Mechanical Compliance Certificate
Project lnformation
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
252 C.R. 167
GLENWOOD SPRINGS, Colorado
81"601
202L IECC
23045 - Schafer and Company Warehouse
Glenwood Springs, Colorado
5b
Addition
Owner/Agent:
Bucky Schafer
Schafer & Company
303-819-9706
bucky@scmetals.com
Desig ner/Contractor:
Mark Sorensen
AEC
PO BOX 8489
Avon, Colorado 81620
970-748-8520
mark@aec-vail,com
Mechanical Systems List
QuantitySystem Type & Description
1 HP-l (Unknown):
VRF Condensing Unit, Air Cooled Heat pump
Heating Mode: Capacity = 34 kBtu/h,
Proposed Efficiency = 12,00 HSpF, Required Efficiency = 7.70 HSpF
Cooling Mode: Capacity = Zg kBtu/h,
Proposed Efficiency = 22.30 SEER, Required Efficiency = 13.00 SEER
Proposed Part Load Efficiency = 0,00 , Required part Load Efficiency = 0.00
Fan System: None
1 FC-l (Single Zone):
Cooling; 1 each , VRF Zone Fan Unit, Capacity = 7 kBtu/h, Unknown Economizer
No minimum efficiency requirement applies
Fan System: FC-1 | Kitchen/Living -- Compliance (Motor nameplate Hp and fan efficiency method) : passes
Fans:
, FAN l Supply, Single-Zone vAv,297 cFM, 0,1 motor nameplate hp, 1.00 fan energy index, fan exception: singlefan < 1 HP or < 0.89 kW
1 FC-2 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 5 kBtu/h, Unknown Economizer
No minimum efficiency requirement applies
Fan System; Fc-2 & 3 | Bedroom 1 -- compliance (Motor nameplate Hp and fan efficiency method) : passes
Fa ns:
, FAN 2 Supply, Single-Zone VAV, 237 cFM, 0.1 motor nameplate hp, 1.00 fan energy index , fan exception: Singlefan < 1 HP or < 0.89 kW
1 FC-3 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity : 5 kBtu/h, Unknown Economizer
No minimum efficiency requirement applie's
Fan system: Fc-2 & 3 | Bedroom 1 -- compliance (Motor nameplate Hp and fan efficiency method) : passes
Fans:
FAN 2 Supply, Single-Zone VAV, 237 CFM, 0.1 motor name plate hp, 1.00 fan energy index , fan exception: Singlefan < 1 HP or < 0.89 kW
F-1 (Single Zone):
Heating: 1 each - Central
Proposed Efficiency =
Fan System: F-1 | Office
Furnace, Gas, Capacity: 120 kBtu/h
96,50% Et, Required Efficiency: 80.00 % Et or 80% AFUE
-- Compliance (Motor nameplate Hp and fan efficie
1
ncy method) : Passes
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report dale: O4lI2l24
Page 1 of 11
QuantitySystem Type & Description
Fans:
FAN 3 Supply, constantVolume, 2200 cFM, 1,0 motor nameplate hp, 1.00 fan energy index
CU-1 (Single Zone):
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exceptionHeat Recovery System
Proposed Efficiency = 16,00 SEER2, Required Efficiency = 13.40 5EER2
Proposed Part Load Efficiency = 0,00 , Required Part Load Efficiency = 0,00
Fan System: F-1 | Office - Compliance (Motor nameplate HP and fan efficiency method) i passes
Fans:
FAN 3 Supply, Constant Volume, 2200 CFM, 1,0 motor nameplate hp, 1.00 fan energy index
WH-1:
Gas Storage Water Heater, Capacity: 50 gallons, lnput Rating: 100 kBtu/h w/ Circulation pump
Proposed Efficiency: 96.00 % Et, Required Efficicncy: 80.00 % Et
Mechanical Compliance Statement
Compliance Sfatement The proposed mechanical design represented in this document is consistentwith the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have-bbendesigned to meet the 202.1 IECC reguirements in COMcheck Verslon COMcheckWbb ind to comply with iny applicablemandatory requirements listed in the lnspection Checklist.
Mark $orensen EIT ,4*rs-au12t24
1
1
ame -e Si gnatu re Date
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4lI2/24
Page 2 of 11.
COMcfi eck Software Version CoMcheckWeb
lnspection Checklist
Energy Code: 2O2L IECC
Requirements: 0.0% were addressed directly in the coMcheck software
Text in the "Comments/Assumptions" column is.provided by the user in the CoMcheck Requirements screen, For eachrequirement, the user certifies that a code requirement wili be met and how that is documented, or that an exceptionis being claimed. Where compliance is itemized in a separate table, a reference to that table is proviOeO.
Additional Comments/Assumptions:
I High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
#
&D
Plan Review Complies?Comments/Assumptlons
: Plans, specifications, and/or
icalculations provide all information
:with which compliance can be
, determined for the mechanical and
'service water heating systems and
'document where exceptions to the
,standard are claimed. Load
' calculations per acceptable
tengineering standards and
, handbooks. Hot water system sized
r manufacturer's sizing guide.
c103.2
lPR2ll
Complies
Does Not
Not Observable
Not Applicable
:n
rl:l
:Group R-2 dwelling units have
; separate electrical meters.llooes Not
I lNot Observable
!Complies
blerltttot
c405.6
lPR16l1
: Plans, specifications, and/or
i calculations provide all information
:with which compliance can be
rmdete ned for the ddiri eneonal vrg
effic ons.en ccypa
Does Not
pliesc406
lPR9l1
INot Observable
nNot Applicable
23045 - Schafer and Company WarehouseProject Title:
Data filename:
Report date: 04112/24
Page 3 of 11
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature above 50F and
outdoor temperature above 40F.
Complies
lDoes Not
Observable
Applicable
Additional Comments/Assumptions:
1 High lmpact (Tier 1) f,Medium lmpact (Tier 2)3 Low Impact (Tier 3)
23045 - Schafer and Company WarehouseProject Title:
Data filename
Report date: 04112/24
Page 4 of 11.
Complles?
Section
#
& Req.lD
Plumblng Rough-ln lnspectlon Comments/Assumptlons
c404.5,
c404.5,1,
c404.5.2
IPL6I3
'Heated water supply piping conforms
:to pipe length and volume
requirements. Refer to section details.
Complies
:
Does Not :
Not Observable :
Not Applicable ,
c404.6.t,
c404.6.2
lPL3l1
tAutomatic time switches installed to
iautomatically switch ofF the
:recirculating hot-water system or heat
; trace,
ncomplies
nDoes Not
:!Not Observable
;nNot Applicable
Pumps that circulate water between a inComplies
heater and storage tank have controls lnDoes Not :
that limit operation from startup to
:<= 5 minutes after end ";';;;ti"; .[Not observable .
,cycle, " .LlNot APPlicable :
c404,6.3
IPL7]3
nDoes Not
flNot Observable
flNot Applicable
Demand recirculation water systems
have controls that start the pump
: upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
:piping to 104'F.
c404.6.1,
c404,6.1.I
lPL8l3
Ies
Additional Comments/Assumptions:
I High lmpact (Tier 1-)2 Medium lmpact (Tier 2)3 Low lm ct (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4lI2/24
Page 5 of 11
Section
#
& Req.lD
Mechanlcal Rough-ln lnspectlon Complles?Comments/Assumptlons
Thermally ineffective panel surfaces of ,nComplies
sensible heating panels have lnDoes Not
insulation >: R-3.5. nNot Observable
.nruot Rpplicable
c402.2.6
lME41l3
,EComplies :See the Mechanical Systems tist for values.
,nooes Not :
:!ttot Observable ,
.nruot Applicable :
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
c403.8.1
lME6513
nComplies
nDoes Not
INot Observable
!t,tot Rpplicable
Fans have a fan energy index (FEl) >:
1.00. Variable volume fans will have
an FEI >= 0.95,
c403.8.3
lME117l'
;!Complies
inOoes trtot
,!ltot Observable
.nruot applicable
Motors for fans that are not less than
llI2 hp and less than t hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adiust motor speed.
c403.8.4
lME14212
and chiller water/evaporative cooling :nDoes Not
system with fans > 1/4 hp are
designed to vary ffre inoJoltJn airflow !Not observable
as alunction of load and comply with LlNot Applicable
Each DX cooling system > 65 kBtu I nComplies
detailed rements of this section
c403.8.6
IME 14312
Large diameter fans where installed
shall be tested and labeled in
accordance with AMCA 230.:I
:tr Not licable
:nDoes ttot
lies
Not Observable
c403.9
lME14412
HVAC equipment efficiency verified. ,[Complies ,See the Mechanical Systems list for values.
:nDoes Not l
nNot Observable
nruot Rpplicable
c403,3
lMEssl,
,nComplies
inooes Not
jnNot observable
,nNot Applicable
rNatural or mechanical ventilation is
iprovided in accordance with
: lnternational Mechanical Code
iChapter 4, Mechanical ventilation has
, capability to reduce outdoor air supply
:to minimum per IMC Chapter 4.
c403.2.2
IM E59]1
!complies
nDoes Not
nNot Observable
nNot Applicable
Demand control ventilation provided
,for spaces >500 ft2 and >15
: people/l000 ft2 occupant density and
,served by systems with air side
, economizer, auto modulating outside
air damper control, or design airflow
r>3,000 cfm.
c403.7.1
lM Es9l1
:IComplies
:nDoes Not
lnNot observable
nNot applicable
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50Vo or less of design capacity
c403,7.2
lM E 115l3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403,7.6,1 and C403.7,6.2).
!Not Applicable
c403.7.6
IM E 141]3
ncomplies
,flDoes Not
:INot Observable
1 ct (Tier 1)Hi hlm Medium lm act (Tier 2)3 Low lmpact (Tier 3)
23045 - Schafer and Company WarehouseProject Title:
Data filename
Report date: O4lI2l24
Page 6 of 11
Section
#
& Req.lD
Mechanical Rough-ln lnspection Complles?Comments/Assumptlons
Exhaust air energy recovery on
systems meeting Table C403,7.4(1)
and C403.7.4(2).
nn
trn
Complies
:
Does Not i
Not Observable ,
Not Applicable .
c403.7.4
lM E5711
Kitchen exhaust systems comply with nComplies
replacement air and conditioned ,nDoes Not
supply air limitations, and satisfv hood -., , ^,rating requirements and ;;;;;;;""" nNot observable
exhaust r'ate criteria. L-JNot Applicable
c403,7.5
lME11613
valve to bypass all heat pump water
flow around the tower, Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulatlon pump on the
cool tower loop.
atic ,nDoes
c403,4.3
3.2
lME12113 bypass valve or lower leakaqe positive
ciosure dampers. opun-JiiIu'ii i"*;;- - ENot observable
within heat dump tdop have automat;6 LJNot Applicable
Closed-circuit cooling tower within
heat pump loop have either autom
lies
Not
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <:
60F and cooling setpoint >: BOF.
nNot Applicable
nComplies :
nDoes Not i
DNot Observable ,
c403,4.1
lME6312
nComplies
nDoes Not :
nNot Observable
nNot Applicable :
c403.3.3
lM E3511
Hot gas bypass limited to: <:240
kBtu/h - 50Vo >240 kBtu/h - 25%
Gas-fired water-heating equipment
installed in new buildings: where a
singular piece of water-heating
equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency>: 92 Et. Where multiple pieces of
water-heating equipment serve the
building with combined rating >=
1,000 kBtu/h, the combined input-
capacity-weighted-average thermal
efficiency >: 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <: 100
kBtu/h.
,nComplies
:IDoes Not
,nNot Observable
,!Not Applicable
:
:
;
c404.2.1.
lM E1r.1t,
c408.2.2
1
lME5313
Air outlets and zone terminal devices
have means for air balancing.,!ooes trtot
plies
nNot Observable
,nNot Applicable ,
1 ct (Tier 1)Hi hlm 2 Medium (Tier 2)3 (Tier 3)Low
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4lL2l24
Page 7 of 11
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403,1 1.3.1 and refrigeration
compressor systems that comply with
c403.1" l".3.2..
nDoes Not
res
Not Observable
Not Applicable
c403.11.3
,1,
Additional Comments/Assumptions:
I hlm ct (Tier 1)H Medium Im ct (Tier 2)(Tier 3)Low
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4lL2l24
Page 8 of 11
Complles?Comments/Assumptlons
Section
#
& Req.lD
Rough-ln Electrlcal lnspectlon
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
inComplies .
inDoes Not :
:!ruot Observable,
:nNot Applicable ,
c405.7
lEL26l?
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) throush C405.7 (4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
proqrams do not exist).
;nComplies
ilOoes trtot
inNot observable
j!ruot applicable
c405.8
lEL2712
C405.9.1, Escalators and moving walks comply
C405.9.2 'with ASME A17,1/CSA 844 and have
lEL28l'? automatic controls configured to
reduce speed to the minimum'permitted speed in accordance with
ASME A17.1/CSA 844 or applicable
local code when not conveying
;nnoes trtot
,!Not Observable
inruot applicable
rs.
tes
Total voltage drop across the
combination of feeders and branch
circuits <: 5o/o,
:[ooes Not
,INot Observable
:nruot icable ,
tesc405.10
lEL29l2
'At least 90Vo of dwelling unit
permanently installed lighting shall
have lamp efficacy >= 65 Im/W or
luminaires with efficacy >: 45 lm/W
:[ooes Not
lENot observable,
i[ruot Rpplicable ,or com with C405.2.4 or C405.3
tesc405.1.1
lEL3ol2
C405.11, 5O% of 15/20 amp receptacles
C405.11.1 installed in enclosed offices,
[EL31]2 conference rooms, copy rooms, break
rooms, classrooms and workstations
and > 25Vo of branch circuit feeders
for modular furniture will have
automatic receptacle control in
accordance with C405.11,1,
les
ilooes trtot
,INot Observable
.!Not Applicable
Additional Comments/Assumptions:
1 hlm ct (Tier 1)H 2 Medium I (Tier 2)3 Low I act (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4lI2l24
Page 9 of 11
Section
#
& Reo.lD
Final lnspection Complles?Comments/Assumptions
c303.3,
c408.2.5
3
lFt8l3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
:!Complies
;nOoes trtot
ilNot observable
;flNot Applicable
HVAC systems and equipment
capacity does not exceed calculated
loads.
,flComplies ,
,nooes Not
'nNot Observable,
:!Not Applicable :
c403.3.1
lFt27l3
Heating and cooling to each zone is rnComplies i
controlled by a thermostat control. ,nDoes Not
Minimum one humidity control device :aNot
Observableper installed
humidification/dehumidification lnNot Applicable ;
svstem.
c403.4.1
lFt4713
c403.4.1
1
lFt42)3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
,nooes Not
inNot observable
plies
rntlot
c403.4.1
2
tFt38l3
,ncomplies
ilDoes ttot
llNot observable
;[Not Applicable
Thermostatic controls have a 5 'F
deadband.
c403.4.I
3
lFr20l3
Temperature controls have setpoint
overlap restrictlons.
nComplies
[ooes t',tot
:INot Observable
.!Not applicable
,lComplies .
jnooes Not .
:!trtot Observable,
.!Not Applicable r
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
c403.4.2
lFt3913
Automatic Controls: Setback to 55'F
(heat) and 85'F (cool); 7-day clock, 2-
hour occupant override, 10-hour
bac ku p
c403.4.2
1,
c403.4.2
2
lFt40l3
,!Complies
'nooes Not
INot Observable
nNot Applicable
:nComplies
lnDoes Not
,nNot Observable
1!Not Applicable
c403.4.2
3
lFt41l3
Systems include optimum start
controls.
nComplies
IDoes Not
!Not Observable
flNot Applicable
Heat traps installed on supply and
discharge piping of non-circulating
systems.
c404.3
lFt 1 113
All piping insulated in accordance with ,L-JComplies
section details and Table C403.12.3. :nDoes Not
;nNot Observable
:nNot Applicable
c404.4
lFt2512
Icomplies
nDoes Not
INot Observable
lNot applicable
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
c404.6.1
lFr1213
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lm act (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: 04/L2124
Page 10 of 11
Comments/Assumptlons
Section
#
& Reo.lD
Flnal lnspectlon Complles?
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated,
'nNjnrrr
C408.1.1 lBuilding operations and maintenance
lFl5711 ,documents will be provided to the
.!Complies
:EDoes trtot
ot Observable :
ot Applicable .
C408.2.I :Commissioning plan developed by
tFl28l1 !registered design professional or
:approved agency.
lncomplies
,!Oo"t ttot
inruot observable
:!ruot nppticable
system-to-system relationships have
been tested to ensure proper
operation.
:nComplies i
jlooes ruot i
illtot observable.
inruot Applicable ,
c408.2.3,
1
lFt31l1
, HVAC equipment, systems and
HVAC and service water heating
control systems have been tested to
ensure proper operation, calibration
and adjustment of controls.
,EComplies
,nDoes Not
,!Not Observable
;[ruot npplicable
c408.2.3
2
lFr 1ol1
.4,Preliminarycommissioningreport,nComplies
,completed and certified by registered tlDoes ltot i
design professional or approved nNot Observableasency. -_;iffiil;;r"-
2
1
c408
lFt29
Furnished HVAC as-built drawings
submitted within 90 days of system
accepta nce.,!Not
lIt'lot
:nooes Not
plies
Observable
cable
c408,2.5
lFt 713
:!compliesC408.2.5. ;An air and/or hydronic system
lbalancing report is provided for HVAC lnooes Not
systems.
1
lFt43l1 ,nNot Observable
lnNot Applicable
:Final commissioning report due to
'building owner within 90 days of
I receipt of certificate of occupancy
,nComplies
,[ooes Not
,INot Observable
;nNot Applicable
c408.2.5.
2
lFt3oll
Additional Comments/Assumptions:
2 Medium I (Tier 2)3 Low lm act (Tier 3)1 High lmpact (Tier 1)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: 04112124
Page 11 of 11