Date of Test: 3/27/2025
Customer: RAM Development, Inc.
12370 Highway 82
Carbondale, CO 81623
Phone: 970-987-1569
Email: bobby@ramdev.build
Website: ramdev.build
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve
4. Test Settings:
5. Accuracy Level
Infiltration Estimates
BUILDING LEAKAGE TEST
Frostbusters & Coolth Co.
PO Box 94
Basalt, CO 81621
Email: fritzd@frostbusters.com Website: frostbusters.com
Test File: 12730 Hwy 82 - Blower Door Test 3-27-2025
Technician: Fritz Diether
Project Number: Final Blower Door Test
Building Address: Almazan ADU/Garage
12370 Highway 82
Carbondale, CO 81623
1001 CFM50 (+/- 0.6 %)
3.44 ACH50
55.1 in2 LBL E12* @ 4 Pa
Flow Coefficient ( ) = 96.3 ( +/- 3.4 %)
Exponent (n) = 0.5 8 ( +/- 0.010 )
Correlation Coefficie t = 0.99981
Test Standard: RESN T Multi -Point Test
Test Mode: Depressuri ti-
Standard Level of Accurac Test
1. Estimated Average Annual Infiltration Rate: 56.7 CFM
0.19 ACH
18.9 CFM
2. Estimated Design Infiltration Rate: Winter: 105.6 CFM
0.36 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate:
Base Rate:
37.4 CFM
37.4 CFM
From the 2021 IECC:
Exception: When testing individual dwelling
units, an air leakage rate not exceeding
0.30 cubic feet per minute per square
foot [0.008 m3/(s x m2)] of the dwelling unit
enclosure area, tested in accordance with
ANSI/RESNET/ICC 380, ASTM E779 or
ASTM E1827 and reported at a pressure of
0.2 inch w.g. (50 Pa), shall be permitted in
all climate zones for:
1. Attached single and multiple- family
building dwelling units.
2. Buildings or dwelling units that are
1,500 square feet (139.4 m2) or smaller.
Results:
1,001 CFM/ 5,394 Sq Ft Surface
Area = .19 CFM/Sq Ft.
I I Building Passes.
From the 2018 IECC: R402.4.1.2 Testing.
The building or dwelling unit shall be tested
and verified as having an air leakage rate
not exceeding (3.00 ACH50) three air
changes per hour in Climate Zones 3
through 8. Testing shall be conducted in
accordance with RESNET/ICC 380, ASTM
E779 or ASTM E1827 and reported at a
pressure of 0.2 inch w.g. (50 Pascals).
Where required by the code official, testing
shall be conducted by an approved third
party. A written report of the results of the
test shall be signed by the party conducting
the test and provided to the code official.
Testing shall be performed at any time after
creation of all penetrations of the building
thermal envelope.
Building is at 3.44 ACH50.
BUILDING LEAKAGE TEST Page 2 of 4
COOLSH
Date of Test: 3/27/2025 Test File: 12730 Hwy 82 - Blower Door Test 3-27-2025
Building Information
Volume
17477
Surface Area
5394
Floor Area
1489
Height
24
# of Bedrooms
2
# of Occupants
3
Year of Construction
2025
Wind Shield
E
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Location Climate Information
Ventilation Weather Factor
0.80
Energy Climate Factor
19.00
Heating Degree Days
9000
Cooling Degree Days
28
Design Winter Wind Speed
1.6 mph
Design Summer Wind Speed
10.9 mph
Design Winter Temp Diff
77 deg F
Design Summer Temp Diff
11 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
-
Micromanometer
Energy Conservatory
DG700
p9S S UST
44��v
�V
o. BUILDING LEAKAGE TEST Page 3 of 4
cool
Date of Test: 3/27/2025 Test File: 12730 Hwy 82 - Blower Door Test 3-27-2025
Depressurization Test:
Environmental Data
Indoor Temperature (OF)
Outdoor Temperature (OF)
Altitude (ft)
74.0
51.0
6155.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan
Building Pressure Building Pressure Pressure
(Pa) (Pa) (Pa)
-0.5
n/a
n/a
-60.0
-59.3
38.0
-55.0
-54.3
34.0
-50.0
-49.3
30.0
-45.0
-44.3
26.0
-40.0
-39.3
219.0
-35.0
-34.3
185.0
-30.0
-29.3
155.0
-25.0
-24.3
124.0
-20.0
-19.3
91.0
-15.0
-14.3
64.0
-0.9
n/a
n/a
Time Averaging Period: 10
None
Nominal Adjusted
Flow Flow Fan
(cfm) (cfm) % Error Configuration
1120
1111
0.2
Ring A
1061
1052
0.0
Ring A
998
990
-0.3
Ring A
931
923
-0.9
Ring A
876
869
0.3
Ring B
806
799
0.0
Ring B
738
732
0.7
Ring B
661
656
0.8
Ring B
567
562
-0.7
Ring B
476
472
-0.2
Ring B
Deviations from Standard RESNET Multi -Point Test - Test Parameters
BUILDING LEAKAGE TEST Page 4 of 4
COOL-O
Date of Test: 3/27/2025 Test File: 12730 Hwy 82 - Blower Door Test 3-27-2025
Comments
None