Com pl ia nce Certificate
Project 826 County Road 237 (Montanez Barndominium)
Energy Code:
Location:
Construction Type:
Project Type:
Project SubType:
Conditioned Floor Area
Glazing Area
Climate Zone;
Permit Date:
Permit Number:
All Electric
ls Renewable
Has Charger
Has Battery:
Has Heat Pump:
2018 rECC
Rifle, Colorado
Single-family
New Construction
None
L,2OO it2
8o/o
s (6881 HDD)
false
false
false
false
false
Construction Site:
825 County Road 237
silt, co 81652
Ceiling: Raised or Energy Truss
Wall - Main Floor: Wood Frame, 16" o.c.
Entry Door: Solid Door (under 5Oo/o glazing)
Window: Metal Frame w/Thermal Break
Garage Common: Wood Frame, 16" o.c.
Floor: Slab-On-Grade (Unheated)
lnsulation depth: 4.0'
lnsulation position: Vertical lnsulation
Owner/Agent:Desig ner/Contractor:
Jeff Johnson
jeff@jja rchitectura l.com
\
$
Nl\
l+.'
s\
.\n
\
\l
N
Compliance: 10,37o Better Than Code Maximum UA: 194 Your UA: 174
The%BetterorWorseThanCodelndexreflects howclosetocompliancethehouseisbasedoncodetrade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Slab-on-grade tradeoffs are no longer considered in the UA or performance compliance path in REScheck. Each slab-on-grade
assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements.
Envelope Assemblies
2,320
1,100
24
135
500
140
49.0
26.0
19.0
0.0
0,0
0.020
0.052
0.330
0.300
0.060
0.026
0.060
0.300
0.300
0.060
46
49
I
41
30
60
56
4t
7
0.0
10.0 0.480 0.s40
30
0 0
Compliance: Passes using UA trade-off
Cavity
R-Value
Cont.
R-Value
Prop. Req.
U-Factor U-Factor
Req
UA
Gross Area
Assembly
Perimeter
Prop.or UA
Project Title: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: Il-lOLlz4
Page 1 of10
ROOM DETAIL
Room name: Living Space
Heated square footage:
Cooled square footage: '
Heated volume (above grade CF):
Cooled volume (above grade CF):
Exposod wall area (SF):
I@I@l!t@
r4@I@
Total Cooling BTUH:
Total Heating BTUH:
CFM:
20,000
@
@
@
Coulrrrg
Heatlng
4,000
Load Calculation
10.000
AED Graph (mid-summer)
0 30,000
BTUH
I
F-o 2,000
6,000
4,000
2,000
0
8 9 10 11
-
BTUH
12 13 14 15 16 17 18
-
Average
-
Average * 1.3
19
AED graph (fall)
>
Pa
0 I 9 10 11
-
BTUH
12 13 14 15 16 17 18
-
Average
-
Average * 1.3
19
REScheck Software Version : REScheck-Web
lnspection Checklist
Energy Code: 2018 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Additional Comments/Assum ptions:
Section
#
& Req.lD
Pre-l nspection/Plan Review Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
103.1,
103.2
lPR1l1
.V/
Construction drawings and
documentation demonstrate
energy code compliance for the
building envelope. Thermal
envelope represented on
construction documents.
lComplies
EDoes Not
nNot Observable
nNot Applicable
Construction drawings and
documentation demonstrate
energy code compliance for
lighting and mechanical systems.
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
nComplies
nDoes Not
nNot Observable
nNot Applicable
103.1,
r03.2,
403.7
lPR3l1
!-ti
Heating and cooling equipment is
sized per ACCA Manual S based
on loads calculated per ACCA
Manual J or other methods
approved by the code official.
Heating:
Btu/hr_
Cooling:
Btu/hr
Heati ng:
Btu/hr_
Cooling:
Btu/hr
nComplies
EDoes Not
nNot Observable
nNot Applicable
302.r,
403.7
lPR2l2
.AJ
1 ht (Tier 1)H 2 Medium I (Tier 2)3 Low lmpact (Tier 3)
Project Title: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: LLl0Ll24
Page 3 of10
Compliance Statemenil The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application, The
REScheck Version : REScheck-Web and to comply with
Amanda Poindexter, Energy Consultant
Name - Title
ng has been designed to meet the 2018 IECC requirements in
listed in the REScheck lnspection Checklist.
111112024
Date
ProjectTitle: 826 County Road 237 (Montanez Barndominium)
Data filcnamc:
Report date: lIlOIl24
Page 2 of10
S€ctlon
#
& Red.lD
Foundation lnspection Plans Vorifled
Value
Field verified
Val'ue Complies?CommEnts/Arsumptions
402.L.2 ;Slab edge insulation R-value
lFol-]l i
8;
R-_
! Unheated
I Heated
R-_
I Unheated
i I Heated
nComplies
lDoes Not
ENot Observable
!Not Applicable
See fhe Envelope Assemblies
table for values.
402.L.2
lFo3l1
&
Slab edge insulation
depth/length.
ft ft nComplies
nDoes Not
nNot observable
[JNot Applicable
See the Envelope Assemblies
table for values.
3r03,.2;l
[Fo:m;a
, :A protective covering is installed
to protect exposed exterior
insulation and extends a
, minimum of 6 in. below grade.
IComplies
nDoes Not
nNot Observable
!Not Applicable
nComplies
lDoes Not
nNot Observable
ENot Applicable
Additiona I Com ments/Assumptions:
1 High lmpact (Tier 1)z Medium lmpact (Tier 2)Jr Low lmpact (Tier 3)
ProjectTitle: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: LLlOLl24
Page 4 of10
Section
#
& Req.lD
Framing / Rough-ln lnspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.r.1,
402.3.4
lFR1l1
''ldr
EComplies
nDoes Not
nNot Observable
!Not Applicable
Door U-factor See the Envelope Assemblies
table for values.
U-U.
402.L.r,
402.3.r,
4 02.3.3,
402.5
lFR2l1
'SJ
!Complies
nDoes Not
nNot Observable
ENot Applicable
See the Envelope Assemblies
table for values.
U-U-Glazing U-factor (area-weighted
average),
Complies303.1.3
lFR4l1
t,
402.4.r.r
lFR23l1
.9,,
U-factors of fenestration products
are determined in accordance
with the NFRC test procedure or
taken trom the default table.
Air barrier and thermal barrier
insta lled per manufacturer's
i nstructions.
!Complies
nDoes Not
!Not Observable
!Not Applicable
lDoes Not
nNot Observable
nNot Applicable
402.4.3
lFR20l1
'Sr
Fenestration that is not site built
is listed and labeled as meeting
AAMA /WDMA/CSA 101/I.S.2I A44O
or has infiltration rates per NFRC
400 that do not exceed code
limits.
nComplies
lDoes Not
nNot Observable
nNot Applicable
lC-rated recessed lighting fixtures
sealed at housing/interior tinish
and labeled to indicate <2.0 cfm
leakage at 75 Pa.
IComplies
nDoes Not
nNot Observable
nruot Applicable
402.4.5
lFRr.6l2
Supply and return ducts in attics
insulated >= R-B where duct is
>= 3 inches in diameter and >= l
R-6 where < 3 inches. Supply and I
return ducts in other portions of
ihe bLrilding insulated >= R-6 for :
diameter >= 3 inches and R-4.2 i
for < 3 inches in diameter.
nComplies
nDoes Not
nNot Observable
nNot Applicable
403.3.1
lFR12l1
tr'
403.3.2
lFR13l1
Sj
Ducts, air handlers and filter
boxes are sealed with
joints/seams complia nt with
lnternational Mechanical Code or
lnternational Residential Code, as
applicable.
nComplies
nDoes Not
nNot Observable
nNot Applicable
403.3.s
lFR15l3
LJr
Building cavities are not used as
ducts or plenums.
nComplies
nDoes Not
nNot Observable
nNot npplicable
1 High lnrpact (Tier 1)2 Mediurrt lrlpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: 826 County Road 237 (Montanez Barndominium)
Dato filename:
Report date: L1,l0Il24
Page 5 of10
Section
#
& Req.lD
Framing / Rough-ln lnspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
403.3.7
lFR28l3
'9,
Ducts declared to be within the
conditioned space are either 1)
completely within the continuous
air barrier and within the building
thermal envelope, 2) buried
within ceiling insulation in
accordance with Section
R403.3.6 and the air handler is
located completely within the
continuous air barrier and within
the building thermal envelope
and the duct leakage is <= 1.5
cfm / 100 square feet of
conditioned floor area served by
the duct system, or 3) the ceiling
insulation R-value installed
against and above the insulated
duct >= to the proposed ceiling
insulation R-value, less the R-
value of the insulation on the
nComplies
lDoes Not
nNot Observable
nNot Applicable
403.4
lFR1712
,.9
HVAC piping conveying fluids
above 105 sF or chilled fluids
below 55 eF are insulated to >R-
3.
R-R nComplies
nDoes Not
nNot Observable
nruot Applicable
!Complies
nDoes Not
ENot Observable
nNot Applicable
403.4.7
lFR24l1
Sr
Protection of insulation on HVAC
piping.
403.5.3
lFR18l2
.g
Hot water pipes are insulated to
>R-3.
R R-nComplies
nDoes Not
nNot Observable
!Not applicable
403.6
lFR1912
Automatic or
installed on a
gravity dampers are
ll outdoor air
nComplies
lDoes Not
nNot Observable
nruot Applicable
intakes and exhausts
Additional Comments/Assum ptions:
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: ILlOIl24
Page 6 of10
lns.ulation lnspection Plans Vorified
\fatso:#camplies?Field Verlfied IV?trr6
I
Corn m€nti/Assu rnpta ons
'All installed insulation is labeled
' or the installed R-valuesrprovided.EDoes Not
LlNot Observable
flNot epplicable
lies
402.1,.I,
402.2.5,
402.2,6
ltN311
#
R-
nnn
llComplies
'Ennes Nnt
L_.lNot Observable
L-Jruot npplicable
,See the Envelope Assemblies
:table for values.
,
i
Wnnd
Mass
sreelrequirenrer tI applies (FR10)
Wall insulation R-value. lf this is a R-
E wooo
! Mass
n steet
imass wall with at least % of the
;wall insulation on the wall
: exterior, the exterior insulation
,Wall insulation is installed per
man ufacturer's instructions.
303.2
lrN4l1
Complies
Does Not
Not Observable
lNot Applicable
Additiona I Comments/Assum ptions:
1 High lrrrpact (Tier 1) l.dt{Uettium tmpact (Tler 2)3,Low lmpact (lier J)
Project Tltle: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: LllOLl24
Page 7 ofL0
Section
#
& Req.lD
Final lnspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.7.1, Ceiling insulation R-value
402.2.r,
402.2.2,
402.2.6
lFr1l1
R-_
! Wood
I Steel
R-nComplies
nDoes Not
nNot Observable
!Not Applicable
see the Envelope Assemblies
table for values.! Wood
! Steel
303.1.1.1, Ceiling insulation installed per
303.2 manufacturer's instructions.
IFl2]1 Blown insulation marked every
300 ft,.
nComplies
nDoes Not
nNot Observable
nruot npplicable
402.2.3
IFt22]2
Vented attics with air permeable
insulation include baffle adjacent
to soffit and eave vents that
extends over insulation.
EComplies
nDoes Not
nNot Observable
DNot Applicable
402.2.4
IFt3]1
Attic access hatch and door
insulation >R-value of the
adjacent assembly.
R-_R nComplies
nDoes Not
nNot Observable
ENot Applicable
402.4.r.2
I Fr17 ]1
Blower door test @ 50 Pa. <:5
ach in Climate Zones 1-2, and
<:3 ach in Climate Zones 3-8.
ACH 50 =ACH 50 nComplies
nDoes Not
flNot Observable
nNot Applicable
403.3.3
[Ft27]r
Ducts are pressure tested to
determine air leakage with
either: Rough-in test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
iP-cfm/100 ft-cfm/100 nComplies
lDoes Not
nNot Observable
nNot Applicable
403.3.4
lFt4l1
Duct tightness test result of <:4
cfm/l00 ft2 across the system or
<:3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in
tests, verification may need to
occur during Framing lnspection.
cfm/100 F-cfm/100 EComplies
nDoes Not
ENot Observable
nNot Applicable
ft2
403.3.2.r
lFt241r
Air handler leakage designated
by manufacturer at <=2o/o of
design air flow.
!Complies
nDoes Not
nNot Observable
nNot Applicable
403.1.1
lFt9l2
Progra mmable thermostats
installed for control of primary
heating and cooling systems and
initially set by manufacturer to
code specifications.
nComplies
nDoes Not
nNot Observable
nruot Applicable
403.1.2
lFr 1012
Heat pump thermostat installed
on heat pumps.
lComplies
nDoes Not
!Not Observable
nruot Applicable
403.5.1
I Ft11]2
Circulating service hot water
systems have automatic or
accessible manual controls.
nComplies
nDoes Not
nNot Observable
nNot Applicable
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: IIlOLl24
Page 8 of10
Section
#
& Req.lD
Final Inspection Provisions Plans Verified
v dturj
Field Verified
vdtue Complies?Comments/Assumptions
All mechanical ventilation system
fans not part of tested and listed
HVAC equipment meet efficacy
and air flow limits per Table
R403 .6. 1 .
!Complies
nDoes Not
nNot Observable
nNot Applicable
403.6.1
lFt25l2
Hot water boilers supplying heat
through one- or two-pipe heating
systems have outdoor setback
control to lower boiler water
nComplies
nDocs NoL
nNot Observable
nNot Applrcable
403.2
tFr26t'
temperature based on outdoor
temperature.
Heated water circulaLion systems '
have a circulation pump. The
system return pipe is a dedicated
reLurrr pipe or a cold wdter supply
pipe. Gravity and thermos-
syphon circulation systems are
not present. Controls for
circulating hot water system
pumps staft the pump with signal
for hot water demand within the
lies403.5.1.1
lFr28l2
403.5.7.2
I trr?o 12
Electric heat trace systems
comply with IEEE 515.1 or UL
515. Controls automatically
adjust the energy input to the
heat tracing to maintain the
desired water temperature in the
piping.
nComplies
T-l^tluoes t\ot
nNot Observable
nNot Applicable
occupancy. Controls
automatically turn off the pump
when water is in circr.rlation loop
is at set-point temperature and
no demand for hot water exists.
nDoes Not
nNot Observable
nNot Applicable
Demand recirculation water
systems have controls that
manage operation of the pump
and limit the temperature of the
water entering the cold water
piping to <: 104qF.
nComplies
EDoes Not
nNot Observable
ENot Applicable
403.s.2
lFt30l2
Drain water heat recovery units
tested in accordance with CSA
855.1. Potable water-side
pressure loss of drain water heat
recovery units < 3 psi for
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
IreaL recovery units < 2 psi for
individual units connected to
three or more showers.
403.5.4
lFtlrlz
nComplies
nDoes Not
nNot Observable
!Not Applicable
flComplies
nDoes Not
nNot Observable
nNot Applicable
404.r
lFt6l1
90o/o or more of permanent
fixtures have high efflcacy lamps.
404.r.1,
lFr2313
p.,
nComplies
l--ln^^- rr^*
llNot Observable
flNot Appllcahle
Fuel gas lighting systems have
no continuous pilot light.
IComplies
nDoes Not
!Not Observable
lNot Applicable
Complia nce certificate posted401.3
[Ft712
1 Higlr lrrrpacL (Tier L)2 Medlum lmpact (Tier 2)3 Low lmpact ( lier J)
Project -title: 82b County Road 237 (Montanez Barndominium)
ha+- f,il^.-^.-^^.uoLo I ilct tdt I tE.
Report date: LI|)Il24
Page 9 ofi0
Sectlon
#
& Rco.ID
Final lnspection Provisions Plans Verified
Valus
Field Verified
Value-Complies?Commonts/Assumptions
3,03,3
[Ftrgl!
Manufacturer manuals for
mechanical and water heating
systems have been provided.
flComplies
,nDoes Not
'flNot Observable
nNot Applicable
Additiona I Comments/Assumptions :
3 Low lm (Tier 3)1 High lmpact (Tier 1)Medium lm r2)
Project Title: 826 County Road 237 (Montanez Barndominium)
Data filename:
Report date: IIlOll24
Page 10 of10
2018 IECC Energy
Efficiency Certificate
Above-Grade Wall
Below-Grade Wall
Floor
Ceiling / Roof
Ductwork (unconditioned spaces):
Window
Door
Heating System
Cooling System:_
Water
Name:
Comments
26.OO
o.oo
10.oo
49.OO
o.30
o.33
Date:
lnsulation Rating R-Value
Glass & Door Rating U-Factor SHGC
Heating & Cooling Equipment Efficiency