Loading...
HomeMy WebLinkAbout Blower Door Test 52 Grosbeak Pl, July 31st, 2025 Glenwood Springs, CO 81601 Re: Blower Door Test for 52 Grosbeak Pl, To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on July 31st, 2025, at 2:00 PM. The total volume of the conditioned space for the entire home was calculated to be approximately 68,820 cubic feet. The blower door number achieved @ -50 pascals was 3,338 CFM, equal to 2.9 ACH @ -50 pascals. The building meets the air tightness requirement and is compliant with code. Weather conditions: 79 Degrees, Wind 15 MPH, No Precipitation, 34% Humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Ari-al Raeburn (E3 power) 518-222-2453 Building Analyst (BPI)