HomeMy WebLinkAboutHeat CalcsCoryell Ranch Rev 2 - Permit HVAC Load Calculations for Carbondale, CO, 81623 Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page2 Load Calculation Project Report General Project lnformation Project Title: Project Date: Designed By: Project Comment: Client City: Coryell Ranch Rev 2 - Permit 6t27t2024 Greg Wentzell BLDG Permit Carbondale, CO,81623 Design Data Reference City: Building Orientation: Daily Temperature Range Latitude: Elevation: Altitude Factor: Carbondale, Co, Colorado, United States Front door faces NW High 39 Degrees 6200 feet 0.795 Outdoor Dry Bulb -5 87 Outdoor Outdoor Rel.Hum 100% 41% lndoor Rel.Hum nla 50Yo lndoor Grains Difference nla 18 Wet Bulb Dry Bulb Winter Summer E 68 70 75 Check Figures Supply Square Volume Volume CFM: ft. of Room Area 3 3 47 47 ,090 ,415 ,325 ,325 CFM per Square ft. Square ft. per ton: 0.905 519 (ft") (ft') of Cond. Space: (Total): Build Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 82,250 Btuh 59,202 Btuh 6,333 Btuh 65,536 Btuh 82.250 MBH 90 o/o 10% 5.46 Tons (Based On Sensible + Latent) 6.58 Tons (Based On75% Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D, All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per Miscellaneous Report System 1 Great Room SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: -5 87 70 7568 100o/o 41% nla 50% nla 17.56 System 2 Master Wing SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: -5 87 70 75 nla-5 68 100o/o 41o/o 50o/o nla 17.56 Rhvac Online Alius Design Corps Carbondale, CO * Elite Soflware Development, lnc. Coryell Ranch Rev 2 Per Page 3 System 3 Guest Wing SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: -5 87 50o/o nla 17.56 70 75 nla_q 68 100% 41o/o Outside Air Data I nfiltration Specified lnfiltration Actual: Above Grade Volume: Total Building lnfiltration: Total Building Ventilation Winter 0.100 AC/hr 79 CFM 0.000 AC/hr x47.325 ff 0 ft3/hr x 0.0167 O CFM 235 CFM Summer 0.050 AC/hr 39 CFM 0.000 AC/hr x47.325 ft" 0 ft'/hr x 0.0167 O CFM 235 CFM --System'l-- lnfil. & Vent. Sensible Gain Multiplier: 10.50 = (1 .10 X 0.795 X 12.00 Summer Temp. Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent. Sensible Loss Multiplier: 65.62 = (1.10 X 0.795 X 75.00 Winter Temp. Difference) Winter lnfiltration Specified: 0.100 AC/hr (50 CFM), Construction: Tight Summer lnfiltration Specified: 0.050 AC/hr (25 CFM), Construction: Tight --System 2-- lnfil.&Vent.SensibleGainMultiplier: 10.50 =(1.10X0.795X12.00SummerTemp.Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent, Sensible Loss Multiplier: 65.62 = (1.10 X 0.795 X 75.00 Winter Temp. Difference) Winter lnfiltration Specified: 0.100 AC/hr (13 CFM), Construction: Tight Summer lnfiltration Specified: 0.050 AC/hr (7 CFM), Construction: Tight --System 3--- lnfil.&Vent.SensibleGainMultiplier: 10.50 =(1.10X0.795X12.00SummerTemp.Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent. Sensible Loss Multiplier: 65.62 = (1 .10 X 0.795 X 75.00 Winter Temp. Difference) Winter lnfiltration Specified: 0.100 AC/hr (15 CFM), Construction: Tight Summer lnfiltration Specified: 0.050 AC/hr (8 CFM), Construction: Tight Coryell Ranch Rev 2 Per Supply Return Attic Attic 168 168 0.12 0.24 6 6 502.2 186 No No Supply Return Attic Attic 168 168 0.12 0.24 6 6 191.7 71 No No Supply Return Attic Attic 168 168 0.12 0.24 6 6 228.1 84.5 No No Coryell Ranch Rev 2 Per Total Building Summary Loads Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page 5 Component Description Area Quan Sen Lat Gain Sen Gain Total GainLoss I ECC: Glazing-20 1 8_l ECC_glass, U-value 0.3, SHGC 0, 3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_csJlr, U-value 0.03 Subtotals for structure: People: 14 Equipment: Lighting: 4.2 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 235, Summer CFM: 235 AED Excursion: Total Building Load Totals: 772.5 319 3275.5 3635 3415 17,381 11,964 13,264 5,453 4,803 52,865 23,988 0 5,397 0 82,250 17,220 9,056 3,274 946 17,220 9,056 3,274 946 769 31,265 6,020 5,266 14 13,428 0 3,096 6,447 65,536 0 0 0 0 0 0 2,800 1,301 0 2,232 0 6,333 769 31,265 3,220 5,266 14 12,127 0 864 6,447 59,202 0 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space: Volume (ft")(Total): 3,090 3,415 47,325 47,325 CFM per Square ft. Square ft. per ton: 0.905 519 Building Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 82,250 Btuh 59,202 Btuh 6,333 Btuh 65,536 Btuh 82.250 MBH 90 o/o 10 o/o 5.46 Tons (Based On Sensible + Latent) 6.58 Tons (Based On75% Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. CoryellRanch Rev 2 Per System 1 Great Room SSHP Summary Loads Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, Inc. Coryell Ranch Rev 2 Per Page 6 Component Description Area Quan Sen Lat Gain Sen Gain Total GainLoss IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: 6 Equipment: Lighting: 1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 115, Summer CFM: 115 AED Excursion: System 1 Great Room SSHP Load Totals: 536 197 1118 2080 1 860 12,060 7,388 4,527 3,120 2,616 29,711 13,072 0 2,641 0 45,425 11,394 5,286 1,117 541 11,394 5,286 1,117 541 419 18,757 2,580 4,333 6 7,336 0 1,515 6,1 80 40,706 0 0 0 0 0 419 0 1,200 0 707 0 1,092 0 3,000 18,757 1,380 4,333 b 6,628 0 423 6,1 80 37,706 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space: Volume (ft3) (Total): 997 860 220 220 1 1 30 30 CFM per Square ft. Square ft. per ton: 1.074 444 Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air Loads 45.425 MBH 93 o/o 7 o/o 3.39 Tons (Based On Sensible + Latent) 4.19 Tons (Based On75o/o Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. 45,425 Btu 37,706 Btu 3,000 Btu 40,706 Btu h h h h Coryell Ranch Rev 2 Per System 2 Master Wing SSHP Summary Loads IECC: Glazing-2O18_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 2018_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 201 8_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fl r, U-value 0.03 152.5 80 1062.5 710 3,431 3,000 4,303 1,065 0 0 0 0 4,064 2,667 1,062 185 4,064 2,667 1,062 185 710 998 0 160 160 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 40, Summer CFM: 40 12,797 0 8,1 38 460 933 2 2,518 0 147 8,1 38 860 933 2 2,788 0 527 19,248 2 400 0 0.6 5,011 0 919 270 0 380 System 2 Master Wing SSHP Load Totals:18,727 1,050 12,198 Supply CFM: Square ft. of Room Area: Volume (ff) of Cond. Space: Volume (ft3) (Total): 638 710 7,810 7,810 CFM per Square ft. Square ft. per ton: 0.899 524 Total Heating Required lncluding Ventilation Air: TotalSensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 18,727 Btuh 12,198 Btuh 1,050 Btuh 13,248 Btuh 18.727 MBH 92 o/o 8% 1 .1 0 Tons (Based On Sensible + Latent) 1.36 Tons (Based On75% Sensible Capacity) Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per System 3 Guest Wing SSHP Summary Loads Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page I Component Description Area Quan Sen Loss Lat Sen Total GainGain Gain IECC: Glazing-2O18_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 2018_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_cs_flr, U-value 0. 03 Subtotals for structure: People: 6 Equipment: Lighting: 1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 80, Summer CFM: 80 AED Excursion: 84 42 1 095 845 1,890 1,576 4,434 1,268 1,762 1,103 'r,095 220 1,762 1 ,'1 03 1,095 220 0 0 0 0 845 1,189 10,357 5,904 0 1,837 0 18,098 190 4,370 1,380 0 b 2,980 0 294 267 9,297 190 4,370 2,580 0 6 3,304 0 1,054 267 11 ,581 0 0 1,200 0 324 0 760 0 2,284 Supply Square Volume Volume 3 Guest Wing SSHP Load Totals: CFM: ft. of Room Area of Cond. Space: CFM per Square ft Square ft. perton: 455 845 9,295 9,295 0.538 818 Check Figures (ft") (ft")(Total Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 18,098 Btuh 9,297 Btuh 2,284 Btuh '11 ,581 Btuh 18.098 MBH 80 Vo 20% 0.97 Tons (Based On Sensible + Latent) 1.03 Tons (Based On 75o/o Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. System Loads Coryell Ranch Rev 2 Per System 1, Zone 1 Summary Loads (Peak Load Procedure for Rooms) IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 I ECC : Wall-Frame, Custom, 20 1 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0,02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fl r, U-value 0.03 36 68 80 80 810 275 120 0 0 0 828 68 21 828 68 21 113 0 0 400 18 18 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 1 ,318 935 460 1,733 2 442 0 4,207 935 860 1,733 2 442 0 4,607 2 0 0.6 443 0 0 0 1,Zone 1 Load Totals:1,761 Supply CFM: 240 CFM per Square ft. 3.005 Squbieft. ofRoomArea: 80 Squareft. perton: 156 Volume (ft3) of Cond. Space: 1,040 Volume (ft3) (Total): 1,040 Total Heating Required: Total Sensible Gain 1,761 Btuh 4,2Q7 Btuh 400 Btuh 4,607 Btuh 1.761 MBH 91 o/o 9 o/oTotal Latent Gain: TotalCooling Required 0.38 Tons (Based On Sensible + Latent) 0.51 Tons (Based On75% Sensible Capacity) Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per System 1, Zone 4 Summary Loads (Peak Load Procedure for Rooms) IECC: Floor-Over enclosed crawl space, Custom,180 253 0 41 41 201 8_iecc_cs_fl r, U-value 0.03 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 253 0 0 0 0 0 41 41 0 0 2 o 0 58 0 0 0 2 6 0 0.6 85 0 1, Zone 4 Load Totals 338 0 58 Supply Square Volume Volume CFM: ft. of Room Area: 3 180 1,980 1,980 CFM per Square ft. Squareft. perton: 0.018 37,330 (ft") (ft") ofCond. Space: (Total): Total Heating Required Total Sensible Gain Total Latent Gain: TotalCooling Required 338 Btuh 58 Btuh 0 Btuh 58 Btuh 0.338 MBH 100 Vo 0 o/o 0.00 Tons (Based On Sensible + Latent) 0.00 Tons (Based On75o/o Sensible Capacity) Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Inc. Coryell Ranch Rev 2 Per Page 11 System 1, Zone 5 Summary Loads (Peak Load Procedure for Rooms) Component Description Area Quan Sen Lat Sen Gain Total GainLossGain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 2018 iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: 4 Equipment: Lighting: 0.6 Ductwork: lnfiltration:Winter CFM: 0, Summer CFM: 0 500 197 '1050 2000 11,250 7,388 4,252 3,000 0 0 0 0 14,695 7,118 1,049 520 14,695 7,118 1,049 520 1 600 2,250 28,140 0 0 360 360 1, Zone 5 Load Totals: 9,455 0 37,595 800 0 0 0 800 23,742 920 2,600 2 3,849 0 36,649 23,742 1,720 2,600 2 3,849 0 37,449 Supply Square Volume Volume CFM: ft. of Room Area 2 I 27 27 094 600 200 200 CFM per Square ft. Square ft. per ton: 1.309 474 (ft") (ft") of Cond. Space: (Total): Zone Loads Total Heating Required Total Sensible Gain 37,595 Btuh 36,649 Btuh 800 Btuh 37,449 Btuh 37.595 MBH 98% 2 o/o 3.12 Tons (Based On Sensible + Latent) 3.38 Tons (Based On 75o/o Sensible Capacity) Total Latent Gain: Total Cooling Required Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Check Figures Coryell Ranch Rev 2 Per s 2, Zone I Summary Loads (Average Load Procedure for Rooms IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 I ECC : Wall-Frame, Custom, 201 8_iecc_flr, U-val ue 0. 054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc-rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fl r, U-value 0.03 152.5 80 1062.5 710 3,431 3,000 4,303 1,065 0 0 0 0 4,064 2,667 1,062 185 4,064 2,667 1,062 185 710 998 0 160 160 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration:Winter CFM: 0, Summer CFM: 0 12,797 8,138 460 933 2 1,633 0 8 138 860 933 2 633 0 566 2 400 0 0 0 400 0.6 3,826 0 1 2, Zone 1 Load Totals:16,623 11,166 11, Supply Square Volume Volume CFM: ft. of Room Area 638 CFM per Square ft. Square ft. per ton: 0 899 670 (ft') (ft') of Cond. Space: 10 10 10 Total Heating Required: Total Sensible Gain 16,623 Btuh 11,166 Btuh 400 Btuh 11,566 Btuh 16.623 MBH 97% 3 o/o 0.96 Tons (Based 1.06 Tons (Based Capacity) Total Latent Gain: TotalCooling Required On Sensible + Latent) On 75o/o Sensible Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO ft Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page 13 System 3, Zone 1 Summary Loads (Average Load Procedure for Rooms) Component Description Area Quan Sen Loss Lat Gain Sen Gain Total Gain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 20'1 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fl r, U-value 0. 03 Subtotals for structure: People: 6 Equipment: Lighting: '1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 System 3, Zone 1 Load Totals: 84 42 1 095 845 1,890 1,576 4,434 1,268 0 0 0 0 1,762 1,103 1,095 220 1,762 1,103 1,095 220 845 1,189 10,357 0 190 190 4,370 2,580 0 6 1,934 0 9,158 0 1,200 0 4,370 '1,380 0 6 1,934 0 7,958 4,510 0 14,867 0 0 1,200 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space Volume (ft")(Total): 455 845 9,295 9,295 CFM per Square ft. Square ft. per ton: 0.538 1,058 Zone Loads Total Heating Required Total Sensible Gain Total Latent Gain: Total Cooling Required 14 7 1 o ,86 ,95 ,20 ,15 7 8 0I Btu Btu Btu Btu h 14.867 MBH 87 o/o 13% 0.76 Tons (Based On Sensible + Latent) 0.80 Tons (Based On 75o/o Sensible Capacity) h h h Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO t Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page 14 Detailed Room Loads - Room 6 - Office (Peak Fenestration Gain Procedure) General Room is in zone 1, which peaks at 9 am Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 80.0 13.0 1,040 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: SupplyAir: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 1 1 240 13.9 5 2 12 5 CFM AC/hr CFM % CFM oh NE-Wa||-IECC 8 X 13 NE-Gls-IECC shgc-0.3 0%S UP-Roof-IECC 80 X 1 Floor-IECC 1 X 80180 Subtotals for Structure: lnfil.: Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Equipment: Lighting: Room Totals: 68 36 80 80 104 0.054 0.300 0.020 0.030 4.1 22.5 1.5 1.4 275 810 120 113 1 ,318 0 443 1.0 23.0 0.3 0.2 0 0 0 0 0 0 68 828 21 18 935 0 442 635 460 1,733 2 4,207 0.000 0.000 2 400 0 400 1 1,761 Computer and monitor Laser printer Color television Total 1,536 512 683 0 0 0 35 100 100 100 100 100 538 512 683 1,733 0 0 0 0 Item Description Area Quantity -u-Htg HTM Sen clg HTM Lat Sen GainValueLossGain Equipment Cooling Loads Item Name Cont. Output Sensible Btuh Cont. Output Latent Btuh Average ln-Use Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh Coryell Ranch Rev 2 Per Detailed Room Loads - Room 1 - Mudroom Fenestration Gain Proced ure Room is in zone 4, which peaks at 7 pm Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 180.0 11.0 1,980 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual WinterVent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 1 4 3 CFM 0.1 AC/hr 1 CFM 30 o/o O CFM 5 o/o Floor-IECC 1 X 1801180 180 0.030 1.4 253 0.2 0 o 0 41 41Subtotals for Structure: lnfil.: Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: Lighting: Room Totals: 0 0.000 253 0 85 Cae 0.000 0 6 I 2 58 1 0 CoryellRanch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Inc. Coryell Ranch Rev 2 Per Page 16 Detailed Room Loads - Room 5 - Kitchen-Living (Peak Fenestration Gain Procedure) General Room is in zone 5, which peaks at 5 pm Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 1,600.0 17.0 27,200 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 1 5 2,094 4.6 109 5 103 5 CFM AC/hr CFM % CFM o/o NW-Wa||-IECC 65 X 13 SE-Wa||-IECC 50 X 13 NW-Wa||-IECC 36 X 7 NW-Gls-IECC shgc-O.3 0%S SE-Gls-IECC shgc-O.3 0%S SE-Gls-doors shgc-0.35 0%S NW-Gls-IECC shgc-O.3 0%S NW-Gls-doors shgc-0. 35 0%S UP-Roof-IECC 2000 X'l Floor-IECC 1 X 160011600 Subtotals for Structure: lnfil.: Win.: 0.0, Sum,: 0.0 Ductwork: AED Excursion: People: 200 laVper, 230 sen/per: Equipment: Lighting: Room Totals: 329 559 162 90 70 21 340 176 2000 1 600 0.054 0.054 0.054 0.300 0.300 0.500 0.300 0.500 0.020 0.030 4.1 4.1 4.1 22.5 22.5 37.5 22.5 37.5 1.5 1.4 1,332 2,264 656 2,025 1,575 788 7,650 6,600 3,000 2,250 28,140 0 9,455 1.0 1.0 1.0 30.6 21.7 26.9 30.6 37.2 0.3 0.2 0 0 0 0 0 0 0 0 0 0 0 0 329 558 162 2,757 1,522 564 10,416 6,554 520 360 23,742 0 3,849 5,536 920 2,600 2 36,649 1,747 0.000 0.000 4 800 0 1 37,595 800 Whole House DefaultAppliance Load, Refrigerator and range with vented hood. Note: 1200 Btuh applied to the kitchen. Whole House Scenario Adjustment Option D, Large 1,200 0 100 100 1,200 0 1,400 0 100 100 1 ,400 0 fam duri ilv using TVs, stereos, computers and laundry room the late afternoon in midsummer. Note: This is an nal 410 watt allowance for AA/ or computeradd ng itio equipment. Total 0 Item Area Quantity -u- Value Htg HTM Sen clg HTM Lat Sen Loss Gain Gain Equipment Cooling Loads Item Name Cont. Cont.Output Output AverageSensible Latent ln-UseBtuh Btuh Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh 2,600 Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO * Elite Sofiware Development, lnc. Coryell Ranch Rev 2 Per Page 17 Detailed Room Loads - Room 7 - Master_Bed (Average Load Procedure) General Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil. Htg. & clg. nla nla 710.0 11.0 7,810 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual WinterVent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 2 I 638 4.9 40 6 40 6 CFM AC/hr CFM o/o CFM o/o NW-Wall-IECC 35 X 13 SE-Wa||-IECC 30 X 13 SW-Wa||-IECC 30 X 15 NW-Gls-IECC shgc-O.3 0%S SE-Gls-doors shgc-0.35 0%S SE-Gls-IECC shgc-0.3 0%S SW-Gls-IECC shgc-O.3 0%S UP-Roof-IECC 710 X I Floor-IECC 1X7101710 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: People: 200 laVper, 230 sen/per: Equipment: Lighting: Room Totals: 442.5 220 400 0.054 0.054 0.054 0.300 0.500 0.300 0.300 0.020 0.030 4.1 4.1 4.1 22.5 37.5 22.5 22.5 1.5 1.4 1,792 891 1,620 281 3,000 2,025 1,125 1,065 998 12,797 0 3,826 1.0 1.0 1.0 22.3 33.3 27.0 27.0 0.3 0.2 0 0 0 0 0 0 0 0 0 0 0 442 220 400 279 2,667 2,433 1,352 185 160 8,138 0 1,633 460 933 2 11,166 12.5 80 90 50 710 710 1,295 0.000 0.000 2 400 0 400 1 16,623 Ceiling fan Color television Total 250 683 0 0 100 100 100 100 250 683 933 0 0 0 Item Description Area Quantity -u-Htg HTM Sen Loss clg HTM Lat Gain Sen Value Gain Equipment Cooling Loads Item Name Cont. Cont.Output Output AverageSensible Latent ln-UseBtuh Btuh Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh Coryell Ranch Rev 2 Per Detailed Room Loads - Room 2 - ADU-GYM (Average Load Procedure) Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 285.0 11.0 3,135 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 3 1 80 CFM 1.5 AC/hr 19 CFM 24 o/o 14 CFM 18 o/o N-Wall-IECC 13 X 11 NE-Wall-IECC 18 X 11 SE-Wa||-IECC 6 X 11 UP-Roof-IECC 285 X 1 F!9or-fEcc 1x2851285 Subtotals for Structure: lnfil.: Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Lighting: Room Totals: 143 198 66 285 285 0.054 0.054 0.054 0.020 0.030 4.1 4.1 4.1 1.5 1.4 579 802 267 428 401 1.0 1.0 1.0 0.3 0.2 0 0 0 0 0 143 198 66 74 64 545 0 338 47 460 2 1,392 407 0.000 2,477 0 1,079 0.000 0 0 2 1 400 4003,556 Coryell Ranch Rev 2 Per Detailed Room Loads - Room 3 - Guest 2 (Average Load Procedure) Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil. Htg. & clg. nla nla 280.0 11.0 3,080 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: SupplyAir: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 3 1 156 CFM 3.0 AC/hr 30 CFM 20 o/o 27 CFM 18% NE-Wall-IECC 20X 11 SE-Wall-IECC 17 X 11 SE-Gls-IECC shgc-0.3 68%S SE-Gls-doors shgc-0.35 68%S UP-Roof-IECC 280 X 1 Floor-IECC 1 X 2801280 220 124 42 21 280 280 407 0.054 0.054 0.300 0.500 0.020 0.030 4.1 4.1 22.5 37.5 1.5 1.4 891 502 945 788 420 394 3,940 0 1,716 1.0 1.0 14.9 19.2 0.3 0.2 0 0 0 0 0 0 o 0 220 124 627 403 73 63 1,510 0 663 92 460 2 2,726 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Lighting: Room Totals: 0.000 0.000 2 I 400 4005,656 CoryellRanch Rev 2 Per I I I I Ifr:t i:,ioliil',{; I rir:t I rlr)V, j ir4 n) n n1,,1 6]i i, ] I rtrl l1:lc111v1lll I ii:,Uirt,'jiri i rillr ;:'l l1'|,1 I i.il ll,',t: t,; ( t) ni I i n r, I iiiLl ti: j i r\,'I: iftllitt (( iirr)ij0l:,r ,1 1ll,1r 1 111, I d! r,, {r l; rr j'):r11]i;t 2{tl) il I Detailed Room Loads - Room 4 - Guest I (A Load Procedure Calculation Htg. & clg. nla nla 280.0 sq.ft. 11.0 ft. 3,080 cu.ft. O CFM O CFM Occurrences: System Number: Zone Number: SupplyAir: SupplyAir Changes: Actual WinterVent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 3 ,l 219 4.3 30 14 39 18 Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: ActualSummer lnfil. CFM AC/hr CFM o/o CFM % NE-Wall-IECC 20X11 SE-Wa||-IECC 17 X11 SE-Gls-IECC shgc-0.3 0%S SE-Gls-doors shgc-0.35 0%S UP-Roof-IECC 280 X 1 Floor-IECC 1 X 2801280 220 124 42 21 280 280 0.054 0.054 0.300 0.500 0.020 0.030 4.1 4.1 22.5 37.5 1.5 1.4 891 502 945 788 420 394 1.0 1.0 27.0 33.3 0.3 o.2 0 0 0 0 0 0 220 124 1,135 700 73 63 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Lighting: 407 0.000 3,940 0 1,716 0.000 0 0 2,315 0 933 129 460 2 2 400 1 Room Totals:5,656 400 3,839 rrilltl i ,) r i r,r ,'l lt',t'i,i i l it,r.,r,'ll , I i,,,, I ir'i r..t,: :' ; Lt il i, I i .l ' i, , i' Coryell Ranch Rev 2 Per Manual S Performance Data - System I - Great Room SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb: lndoor Dry Bulb: lndoor RH: Supply Airflow: 0 68 75 50 0 Sensible Gain: Latent Gain: Total Gain: Load SHR: Entering Dry Bulb: Entering Wet Bulb: 37.706 3.000 40.706 0.93 0 0 Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb: Supply Airflow: 45.425 60.9 648 This system's equipment was selected in accordance with ACCA Manual S. Cooling: ModelType:Air Source Heat Pump, Outdoor Model: NTXMSH48A182AA, lndoor Model: TPEFYPOS4MA144A AHRI Reference Number: 207517167, Nominal Capacity: 54.000, Manufacturer: Mitsubishi lnterpolation Results: Percent Load 37.706 3.000 40.706 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 0o/o 00h 0o/o Heating: Model Type:Air Source Heat Pump, Model: NTXMSH48A182AA, Nominal Capacity: 54.000, Manufacturer: Mitsubishi Results: PercentLoad of Load Heating Capacity: 54.000 45.425 119% Coryell Ranch Rev 2 Per Manual S Performance Data - System 2 - Master Wing SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb: lndoor Dry Bulb: lndoor RH: SupplyAirflow: 0 68 75 50 0 Sensible Gain: Latent Gain: TotalGain: Load SHR: Entering Dry Bulb: 12.198 1.050 13.248 0.92 0 0Wet Bulb Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb Supply Airflow: 18.727 61.9 271 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type: Air Source Heat Pump, Outdoor Model: NTXMSH36A142AA,lndoor Model: TPEADAO241AA80A, NTXDKS12A112AA AHRI Reference Number: 207517163, NominalCapacity: 36.000, Manufacturer: Mitsubishi lnterpolation Results: Percent Load 12.198 1.050 13.248 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 lYo 0o/o 0o/o Heating: Model Type: Air Source Heat Pump, Model: NTXMSH36Al42AA, Nominal Capacity: 45.000, Manufacturer: Mitsubishi Results: PercentLoad of Load Heating Capacity: 45.000 18.727 240% Goryell Ranch Rev 2 Per Manual S Performance Data - System 3 - Guest Wing SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb lndoor Dry Bulb: lndoor RH: SupplyAirflow: 0 68 75 50 0 Sensible Gain: Latent Gain: TotalGain: Load SHR: Entering Dry Bulb: Entering Wet Bulb: 9.297 2.284 11.581 0.80 0 0 Heating: Outdoor Dry Bulb lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb: SupplyAirflow: 18.098 56.9 243 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model AHRI Type:Air Source Heat Pump, Outdoor Model: NTXMSH36A'l42AA,lndoor Model: NTXDKS09A112PA, Reference Number: 207517163, Nominal Capacity: 36.000, Manufacturer: Mitsubishi lnterpolation Results: Percent Load 9.297 2.284 11.581 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 0% 0% 0% Heating: Model Type: Air Source Heat Pump, Model: NTXMSH36A142AA, Nominal Capacity: 45.000, Manufacturer: Mitsubishi Results: PercentLoad of Load Heating Capacity: 45.000 18.098 249% Coryell Ranch Rev 2 Per System 1 Room Load Summary 6 Office 80 1,761 29 0-0 0 4,207 400 240 240 - Zone 1 subtotal --Zone 4---'l Mudroom - Zone 4 subtotal --Zone 5-- 5 Kitchen-Living 80 1,761 29 4,207 58 400 240 03 03 800 2,094 240 180 338 338 6 0-0 0 3 180 1,600 6 58 3 37,595 614 0-0 0 36,649 2,094 2,094- Zone 5 subtotal 1,600 37,595 614 - Ventilation - Duct Latent - Return Duct - System 1 total 2,641 423 1,092 359 3483,090 2,332 1,860 45,425 648 1,997 Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure + Excursion" method. Net Required: Recommended 3.39 4.19 93o/o l7o/o 75o/o I 25o/o 37,706 37,706 3,000 12,569 40,706 50,275 Coryell Ranch Rev 2 Per System 2 Room Load Summary 7 Master_Bed 710 16,623 271 0 11,166 400 638 638 - Ventilation - Duct Latent - Return Duct 919 147 380 137 1331,185 885 - System 2 total 710 18,727 271 12,198 1,050 638 638 Net Required: Recommended 1.10 1.36 92o/o I 8o/o 75Vo l25o/o 12,198 12,198 1,050 4,066 13,248 16,265 ..1 Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page 26 System 3 Room Load Summary 2 ADU-GYM 3 Guest 2 4 Guest 1 - Ventilation - Duct Latent - Return Duct - System 3 total 285 280 280 3,556 5,656 5,656 1,837 58 92 92 24; 0-0 0-0 0-0 0 0 0 1,392 2,726 3,839 294 400 400 400 760 166 158 2,284 80 156 219 80 156 219 845 1,394 '18,098 1,046 9,297 455 455 Net Required: Recommended: Actual: 0.97 1.03 3.00 80o/o I 20o/o 75oA I 25o/o 67Vo I 33o/o 9,297 9,297 24,000 2,284 3,099 12,000 11,581 12,397 36,000 Equipment Data Type: Model: lndoor Model: Brand: Efficiency: Sound: Capacity: Adjusted Capacity: Sensible Capacity: Latent Capacity: AHRI Reference No.: Heating System Air Source Heat Pump NTXMSH36A142AA Cooling System Air Source Heat Pump NTXMSH36A142AA NTXDKSOgAll2AA 0 45,000 Btuh nla nla nla nla O SEER 0 36,000 Btuh 33,200 Btuh 24,000 Btuh 12,000 Btuh 207517163 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 87F, SOWB: 68F, WODB: -5F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 9,297 Btuh, Lat. gain:2,28481uh, Sen.loss: 18,098 Btuh, Entering clg. coilDB:78.3F, Entering clg. coilWB:63.1F, Entering htg. coilDB:56.9F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 455 CFM, Req. htg. airflow: 243 CFM Room No Name Htg Sens Btuh Htg CFM Run Duct Size Run Duct Vel clg Sens Btuh clg Lat clg CFM Act sys CFM Min Min Area SF Btuh Cooling System Summary Cooling Tons Sensible/Latent Split Sensible Btuh Latent Btuh Total Btuh Coryell Ranch Rev 2 Per RhvacOnline Alius Design Corps Garbondale, CO a Elite Sofiware Development, lnc. Coryell Ranch Rev 2 Per Page27 Equipment Data - System I - Great Room SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH48A182AA TPEFYPOs4MA144A Mitsubishi 207517167 54000 27600 O SEER Heating System Type: Model: Manufacturer: Capacity: Efficiency: Air Source Heat Pump NTXMSH48A182AA Mitsubishi 54000 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 87F, SOWB: 68F, WODB: -5F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gai Lat. gain:3,000 Btuh, Sen. loss: 45,425 Btuh, Entering clg. coilDB:76.6F, Entering clg. coilWB:62.3F, Entering htg. Clg. coilTD:20F, Htg. coilTD:70F, Req. clg. airflow: 1997 CFM, Req. htg. airflow:648 CFM n: 37,706 Btuh, coil DB:60.9F, Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO a Elite Software Development, lnc. Coryell Ranch Rev 2 Per Page28 Equipment Data - System 2 - Master Wing SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH36A142AA TPEADAO24I AA8OA, NTXDKS 1 2A112AA Mitsubishi 207517163 36000 32800 O SEER Heating System Type: Air Source Heat Pump Model: NTXMSH36A142AA Manufacturer: Mitsubishi Capacity: 45000 Efficiency: This system's equipment was selected in accordance with ACCA Manual S. ManualS equipment sizing data: SODB:87F, SOWB:68F, WODB:-5F, SIDB:75F, SIRH: 50%, WIDB: 70F, Sen. gain: 12,'198 Btuh, Lat. gain: 1,050 Btuh, Sen.loss: 18,727 Btuh, Entering clg. coilDB:76.8F, Entering clg. coilWB:62.4F, Entering htg. coilDB:61.9F, Clg. coilTD: 20F, Htg. coilTD: 70F, Req. clg. airflow: 638 CFM, Req. htg. airflow: 271 CFM Coryell Ranch Rev 2 Per Rhvac Online Alius Design Corps Carbondale, CO a Elite Sofuvare Development, Inc. Coryell Ranch Rev 2 Per Page 29 Equipment Data - System 3 - Guest Wing SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH36A142AA NTXDKSOgAll2AA Mitsubishi 207517163 36000 33200 O SEER Heating System Type: Model: Manufacturer: Capacity: Efficiency: Air Source Heat Pump NTXMSH364142AA Mitsubishi 45000 This system's equipment was selected in accordance with ACCA Manual S. ManualS equipment sizing data: SODB: 87E SOWB: 68F, WODB: -5F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 9,297 Btuh, Lat. gain: 2,2849tuh, Sen. loss: 18,098 Btuh, Entering clg. coilDB: 78.3F, Entering clg. coilWB:63.1F, Entering htg. coilDB:56.9E Clg. coilTD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 455 CFM, Req. htg. airflow: 243 CFM Coryell Ranch Rev 2 Per