HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT
BLCO -07 -25-9396
GARCO PREMIER HANGERS
NEW BRAVO HANGER
375 COUNTY ROAD 352, RIFLE
LOT 43
THE APPROVED PLANS ARE TO BE ON-SITE FOR INSPECTIONS.
SANITARY FACILITIES ARE REQUIRED TO BE PROVIDED FOR WORKERS
A LIST OF REQUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
IS TO PERMIT AND APPROVE THE ELECTRICAL WORK.
HTTPS:/AAAAM COLORADO.GOV/PACI FIC/DORA/DPO ELECTRICAL PLUM Bl NG PER
MITS
UNDERGROUND UTILITY LOCATES IS THE RESPONSIBILITY OF THE OWNER OR
CONTRACTOR. 811 IS THE COLORADO UTILITY LOCATE HOT LINE.
ALL BACKFLOW PREVENTERS ARE REQUIRED TO BE TESTED AND CERTIFIED BY A
LICENSED BACKFLOW SPECIALIST AFTER INSTALLATION AND PRIOR TO ISSUANCE
OF THE CERTIFICATE OF OCCUPANCY.
SEPARATE SIGN PERMITS ARE REQUIRED FOR ANY EXTERNAL SIGNS. PLEASE
CONTACT THE COUNTY PLANNER FOR THE APPLICATION.
ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
tNSPECT|ONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-
3458. PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE
WRITTEN DOCUMENTATION OF THE INSPECTIONS.
THE ELECTRICAL CODE REQUIRES A SEPARATE ELECTRICAL PERMIT FOR LOW
VOLTAGE FIRE ALARMS THAT HAS AN ALARM PANEL AND SEND A NOTIFICATION
TO THE FIRE DISTRICT WHEN UNDER ALARM. A ROUGH-IN INSPECTION WITH THE
STATE ELECTRTCAL |NSPECTOR tS REQUTRED (303) 869-3458. PLEASE HAVE THE
INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN DOCUMENTATION
OF THE INSPECTION.
THE FIRE SPRINKLER AND ALARM ARE REQUIRED TO BE INSPECTED AND
APPROVED BY THE LOCAL FIRE PROTECTION DISTRICT. PLEASE PROVIDE SHOP
DRAWINGS TO THE FIRE DISTRICT FOR REVIEWAND SCHEDULE THE
INSPECTIONS ACCORDINGLY. PLEASE HAVE THE FIRE MARSHAL SIGN THE
INSPECTION CARD WHEN THE ROUGH INSPECTION IS APPROVED AND WHEN THE
FINAL INSPECTION IS APPROVED.
ANY WATER SUPPLY THAT FEEDS A FIRE SUPPRESSION SYSTEM IS TO BE
INSPECTED BY THE FIRE MARSHAL FOR THAT FIRE DISTRICT PRIOR TO
BACKFILLING.
PLEASE PROVIDE SPECIAL INSPECTIONS REPORTS TO THE BUILDING
DEPARTMENT FOR BOLTING AND WELDING.
GEOTECHNICAL OBSERVATION IS REQUIRED WHEN THE EXCAVATION IS
COMPLETE AND WRITTEN VERIFICATION BE SUPPLIED AT FOOTING INSPECTION,
1500PSF.
COMBUSTIBLE MATERIAL IS LIMITED WITHIN TYPE IAND TYPE II CONSTRUCTION
SEE IBC 603 FOR ALLOWED COMBUSTIBLE MATERIALS.
ALL EXTERIOR LIGHTING IS TO BE DOWNCNST NND SHIELDED
ANY MEMBRANE AND THROUGH PENETRATIONS OF THE FIRE RESISTIVE
CONSTRUCTION WILL BE REQUIRED TO BE FIRE-STOPPED WITH LISTED FIRE
STOPPING ASSEMBLIES. THE CONTRACTOR IS TO PROVIDE A CUT SHEET FOR THE
ASSEMBLTES AT THE FRAMTNG TNSPECT|ON. (tBC 713)
A KNOX BOX IS REQUIRED TO BE MOUNTED ADJACENT TO THE FRONT DOOR.
PLEASE CONTACT THE LOCAL FIRE DISTRICT FOR EXACT LOCATION.
IF THE FIRE SPRINKLER SYSTEM REQUIRES A FIRE PUMP. THEN THE UTILITY
nnnll Tl IAT I l^l t6r6 Tl t- nt tltn lAfll I hF hFAt ttFFh ?A hr nlt- I tnl tnn\.r\.4vt r nA I nL,rrJoEo I FIE rutvtr vvtLL Dtr r\E\,lutr\EL, I \./ DE rJt\E-r'l\J\Jr\
CoNSTRUCTTON. (rBC TABLE 508.2.5)
THE WALLS SURROUNDING THE TOILET ARE TO BE NON-ABSORBENT FOR A
HEIGHT OF 48'AND 2'PAST ON EACH SIDE OF THE TOILET.
ALL ACCESSIBLE DOOR HARDWARE SHALL HAVE A SHAPE THAT IS EASY TO GRIP,
INCLUDING POCKET AND SL|D|NG DOORS. (ANSI A117.1 - 404.2.6)
GRAB BAR BACKING IS TO BE IN PLACE FOR THE TOILET
THE LAYOUT OF THE RESTROOM WILL REQUIRE A RIGHT-HAND FLUSH WATER
CLOSET.
A VERTICAL GRAB BAR IS REQUIRED ADJACENT TO THE WATER CLOSET