Loading...
HomeMy WebLinkAboutDuct Test ReportRetrotec rCloud 1 Quality Assurance Report Iecc Duct Test PASS Your Result: 2.9 CFM/100 ft² (71 CFM * 100 / 2460 ft²) Target < 4 CFM/100 ft² Test Information Test Name puma paw duct test Test Date 2024-08-15 12:38 PM (MDT) Export id DR1N9PAB Company Name Elite Energy Concepts Technician Name Coltan Gechter Technician Email coltan@eliteenergyconcepts.com Building Information Address 1793 County Rd 219, Puma Paw ranch house City Rifle State CO Zip/postal Code 81650 Country United States Year Constructed Not available Elevation 5200 ft Address Verified?No Building Latitude, Longitude Your location has not been validated. GPS validation Latitude/Longitude: 39.669363, -107.786469; Accuracy: 16 ft Estimated Distance From Address Not available Test Equipment Fan Model Retrotec 300 Fan Serial Number 3XLFT00701 Pressure Gauge Model Retrotec DM32 10A Gauge Serial Number 415340 Environmental Conditions Pre-test Indoor Temperature 75 °F Pre-test Outdoor Temperature 75 °F Wind Speed Unknown Average Barometric Pressure 100 kPa Test Dimensions Conditioned Floor Area 2460 ft² Volume 28000 ft³ Retrotec rCloud 2 Test Results Summary Test Type Iecc Duct Test Flow Reference Pressure 25 Pa Time Averaging 10 seconds Induced Duct Pressure (includes baseline)-24.35 Pa Nominal Fan Flow 70.94 CFM @ 25 Pa Test Results Test Data Set 1 Flow Direction Depressurize Gauge Location Outside Measured Pressure (Pa)-24.35 Fan Pressure [300 - 74] (Pa)93.47 Flow (CFM)69.83 Retrotec rCloud 3 Test Notes No notes entered. Flow Equation Parameters - Factory Default Fan Model Retrotec 300 Fan Serial Number 3XLFT00701 Flow Equation Parameters - B1 Units Used For Flow Parameters in Equation CFM Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated by subtracting the measured room pressure from the absolute value of the fan pressure. If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA If PrA is less than 0 or fan is self-referencing: FP = PrB Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|) FP = fan pressure, RP = room pressure Range N K K1 K2 K3 K4 MF Open 0.5010 28.9100 0.0000 0.4000 0.0000 1 20 74 0.5045 7.0770 0.0000 0.2500 0.0000 1 15 47 0.5000 3.2410 0.0000 0.1000 0.0000 1 10 29 0.5020 1.1900 0.0000 0.2000 0.0000 1 20 18 0.4990 0.4570 0.0000 0.2500 0.0000 1 25 11 0.4800 0.2080 0.0000 0.2500 0.0000 1 25 7 0.5000 0.0718 0.0000 0.1100 0.0000 1 25 102 0.5900 10.7000 0.0000 0.4000 0.0000 1 100 flow = (FP - RP x K1)n x (K + K3 x FP) x K4