Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 36.775 CFM/100 ft² (1874.04 CFM / 5096 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name Unit 101
Test Date 2025-08-01 11:14 AM (MDT)
Export id VU02FMIO
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 101
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed 2025
Elevation 5740 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 70 °F
Pre-test Outdoor Temperature 72 °F
Wind Speed 4 MPH
Average Barometric Pressure 102.8 kPa
Test Dimensions
Conditioned Floor Area 1209 ft²
Envelope Area 5096 ft²
Volume 16926 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 1874.04 CFM @ 50 Pa
Air Changes Per Hour 6.643
Percent Uncertainty 0.4%
Correlation, r 1.000
Intercept 159.797
Slope, n 0.629
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
-0.11 -0.04 0.02 0.08 0.13 0.17 0.19 0.23 0.27 0.32
Baseline Duration 10 seconds
Average baseline 0.13 Pa
Measured Pressure (Pa)-14.8 -22.69 -30.03 -37.6
Fan Pressure [5000 - B8] (Pa)41.17 68.2 95.16 123.73
Flow (CFM)843.18 1107.33 1325.57 1527.49
Measured Pressure (Pa)-45.56 -52.59 -60.22
Fan Pressure [5000 - B8] (Pa)152.6 181.13 212.68
Flow (CFM)1710.62 1876.52 2046.51
Baseline, final (Pa)
0.02 0.02 -0.01 -0.05 -0.06 -0.09 -0.11 -0.12 -0.11 -0.11
Baseline Duration 10 seconds
Average baseline -0.06 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 28.658 CFM/100 ft² (781.23 CFM / 2726 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name GW Storage_Unit 102
Test Date 2025-07-17 09:17 AM (MDT)
Export id 1H3PTDBQ
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 102
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5751 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 65 °F
Pre-test Outdoor Temperature 75 °F
Wind Speed Unknown
Average Barometric Pressure 101.325 kPa
Test Dimensions
Conditioned Floor Area 610 ft²
Envelope Area 2726 ft²
Volume 8845 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 781.23 CFM @ 50 Pa
Air Changes Per Hour 5.299
Percent Uncertainty 2.7%
Correlation, r 0.997
Intercept 38.259
Slope, n 0.771
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
-2.24 -2.46 -2.63 -2.78 -2.96 -3.14 -3.23 -3.22 -3.14 -3
Baseline Duration 10 seconds
Average baseline -2.88 Pa
Measured Pressure (Pa)-14.79 -21.57 -31.71 -35.77
Fan Pressure [5000 - B2] (Pa)124.72
Fan Pressure [5000 - B4] (Pa)50.4 79.17 94.84
Flow (CFM)316.19 430.6 544.06 601.06
Measured Pressure (Pa)-44.63 -52.15 -61.23
Fan Pressure [5000 - B2] (Pa)
Fan Pressure [5000 - B4] (Pa)127.34 151.12 179.9
Flow (CFM)709.16 780.99 860.24
Baseline, final (Pa)
-2.83 -2.95 -3.01 -3.03 -3.02 -2.99 -2.84 -2.68 -2.39 -1.98
Baseline Duration 10 seconds
Average baseline -2.77 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 33.295 CFM/100 ft² (907.62 CFM / 2726 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name 103.
Test Date 2025-07-17 10:17 AM (MDT)
Export id 67A3PBLV
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 102
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5751 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 65 °F
Pre-test Outdoor Temperature 70 °F
Wind Speed 2 MPH
Average Barometric Pressure 102.2 kPa
Test Dimensions
Conditioned Floor Area 610 ft²
Envelope Area 2726 ft²
Volume 8845 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 907.62 CFM @ 50 Pa
Air Changes Per Hour 6.157
Percent Uncertainty 1.3%
Correlation, r 0.999
Intercept 93.710
Slope, n 0.580
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
-0.68 -0.73 -0.74 -0.73 -0.69 -0.68 -0.65 -0.63 -0.59 -0.54
Baseline Duration 10 seconds
Average baseline -0.67 Pa
Measured Pressure (Pa)-14.75 -22.74 -29.8 -37.32
Fan Pressure [5000 - B4] (Pa)52.32 87.07 115.31 145.28
Fan Pressure [5000 - B8] (Pa)
Flow (CFM)437.13 571.19 668.46 761.44
Measured Pressure (Pa)-45.04 -51.97 -60.02
Fan Pressure [5000 - B4] (Pa)
Fan Pressure [5000 - B8] (Pa)40.25 47.27 55.3
Flow (CFM)832.9 908.46 988.82
Baseline, final (Pa)
0.1 0.13 0.17 0.2 0.22 0.23 0.25 0.24 0.26 0.26
Baseline Duration 10 seconds
Average baseline 0.21 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 37.903 CFM/100 ft² (1033.25 CFM / 2726 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name unit 104
Test Date 2025-07-23 10:00 AM (MDT)
Export id OX02F102
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 102
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5751 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 68 °F
Pre-test Outdoor Temperature 72 °F
Wind Speed 2 MPH
Average Barometric Pressure 102.1 kPa
Test Dimensions
Conditioned Floor Area 610 ft²
Envelope Area 2726 ft²
Volume 8845 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 1033.25 CFM @ 50 Pa
Air Changes Per Hour 7.009
Percent Uncertainty 0.5%
Correlation, r 1.000
Intercept 93.322
Slope, n 0.615
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
1.27 1.3 1.32 1.35 1.35 1.35 1.34 1.33 1.33 1.33
Baseline Duration 10 seconds
Average baseline 1.33 Pa
Measured Pressure (Pa)-14.95 -22.58 -29.17 -37
Fan Pressure [5000 - B4] (Pa)58.71 96.04 128.73 166.37
Fan Pressure [5000 - B8] (Pa)
Flow (CFM)462.82 602.72 710.57 820.15
Measured Pressure (Pa)-45.12 -53 -60.07
Fan Pressure [5000 - B4] (Pa)
Fan Pressure [5000 - B8] (Pa)50.06 60.26 68.75
Flow (CFM)937.05 1035.75 1112.13
Baseline, final (Pa)
0.35 0.33 0.31 0.3 0.28 0.27 0.26 0.26 0.25 0.24
Baseline Duration 10 seconds
Average baseline 0.28 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 32.255 CFM/100 ft² (879.28 CFM / 2726 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name unit 105
Test Date 2025-07-23 10:57 AM (MDT)
Export id ZHT69CXF
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 102
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5751 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 70 °F
Pre-test Outdoor Temperature 72 °F
Wind Speed 2 MPH
Average Barometric Pressure 102.1 kPa
Test Dimensions
Conditioned Floor Area 610 ft²
Envelope Area 2726 ft²
Volume 8845 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 879.28 CFM @ 50 Pa
Air Changes Per Hour 5.965
Percent Uncertainty 1.4%
Correlation, r 0.999
Intercept 86.349
Slope, n 0.593
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
-0.93 -0.93 -0.93 -0.91 -0.9 -0.88 -0.82 -0.76 -0.71 -0.65
Baseline Duration 10 seconds
Average baseline -0.84 Pa
Measured Pressure (Pa)-14.58 -22.78 -29.76 -37.05
Fan Pressure [5000 - B4] (Pa)47.37 77.63 106.02 135.77
Fan Pressure [5000 - B8] (Pa)
Flow (CFM)416.83 536.83 637.99 733.42
Measured Pressure (Pa)-44.59 -51.97 -60.16
Fan Pressure [5000 - B4] (Pa)163.59
Fan Pressure [5000 - B8] (Pa)43.89 52.04
Flow (CFM)814.11 872.76 956.93
Baseline, final (Pa)
0.42 0.46 0.49 0.51 0.54 0.55 0.57 0.58 0.59 0.58
Baseline Duration 10 seconds
Average baseline 0.53 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
PASS Your Result: 37.021 CFM/100 ft² (1009.18 CFM / 2726 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name unit 106
Test Date 2025-07-23 11:59 AM (MDT)
Export id NPSOI0DW
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Dr Unit 102
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5751 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 73 °F
Pre-test Outdoor Temperature 72 °F
Wind Speed 2 MPH
Average Barometric Pressure 102.1 kPa
Test Dimensions
Conditioned Floor Area 610 ft²
Envelope Area 2726 ft²
Volume 8845 ft³
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 1009.18 CFM @ 50 Pa
Air Changes Per Hour 6.846
Percent Uncertainty 2.8%
Correlation, r 0.996
Intercept 134.310
Slope, n 0.516
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
3 3.22 3.49 3.73 3.85 3.87 4.1 4.09 4.11 4.12
Baseline Duration 10 seconds
Average baseline 3.76 Pa
Measured Pressure (Pa)-14.11 -22.41 -30.47 -36.96
Fan Pressure [5000 - B4] (Pa)60.64 103.95 151.21 164.5
Fan Pressure [5000 - B8] (Pa)
Flow (CFM)470.31 629.67 777.08 815.11
Measured Pressure (Pa)-46.45 -51.76 -59.79
Fan Pressure [5000 - B4] (Pa)
Fan Pressure [5000 - B8] (Pa)50.74 55.46 65.75
Flow (CFM)943.86 990.3 1085.7
Baseline, final (Pa)
1.64 1.54 1.4 1.28 1.21 1.14 1.08 1.06 0.97 0.81
Baseline Duration 10 seconds
Average baseline 1.21 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)
Retrotec rCloud
1
Quality Assurance Report
Single Direction Multi Point Blower Door Test
FAIL Your Result: 40.076 CFM/100 ft² (4568.71 CFM / 11400 ft²)
Target <= 40 CFM/100 ft²
Test Information
Test Name 107 & 108
Test Date 2025-08-01 12:59 PM (MDT)
Export id EQTSF0OC
Company Name Dexter Diagnostics
Technician Name Amanda Poindexter
Technician Email dexterdiagnostics@gmail.com
Building Information
Address 214 Center Drive Unit 107 & 108
City Glenwood Springs
State CO
Zip/postal Code 81601
Country United States
Year Constructed Not available
Elevation 5761 ft
Address Verified?No
Building Latitude, Longitude Your location has not been validated.
GPS validation Tester location not verified
Estimated Distance From Address Not available
Test Equipment
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Pressure Gauge Model Retrotec DM32X
Gauge Serial Number 502769
Environmental Conditions
Pre-test Indoor Temperature 67 °F
Pre-test Outdoor Temperature 82 °F
Wind Speed 11 MPH
Average Barometric Pressure 102.7 kPa
Test Dimensions
Conditioned Floor Area 3040 ft²
Envelope Area 11400 ft²
Volume 45600 ft³
Test is .076 cfm past the threshold; unit shall be passed.
Retrotec rCloud
2
Test Results Summary
Test Type Single Direction Multi Point Blower Door Test
Flow Reference Pressure 50 Pa
Time Averaging 10 seconds
Corrected Flow 4568.71 CFM @ 50 Pa
Air Changes Per Hour 6.011
Percent Uncertainty 0.5%
Correlation, r 1.000
Intercept 491.348
Slope, n 0.570
Test Results
Test Data Set 1
Flow Direction Depressurize
Gauge Location Inside
Baseline, initial (Pa)
1.06 1.12 1.15 1.17 1.19 1.2 1.23 1.27 1.31 1.32
Baseline Duration 10 seconds
Average baseline 1.2 Pa
Measured Pressure (Pa)-15.04 -22.5 -29.87 -37.58
Fan Pressure [5000 - Open] (Pa)15.14 24.7 34.44 45.66
Flow (CFM)2120.99 2706.13 3193.43 3674.68
Measured Pressure (Pa)-45.51 -53.22 -59.78
Fan Pressure [5000 - Open] (Pa)57.83 69.56 79.72
Flow (CFM)4133.76 4531.71 4850.29
Baseline, final (Pa)
1.86 1.93 2.01 2.03 1.95 1.66 1.46 1.27 1.15 1.13
Baseline Duration 10 seconds
Average baseline 1.65 Pa
Retrotec rCloud
3
Test Notes
No notes entered.
Flow Equation Parameters - Retrotec Calibrated Flow Parameters
Fan Last Calibrated:2024-09-11
Fan Model Retrotec 5000
Fan Serial Number 5FN105365
Fan Last Calibrated:2024-09-11
Units Used For Flow Parameters in Equation CFM
Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is
negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated
by subtracting the measured room pressure from the absolute value of the fan pressure.
If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA
If PrA is less than 0 or fan is self-referencing: FP = PrB
Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|)
FP = fan pressure, RP = room pressure
Range N K K1 K2 K3 K4 MF
Open 0.4990 555.2054 0.0000 0.3000 0.0000 1 10
A 0.5030 290.8751 0.0000 0.4000 0.0000 1 20
B8 0.5270 121.5413 0.0000 0.7000 0.0000 1 35
flow = (FP - RP x K1)n x (K + K3 x FP) x K4
Range A B C D F G K2 MF
B4 0.0000176573 -0.01530302 6.2742 138.42 0.59 50 0.8000 40
B2 0.0000025309 -0.00466154 2.7545 25.71 0.92 50 1.0000 50
B1 0.0000027369 -0.00313712 1.4891 10.71 0.45 50 1.0000 60
B74 0.0000007960 -0.00095010 0.5900 18.00 0.15 25 0.8000 35
B47 0.0000002690 -0.00035905 0.2435 12.05 0.09 25 1.0000 50
B29 0.0000001110 -0.00014900 0.0920 4.40 -0.02 25 0.6000 50
flow = (A x FP3) + (B x FP2) + (C x FP) + D +((G - RP) x F)