Quality Assurance Report
Iecc Duct Test
PASS Your Result: 2.9 CFM/100 ft² (71 CFM * 100 / 2460 ft²)
Target < 4 CFM/100 ft²
Test Information
Test Name puma paw duct test
Test Date 2024-08-15 12:38 PM (MDT)
Export id DR1N9PAB
Company Name Elite Energy Concepts
Technician Name Coltan Gechter
Technician Email coltan@eliteenergyconcepts.com
Building Information
Address 1793 County Rd 219, Puma Paw ranch house
City Rifle
State CO
Zip/postal Code 81650
Country United States
Year Constructed Not available
Elevation 5200 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Latitude/Longitude: 39.669363, -107.786469;
Accuracy: 16 ft
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 300
Fan Serial Number 3XLFT00701
Pressure Gauge Model Retrotec DM32 10A
Gauge Serial Number 415340
Environmental Conditions
Pre-test Indoor Temperature 75 °F
Pre-test Outdoor Temperature 75 °F
Wind Speed Unknown
Average Barometric Pressure 100 kPa
Test Dimensions
Conditioned Floor Area 2460 ft²
Volume 28000 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Iecc Duct Test
Flow Reference Pressure 25 Pa
Time Averaging 10 seconds
Induced Duct Pressure (includes baseline)-24.35 Pa
Nominal Fan Flow 70.94 CFM @ 25 Pa
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Outside
Measured Pressure (Pa)-24.35
Fan Pressure [300 - 74] (Pa)93.47
Flow (CFM)69.83
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Factory Default
Fan Model Retrotec 300
Fan Serial Number 3XLFT00701
Flow Equation Parameters - B1
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.5010 28.9100 0.0000 0.4000 0.0000 1 20
74 0.5045 7.0770 0.0000 0.2500 0.0000 1 15
47 0.5000 3.2410 0.0000 0.1000 0.0000 1 10
29 0.5020 1.1900 0.0000 0.2000 0.0000 1 20
18 0.4990 0.4570 0.0000 0.2500 0.0000 1 25
11 0.4800 0.2080 0.0000 0.2500 0.0000 1 25
7 0.5000 0.0718 0.0000 0.1100 0.0000 1 25
102 0.5900 10.7000 0.0000 0.4000 0.0000 1 100
flow = (FP - RP x K1)n x (K + K3 x FP) x K4