HomeMy WebLinkAboutHeat CalcsRECEIVEN @ 2925 Project lnformation Project#: 07012025 Name: ENLOE RESIDENCE Location: 29 SAGES CT LOT H4-GLENWOOD SPRGS, CO ManualJ Load Summary Total Heating: 130,111 Btu/hr Outdoor Conditions Location: Total Sensible: 46,856 Btu/hr (User Specifi ed) Carbondale, CO,Colorado 60&{' 41 Cooling 89.0'F Medium 73.O "F Notes: FOR TOM WEBBER Total Latent: 11,723 Btu/hr lndoor Gonditions Heating 70"F 72.O"F 35 Ventilation Num Occupants: Type: ACH: Outside Air: Sensible Eff: Load Report Manual JB Load Galculation Prqed#:O70'12O25 July 01, 2025 Gooling Heat Recovery 0.30 216 cfm 50% Created Using LoopCAD 2025 REHAU (91212025) Version:25.0.0196 R Page 1 of7 r-.:" :.J GA.'i.FiELD CCi"JI{TY C rlr l,l iil I li iTY * [l'EI-CFME]tT Elevation: Latitude: Dry Bulb: Daily Range: Wet Bulb: lnfiltration Method: Stories: Construction: Exposure Category: Num Fireplaces: Net Air Changes (HeaUCool): Net Flow (HeaVCool): Floorplan/Levels Main Floor Heating -2.0'F Simple 1 Tight Three or Four Exposures 2 (Tisht) 0.11 / 0.05 79 cfm / 36 cfrn 4,324 fi. Room Temp: Design Temp Diff: Humidity: Moisture Diff (Grains) Total Heated Area: Total Cooled Area: 5 Heating Heat Recovery 0.30 216 dft1 50 o/o 4,324 tr 4,324 tr Cooling 72'F 17.O "F 35 76.9 Type: ACH: Outside Air: Sensible Eff: $ {. \ -\ :\ (1) AT: Difference belween supply air and retum air (2) Estimated air flow based on specified supply air AT Length=ft Area=fi' Temperature='F Flowrate=USGPM AirFlow=ctm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'ft') HeadLoss=frwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimers. Rv = hr.ft'''F/btu N = Not Heated Name:BUSO RESIDENCE Prqed#:07012025 Constructions Walls Load Report July 01,2025 12F-Osw Code Frame Wall or Partition; Wood Framing; R-2'l lnsulation in 2 x 6 Stud Cavity; Stucco or Wood Siding; Plus lnterior Finish Description 0.065 U-Value 3,330 Area 15,583 Heating 3,744 Cooling Floors Gypsum Thin Slab-r Code Gypsum Thin Slab - Description 0.1 59 U-Value 4,324 Area 66,502 Heating 8,227 Gooling 168-50ad Code FHA vented attic; No radiant barrier over ceiling or same type of air space behind an attic knee wall; R-50 lnsulation; Materials: Asphalt Shingles(a), Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d); Description 0.020 U-Value 4,324 Area 6,226 Heating 4,496 Cooling Ceilings Glazing Windows (1) AT: Difference between suppl)' air and retum air (2) Esiimated air flow based on specified supply air AT Length=ft Area=ff' TemperEture='F Flowrab=USGPM AirFlow=cfrn HeatLoss=Btu/hr UnitFbatLoss=Btu/(hr'ft'z) HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmeft See end of report for inportant Notes and Disclaimerc. Rv = hr'fi'z''F/btu N = Not Heated Created Using LoopCAD 2025 REHAU (9/2/2025) Version:25.0.0196 R Custom Custom Custom Custom 1F-Orf 1F-Orf 1F-Orf 1F-Orf Code Double Pane low-e glass, BlindsMedium45 (50%) Double Pane low-e glass, BlindsMedium45 (50%) Double Pane low-e glass, BlindsMedium45 (50%) Double Pane low-e glass, BlindsMedium4S (50%) Triple pane window or sliding glass door, with Reflective Glass - lnsulated Fiberglass Framing, BlindsMedium45 (50%) Triple pane window or sliding glass door, with Reflective Glass - lnsulated Fiberglass Framing, BlindsMedium45 (51o/r) Triple pane window or sliding glass door, with Reflective Glass - lnsulated Fiberglass Framing, BlindsMedium45 (50%) Triple pane window or sliding glass door, with Reflective Glass - lnsulated Fiberglass Framing, BlindsMedium45 (50o/o) Description N E S W E N S Exposure 0.30 0.30 0.30 0.30 0.38 0.38 0.38 0.38 U-Value 0.56 0.56 0.56 0.56 0.18 0.18 0.18 0.18 SHGC 192 109 109 193 23 280 288 20 Area 4,147 2,353 2,362 4,1 60 638 7,660 7,880 547 Heating 2,058 4,735 4,752 3,932 462 5,543 2,423 236 Gooling Page 2 of 7 Name:BUSO RESIDENCE Proiec.#'.07012025 lnternal Loads Description Default (1,200 Btuh) 5 Occupants: Total Other Loads Blower LoadSensible 1,200 1 ,150 2,350 Latent 0 '1,000 1,000 (1) AT: Difference between supply air and retum air (2) Estimaled airflow based on specified supply air AT Length=ftArea=fr, Temperature='F Flowrate=USGPM AirFlow=ctrn HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'n'z) HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OlherHeating SM=Snownelt See end of report for important Notes and Disclaimer. Rv = hr'ff''"F/btu N = Not Heated Load Report July 01, 2025 1,706 Btu/hr Created Using LoopCAD 2025 REHAU (91212025) Version:25.0.01 96 R Page 3 of 7 Name:BUSO RESIDENCE Prcjed#:.07012025 Load Breakdown *Average Load Procedure Heatinq AT': 70.0 Coolinq ATr: 22.0 Est. Heatinq CFM?:.2078 Est. Coolinq CFM': 2381 JSHR: 0.8O MJ8 Tons:4.88 SqFUTon: 886 CFM/SqFI 0.55 Ceilings Heating Load Breakdown Walls Back Sensible Load Breakdown Rv = hr.fiz."F/btu N = Not Heated Load Report July 01, 2025 Windo'nrs* lBlower Heat lntemal Ventilation lnfiltration Created Usintl LoopCAD 2025 REHAU (91212025) Version:25.0.0196 R hfiltration Verfilation Walls Ceilings (1) AT: Difference betwen supply air and retum air (2) Estimated air flow based on specified supply air AT Lengt6=11 Area=fiz Temperature="F Flowrate=USGPM AirFlow=cfrn HeatLoss=Btu/hr UnitHealLoss=Biu/(hr.ft2) HeadLoss=fiwater RH=RadianlFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM-Snowmelt See end of report for important Notes and Disclaimerc. Total Area Total AED* Blower Heat Radiant Back Loss Piping Load Humidification Ventilation Duct Loads Other lntemal lnfiltration Floors Ceilinqs Below Grade Walls Walls Doors Skylights. Windows* Name 4,324ft2 130,111 66,502 0 0 6,962 0 0 5,092 0 6,226 0 15,583 0 0 29,747 Heating 4,324fi' 46,856 0 1,706 1,644 0 2,350 548 8,227 4,496 3,744 0 0 24,141 Sensible t,7n 9,191 0 1,000 1,532 Latent Page 4 ol 7 Name:BUSO RESIDENCE Proiect #:07012025 AED Load Report July 01, 2025 t dl 42000 40000 38000 36000 34000 32000 30000 28000 26000 24000 22000 20000 '18000 16000 14000 12000 10000 8000 8 I Average Load: 31,425 Btu/hr Excursion Limit: 40,853 Btu/hr Fenestration Load vs Hour of Day - Block Load (Summer) 12 13 14 15 16 17 Hour of Day Legend - Load Line - Average - 30 Percent 10 11 Peak Load: 36,219 Btu/hr AED Load: 0 Btu/hr 18 19 20 (1 ) AT: Difference between supply air and retum air (2) Estimated air flow based on specified supply air AT Length=ft Area=ff, Temperature='F Flowrate=USGPM AirFlow=cfrn HeatLoss=Btu/hr UnitHeatLoss=Btu/(hrft') HeadLoss=fiwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmeli See end of report for important Notes and Disclaimerc. Created Using LoopCAD 2025 REHAU (91212025) Version:25.0.0196 RRv = hr'ft2 'Flbtu N = Not Heated Page 5 of 7 Name:BUSO RESIDE\CE Prqed#:.07012025 Heating Zones Load Report ,luly 01,2025 Zone 101 Zone 4,324 Area 70 Room Temp 130,111 Total Load Heating Rooms * The sum of room loads mav not be equal to the project total due to additional system loads. Cooling Zones Room A-01 OFFICE MUD/LAUNDRY/H.ALL MASTER BED MASTER BATFVCLCSET LIVING/DINING/E]'.ITRY AREAS KITCHEN/BAR AREAS GUEST BATH GARAGE Room 269 137 321 292 313 781 833 113 1,265 Area 70 70 70 70 70 70 70 70 70 Room Temp 6,975 4,755 10,706 9,220 9,745 22,237 23,208 3,385 39,881 Total Load* Entire Building Zone 4,324 Area 72 Room Temp YES AED 43,5Ct7 Sensible Load (Average Load Procedure) Gooling Rooms * (Average Load Procelure.l The sum of room loads may not equal the project total due to variations in solar gain and system loads. (1 ) AT: Difference between supply air and retum air (2) Estimated air flow based on specified supply air AT Len$h=ft Area=ft' Tempetalure='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitleatLoss=Btu/(hr.ft') HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimers. Rv = hr.ft'1.'Flbtu N = Not Heated Created Using LoopCAD 2025 REi.lAU (9/2/2025) Versbn:25.0.0196 R Room A-01 OFFICE MUD/LAUNDRY/HALL MASTER BED MASTER BATH/CLOSET LIVING/DIN ING,'ENTRY AREAS KITCHEN/BAR AR--AS GUEST BATH GARAGE Room 269 137 321 292 313 78'l 833 113 1,265 Area 72 72 72 72 72 72 72 72 72 Room Temp NO NO YES NO NO NO NO NO YES AED 2,74'l 3,1 59 3,421) 4,161) 3,85t) 10,792 9,48rj 1,60,4 11,049 Sensible Load* Page 6 of 7 Name:BUSO RESIDENCE Prqed#:07012O25 Design Locaton Location: Province/State: Country: Outdoor Heating Design Temp: Outdoor Cooling Design Temp: MJSCustom Carbondale, CO Colorado United States -2.0 "F 89.0 'F Altitude: Latitude: Wet Bulb Temperature Daily Range: 6064' ff 41 73.0 'F Medium Load Report July 01, 2025 Created ljsing LoopCAD 2025 REHAU (91212025) Version:25.0.0196 R Disclaimers ACCA, Manual J and Powered by ACCA Manual J are registered trademarts of the Air Conditioning Contractors of America. All rights reserved" information to meet code requirements for any particular project, nor regarding the accuracy of the costing of any project based upon this information. applicable codes and local climate conditions. tN NO EVENT WLL AVENTR SOFTWARE tNC. CAVENTR) OR tTS AFFTLTATES BE LTABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY ARISING FRoM THE USE THIS REPoRT, AND REGARi'LESS oF THE FoRM oF THE AcTIoN, SHALL BE LIMITED To NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. (1) AT: Difference between supply air and return air (2) Estimated air flow based on specified supply air AT ldngrth=ft Area=ft" Temperalure='F Flowrate=USGPM AirFlow=cfrn HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'fi':) HeJdLoss=flwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snownelt See end of report for important Notes and Disclaimers. Rv = hr.fr'?.'F/btu N = Not Heated PageT oI7