRECTLY HEATED SPACE SEPERATED BY UNINSULATED CEILINGS
MAY BE CONSIDERED A CONDITIONED SPACE PER IECC CHAPTER 2 DEFINITION. PER IECC SECTION C403.2.9 INSULATION IS ONLY REQUIRED FOR UNCONDITIONED SPACES.
2. INSULATION IS NOT REQUIED VIA IECC C403.2.9 EXCEPTION 2. THE DESIGN TEMPERATURE DIFFERENCE FOR THIS SYSTEM IS LESS THAN 15 DEGREES.
SPECIFICATION:
ALL INSTALLATION METHODS, INCLUDING APPLICATION, SEALING, JOINTS, ETC. SHALL BE PER THE MANUFACTURER'S RECOMMENDATIONS.
ALL INTERIOR INSULATION SHALL BE PLENUM RATED.
ALL PRODUCTS SHALL BE LABELED FOR NFPA 90A AND 90B COMPLIANCE.
LINER:
1. JM LINEACOUSTIC RC.
WRAP:
1. INTERIOR
A. JM MICROLITE FSK 0.75 LB DENSITY.
B. COMPOSITE FHC 25/50
2. EXTERIOR
A. JM 800 SERIES SPIN GLASS 3 LB DENSITY.
B. FLEXCLAD 250 ALUMINUM JACKET APPLIED OVER INSULATION, SUITABLE FOR EXPOSED EXTERIOR INSTALLATIONS.
C. COMPOSITE FHC 25/50
3. 2-HOUR FIRE RATED BARRIER:
A. 3M FIRE BARRIER DUCT WRAP 615+, 1.5 INCH, 6 PCF DENSITY RATED FOR CONTINUOUS USE AT 1832F.
B. 3M FIRE BARRIER SEALANT.
C. ASTM E2336.
D. 3M FIRE BARRIER DUCT WRAP 615+.
E. ZERO CLEARANCE TO COMBUSTIBLES.
F. FOIL SCRIM BACKING.
OUTDOOR AIR VENTILATION CALCULATION PER IMC
ZONE
EQUIPMENT
TAG
SYSTEM TYPE
(EQUATION
FOR VOT)
SPACE
ZONE FLOOR
AREA
(AZ)
(SQ. FT.)
OCCUPANT
DENSITY
(PEOPLE PER
1,000 SQ. FT.)
ZONE
POPULATION -
PER
ARCHITECTURA
L LAYOUT
OA FLOW RATE
PER PERSON
(RP)
(CFM/PERSON)
OA FLOW RATE
PER UNIT AREA -
TABLE 6-1 (RA)
CFM/SF
ZONE
POPULATION
(PZ)
SYSTEM
POPULATION
(PS)
BREATHING ZONE
OA FLOW
(VBZ)
(CFM)
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
(EZ)
ZONE
OUTDOOR
AIRFLOW
(VOZ)
(CFM)
ZONE
PRIMARY OA
FRACTION
(ZP)
SYSTEM
VENTILATION
EFFICIENCY -
TABLE 6-3 OR
APPENDIX A
(EVZ)
UNCORRECTED
OUTDOOR AIR
INTAKE
(VOU)
(CFM)
SYSTEM
VENTILATION
EFFICIENCY - TABLE
6-3 OR APPENDIX A
(EV = MIN(EVZ))
OA
REQUIRED
(VOT)
(CFM)
OA
PROVIDED
(ZRTU)
(CFM)
COMPLIES
WITH CODE
(ZRTU>VOT)
F-1 / ERV-1 SINGLE ZONE FRONT OF HOUSE 937 NA 63 7.5 0.18 63 63 641 1.0 641 NA NA NA NA 641 650 YES
F-2 / ERV-1 SINGLE ZONE BACK OF HOUSE 373 NA 2 7.5 0.12 2 63 60 1.0 60 NA NA NA NA 60 75 YES
REMARKS:
1. IMC CHAPTER 4 IS BASED ON THE ASHRAE 62.1. OCCUPANT DIVERSITY MAY BE IMPLIED IN SOME ZONES. REFER TO SECTION 403, EQUATION 4-7.
2. SOME HEATED SPACES WILL BE IN COOLING MODE DURING FULL OCCUPANCY; THEREFORE EV VALUES REFLECT ACTUAL OPERATING CONDITION AT TIME OF DESIGN OCCUPANCY.
3. BACK OF HOUSE VENTILATED VIA KITCHEN EXHAUST FAN AND MAKE-UP AIR UNIT.
COMBUSTION AIR AND FLUE SPECIFICATION
SYSTEM DESCRIPTION
MAX.
OPERATING GAS
TEMPERATURE
NOMINAL SIZE MANUFACTURER & MATERIAL FITTINGS TERMINATION AND
ADAPTERS LISTING
FURNACES
F-1, F-2
HIGH EFFICEINCY
FURNACE
COMBUSTION AIR
INTAKE AND VENTING
FOR CATEGORY IV
FURNACES
230F 3"
CENTROTHERM INNOFLUE
SINGLE-WALL RIGID
POLYPROPYLENE
SINGLE-WALL RIGID
POLYPROPYLENE
AS SPECIFIED BY THE
PIPE
MANUFACTURER.
UL 1738 LISTED
VENTING FOR CATEGORY IV GAS-
BURNING APPLIANCES.
WATER
HEATER
IWH-1
HIGH EFFICEINCY
WATER HEATER
COMBUSTION AIR
INTAKE AND VENTING
FOR CATEGORY IV
FURNACES
230F 3"
CENTROTHERM INNOFLUE
SINGLE-WALL RIGID
POLYPROPYLENE
SINGLE-WALL RIGID
POLYPROPYLENE
AS SPECIFIED BY THE
PIPE
MANUFACTURER.
UL 1738 LISTED
VENTING FOR CATEGORY IV GAS-
BURNING APPLIANCES.
NOTE: ALL CA AND FV SYSTEMS SHALL BE INSULATED WITH 1/2" THICK ARMAFLEX-TYPE INSULATION OR APPROVED EQUAL PER MANUFACTURER'S REQUIREMENTS.
APPLIANCE FLUE AND COMBUSTION AIR VENT
CALCULATIONS
F-1 (FV)
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
FLUE VENT DUCT NA NA 37.3
3" DIA 45 SHORT ELBOW 0 5 0
3" DIA 90 SHORT ELBOW 3 10 30
TERMINATION 1 0 0
TOTAL (NOTE 2) 67.3
F1 (CA)
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
COMBUSTION AIR DUCT NA NA 28
3" DIA 45 SHORT ELBOW 2 5 10
3" DIA 90 SHORT ELBOW 1 10 10
BIRD SCREEN 1 0 0
TOTAL (NOTE 2) 48
F-2 (FV)
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
FLUE VENT DUCT NA NA 27
3" DIA 45 SHORT ELBOW 1 5 5
3" DIA 90 SHORT ELBOW 2 10 20
TERMINATION 1 0 0
TOTAL (NOTE 2) 52
F2 (CA)
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
COMBUSTION AIR DUCT NA NA 24
3" DIA 45 ELBOW 2 5 10
3" DIA 90 ELBOW 1 10 10
BIRD SCREEN 1 0 0
TOTAL (NOTE 2) 44
WATER HEATER FLUE VENT
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
3" 45-ELBOW 2 2.5 5
3" 90-ELBOW 1 0 0
3" FLUE VENT DUCT NA NA 32
TOTAL (NOTE 3) 37
WATER HEATER COMBUSTION AIR
FITTING QUANTITY
EQUIVALENT
LENGTH
(FT)
LENGTH
(FT)
3" 45-ELBOW 2 0 0
3" 90-ELBOW 2 0 0
3" COMBUSTION AIR DUCT NA NA 31
TOTAL (NOTE 4) 31
NOTES:
1.CALCULATION PER MANUFACTURER'S IOM AND LAYOUT INDICATED ON THE PLANS.
2. FURNACE (TRANE S9V2C100U4VS...) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE 150' IN 3"
SIZE OR AT ELEVATIONS UP TO 5400'.
3. WATER HEATER (RHEEM RTR-WM220DVLN) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE
38' IN 3" SIZE OR 94' IN 4" SIZE (WITH 0 OR 1 90 DEGREE ELBOWS) PER MANUFACTURER'S
SPECIFICATIONS.
4. WATER HEATER (RHEEM RTR-WM220DVLN) VENT MAXIMUM EQUIVALENT LENGTHS SHALL BE
36.5' IN 3" SIZE WITH (2) 90 DEGREE ELBOWS PER MANUFACURER'S SPECIFICATIONS.
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
1
6
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
SPECIFICATIONS
M002
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 20 of 26
MAIN LEVEL
0' -0"
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
EXIST T.O. PLATE
10' -10"
L1 16"x24"
725 CFM L2 16"x24"
725 CFM
MAU-1 KEF-1
CU-K1
CU-1
CU-2
CA INTAKES
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
2
0
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
ELEVATIONS
M201
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
SCALE: 1/4" = 1'-0"1 MECHANICAL - NORTH ELEVATION
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 21 of 26
EQUIPMENT
4"
M
I
N
EXTEND PAD 4" BEYOND
EQUIPMENT PERIMETER
ON ALL SIDES
4"
4"
ROOF MOUNTED UNIT
REQUIRING CURB
BASE RAIL
UNIT OVERHANGS
CURB
TOP OF CURB
WOOD NAILER STRIP
GALVANIZED METAL CURB.
REFER TO PLANS FOR CURB
HEIGHT.
BATTING TO MATCH ROOF
INSULATION R-VALUE
CURB SUPPORTED DIRECTLY ON
STRUCTURAL DECK, STRUCTURAL
SUPPORT, OR SHIM. DO NOT REST
ON ROOF INSULATION.
COUNTER FLASHING
RIGID INSULATION
FLASHING
CANTILEVER
STRIP
SEALED ROOFING LAYER
ROOFING INSULATION
ROOF DECK
R
4
-
1
/
2
"
LOCKING LUG
26 GAUGE MIN.
FRAME
DUCT
VANED ELBOW TURNING VANE
NOTES:
1. PROVIDE LOCKING LUGS INTEGRAL WITH VANE.
2. VANES SHALL BE 4" WIDE.
3. LIMIT VANE BANK HEIGHT TO 36".
4. FRAMES SHALL BE BOLTED OR RIVETED TO ELBOW.
5. VANES SHALL BE SAME GAUGE AS ELBOW.
NO TRAILING EDGE3-1/2"AIRFLOW
DIRECTION
SPIN-IN
FITTING WITH MANUAL
VOLUME DAMPER
ROUND RIGID DUCT
2" 24 GA.
STRAP
SUPPORT TO STRUCTURE
WITH WIRE HANGER
FLEXIBLE DUCT
CEILING
DIFFUSER
LAY -IN CEILING
LOW PRESSURE
SUPPLY
SCREW DRIVER
OPERATED BAND
FLEXIBLE CONNECTION
SUPPLY AIR DUCT
CONDENSATE PIPE FROM
EVAPORATOR COIL AND HEAT
EXCHANGER
CONDENSATE NEUTRALIZER.
TERMINATE ABOVE FLOOR SINK
VIA AIR GAP (6" MIN.)
VIBRATION ISOLATION
MOUNTING PADS
FLEXIBLE CONNECTION
RETURN AIR DUCT
GAS SUPPLY PIPE WITH SEDIMENT TRAP
COMBUSTION AIR
INTAKE AND VENT PIPE
EVAPORATOR COIL
3-VANDAL PROOF SET SCREWS
WATER PROOF PERMASEAL
STEEL REINFORCING BOOT
STRUCTURAL MEMBER
SECURE TO STRUCTURE
ANGLE IRON
1/2" U-BOLT
ROOFING
LEAD FLASHING
COUNTERFLASHING CAP
CAULK WITH ROOF MASTIC
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
2
2
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
DETAILS
M501
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
NO SCALE1CONCRETE EQUIPMENT PAD
NO SCALE2ROOF CURB
NO SCALE3DUCT ELBOW TURNING VANE - SINGLE THICKNESS
NO SCALE5LAY-IN MOUNTED CEILING DIFFUSER CONNECTION DETAIL
NO SCALE6UPFLOW GAS FURNACE
NO SCALE4PIPE THROUGH ROOF DETAIL
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 22 of 26
MAU-1
KEF-1
HD-1
CU-K1
CU-1
CU-2
1
4
"
x
2
0
"
G
E
26
"
x
1
4
"
S
A
3 "ø C A
3 "ø C A 3 "ø C A
3 "ø C A
3"ø FV
3"ø FV
3"ø FV
3"ø FV
ERV-1
F-1
F-2L116"x24"
725 CFM
L2 16"x24"
725 CFM
IWH-1
MAU-1
KEF-1
L2 16"x24"
725 CFM
14"x20" GE
26
"
x
1
4
"
S
A
14"x26" SA
ERV-1
Title:
Dwg No.
Job No.
Drawn by:
Print Date:
PE:QC:
Pr
o
j
e
c
t
M
i
l
e
s
t
o
n
e
:
11
8
W
e
s
t
S
i
x
t
h
S
t
r
e
e
t
,
S
u
i
t
e
2
0
0
Gl
e
n
w
o
o
d
S
p
r
i
n
g
s
,
C
O
8
1
6
0
1
97
0
.
9
4
5
.
1
0
0
4
ww
w
.
s
g
m
-
i
n
c
.
c
o
m
File:
Ce
n
t
r
a
l
M
o
d
e
l
:
C:
\
U
s
e
r
s
\
p
g
o
r
r
a
\
D
o
c
u
m
e
n
t
s
\
R
B
G
_
M
E
P
_
R
2
3
_
p
a
b
l
o
g
R
Y
F
V
F
.
r
vt
1
0
/
2
3
/
2
0
2
3
1
1
:
2
6
:
2
4
A
M
BA
T
T
L
E
M
E
N
T
M
E
S
A
GO
L
F
C
O
U
R
S
E
PE
R
M
I
T
S
E
T
2023-316
PG
10/23/23
THIB
AXONOMETRICS
M901
RE
S
T
A
U
R
A
N
T
/
K
I
T
C
H
E
N
AD
D
I
T
I
O
N
RBG_MEP_R23
I:
\
2
0
2
3
\
2
0
2
3
-
3
1
6
-
T
h
e
R
o
u
g
h
B
a
r
G
r
i
l
l
e
\
0
0
1
-
M
E
P
\
H
-
D
w
g
s
\
M
ep
\
R
e
v
i
t
\
R
B
G
_
M
E
P
_
R
2
3
.
r
v
t
NO SCALE1MECHANICAL AXONOMETRIC - NORTHWEST
NO SCALE2MECHANICAL AXONOMETRIC - SOUTHEAST
#
R
e
v
i
s
i
o
n
:
D
a
t
e
:
B
y
:
10/23/2023
Page 23 of 26
Denver Office
REGION 42
PHONE: (720) 570 - 0981
EMAIL: reg42@captiveaire.com
FOR QUESTIONS, CALL THE
HOOD INFORMATION - JOB#6145305
1
6624
ND-2-PSP-F
CAPTIVEAIRE 12' 6"
600
DEG
I HEAVY 250 3125 4"18"3125 1768 -1.032"2500
430 SS
WHERE EXPOSED
ALONE ALONE
HOOD
NO
TAG MODEL MANUFACTURER LENGTH
MAX
COOKING
TEMP
TYPE
APPLIANCE
DUTY
DESIGN
CFM/FT
TOTAL
EXH CFM
EXHAUST PLENUM
RISER(S)
WIDTH LENG HEIGHT DIA CFM VEL SP
TOTAL
SUPPLY
CFM
HOOD
CONSTRUCTION
HOOD CONFIG
END TO
END
ROW
HOOD INFORMATION
1 CAPTRATE SOLO FILTER 9 20"16"
85% SEE FILTER
SPEC
5 RECESSED ROUND NO LEFT 12"x66"x24"TANK FS 4.0/4.0 DCV-1111
1 LIGHT
1 FAN
YES
1290
LBS
HOOD
NO
TAG
FILTER(S)
TYPE QTY HEIGHT LENGTH
EFFICIENCY @ 7
MICRONS
LIGHT(S)
QTY TYPE
WIRE
GUARD
UTILITY CABINET(S)
LOCATION SIZE
FIRE SYSTEM
TYPE SIZE
ELECTRICAL
MODEL #
SWITCHES
QUANTITY
FIRE
SYSTEM
PIPING
HOOD
HANGING
WEIGHT
HOOD OPTIONS
1
FIELD WRAPPER 18.00" HIGH FRONT, LEFT.
BACKSPLASH 122.00" HIGH X 181.00" LONG 430 SS VERTICAL.
RIGHT SIDESPLASH 122.00" HIGH X 84.00" LONG 430 SS VERTICAL.
RIGHT END STANDOFF (FINISHED) 1" WIDE 66" LONG INSULATED.
INSULATION FOR TOP OF HOOD.
INSULATION FOR BACK OF HOOD.
LEFT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
SS.
RIGHT WALL AS END PANEL.
HOOD
NO
TAG OPTION
PERFORATED SUPPLY PLENUM(S)
1 Front 163"16"6"
MUA
MUA
MUA
12"
12"
12"
28"
28"
28"
833
833
833
0.222"
0.222"
0.222"
HOOD
NO
TAG POS LENGTH WIDTH HEIGHT TYPE
RISER(S)
WIDTH LENG DIA CFM SP
FIRE SYSTEM INFORMATION - JOB#6145305
1 TANK FS 4.0/4.0 40 37 FIRE CABINET LEFT LEFT, HOOD 1
FIRE
SYSTEM
NO
TAG TYPE SIZE MAX FP
DESIGN
FP
INSTALLATION
SYSTEM LOCATION ON HOOD
GAS VALVE(S)
1 SC ELECTRICAL 2.000 CAPTIVEAIRE SYSTEMS
FIRE
SYSTEM
NO
TAG TYPE SIZE SUPPLIED BY
System Design Verification (SDV)
If ordered, CAS Service will perform a System Design Verification (SDV) once all equipment
has had a complete start up per the Operation and Installation Manual. Typically, the SDV will
be performed after all inspections are complete.
Any field related discrepancies that are discovered during the SDV will be brought to the
attention of the general contractor and corresponding trades on site. These issues
will be documented and forwarded to the appropriate sales office. If CAS Service has to
resolve a discrepancy that is a field issue, the general contractor will be notified and
billed for the work. Should a return trip be required due to any field related discrepancy
that cannot be resolved during the SDV, there will be additional trip charges.
During the SDV, CAS Service will address any discrepancy that is the fault of the
manufacturer. Should a return trip be required, the general contractor and appropriate
sales office will be notified. There will be no additional charges for manufacturer
discrepancies.
*** NOTE ***
ALL WALLS AND STRUCTURES
THAT COME WITHIN 18" OF
HOOD MUST BE METAL STUDS
AND SHEETROCK. WOOD STUDS
OR ANY OTHER COMBUSTIBLE
MATERIAL WITHIN 18" OF HOOD
NOT ALLOWED
*** NOTE ***
HOOD MANUFACTURER
RECOMMENDS NO RETURNS
OR 4-WAY DIFFUSERS
WITHIN 10 FEET OF HOOD
IN ALL DIRECTIONS.
*** NOTE ***
MAKE-UP AIR SHALL BE
DELIVERED INTO SPACE
IN MANNER THAT WILL NOT
DISRUPT HOODS ABILITY
TO CAPTURE AND CONTAIN.
HOOD CORNER
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR HOOD)
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING
ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4" OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE
ALL HEX NUTS TO 57 FT-LBS.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
HOOD CORNER
HANGING ANGLE
(HARDWARE BY INSTALLER)
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
FULL LENGTH
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR HOOD)
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION ABOVE CEILING
ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS
ACCEPTABLE FOR FULL LENGTH HANGING ANGLES.
MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM
HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS.
FULL LENGTH
HANGING ANGLE
(HARDWARE BY INSTALLER)
SUPPLY PLENUM
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR SUPPLY
PLENUM)
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION ABOVE CEILING
ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS
ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4" OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE
ALL HEX NUTS TO 57 FT-LBS.
SUPPLY PLENUM
HANGING ANGLE
(HARDWARE BY INSTALLER)
Hoods are ETL Listed And Complies with UL710, ULC710, and ULC-S646
Standards. Fire Systems ETL Listed and Complies With Ul300 and
Meets requirements of NFPA 96 and NFPA 17A
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
DESCRIPTION
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
DATE:
AC
C
O
R
D
A
N
C
E
No
.
9
6
BU
I
L
T
NF
P
A
WI
T
H
IN
S
LI
D
TE
R
C
U
S
6145305
MASTER DRAWING
tom.oates
1
10/11/2023
Th
e
R
o
u
g
h
B
a
r
3/4" = 1'-0"
PA
R
A
C
H
U
T
E
,
C
O
,
8
1
6
3
5
De
n
v
e
r
O
f
f
i
c
e
73
0
0
S
A
l
t
o
n
W
a
y
B
u
i
l
d
i
n
g
5
,
S
u
i
t
e
B
,
C
e
n
t
e
n
n
i
a
l
,
C
O
,
8
0
1
1
2
P
H
O
N
E
:
(
7
2
0
)
5
7
0
-
0
9
8
1
F
A
X
:
9
1
9
2
2
7
5
9
9
9
E
M
A
I
L
:
r
e
g
4
2
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
Page 24 of 26
12' 6"NOM./12' 6.00"OD.
13'-7.00" OVERALL LENGTH
66"
12"
UTILITY
CABINET.
SC
-
2
4
X
1
8
X
8
.
6
2
B
O
X
16"
44"
8"
12"
28"
37 1/2"
8"
12"
28"
54 1/4"
8"
12"
28"
1" LAYER OF INSULATION
FACTORY INSTALLED IN
1.00" END STANDOFF MEETS
0" REQUIREMENTS CLEARANCE
TO COMBUSTIBLE SURFACES.
1"
1" LAYER OF INSULATION FACTORY
INSTALLED IN INTERNAL BACK STANDOFF.
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO COMBUSTIBLE SURFACES.
3"
§
75"75"
12"
∅18"
U.L. LISTED RECESSED ROUND LED
FIXTURE AND LED LIGHT.
INSTALLER MUST CONFIRM HOOD IS INSTALLED SUCH
THAT THE SPECIFIED WALL, ACTING AS AN END PANEL,
IS MATED TIGHT TO THE CORRECT END OF HOOD TO
ACHIEVE A REDUCED MINIMUM EXHAUST CFM LISTING.
NON-COMPLIANCE WILL NULLIFY THE ETL LISTING,
VOID THE MANUFACTURER'S WARRANTY, AND HOLD THE
CONTRACTOR LIABLE FOR ANY AND ALL LOSSES, COSTS,
AND EXPENSES RELATED TO THE NON-CONFORMANCE OF
THE MANUFACTURER'S SPECIFIED INSTRUCTION. THE
WALL ACTING AS AN END PANEL MUST EXTEND NO LESS
THAN 20" FROM THE INTERSECTING WALL ON WHICH HOOD
IS MOUNTED AND MUST EXTEND NO LESS THAN 20" UNDER
BOTTOM OF HOOD TO BE ELIGIBLE FOR REDUCED
MINIMUM EXHAUST CFM LISTING.
PLAN VIEW - HOOD #1
12' 6.00" LONG 6624ND-2-PSP-F
NOTE: ADDITIONAL HANGING ANGLES PROVIDED FOR HOODS 12' AND LONGER.
1" LAYER OF INSULATION FACTORY
INSTALLED IN 3" INTERNAL STANDOFF.
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO COMBUSTIBLE SURFACES.
GREASE DRAIN
WITH REMOVABLE CUP.
SEE HOOD TABLE.
§
EXHAUST RISER.
HANGING ANGLE.
RECESSED ROUND LED FIXTURE AND LED LIGHT,
3500 K WARM OUTPUT.
23.5% OPEN STAINLESS
STEEL PERFORATED PANEL.
ATTACHING PLATES.
SUPPLY RISER WITH
VOLUME DAMPER.
6"
2 3/4"
16"
18"
BACKSPLASH 122.00" HIGH
X 181.00" LONG.
FIELD WRAPPER 18.00" HIGH
(SEE HOOD OPTIONS TABLE).
1" LAYER OF INSULATION FACTORY INSTALLED
ON TOP OF HOOD. MEETS 0 INCH
REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE
SURFACES.
RIGHT WALL AS END PANEL.
20"
4"
4 1/2"
21"
27"
80"
LEFT VERTICAL END PANEL
WITH ADJUSTABLE LEGS.
GAS CHASE CUTOUT
(FOR GAS AND POWER LINES).
EQUIPMENT
BY OTHERS.
48.0" MAX.
80"
24" NOM.
66"
SECTION VIEW - MODEL 6624ND-2-PSP-F
HOOD - #1
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED-COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
20" CAPTRATE SOLO
FILTER WITH HOOK.
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
DESCRIPTION
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
DATE:
AC
C
O
R
D
A
N
C
E
No
.
9
6
BU
I
L
T
NF
P
A
WI
T
H
IN
S
LI
D
TE
R
C
U
S
6145305
MASTER DRAWING
tom.oates
2
10/11/2023
Th
e
R
o
u
g
h
B
a
r
3/4" = 1'-0"
PA
R
A
C
H
U
T
E
,
C
O
,
8
1
6
3
5
De
n
v
e
r
O
f
f
i
c
e
73
0
0
S
A
l
t
o
n
W
a
y
B
u
i
l
d
i
n
g
5
,
S
u
i
t
e
B
,
C
e
n
t
e
n
n
i
a
l
,
C
O
,
8
0
1
1
2
P
H
O
N
E
:
(
7
2
0
)
5
7
0
-
0
9
8
1
F
A
X
:
9
1
9
2
2
7
5
9
9
9
E
M
A
I
L
:
r
e
g
4
2
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
Page 25 of 26
6"
24"
SERVICE.
24"
SERVICE.
24"
SERVICE.
24"
SERVICE.
18"18"
CONDENSER CLEARANCES
48" CLEARANCE REQUIRED ABOVE CONDENSERS.
(NOTE: **CONDENSERS SHOWN HERE ARE NOT DRAWN AT SCALE).
6"
12"
12"
12"
12"
18"
145"
1 9/16"18"
4 5/16"
22 3/8"
AIRFLOW.
LIFTING LUG.
3 3/4"
AIRFLOW.
COOLING
COIL
MODULE.
1" MPT CONNECTION FOR
SS PITCHED DRAIN PAN.
COIL
ACCESS
DOOR.
FLEX
CONDUIT
FOR FIELD
WIRING.
AIRFLOW.
BLOWER/MOTOR
ACCESS DOOR
24" SERVICE
CLEARANCE REQ.
SERVICE DISCONNECT
SWITCH.
AIRFLOW.
1" NPT.
7 13/16"
39 9/16"
DIRECT FIRED MODULE.
AIRFLOW.
49 3/8"
16 1/4"
20"
31"
20" EQUIPMENT CURB.
CURB OUTER WALL.
DISCHARGE OPENING.
24 1/4"
36 3/4"
42 1/8"
47 3/4"
40 1/8"42 1/8"
202 1/4"
MIN. 20"
MINIMUM
STRAIGHT
DUCT
PER AMCA*
FAN #2 A2-D.250-20D-MPU - HEATER
1. DIRECT GAS FIRED HEATED MAKE UP AIR UNIT WITH 20" MIXED FLOW DIRECT DRIVE FAN.
2. INTAKE HOOD WITH EZ FILTERS.
3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT.
4. GAS PRESSURE GAUGE, 0-35", 2.5" DIAMETER, 1/4" THREAD SIZE.
5. GAS PRESSURE GAUGE, -5 TO +15 INCHES WC., 2.5" DIAMETER, 1/4" THREAD SIZE.
6. BUTTERFLY MOD VALVE OPTION FOR MOD SIZE 2 (1" MOD VALVE).
7. SHIP LOOSE GAS STRAINER. TO BE INSTALLED UPSTREAM OF UNIT CONNECTION. 1" CONNECTION.
8. CASLINK BUILDING MONITORING SYSTEM COMMUNICATIONS MODULE. REQUIRES INTERNET & FIELD WIRED ETHERNET CONNECTION
OR 3G CELLULAR SERVICE. INCLUDES REV 3 COMM MODULE, RJ45 TO MODBUS CONVERTER, 3 FT CAT5 CABLE, AND 1 FT OF
SHIELDED TWISTED PAIR.
9. MOTORIZED BACK DRAFT DAMPER 22.75" X 24" FOR SIZE 2 STANDARD & MODULAR HEATER UNITS W/EXTENDED SHAFT, STANDARD
GALVANIZED CONSTRUCTION, 3/4" REAR FLANGE, LOW LEAKAGE, LF120S ACTUATOR INCLUDED.
10. 5 TON, SINGLE CIRCUIT MODULAR PACKAGED AC COOLING OPTION FOR SIZE 2 DF/EH MODULAR PACKAGED UNIT. INCLUDES
CONDENSER, DX COIL, FILTER/DRYER KIT, THERMAL EXPANSION VALVE. (1,000 TO 2,750 CFM) WHEN ORDERED WITH OPPOSITE
AIRFLOW CONDENSERS ACCESS AND COIL PIPING WILL REMAIN IN STANDARD POSITION. DRAIN AND SLEDS WILL MOVE TO THE
OPPOSITE SIDE. ANY OTHER CHANGE WILL REQUIRE CLI. CONDENSERS REQUIRE SEPARATE 208V, 3 PHASE POWER SUPPLY UNLESS
ORDERED WITH SINGLE POINT CONNECTION. COIL = 3EY1102.
11. SHIP CONDENSER LOOSE. THE REFRIGERATION LINES WILL NEED TO BE STUBBED OUT 12 INCHES. THE SUCTION LINE NEEDS
TO BE INSULATED INSIDE THE COIL MODULE. ROTARY DISCONNECT SHOULD NOT BE INSTALLED ON THE POST, BLANK POST SHOULD
BE USED IN PLACE. ALL PIPING AND WIRING BETWEEN INDOOR AND OUTDOOR UNITS BY OTHERS.
12. DOWNTURN PLENUM FOR SIZE 2 COOLING COIL MODULE - REQUIRED FOR DOWN DISCHARGE COOLING COIL APPLICATIONS.
13. SEPARATE 120VAC WIRING PACKAGE FOR MAKE-UP AIR UNITS. OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE
PANEL OR WITH DCV PACKAGE. PROVIDES SEPARATE 120VAC INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY
ELECTRICIAN FROM DCV TO MUA SWITCH.
14. PROFILE PLATE CONFIGURATION FOR SIZE 2 DIRECT FIRED UNIT FOR LOW CFM APPLICATIONS.
15. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER/MPU SECTION).
16. 2 YEAR PARTS WARRANTY.
*NOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED
DOWNSTREAM OF UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST
BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD
NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL
DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE
TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT.
SUGGESTED STRAIGHT DUCT SIZE IS 20" x 20".
**NOTE: CONDENSERS SHIPPED LOOSE FOR REMOTE MOUNTING. ALL WIRING AND PIPING BETWEEN INDOOR AND OUTDOOR UNIT TO BE
COMPLETED BY OTHERS.
SUPPLY SIDE HEATER INFORMATION:
WINTER TEMPERATURE = 8°F. TEMP. RISE = 67°F.
BTUs CALCULATED OFF ACTUAL AIR DENSITY.
OUTPUT BTUs AT ALTITUDE OF 0.0 FT. = 178947.
INPUT BTUs AT ALTITUDE OF 0.0 FT. = 194508.
OUTPUT BTUs AT ALTITUDE OF 5594 FT. = 145613.
INPUT BTUs AT ALTITUDE OF 5594 FT. = 158275.
L ETS
DI
R
6"
6"
3" FLANGE.
20 GAUGE
CONSTRUCTION.
STEEL
20"
31"
145"
OPTIONS:
- FULL BOTTOM CORNERS.
CURB.
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
DESCRIPTION
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
DATE:
AC
C
O
R
D
A
N
C
E
No
.
9
6
BU
I
L
T
NF
P
A
WI
T
H
IN
S
LI
D
TE
R
C
U
S
6145305
MASTER DRAWING
tom.oates
4
10/11/2023
Th
e
R
o
u
g
h
B
a
r
1/2" = 1'-0"
PA
R
A
C
H
U
T
E
,
C
O
,
8
1
6
3
5
De
n
v
e
r
O
f
f
i
c
e
73
0
0
S
A
l
t
o
n
W
a
y
B
u
i
l
d
i
n
g
5
,
S
u
i
t
e
B
,
C
e
n
t
e
n
n
i
a
l
,
C
O
,
8
0
1
1
2
P
H
O
N
E
:
(
7
2
0
)
5
7
0
-
0
9
8
1
F
A
X
:
9
1
9
2
2
7
5
9
9
9
E
M
A
I
L
:
r
e
g
4
2
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
Page 26 of 26
For Asset:
Calibrated Int. MTh's
12-Mar-2024 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
5756 5/2026
Serial Number Description Re-CalManufacturerModel
NEBB Procedure
Shimpo MT-200
1) As-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
As-Received Physical Condition(s)
Calibration Event:
C-Procedure Environmental
73.4°F ±9°F, 40 to 65%RH
Jedi Balancing
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
568 Briggs St. PO Box 525 Erie, CO 80516
This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
221576.5299Certificate Number:
Customer Purchase Order:
B175B5016P
Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
Calibration Type:CAL-2 NEBB
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
Projected Re-
Cal.
CALIBRATION LOCATION:Laerie Inc. Laboratory
NDH
Laboratory Altitude: 5,063.25 Ft.
Description
Procedure Executed by:
Primary References Traceability Number Used in Calibration
REF Description
Strobe
Certificate of Accredited and Traceable Calibration
B175B5016P Pocket Tachometer, contact non contact 12-Mar-2025
56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990 www.laerie.com TCC 2023-8A
Comments:
Veridical Review By:
L. E. Armfield CEO/President
REF Projected Re-
Cal.LA
E
R
I
E
Ca
l
i
b
r
a
t
i
o
n
&
M
e
t
r
o
l
o
g
y
S
e
r
v
i
c
e
s
Ca
l
i
b
r
a
t
i
o
n
E
v
e
n
t
:
FO
U
ND-
L
E
F
T
Ma
n
u
f
a
c
t
u
r
e
r
:
Mo
d
e
l
:
De
s
c
r
i
p
t
i
o
n
:
S/
N:
B1
7
5
B
5
0
1
6
P
ID
:
B1
7
5
B
5
0
1
6
P
Ca
l
T
y
p
e
Ca
l
-
2
N
E
B
B
CA
L
-
D
A
T
E
:
3/
1
2
/
2
0
2
4
CA
L
-
D
U
E
:
3/
1
2
/
2
0
2
5
En
v
i
r
o
m
e
n
t
a
l
:
Te
c
h
n
i
c
i
a
n
:
ND
H
St
o
b
e
1,
0
0
0
.
0
1,
0
0
0
.
0
99
5
.
0
10
0
5
.
0
PA
S
S
2,
2
5
0
.
0
2,
2
4
9
.
9
2,
2
4
5
.
0
22
5
5
.
0
PA
S
S
3,
5
0
0
.
0
3,
4
9
9
.
9
3,
4
9
5
.
0
35
0
5
.
0
PA
S
S
4,
0
0
0
.
0
3,
9
9
9
.
9
3,
9
9
5
.
0
40
0
5
.
0
PA
S
S
5,
0
0
0
.
0
5,
0
0
0
.
0
4,
9
9
5
.
0
50
0
5
.
0
PA
S
S
RE
F
5
7
5
6
S
t
o
b
e
Cu
s
t
o
m
e
r
:
Sh
i
m
p
o
MT
-
2
0
0
La
s
e
r
T
a
c
h
o
m
e
t
e
r
68
°
F
±
(
2
°
F
)
/
(
1
0
-
4
5
)
%
R
H
Li
g
h
t
n
i
n
g
Sy
s
t
e
m
s
Ca
l
i
b
r
a
t
i
o
n
&
M
e
t
r
o
l
o
g
y
S
e
r
v
i
c
e
s
56
G
a
t
e
w
a
y
C
i
r
c
l
e
Th
i
s
r
e
p
o
r
t
s
h
a
l
l
n
o
t
b
e
m
o
d
i
f
i
e
d
o
r
r
e
p
r
o
d
u
c
e
d
e
x
c
e
p
t
i
n
f
u
l
l
a
n
d
w
i
t
h
t
h
e
w
r
i
t
t
e
n
a
p
p
r
o
v
a
l
o
f
L
a
e
r
i
e
I
n
c
.
ww
w
.
l
a
e
r
i
e
.
c
o
m
TF
:
1
-
8
7
7
-
5
3
2
-
7
9
9
0
Of
f
i
c
e
:
9
7
0
-
5
3
2
-
7
9
9
0
Be
r
t
h
o
u
d
,
C
o
l
o
r
a
d
o
8
0
5
1
3
Ca
l
i
b
r
a
t
i
o
n
D
e
s
c
r
i
p
t
i
o
n
ST
D
I
n
d
.
R
P
M
UU
T
I
n
d
.
R
P
M
Ma
x
Co
m
p
i
l
a
t
i
o
n
Mi
n
La
b
o
r
a
t
o
r
y
A
l
t
i
t
u
d
e
:
5
,
0
4
4
f
t
Ve
r
i
d
i
c
a
l
R
e
v
i
e
w
C
o
n
t
a
c
t
:
v
r
@
l
a
e
r
i
e
.
c
o
m
Pa
g
e
1
o
f
1
For Asset:
Calibrated Int. MTh's
14-Jul-2023 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
5467 5/2024
www.laerie.com
Certificate of Accredited and Traceable Calibration
1700353 Insertion Temperature Probe 14-Jul-2024
56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990 TCC 2021-18C
Comments:
Veridical Review By:
L. E. Armfield CEO/President
REF Projected Re-
Cal.
Procedure Executed by:
Primary References Traceability Number Used in Calibration
REF Description
Dry Dual Block Calibrator
Projected Re-
Cal.
CALIBRATION LOCATION:Laerie Inc. Laboratory
JRN
Laboratory Altitude: 5,063.25 Ft.
Description
Jedi Balancing
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
568 Briggs St. PO Box 525 Erie, CO 80516
This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
187606.4885Certificate Number:
Customer Purchase Order:
1700353
Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
Calibration Type:CAL-2 NEBB
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
Serial Number Description Re-CalManufacturerModel
MPS/LAP
Evergreen Telemetry PR-T-1
1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
As-Received Physical Condition(s)
Calibration Event:
C-Procedure Environmental
73.4°F ±9°F, 40 to 65%RH
NEBB 2023 LAERIE
Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)%
UUT Manufacturer:
Model:Description:
S/N:ID:
CAL-DATE:CAL-DUE:
REF
NOMINAL REF Min UUC Ind Max Compilation
40.0 °F 39.83404 °F 37.6 °F 39.8 °F 42.0 °F Calibrated
100.0 °F 99.98052 °F 97.5 °F 100.0 °F 102.5 °F Calibrated
160.0 °F 160.00263 °F 157.2 °F 159.7 °F 162.8 °F Calibrated
TF: 1-877-532-7990 Fax: 970-532-7992
www.laerie.com
This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc.
LAERIE
Calibration & Metrology Services
56 Gateway Circle
Berthoud, Colorado 80513
Office: 970-532-7990
FOUND-LEFT
Temperature
±.5% R ± 2 °F
Range 0-200 °F
Evergreen Telemetry Calibration Event:FOUND-LEFT Calibration Performance Report for:
Temperature Probe
JEDI Balancing17003531700353Eng. / Metrologist:
7/14/2023 7/14/2024 JRN
Calibration Performed:
Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1
For Asset:
Calibrated Int. MTh's
14-Jul-2023 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
5467 5/2024
www.laerie.com
TCC 2021-18C
Certificate of Accredited and Traceable Calibration
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
568 Briggs St. PO Box 525 Erie, CO 80516
Jedi Balancing
Calibration Type:
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
180173.4803Certificate Number:
Customer Purchase Order:
1700204
CAL-2 NEBB
CALIBRATION LOCATION:Laerie Inc. Laboratory
Projected Re-
Cal.REF Projected Re-
Cal.
Procedure Executed by:56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990
This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
Dry Dual Block Calibrator
Primary References Traceability Number Used in Calibration
73.4°F ±9°F, 40 to 65%RH
Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
Comments:
JRN
DescriptionREF
Laboratory Altitude: 5,063.25 Ft.Veridical Review By:
L. E. Armfield CEO/President
MPS/LAP
Description
Calibration Event:
Evergreen Telemetry PR-T-4-6"1700204 Water Insertion Probe
Environmental As-Received Physical Condition(s)
14-Jul-2024
C-Procedure
Manufacturer Model Serial Number Description Re-Cal
NEBB 2023 LAERIE
Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)%
UUT Manufacturer:
Model:Description:
S/N:ID:
CAL-DATE:CAL-DUE:
REF
NOMINAL REF Min UUC Ind Max Compilation
40.0 °F 40.01068 °F 40.1 °F 40.2 °F 42.2 °F Calibrated
100.0 °F 99.98815 °F 97.5 °F 100.0 °F 102.5 °F Calibrated
160.0 °F 160.07153 °F 157.3 °F 160.0 °F 162.9 °F Calibrated
Temperature
±.5% R ± 2 °F
Range 0-200 °F
Evergreen Telemetry Calibration Event:FOUND-LEFT Calibration Performance Report for:
Temperature Probe Jedi Balancing17002041700204Eng. / Metrologist:
7/14/2023 7/14/2024 JRN
Calibration Performed:
TF: 1-877-532-7990 Fax: 970-532-7992
www.laerie.com
This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc.
LAERIE
Calibration & Metrology Services
56 Gateway Circle
Berthoud, Colorado 80513
Office: 970-532-7990
Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1
For Asset:
Calibrated Int. MTh's
14-Jul-2023 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
4272 4/2024
4273 4/2024
A727 8/2023
www.laerie.com
TCC 2021-18C
Certificate of Accredited and Traceable Calibration
Veridical Review By:
Procedure Executed by:
MPS/LAP
Laboratory Altitude: 5,063.25 Ft.
73.4°F ±9°F, 40 to 65%RH
Description
Humidity/Thermometer
L. E. Armfield CEO/President
JRN
Environmental
Calibration Event:
Calibration Salt
Temperature Kit Sensor
As-Received Physical Condition(s)
1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
Primary References Traceability Number Used in Calibration Comments:
56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990
Projected Re-
Cal.
Projected Re-
Cal.
Customer Purchase Order:
1700295 This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
S-H-3-5"1700295 Humidity Sensor
Calibration Type:568 Briggs St. PO Box 525 Erie, CO 80516
14-Jul-2024
Re-Cal
Jedi Balancing
CALIBRATION LOCATION:Laerie Inc. Laboratory
CAL-2 NEBB
REF Description REF
Manufacturer Model Serial Number Description
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
Certificate Number:111978.9285
C-Procedure
Evergreen Telemetry
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
NEBB 2022 LAERIE
Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)%
UUT Manufacturer:
Model:Description:
S/N:ID:
CAL-DATE:CAL-DUE:
REF RH Min RH UUC Ind RH Max Compilation
33.07 % RH 30.1 % RH 36.0 % RH 36.1 % RH Calibrated
42.34 % RH 39.3 % RH 44.1 % RH 45.3 % RH Calibrated
75.47 % RH 72.5 % RH 73.1 % RH 78.5 % RH Calibrated
HUMIDITY
Extech Calibration Event:FOUND-LEFT Calibration Performance Report For:
RH390 Psychrometer
JEDI Balancing17002951700295Eng. / Metrologist:
14-Jul-2023 14-Jul-2024 JRN
Calibration Performed:
TF: 1-877-532-7990 Fax: 970-532-7992
www.laerie.com
This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc.
LAERIE
Calibration & Metrology Services
56 Gateway Circle
Berthoud, Colorado 80513
Office: 970-532-7990
Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1
For Asset:
Calibrated Int. MTh's
24-Apr-2024 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
TOC22 4/2025
9707 5/2024
Serial Number Description Re-CalManufacturerModel
LAP: NEBB 2024
Fluke 323
1) As-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
As-Received Physical Condition(s)
Calibration Event:
C-Procedure Environmental
73.4°F ±9°F, 40 to 65%RH
Jedi Balancing
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
568 Briggs St. PO Box 525 Erie, CO 80516
This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
96164.1511Certificate Number:
Customer Purchase Order:
49251381WS
Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
Calibration Type:CAL-2 NEBB
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
Projected Re-
Cal.
CALIBRATION LOCATION:Laerie Inc. Laboratory
JRN
Laboratory Altitude: 5,063.25 Ft.
Description
Procedure Executed by:
Primary References Traceability Number Used in Calibration
REF Description
Calibrator
50 Turn Coil
Certificate of Accredited and Traceable Calibration
49251381WS True RMS Clamp Meter 24-Apr-2025
56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990 www.laerie.com TCC 2023-8A
Comments:
Veridical Review By:
L. E. Armfield CEO/President
REF Projected Re-
Cal.
NEBB 2024 LAERIE
Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)%
UUC Manufacturer:
Model:Description:
S/N:ID:
CAL-DATE:CAL-DUE:
Range REF Min UUC Ind Max Compilation
20.0 %120 VAC 117.1 VAC 119.9 VAC 122.9 VAC Calibrated
50.0 %300 VAC 293.5 VAC 299.7 VAC 306.5 VAC Calibrated
80.0 %480 VAC 469.9 VAC 479.5 VAC 490.1 VAC Calibrated
Range REF
AAC
Min
AAC
UUC Ind
AAC
Max
AAC Compilation
Calibrator
Setting for 50
Turn Coil
20.0 %20.000 AAC 19.1 AAC 20.2 AAC 20.9 AAC Calibrated 0.4000 AAC
50.0 %50.000 AAC 48.5 AAC 50.1 AAC 51.5 AAC Calibrated 1.0000 AAC
80.0 %80.000 AAC 77.9 AAC 80.1 AAC 82.1 AAC Calibrated 1.6000 AAC
Calibration Performed:
That is All.
Thank you for using LAERIE Calibration & Metrology Service
56 Gateway Circle
Berthoud, Colorado 80513
Office: 970-532-7990
www.laerie.com
TF: 1-877-532-7990 Fax: 970-532-7992
This report shall not be reproduced except in full and with the written approval of Laerie Inc.
AS-FOUND
AC Volts Accuracy
60 Hz
RANGE 0-600 VAC
Calibration Performed:
AS-FOUND
AC Current Accuracy
60 Hz
RANGE 0-100 AMPS
FLUKE Calibration Event:FOUND-LEFT Calibration Performance Report for:
322 DMM Jedi Balancing49251381WS49251381WSEng. / Metrologist:
24-Apr-2024 24-Apr-2025 JRN
Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1
For Asset:
Calibrated Int. MTh's
25-Jul-2023 12
2FL: NEBB Compliant Calibration performed published data no adjustments required or performed.
10014 9/2023
www.laerie.com
Serial Number Description Re-CalManufacturerModel
NEBB 2023 / LAP
TSI HM675
1) AS-Received Annual maintenance performed, nominal exterior cosmetic wear, exterior cleaned where possible,
initial inspection PASS.
As-Received Physical Condition(s)
Calibration Event:
C-Procedure Environmental
73.4°F ±9°F, 40 to 65%RH
Jedi Balancing
Laerie, Inc. Issues this Certificate of Calibration to:
Jedi Balancing
568 Briggs St. PO Box 525 Erie, CO 80516
This calibration is traceable to the international system of units(SI), through National Institute of Standards and Technology (NIST).
169394.6759Certificate Number:
Customer Purchase Order:
71646134
Hutchinson's method is used including Guard Banding and TUR Strategy, False-Accept Risk normal distribution and 95% confidence level typical with coverage factor of 2.
Calibration Type:CAL-2 NEBB
: accepts and understands measurement uncertainties and risk assessment in all measurements involved in calibration.
Projected Re-
Cal.
CALIBRATION LOCATION:Laerie Inc. Laboratory
JRN
Laboratory Altitude: 5,063.25 Ft.
Description
Procedure Executed by:
Primary References Traceability Number Used in Calibration
REF Description
Pressure Calibrator
Certificate of Accredited and Traceable Calibration
71646134 Hydronic Manometer 25-Jul-2024
56 Gateway Circle Berthoud, Colorado 80513
877-532-7990 970-532-7990 TCC 2021-18C
Comments:
Veridical Review By:
L. E. Armfield CEO/President
REF Projected Re-
Cal.
NEBB 2023 LAERIE
Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)%
UUC Manufacturer:
Model:Description:
S/N:ID:
CAL-DATE:CAL-DUE:
REF Min UUC Ind.Max Compilation
0.000 PSI -1.000 PSI 0.000 PSI 1.000 PSI Calibrated
60.000 PSI 57.800 PSI 60.03 PSI 62.200 PSI Calibrated
150.000 PSI 146.000 PSI 150.1 PSI 154.000 PSI Calibrated
200.000 PSI 195.000 PSI 200.2 PSI 205.000 PSI Calibrated
NOM REF Min UUC Ind.Max Compilation
18.0 °F -2.000 °F N/A 2.000 °F N/A
105.0 °F -2.000 °F N/A 2.000 °F N/A
192.0 °F -2.000 °F N/A 2.000 °F N/A
TSI Calibration Event:FOUND-LEFT Calibration Performance Report For:
HM675/801290 Hydronic Manometer & Probe
Jedi Balancing7164613471646134Eng. / Metrologist:
56 Gateway Circle
7/25/2023 7/25/2024 JRN
Calibration Performed:
Pressure
±2% R +1 PSI
RANGE 0.4 TO 200 PSI
Calibration Performed:
Temperature
±.5% R + 2 °F
RANGE -40 TO 200 °F
Temperature probe not provided for calibration
LAERIE
Calibration & Metrology Services
Berthoud, Colorado 80513
Office: 970-532-7990
TF: 1-877-532-7990 Fax: 970-532-7992
www.laerie.com
This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc.
Laboratory Altitude: 5,063.25 Ft.Veridical Review: VR@Laerie.com Page 1 of 1