About
Heat Calcs
Manual S Gompliance Report Kitchen AHU Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Rosstla Project lnformation For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Gonditions Outdoor design DB: Outdoor design WB: lndoor design DB: lndoor RH: 93.0'F 58.4'F 75.0'F 50o/o Sensible gain: Latent gain: Totalgain: Estimated airflow: 19413 0 19413 1000 Btuh Btuh Btuh cfm Entering coil DB: Entering coilWB: 79.9'F 62.6"F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split AC Manufacturer: Lennox Model: ML14KC1-030-230A**+CK40DT-30/36C-01 Actualairflow: 1000 cfm Sensible capacity: 18480 Btuh 95% of load Latent capacity: 7920 Btuh 0% of load Total capacity: 26400 Btuh 136% of load SHR: 70% Heating Equipment Design Gonditions Outdoor design DB: lndoor design DB: Heat loss 40058 Btuh Model: ML1 93DF070XE36B-* 113/o of load EnteringcoilDB: 68.0'F Temp. rise:54 "F -1 6'F 72.O"F Manufacturer's Performance Data at Actual Design Gonditions Equipment type: Manufacturer: Actual airflow: Output capacity: Gas furnace Lennox 1000 cfm 45421 Btuh Meets all requirements of ACCA Manual S. tl*,ry:tgltgg*' *,sn."uo" universar 202s 23.0.E5RSU60560 2025-Mar-24 12:20:45 Page 1.g ./ECh.WlProject\3o3o Elk Springs Dr.rup Calc = MJA Front Door faces: S Srlb|lrllrllr Manual S Compliance Report MasterlBeds AHU Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Ross rn+nn Project lnformation For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Gooling Equipment Design Gonditions Outdoor design DB: Outdoor design WB: lndoor design DB: lndoor RH: 93.0"F 58.4'F 75.0'F 50% Sensible gain: Latent gain: Totalgain: Estimated airflow: 20838 0 20838 1 000 Btuh Btuh Btuh cfm Entering coil DB: Entering coilWB 81.4'F 62.7"F Manufacturer's Performance Data at Actual Design Gonditions Equipment type: Split AC Manufacturer: LennoxActualairflow: 1000 Sensiblecapacity: 18480 Latent capacity: 7920 Totalcapacity: 26400 Model: ML't4KC1 -030-230A**+CK40DT-30/36C-01 cfm Btuh Btuh Btuh 89% of load 0% of load 127% of load SHR: 70% Heating Equipment Design Gonditions Outdoor design DB: lndoor design DB: Entering coil DB: 63.9'F Temp. rise 55 "F Heat loss 45576 Btuh Model: MLI 93DF070XE36B-* 102'/o of load -16'F 72.0"F Manufacturer's Performance Data at Actual Design Gonditions Equipment type: Manufacturer: Actual airflow: Output capacity: Gas furnace Lennox 1000 cfm 46649 Btuh Meets all requirements of ACCA Manual S. "rl* wrlghtrrrtt*Right-Suite@ U niversal 2023 23.0.05 RSU60560 2025-Mar-24 12:20:45,g,/ffi,WlProject\3O30 Elk Springs Dr.rup Calc = MJ8 Front Door faces: S Page 2 Gomponent Gonstructions Entire House Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Ross tm0 ct lnformationPro For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Conditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40'N Outdoor: Drybulb ('F) Dailyrange ('F) Wetbulb ("F) Wind speed (mph) Gooling 93 34 (H ) 58 7.5 Indoor: lndoor temperature ('F) Design TD ('F) Relative humidity (%) Moisture difference (gr/lb) Infiltration: Method Construction quality Fireplaces Heati 72 88 30 43.1 Simplified Average 1 (Average) Gooling 75 18 50 -44.5 ng Heating ,16 15.0 Gonstruction descriptions Walls 12F-0sw: Frm wall, vnl ext, 1/2" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions 12F-0sw: Frm wall, 112" gyp.bd ext, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Windows 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1i8" thk; NFRC rated (SHGC=0.32);4.5 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1/8" thk; NFRC rated (SHGC=0.32); B ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 118" thk; NFRC rated (SHGC=0.32);7 ft head ht Or Area U-value Btuh/fl4"F lnsul R ffrF/Btuhtr Htg HTM Btuhff Loss Glg HTM Gain n e s all 986 1197 680 1 165 4029 0.065 0.065 0.065 0.065 0.065 21.0 21.0 21.0 21 .0 21 .0 5.46 4.73 2.92 4.41 4.51 5385 5661 1 987 5137 18170 o.71 0.62 0.38 0.57 0.59 Btuh Btuhlff' 21 .0 5.72 2059 0.26 95 Btuh 701 737 259 668 2364 360 0.065 4A4-2ow'.2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/8" thk; NFRC rated (SHGC=O.32)', 14.58 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1i8" thk; NFRC rated (SHGC=0.32); 17.42 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/8" thk; NFRC rated (SHGC=0.321; 11.92 ft head ht Boldlltalic values have been manually overildden n e all n n e S S s all n s all n s all n s all s 15 15 31 96 96 28 24 94 192 35 565 12 't4 12 38 25 25 50 36 36 73 11 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 0 18.1 26.4 26.4 26.4 26.4 26.4 26.4 26.4 403 403 805 2534 2534 739 634 2482 5069 924 14916 317 370 0 686 660 660 1320 959 959 1918 284 11.6 35.6 23.6 11.6 11.6 35.6 12.9 18.4 18.4 35.6 17.8 11.6 18.4 0 10.4 11.6 18.4 15.0 11.6 18.4 15.0 18.4 177 543 720 1 114 1114 997 308 1726 3525 1247 10032 139 257 0 396 290 459 749 422 667 1 089 't97 'l* y:lerg--tt"Rig ht-Su ite@ U niv ersal 2023 23.O.05 RSU60560 2025-Mat-24 12:2Q:45,€,frft WlProject\303o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S Page 1 444-2ow'.2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=O.32\;14.17 ft head ht 444-2ow'.2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); 15.33 ft head ht 4A4-2ow: 2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); 16.33 ft head ht 444-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); 18.08 ft head ht 444-2ow'.2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 'l18" thk; NFRC rated (SHGC=0.32); 20.83 ft head ht Doors 11D0: Door, wd sc type Gelllngs 17B-34m1: Rf/clg ceiling, mtl roof mat, wd cons, 5" thkns, r-50 ceil ins 18A-38md: Rficlg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 10" thkns, r-50 ceil ins Floors 19D-30cstp: Flr floor, lrmflr, 12" thkns, r-5 ext ins, r-30 cav ins, tight crwl ovr, r-19 wall insul 214-201: Bg floor, light dry soil, 2' depth 18 28 24 39 50 32 1293 3187 3132 1121 0.300 0-300 0.300 0.300 0.300 0.390 0.027 0.029 0.034 o.o27 26.4 26.4 26.4 26.4 26.4 2.38 1.65 462 739 634 1 030 1 320 18.4 18.4 18.4 18.4 18.4 321 514 441 716 918 459 1 087 0 0 0 0 0 s 0 34.3 1098 8.83 283 34.0 38.0 49.0 3073 5272 0.36 0.34 1.05 3273 0.21 669 0 0 00 0 Bold/italic values have been manually overridden d* w.$-",:.'g--::'Right-Suile@ U niversal 2023 23.0.05 RSU60560 2O25-Mat-24 12:20:45 Page 2A.6cL WlProject\3o3o Elk Springs Dr.rup Calc = MJB Front Door faces: S Gomponent Gonstructions Master/Beds AHU Job: Date: By: 3030 Elk Springs Drive March24,2O25 lsaac RossTI|flr0 ect lnformationPro For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Desi n Conditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ('F) Wet bulb ('F) Wind speed (mph) lndoor: lndoor temperafure ('F) Design TD fF) Relative humidity (%) Moisture difference (gr/lb) Infiltration: Method Construction quality Fireplaces Heati 72 88 30 43.1 Simplified Average 1 (Average) Cooling 75 18 50 -44.5 ng Heating -16 15.0 9334 (H ) 58 7.5 lingGoo Construction descriptions Walls 12F-0sw: Frm wall, vnl ext, 1/2" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions 12F-0sw: Frm wall, 112" gyp.bd exl, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Windows 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/8" thK NFRC rated (SHGC=0.32); 8 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/8" thk; NFRC rated (SHGC=0.32\;7 ft head ht 4A4-2ow'.2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/8" thk; NFRC rated (SHGC=0.32\; 11.92 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=O.32);14.17 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr, 114" gap, 1/B" thk; NFRC rated (SHGC=0.32); 16.33 ft head ht Doors (none) Or Area U-value Btuhifl'z-"F 360 0.065 18 0.300 24 0.300 Bold/italic values have been manually overridden lnsul R Htg HTM Loss Clg HTM Gain ft4'F/I}tuh Btuh/ff'Btuh Btuh/fr"Btuhtr n e S all 565 269 193 424 1451 0.065 0.065 0.065 0.065 0.065 21.0 21.O 21.0 21.0 21.O 5.72 5.72 5.72 5.72 5.72 0.74 0.74 0.74 0.74 o.74 3232 1 539 1 "103 2425 8298 421 200 't43 316 '1080 650 1114 997 308 1 138 1763 1247 7218 139 257 396 197 21.O 5.72 2059 0.26 95 n n e s s S all n s all S 56 96 28 24 62 96 35 397 12 14 26 't1 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 1478 2534 739 634 1 637 2534 924 1 0481 317 370 686 284 0 0 0 0 0 0 0 0 0 0 0 0 11.6 11.6 35.6 12.9 '18.4 18.4 35.6 18.2 11.6 18.4 't5.2 18.4 0 26.4 462 18.4 321 0 26.4 634 ',18.4 441 {* y-rgrgt-..*- R is ht-su ire@ u niv ersat 20 23 2s. o. 05 RSU 6 0560 2025-Mat-24 12:20:45 Page 3,g,#cr,WlProject\3o30 EIk Springs Dr.rup Calc = MJ8 Front Door faces: S Ceilings 18A38md: Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 1 0" thkns, r-50 ceil ins Floors 'l 9D-30cstp: Flr floor, frm nr, 12" thkns, r-5 ext ins, r-30 cav ins, tight crwl ovr, r-19 wall insul 2051 0.029 2051 0.034 Boldlltallc values have been manually overrldden 38.0 49.0 2.55 5234 0.53 1080 1.05 2't43 A.21 438 t{* :gltg**3g Rishr-suite@ universat 2020 23.0.0s RSU60560 2O25-Ma.-24 12:20i45 Page 4.&..€cr,WlProject\3030 Elk Spdngs Dr.rup Calc = MJ8 Front Door faces: S fnllrLl|lfdIril Com ponent Gonstructions Kitchen AHU Job: Date: By: 3030 Elk Springs Drive March24,2025 lsaac Ross 2n+rn0 ect lnformationP For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Conditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40"N Outdoor: Drybulb ('F) Dailyrange ('F) Wetbulb ('F) Wind speed (mph) Heating -16 15.0 Gooling 93 34 (H 58 7.5 Indoor: lndoor temperafure ('F) Design TD fF) Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 72 88 30 43.1 Simplified Average 1 (Average) Gooling 75 18 50 -44.5 Gonstruction descriptions Walls '12F-0sw: Frm wall, vnl ext, 1/2" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, '16" o.c. stud Partitions (none) Windows 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1/8" thk; NFRC rated (SHGC=O .32): 4.5 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 118" thk; NFRC rated (SHGC=0.32); B ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,'114" sap, 1/8" thk; NFRC rated (SHGC=0.321;14.58 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1/8" thk; NFRC rated (SHGC=0.32\;17.42 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1/8" thk; NFRC rated (SHGC=0.32); 15.33 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,114" gap, 1/8" thk; NFRC rated (SHGC=0.32); 18.08 ft head ht 4A4-2ow:2 glazing, clr outr, air gas, wd frm mat, clr low-e innr,'114" gap, 1/8" thk; NFRC rated (SHGC=O.32);20.83 ft head ht Doors '1 1D0: Door, wd sc type Or Area U-value tr Bluh/tr-"F 0.300 0.300 s 32 0.390 Boldlitalic values have heen manually overridden lnsul R ffr F/Btuh Htg HTM Loss Glg HTM Gain Btuh/fr'Btuh Btuh/fr"Btuh n e s al 376 721 155 474 1726 0.065 0.065 0.065 0.065 0.065 21 .0 21 .0 21 .O 21 .0 21.0 5.72 5.72 5.72 5-72 5.72 0.74 0.74 0.74 o.74 o.74 280 536 115 353 1284 2153 4123 885 2711 9872 n e all n S s all n S all n S all s 15 't5 31 40 32 96 168 25 25 50 36 Jb 73 28 39 50 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 26.4 403 403 805 '1056 845 2534 4435 660 660 1320 959 959 1918 739 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.6 35.6 23.6 11.6 18.4 18.4 16.8 'l 1.6 18.4 15.0 11.6 18.4 15.0 18.4 177 543 720 464 588 't763 2814 290 459 749 422 667 '1089 514 0 0 26.4 1030 18.4 716 26.4 1320 18.4 918 34.3 1098 8.83 283 dl:"ffleljlst!'Right-Suite@ U niversal 2023 23.0.05 RSU60560 2025-Mar-24 12:20:45 Page 5,+,rcch,WlProject\3o3o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S Geilings 178-34m1: Rflclg ceiling, mtl roof mat, wd cons, 5" thkns, r-50 ceil ins 'l8A-38md: Rf/clg ceiling, mtl roof mat, frm cons,5/8" gypsum board int fnsh, 10" thkns, r-50 ceil ins Floors 19D-30cstp: Flr floor, frm flr, 12" thkns, r-5 ext ins, r-30 cav ins, tight crwl ovr,,r-19 wall insul 1293 0.027 0.02915 1081 0.034 Boldlltalic values have been manually overrtdden 34.0 38.0 49.0 2.38 2.55 3073 38 0.36 0.53 459 8 1.05 1130 0.21 231 tt* HrHS*:*gf Rig ht-Su ite@ [J niv ersal 20 23 23. 0.05 RSU6 0560 2O25-MaF24'12:2Oi45 Page 6^&'WlProiect\3o3o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S ml--HHXil.lttI Project Summary Entire House Job: 3030 Elk Springs Drive Date: March 24,2025By: lsaac Ross ect lnformationPro For:303 303 0 Elk Springs 0 Elk Springs rive rive Boulder Construction Services Glenwood Springs, CO 81601 D D Notes: n lnformationDesi Outside db lnside db Design TD Structure 93 'F75 "F18'F H 50 Yo-44 grllb 29103 Btuh 7277 Btuh 458 Btuh Ducts (R-6.0) Central vent (60 cfm) Humidification Pioino Eriuip.-ment load Method Construction quality Fireplaces Area (ft'?) Volume (ff) Air changes/hour Equiv. AVF (cfm) Structure Ducts (R-6.0) Central vent (60 cfm) Blower Use manufacturer's data Rate/swino multiolier Equipmeni sensible load Structure Ducts Centralvent (60 cfm) Equipment latent load Weather: Winter Design Gonditions Rifle Garfield County AP, CO, US Outside db lnside db Desion TD Daily-range Relative humidity Moisture difference Summer Design Conditions Heating Summary -16'F72 'F 88 "F 71349 Btuh 12047 Btuh 2238 Btuh Sensible Cooling Equipment Load Sizing 0 0 Btuh Btuh Btuh 0 Btuh n 0.98 36101 Btuh -941 Btuh -696 Btuh -699 Btuh 85634 lnfiltration Simplified Average 1 (Average) Coolinq3rcr 36761 0.15 92 Latent Cooling Equipment Load Sizing Make Trade Model AHR|ref Heating Equipment Summary nla nla nla nla 0 Btuh Equipment Total Load (Sen+Lat) 36101 Btuh Req. total capacity at 0.70 SHR 4.3 ton Gooling Equipment Summary Make nlaTrade nlaCond nlaCoil nla AHRI ref nla Efficiency Sensible cooling Latent cooling Total coolino Actual air flow Air flow factor Static pressure Load sensible heat ratio Heating 3132 36761 0.31 192 nla 0 Btuh0'F0 cfm0 cfm/Btuh0 in H2O Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat tn nla 0 0 0 0 0 0 0 nla Btu Btu Btu cfm h h h oH2 cfm/Btuh Boldlltailc values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed {* y":Lg".tt-*::. jT R is ht-su ite@ u niv ersat 20 23 zs . o. oE RSU 6 0560 2025-Mat-24 12:20:45 Page 1.e-,4ccl,WlProject\303O Elk Springs Dr.rup Calc = MJB Front Door faces: S rr*tr-aHH tt+1ft0 Project Summary Kitchen AHU Job: 3030 Elk Springs Drive Date: March 24,2025By: lsaac Ross ect lnformationPro For: Notes: 3030 Er 3030 Er k Sorinos Drive. Boulder Construction Services k Silrinls Drive, Glenwood Springs, CO 81601 Desi n lnformation Outside db lnside db Design TD Structure Ducts (R-6.0) Central vent (0 cfm) (none) Humidification Piping Equipment load Method Construction quality Fireplaces 34391 Btuh 5667 Btuh0 Btuh Weather: Winter Design Gonditions Heating Summary Rifle Garfield County AP, CO, US Outside db lnside db Desion TD Daily"range Relative humiditv Moisture differerice Summer Design Conditions Btuh Btuh Btuh -16 "F72 'F 88 'F 93 'F75 "F 18 "F H50%-44 grllb 14300 Btuh 3406 Btuh0 Btuh 1707 Btuh n U.YO 19024 Btuh Heating Equipment Summary Lennox LENNOX ML1 93DFO7OXE36B-- Sensible Cooling Equipment Load Sizing Structure Ducts (R-6.0) Centra'l vent (0 cfm) (none) Blower Use manufacturer's data Rate/swino multioiier Equipmenl sensible load Latent Gooling Equipment Load Sizing Structure -741 BtuhDucts -284 Btuh Centralvent (0 cfm) 0 Btuh (none) Equiprneirt latent load 0 Btuh Equipment Total Load (Sen+Lat) 19024 Btuh Req. totalcapacity at 0.70 SHR 2.3 ton Gooling Equipment Summary Make LennoxTrade LENNOXCond ML14KC1-030-230A**Coil CK40DT-30/36C-01 AHRI refEfficiency 12.5 EER2,14.5 SEER2 Sensibie cooiing 'i8480 Biuh Latent cooling 7920 Btuh Total coolino 26400 Btuh Actual airfldw 1000 cfm Air flow factor 0.056 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 1.00 0 0 40058 lnfiltration Simplified Averaoe 1 (Averag-e) Aea (ft'?) Volume (ff) Air chan!e's/hour Equiv. AVF (cfm) Heating 1 081 1 8302 0.33 102 t%'f.'n 1 8302 0.16 49 Make Trade Model AHRI ref Efficiency Heaiing inpui Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 93 AFUE 66000 Biuh 45421 Btuh 54 "F 1000 cfm 0.025 cfm/Btuh0 in H2O Bold/ltallc valu* have been manually overrldden Calculations approved by ACCA to meet all requirements of Manual J Bth Ed 4{} rarrlaht3oft-*=*-*-.- j -.- Right-Suite@ U niversal 2023 23.0.05 RSU60560 2O25-Mat-24 12:20:45 ,&,,WlProject\3o3o Elk Sprihgs Dr.rup Calc = MJ8 Front Door faces: S Page 2 **arts-HH 1[G11t[ Project Summary Master/Beds AHU Job: 3030 Elk Springs Drive Date: March 24,2025By: lsaac Ross For: Notes: 3030 Erk 3030 Erk Sorinos Drive. Boulder Construction Services Sjlrinls Drive, Glenwood Springs, CO 81601 Outside db lnside db Design TD Structure Ducts (R-6.0) centrit venf lsER=s|% 6o cfm) Energy recovery Humidification Piping Equipment load lnfiltration Method Construction quality Fireplaces Weather: Winter Design Gonditions Heating Summary 93 'F75 "F 18 'F H 50%-44 grllb -16 "F72 'Fg8 "F Rifle Garfield County AP, CO, US Summer Design Conditions Outside db lnside db Desion TD Daily-range Relative humidity Moisture difference Sensible Cooling Equipment Load Sizing Structure Ducts (R-6.0) centrit veni lsER=s0% 60 cfm) Energy recovery Blower Use manufacturer's data 36958 Btuh 6380 Btuh 2238 Btuh 14803 Btuh 3871 Btuh 458 Btuh 1707 Btuh n 0.98 20421 Btuh 20421 Btuh 2.4 ton 0 Btuh0 Btuh 45576 Btuh Heating Equipment Summary Lennox LENNOX ML1 93DFO7OXE36B-* Rate/swino multiolier Equipmeni sensible load Latent Cooling Equipment Load Sizing Structure -200 BtuhDucts -412 Btuh Central vent (LER=50% 60 cfm) -699 Btuh Enerov recoveru Equipme-ni latent loSd 0 Btuh Equipment Total Load (Sen+Lat) Req. total capacity at 0.70 SHR Cooling Equipment Summary Make LennoxTrade LENNOXCond ML14KC1-030-230A**Coil CK40DT-30/36C-01 AHRIrefEfficiency 11.5 EER2,13.8 SEER2 Sensible coolino 18480 Btuh Latent cooling ' 7920 Btuh Total coolino 26400 Btuh Actual air fldw 1000 cfm Air flow factor 0.054 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 1.00 Simplified Average 1 (Average) Heatinq 205r 18459 0.29 90 Coolino 2051- 1 8459 0.14 43 Aea (ft'z) Volume (ff) Air changes/hour Equiv. AVF (cfm) Make Trade Model AHR|ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 93 AFUE 66000 Btuh 46649 Btuh 55 'F 1000 cfm 0.023 cfm/Btuh0 in H2O Boldlttalic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed *:r*f-p3s=eg Right-Su ite@ U niversal 2023 23.0.05 RSU60560 2O25-Mat-24 12:20:45 Page 3-3 ,4CCf,.WlProject\3o3o Elk Springs Dr.rup Calc = MJB Front Door faces: S JiilFm fi|rrthr-l-Hrll AED Assessment Entire House Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Ross 2E+tft0 Project lnformation For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Gonditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40"N Outdoor: Drybulb ("F) Dailyrange ('F) Wetbulb ('F) Wind speed (mph) lndoor: lndoor temperature ("F) Design TD ('F) Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Heati ng Cooling 75 18 50 -44.5lingCoo 72 88 30 43.1Heating -16 15.0 93 34 (H ) 58 7.5 Test for Adequate Exposure Divers FhrlycdrgLcrl 26,000 0 I turdDay / EDlimit Maximum hourly glazing load exceeds average by 39.0%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1869 Btuh (PFG - 1.3*AFG) Boldlitalic values have been manually overridden dl rarlolrttoft'' .-,-',-i"'*+. <q Rightsuite@ Universal 202323.O.O5 RSU60560 2025-Mab24 12:20:45 ,&..WlProiect\3os0 Elk Springs Dr.rup Calc = MJB Front Door faces: S Page 1 Jilroffi# trltrl-tr-lhll AED Assessment Kitchen AHU Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Ross ffi+ilI0 ect lnformationPro For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Conditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40"N Outdoor: Drybulb ("F) Dailyrange ("F) Wetbulb ('F) Wind speed (mph) Indoor: lndoor temperature ('F) Design TD fF) Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Heati ng Cooling 75 18 50 -44.5 72 88 30 43.1Heating -16 15.0 Cooling 93 34 (H ) 58 7.5 Test for Ade uate E osure Divers 14, 12, 10, FhnyGdrBLd tlourofDay 0 4 / AEO limit Maximum hourly glazing load exceeds average by 42.7%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1307 Btuh (PFG - 1.3*AFG) Boldlitalic values have been manually overrldden {} H:t-fp,llg:" 11" Ris hrsu ire@ u niv er sar 20 2z 23. o. oi R SU 6 0s60 2025-Mat-24 12:20:45 Page 2^+,lcc|\WlProject3o30 Elk Springs Dr.rup Calc = MJA Front Door faces: S lnll.lltr-ntIl AED Assessment Master/Beds AHU Job: 3030 Elk Springs Drive Date: March 24,2025 By: lsaac Ross 2E&tfl0 Project lnformation For:3030 Elk Springs Drive, Boulder Construction Services 3030 Elk Springs Drive, Glenwood Springs, CO 81601 Design Conditions Location: Rifle Garfield County AP, CO, US Elevation: 7035 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) Wet bulb ("F) Wind speed (mph) ingGool lndoor: lndoor temperafure ("F) Design TD CF) Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Heating 72 88 30 43.1 Gooling 75 18 50 -44.5Heating -16 15.0 93 34 (H ) 5B 7.5 Test for Ade uate Ex ure Divers 0 FttrlyGairgLod HdrcfDay 48 I / GDllhlt Maximum hourly glazing load exceeds average by 35.3%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 562 Btuh (PFG - 1.3*AFG) Boldlltatlc values have been manually overridden d* :gf-g.l'3'*--$*Righfsuite@ U niversal 2023 23.0.05 RSU60560 2o25-Mat-24 12:20i45.& ,{CCl'WlProject\3o3o Elk Springs Dr.rup Calc = MJB Front Door faces: S Page 3 JilE6*' rhllLlrhbln}flI0 Right-J@ Worksheet Entire House Job: Date By: 3030 Elk Springs Drive March24,2025 lsaac Ross 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 448.0 ft 11.0 fr 4253.0 ft2 Kitchen AHU 98.0 fr 16.9 ft 1081.0 fr Ty Construction number U-value (Bt uh/f ta'F Or HTM (Bt uh/ft') Area (ft')or perimeter (ft) Load (Bluh) Area (fr)or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1 1 WL--ct^ t----€ L----6L-€l-"c Wl_ctc Wt^rut-G l-----c L-----c l-----G l------c l-----cl+l-cl-Gl+l-Gl-D Wt^t-Ltt^ P c F F 12F-osw 444-2ow 4A.4-2ow 444-2ow 444-2ow 444-2ow 4A4-zowd 1 2F-0sw 444-2ow 444-2ow 12F-osw 1oD-w 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 4A'4-2ow 4A'4-2ow 4A.4-2ow 444-2ow 444-2ow 444-2owd 11D0 12F-0sw 444-2ow 444-2ow 12F-osw 178-34m1 18A-38md 1 9D-30cstp 214-20t 0.065 0.300 0.300 0.300 0.300 0-300 0.300 0.065 0.300 0.300 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.390 0.065 0.300 0.300 0.065 0.027 0.029 0.034 o.o27 5.46 26.40 26.40 26.40 26.40 26.40 26.40 4.73 26.40 26.40 2.92 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 34.32 4.41 26.40 0.00 5.72 2.38 1.65 1.05 0.00 o.7'l 11.61 11.61 11.61 11.61 'I 1.61 1'1.61 0.62 35.62 35.62 0.38 12.85 '18.36 18.36 18.36 18.36 '18.36 18.36 18.36 18.36 18.36 18.36 18.36 8.83 0.57 35.62 0.00 o.26 0.36 0.34 o.21 0.00 1267 15 96 '12 25 36 96 1240 15 28 1267 24 94 11 14 18 25 28 24 36 20 50 192 32 121? 35 12 360 1293 3187 3132 1121 986 0 0 0 0 0 0 1't97 0 0 680 0 0 0 0 0 0 0 0 0 0 0 0 32 1 165 0 0 360 1293 31 87 3132 1121 5385 403 2534 317 660 959 2534 5661 403 739 1987 634 2482 284 370 462 660 739 634 959 1 030 1 320 5069 1 098 5137 924 0 2059 3073 5272 3273 0 701 177 111t 139 290 422 111t 737 543 997 259 308 1726 197 257 321 459 5'14 441 667 716 918 3525 283 668 1247 0 OE 459 1087 669 0 493 15 40 0 25 36 0 736 15 0 493 0 32 0 0 0 25 28 0 36 39 50 96 32 474 0 0 0 1293 15 1 081 0 376 0 0 0 0 0 0 721 0 0 155 0 0 0 0 0 0 0 0 0 0 0 0 32 474 0 0 0 1293 15 1 081 0 2153 403 1 056 0 660 959 0 4123 403 0 885 0 845 0 0 0 660 739 0 959 1030 1320 2534 1 098 2711 0 0 0 3073 38 1 130 0 280 177 464 U 290 422 0 536 543 0 1'15 0 588 0 0 0 459 514 0 667 716 918 1763 283 353 0 0 0 459 d 231 0 6 c) AED excursion 1 869 1307 Envelope loss/gain 57061 22920 26779 1 1093 12 a) lnflltralion b) Room ventilation 14289 0 1402 0 7612 0 747 0 13 lnlernal gains:Occupants @ Appliances/other 230 6 1380 3400 2 460 2000 Sublotal (lines 6 to 1 3)71349 291 03 34391 14300 1 1 4 5 Less external load Less transfer Redistribution Subtotal Duct loads 17%25% 0 0 0 71349 12047 0 0 0 291 03 7277 16%240k 0 0 0 34391 5667 14300 3406 Total room load Air required (cfm) 83396 2000 36380 2000 40058 1 000 17706 1 000 Calr:rrlations ennroved bv ACCA to ^#h ell renrrirements of Manttal .l 8th Ed -t{} wrldartroft'- - '-' ' " Right-Suite@ Universal 202323 0.05 RSU60560 W:\Project\3030 Elk Springs Dr.rup Calc = MJB Front Door faces: S 2025-Mat-24 12:20:45 Page 1 JrUrq*F h.a*rLbt!$+tlil Right-J@ Worksheet Entire House Job: Date: By: 3030 Elk Springs Drive March 24,2025 lsaac Ross 1 2 3 4 Room name Exposed wall Room lreiglrt Hoom drmensrons Room area Master/Beds AHU 254.0 ft 9.0 ft 2051_0 ft, (Uncondilioned) 96.0 ft 9.0 ft 1121.A tt Ty Construclion number U-value (Bl uh/ft'!- "F Or HTM (Bt uh/ft') Area (fr)or perimeler (ft) Load (Btuh) Area (f t') or perimeler (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 I 1 Wl-Gl-Gl--G L-----G l-----G L----€ Wt^rut^ Wl_cl-Gl_cl-G t--.c t-----c L-----c L----{r L-----G L-----c L----€ L-----G L----o W L-----G L----c P c F F 12F-0sw 4A'4-2ow 4A'4-2ow 444-2ow 444-2ow 444-2ow 444-2owd 12F-0sw 4A4-2ow 444-2ow 12F-0sw 10D-w 444-2ow 4A4.-zow 4A4-2ow 444-2ow 4A.4-2ow 444-2ow 4A4-2ow 444-2ow 4A.4-2ow 444-2ow 444-2owd 11D0 12F-0sw 444-2ow 444-2ow 12F-0sw 178-34m1 18A-38md 1 9D-30cstp 21A.-20t 0.065 0.300 0.300 0.300 0.300 0-300 0-300 0.065 0.300 0.300 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.390 0.065 0.300 0.300 0.065 o.o27 0.029 0.034 0.o27 5.46 26.40 26.40 26.40 26.40 26.40 26.40 4.73 26.40 26.40 2.92 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 26.40 34.32 4.4'l 26.40 0.00 5.72 2.38 1.65 1.05 0.00 0.71 11.61 11.61 1 1.61 1 1.61 1 1.61 11.61 o.62 35.62 35.62 0.38 12.85 18.36 18.36 18.36 18.36 18.36 18.36 18.36 18.36 18.36 18.36 18.36 8.83 0.57 35.62 0.00 0.26 0.36 0.34 o.21 0.00 729 0 56 12 0 0 96 257 0 28 441 24 oz 11 14 18 0 0 24 0 0 0 96 0 459 35 0 360 0 2051 2051 0 565 0 0 0 0 0 0 269 0 0 193 0 0 0 0 0 0 0 0 0 0 0 0 0 424 0 0 360 0 2051 2051 0 3232 0 1478 317 0 0 2534 1 539 0 739 1 103 634 1637 284 370 462 0 0 634 0 0 0 2534 0 2425 924 0 2059 0 5234 2143 0 421 0 650 139 0 0 '1114 200 0 997 143 308 1 138 197 257 321 0 0 441 0 0 0 1763 0 316 1247 0 95 0 1 080 438 0 45 0 0 0 0 0 0 207 0 0 333 0 0 0 0 0 0 0 0 0 0 0 0 0 279 0 12 0 0 121 0 121 45 0 0 0 0 0 0 207 0 0 333 0 0 0 0 0 0 0 0 0 0 0 0 0 267 0 0 0 0 1121 0 1121 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 n n 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o c) AED excursion 562 0 Envelope loss/gain 30242 't1a2i 0 0 12 a) lnliltration b) Room ventilation 6676 655 0 0 0 0 0 13 lnternal gains:Occupants @ Appliances/other 230 4 920 1400 0 0 Subtotal (lines 6 to 13)36958 14803 0 0 1 1 4 b Less external load Less transfer Redistribution Subtotal Lluct loads 17%26% 0 0 0 36958 6380 0 0 0 14803 3871 0%o% 0 0 n 0 0 0 0 0 0 0 Tolal room load Air required (cfm) 43338 '1000 18674 1 000 0 0 0 0 Calculations aooroved bv ACCA to meet all reouirements of Manual J 8th Ed. €"da- wrlglrfrofi' Right-Suite@ U niversal 2023 23.0.O5 RSU60560 WlProject\3o3o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S 2025-Mar-24 12:20:45 Page 2 JcfEH,{# r-.r.IfbrEr5+tflo Right-J@ Worksheet Kitchen AHU Job: Date By: 3030 Elk Springs Drive March 24,2O25 lsaac Ross 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Kitchen AHU 98.0 tr 16.9 fi 1081.0 fr Kitchen/Living s8.0 ft heat/cool 1 .0 x 1081 .0 ft 16.9 ft 1081.0 fr Ty Conslruction number U-value (Bl uh/ftl " F Or HTM (Bt uh/ft') Area (fr) perimeter (ft)or Load (Btuh) Area (f t, )or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool o 1 1 Wl-Gl-Gl+l-cl_cle W L----€lc Wt^ret^F-Ut^ =l_Gl-Gl-cl_cl-c L--G L---G L-----c L----o W l-----Grc P c F F 12F-0sw 4A.4-2ow 444-2ow 4A.4-2ow 4A.4-2ow 444-2ow 444-2owd 1 2F-0sw 4A4-2ow 444-2ow 12F-osw 10D-w 4A.4-2ow 4A.4-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 4A4-2owd 11D0 12F-0sw 4A'4-2ow 444-2ow 12F-0sw 178-34m1 18A-38md '19D-30cstp 21A'-20t 0,065 0.300 0-300 0.300 0.300 0.300 0.300 0.065 0.300 0.300 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.390 0.065 0.300 0.300 0.065 o.o27 0.029 0.034 o.o27 5.72 26.40 26.40 0.00 26.40 26.40 0.00 5.72 26.40 0.00 5.72 0.00 26.40 0.00 0.00 0.00 26.40 26.40 0.00 26.40 26.40 26.40 26.40 34.32 5.72 0-00 0.00 0.00 2.38 2.55 1,05 0.00 0.74 11.61 11.6'l 0.00 1 1.61 1 1.61 0.00 o.74 35.62 0.00 0.74 0.00 18.36 0.00 0.00 0.00 18.36 18.36 0.00 '18.36 18.36 18.36 18_36 8.83 0.74 0.00 nnn 0.00 0.36 0.53 o.21 0.00 493 15 40 0 25 36 0 736 15 0 493 0 32 0 0 0 25 28 0 36 39 50 96 32 474 0 0 0 1293 15 1 081 0 376 0 0 0 0 0 0 721 0 U 155 0 0 0 0 0 0 0 0 0 0 0 0 32 474 0 0 0 1293 15 1081 0 2159 403 1056 0 660 959 0 4123 403 0 885 0 845 0 0 0 660 739 0 959 1 030 1320 2534 1098 27 11 n 0 0 3073 38 1 130 0 280 177 464 0 290 422 0 536 543 0 115 0 588 0 0 0 459 514 0 667 716 918 1763 283 353 0 0 0 459 8 231 0 493 15 40 0 25 36 0 736 15 0 493 0 32 0 0 0 25 28 0 36 39 50 96 32 474 0 0 0 1293 15 1 081 0 376 0 0 0 0 0 0 721 0 0 155 0 0 0 0 0 0 0 0 0 0 0 0 32 474 0 0 0 1293 15 1 081 0 2153 403 1 056 0 660 959 0 4123 403 0 885 0 845 0 0 0 660 739 0 959 1030 1320 2534 1 098 2711 0 0 0 3073 38 1 130 0 280 177 464 0 290 422 0 536 543 0 115 0 588 0 0 0 459 514 0 667 7'16 918 763 283 353 0 0 0 459 8 231 0 1 6 c) AED excursion 1307 1307 Envelope loss/gain 26779 1'109:26779 11093 12 a) lnfiltration b) Room ventilation 7612 0 747 0 7612 0 747 0 13 lnternal gains:Occupants @ Appliances/other 230 460 2000 2 460 2000 Subtolal (lines 6 to 1 3)34391 14300 34391 14300 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 160k 24% 0 0 0 34391 5667 0 0 0 '14300 3406 16%2404 0 0 n 34391 5667 0 0 0 14300 3406 Total room load Air required (cfm) 40058 1 000 17706 1 000 40058 I 000 17706 1 000 Calcrrlations anoroved bv ACCA to ^#^ eet all reorrirements of Manual J 8th Ed. +'lf- s71a6t-cft''i -'" - -' Rig hrsu ite@ u niv ersal 2023 23 0 05 RSU6 0560 WlProject\303o Elk Springs Dr.rup Calc = MJB Front Door faces: S 2025-Mat-24 12:20:45 Page 3 ,ililn* Er.hlbha 15+tfl0 Right-J@ Worksheet MasterlBeds AHU Job: Date: By: 3030 Elk Springs Drive March 24,2025 lsaac Ross 1 2 3 4 5 Room nomc Exposed wall Room helght Room dimonsions Room area Master/Beds AHU 254.0 ft 9.0 ft 2051.0 fr Beds/mud rooms 124.0 ft heat/cool1.0 x 1?61 .0 ft 9.0 fr 1261.0 f 12 Ty Construction number U-value (Bi uh/fta'F Or HTM (Bt uh/ft') Area (f t, )or porimeter (ft) Load (Btuh) Area (f r) perimeter (ft)or Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool tt I 1 Wl---c L-----c L----€ L---Gt-+lC Wl_ctc WL--c L----6 L----€ L----{; l-----c l-----€ L----cl--c L---cL-ct--Gl-€tD Wl-GlG P c c F F 12F-0sw 444-2ow 4A.4-2ow 444-2ow 444-2ow 444-2ow 444-2owd 1 2F-osw 444-2ow 4A.4-zow 1 2F-0sw 1oD-w 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 444-2ow 4A.4-2ow 444-2owd 11D0 12F-0sw 4A4-2ow 444-2ow 12F-0sw 178-34m1 18A-38md 1 9D-30cstp 214-20t 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.065 0.300 0.300 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.390 0.065 0.300 0.300 0.065 o.o27 0.029 0.034 o.o27 n n n n n n n e e e s s s s s s s s s s s 5.72 0.00 26.40 26.40 0.00 0.00 26.40 5.72 0.00 26.40 5.72 26.40 26.40 26.40 26.40 26.40 0.00 0.00 26.40 0.00 0.00 0.00 26.40 0.00 5.72 26.40 0.00 5.72 0.00 2.55 1.05 0.00 0.74 0.00 11.61 11.61 0.00 0.00 11.61 o.74 0.00 35.62 0.74 12.85 18.36 18.36 18.36 18.36 0.00 0.00 18.36 0.00 0.00 0.00 18.36 0.00 o.74 35.62 0.00 o.26 0.00 0.53 o.21 0.00 729 0 56 12 0 0 96 297 0 28 441 24 62 11 14 18 0 0 24 0 0 0 96 0 459 35 0 360 0 205'l 2051 0 565 0 0 0 0 0 0 269 0 0 193 0 0 0 0 0 0 0 0 0 0 0 0 0 424 0 0 360 0 2051 2051 0 3232 0 1478 317 0 0 2534 1 539 0 739 1 103 634 1637 284 370 462 0 0 634 0 0 0 2534 0 2425 924 0 2059 0 5234 2143 0 421 0 650 139 0 0 '1114 200 0 997 143 308 1 138 197 257 321 0 0 441 0 0 0 1763 0 316 1247 0 95 0 1 080 438 0 369 0 56 0 0 0 0 45 0 0 81 0 0 0 14 0 0 0 0 0 0 0 0 0 261 35 0 360 0 126',1 1261 0 313 0 0 0 0 0 0 45 0 0 67 0 0 0 0 0 0 0 0 0 0 0 0 0 lzo 0 0 360 0 261 261 0 1 1 1790 0 1478 0 0 0 0 257 0 0 383 0 0 0 370 0 0 0 0 0 0 0 0 0 1293 s24 0 2059 0 3218 1318 0 233 0 650 0 0 0 0 33 0 0 50 0 0 0 257 0 0 0 0 0 0 0 0 0 168 1247 0 95 0 664 270 0 6 o) nED oxouroion 562 212 Envelope loss/gain 30282 't1827 1 3091 3879 12 a) lnfiltration b) Room ventilation 6676 0 655 0 2621 0 257 0 13 lnternal gains:Occupants @ Appliances/other 230 4 920 1400 2 460 500 Subtotal (lines 6 to 13)36958 14803 15711 5096 4 Less external load Less transfer Redistribuiion Subtotal Duct loads 170/o 26V" 0 0 0 36958 6380 14803 3871 210/"31y. 0 0 0 15711 3238 0 0 0 5096 1 589 Total room load Air required (cfm) 43338 1000 18674 1000 1 8949 437 6684 Calculations approved bv ACCA to meet all reouirements of Manual J 8th Ed. J6e. <{a- wrlghtroft-' Rightsuite@ U niversal 2023 23.0.05 RSU60560 WiProject\3o3o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S 2O25-Mat-24 12:20:45 Page 4 Jt{nffi4r l-,ar.Ilbhaffi+trm Right-J@ Worksheet Master/Beds AHU Job: Date: By: 3030 Elk Springs Drive March 24,2025 lsaac Ross 1 2 e 4 5 Room name Exposed wall Room height Room dimensions Room area 9.0 fr 790.0 fr Master/Breeze way 130.0 ft heaUcool 1.0 x 790.0 ft Ty Construction number U-value (Bt uh/ft1'F Or HTM (Bt uh/ft') Area (f r)or perimeter (ft) Load (Btuh) Areaor perimeter Load Heat Cool Gloss N/P/S Heat Cool Gross N/P/S Heat Cool b 1 1 Wl-c1."F-GL--c L----€lc W l-----€le Wl_cl-Gl_cl-cl_ct--c L-----c L----€ L-----c L-----c L-----G L----6l--D wl--GrG P c c F F 12F-0sw 444-2ow 444-2ow 444-2ow 444-2ow 4A4-2ow 4A4-2owd 12F-0sw 444-2ow 444-2ow 1 2F-osw 10D-w 4A.4-2ow 444-2ow 444-2ow 444-2ow 4A4-2ow 444-2ow 4l.4-2ow 444-2ow 4A4-2ow 4A.4-2ow 4A4-2owd 11D0 12F-0sw 444-2ow 444-2ow 1 2F-osw 178-34m1 18A-38md 1 9D-30cstp 21A-20t 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.065 0.300 0.300 0.065 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0-300 0.300 0.300 0.300 0.300 0.390 0.065 0.300 0.300 0.065 o.o27 0.029 0.034 o.o27 5.72 0.00 26.40 26.40 0.00 0.00 26.40 5.72 0.00 26.40 5.72 26.40 26.40 26.40 26.40 26.40 0.00 0.00 26.40 0.00 0.00 0.00 26.40 0.00 5.72 26.40 0.00 5.72 0.00 2.55 1.05 0.00 o.74 0.00 11.61 1 1.61 0.00 0.00 11.61 0.74 0.00 35.62 0.74 12.85 18.36 18.36 18.36 18.36 0.00 0.00 18.36 0.00 0.00 0.00 18.36 0.00 0.74 35-62 0.00 o.26 0.00 0.53 o.21 0.00 360 0 0 12 0 0 96 252 0 28 360 24 62 11 0 18 0 0 24 0 0 0 96 0 198 0 0 0 0 790 790 0 252 0 0 0 0 0 0 224 n 0 126 0 0 0 0 0 0 0 0 0 0 0 0 0 198 0 0 0 0 790 790 0 1441 0 0 317 0 0 2534 128'l 0 739 719 634 1637 284 0 462 0 0 634 0 0 0 2534 0 1 133 0 0 0 0 20'16 826 0 188 0 0 139 0 0 1114 167 0 997 94 308 1 138 197 0 32'l 0 0 441 0 0 0 1763 0 147 0 0 0 0 416 '169 0 b c) AED excursion 349 Envelope loss/gain 17191 7949 12 a) b) lnfiltration Room ventilation 4056 0 3S8 0 13 lnternal gains:Occupants @ Appliances/other 230 460 900 Subtotal (lines 6 to 1 3)9707 1 1 4 A Less external load Less transfer Redistribution Subtotal Duct loads 15V"24% 0 0 0 2'1247 3143 0 0 0 9707 2282 Tolal room load Air required (cfm) 24389 563 11989 642 Calcrrlations anoroved bv ACCA to ^cE* all renrrirements of Manual J 8th Ed. Page 5{t- wrlgfrt-oft'-- "- "' ' - Right-suite@ Universal 202323.0.05 RSU60560 WlProject\3o3o Elk Springs Dr.rup Calc = MJ8 Front Door faces: S 2o25-Mar-24 12'.20:45