INSTALL 120 STANDARD QUICK �4 PLUS I\NFT.TRATOR \
CHAMBERS IN 6 ROWS OF 20 EACH WITH END CAPS
�\ 'INSTALL END CAPS WITH rN PVC INSPECTION PORTS \
_- AND CAPS AT BOTH ENDS OF EACH ROW PLUSH OR
\ ABOVE GRADE (TYPICAL)
CIF r PVC 4 2X MI\
82 LF 4• PVC O 2X MIN.
44 LF 4' PVR\O-ZX MIN.
\ \ 32 U
yL \
"i EXISTING WELL ()qlt X. LOCATOp1 `- 24 LF r PVC O 2% MINN. ^
t VERIFY LOCATION AND SETBACKS \
PRIOR TO CONSTRUCTION
18 LF r PVC O 2X MIN.
PROFILE PIT PRO-2
PROFILE PIT PRO-1 \.
PROFILE PIT l
INSTALL 126 STANDARD QUICK 4 PLUS INFlLT
CHAMBERS IN 6 ROWS OF 20 EACH WITH END
C AND CAPS AT BOTH ENDS OF EACH ROW FLIISN OR�
ABOVE GRADE (TYPICAL)
---�---- PROFILE FIT PRO-3,
45 LF 4' PVC AND LONG SWEEP BENDS O 2X MI
35 LF PVC AND LQNG SWEEP BENDS O 2% MI
- -'F----N----
15 LFLF 4• PVC AND LONG SWEEP BENDS O 2% MI
15 IF 4• PVC AND LONG SWEEP BENDS O 2X MIA
\ 5 LF 4• PVC AND LONG
G Ii BENDS O 2% M11
\ DHSIRIBlON BW( /MppBp�gC,� F
EQUALIZERS. RISERS, AND LLD AT FNISH G
1,000 GALLON 2 COMPARTMENT TANK AND EFFLUENT hL1
24' RISERS. COVERS FLUSH WITH FINISH BRA
--
E-{-N 89'53'13" E 186.34� -j
\ aT
��--------Al" - - - - - - -
RFACE
�A (EFFR TO SANITARY
ARPLANS)
PROPOSED SANTARY DISCHARGE
P
MAIM-
RESIDENCE-
SOIL ',. 48
TREATMENT
INIEROFTOR .�� -\ SWALE
DISTRIBUTION BOXMp B,,OXBC,
.WITH FLOW EQUALIZERS RISERS
I AT FINISH GRADE
4' 45' LONG SWEEP PVC BEND \
PVC CLEAN OUT WT14 RISER
CAP. FLUSH PATH SURFACE
LF r PVC O 2% MIN.
GALLON 2 COMPARTMENT TANK, - ' \ \ R7�
'ISEIM AVERS FLUSH N1TI1 FINSH \� �� _I.
1 1 1 1 1 11 1 I I I I�rl ri IT K4-
PROPOSED �-
5-BEDROOM
MAIN RESIDENCETHE OWNER SHALLVERIFY ADEQUATE
IPRIOORRTTO �S RUUCCTION ID PVC CAPFLU FSH WITH SURFFATH CEROPOSED SANITARY SEWERISCHARGE LOCATION
(REFER TO PLUMBING PLANS) /
---
�_-mom _.. -" _-.__--------------
i
to be Eliminated
a. LOT 1
RUIZ SOUTH MINOR SUBDIVISION
\
RECEPTION NO. 981906
i
\
r w sNSP
-
-�
i VS ��
\ AI on•A v'�z^r rn�cn• I ,
Za. DESIGN FLOWS FOR MAIN RIM�DI EJ�1lENc
PROPOSED RESIDENCE: 5 BEDROOMS
PROPOSED OCCUPANCY: 8 PEOPLE
PROPOSED DISCHARGE: 75 GAL/PERS./DAY
DESIGN FLOW: 600 GAL/DAY
PROPOSED TANK MATERIAL' REINF. CONCRETE
--------MIN. SEPTIC TANK CAPACITY: 1,500 GALLONS
SOIL TYPE 3A, U.S.D.A.: SILTY CLAY LOAM
- - - - - - - - TREATMENT LEVEL: TLI
PROPOSED TREATMENT: CHANG. IN TRENCHES
METHOD OF EFFLUENT APPUCATION: GRAVITY
LONG TERM ACCEPTANCE RATE (LTAR} 0.30
REO'D SOIL TREAT. AREA:504,jGPD=ZOGD S.F.
0.30
SIZE ADJUST. FACTOR FOR APP. METHOD: 1.0
SIZE ADJUST. FACTOR FOR DIST MEGA: 0.7
ADJ. SOIL TREAT. AREA: ZOOOW0.7=1.400 S.F.
MINIMUM N. OF CHAMBERS: 1.400 SF. 120
12 S.F.
PROPOSED SOIL TREATMENT AREA
120 STD. INFILTRATOR WICK 4 PLUS CHAMBERS
/ IN A 6 PARALLEL TRENCH CONFIGURATION OF
20 CHAMBERS EACH. AS SHOWN.
2b. DESIGN FLOWS FOR A,D,U,
PROPOSED A.D.U: 3 BEDROOMS
PROPOSED OCCUPANCY: 6 PEOPLE
PROPOSED DISCHARGE: 75 GAL/PERS./DAY
DESIGN FLOW: 450 GAL/DAY
PROPOSED TANK MATERIAL.• REINF. OCCRETE
MIN. SEPTIC TANK CAPACITY: t,000 GALLONS
SOIL TYPE: 3A. U.&D.A.: SILTY CLAY LOAM
TREATMENT LEVEL.
PROPOSED TREATMENT: CHAMB. IN TRENCHES
METHOD OF EFFLUENT APPLICATION: GRAVITY
LONG TERM ACCEPTANCE RATE (LTAR): 0.30
REO'D SOIL TREAT AREA:451) GPD-1,500 S.F.
0.30
SINE ADJUST. FACTOR FOR APP. METHOD: 1.0
SIZE ADJUST. FACTOR FOR DIST. MEDIA: 0.7
ADJ.. SOIL TREAT. AREA 1,50Dx0.7=1,050 SF
MINIMUM No. OF CHAMBERS: i 050 S.F.
11 F 90
3.
TOPSOIL: SOIL EXCAVATED FROM SITE ACCEPTABLE F NO CLAY IS PRESENT.
4.
VEHICULAR TRAFFIC IS PROHIBITED ON THE TANK AND ON Tiff FIELD.
5.
CLEANOMS ARE REWIRED AT ALL SIENDS AND AT LEAST EVERY 150 FEET.
&
INSTALL RISERS TO BRING ALL ACCESS POINTS AT OR ABOVE THE FINAL GRADE
7.
LOCATIONS OP ALL COMPONENTS MAY BE VARIED AS NECESSARY AS LONG AS ALL
MINIMUM DISTANCES AND SLOPES MEET THOSE REQUIRED.
B.
PROVIDE POSITIVE DRAINAGE OF SURFACE WATERAWAY FROM ABSORPTION AREAS USING
Vr
DRAINAGE SHALES AS NECESSARY.
9.
t(APP,R
THE CONTRACTOR SHALL VERIFY ALL DEPTHS, SLOPES AND CLEARANCES FROM THE
PROPOSED STRUCTURES, WELLS AND PROPERTY LINES, PRIOR TO CONSTRUCTION.
xISL C 10.
x. LOCATION �.IFV
THIS DRAWING DOES NOT CONSTITUTE AN DINTS PERMIT. PERMIT MUST BE OBTAINED FROM
LOCAI
APPROPRIATE COUNTY OFFICIALS.
N SETUACKS'"-11.
Ot TO COHSE.
THIS SYSTEM IS SIZED FOR TYPICAL DOMESTIC WASTES ONLY. BACKWASH OR FLUSHING
FOR REVERSE OSMOSIS UNITS OR WATER SOFTENERS OR FILTERS SHOULD NOT BE
INTRODUCED INTO THIS SYSTEM.
- 12.
SEPTIC TANK SHALL HAVE RISES OVER EACH ACCESS MANHOLE AND ALL RISERS SHALL
EXTEND TO OR ABOVE FINAL GRADE
13.
THE OWNER SHALL VERIFY ADEQUATE SEPARATION DISTANCES, PRIOR TO DRIWNG WELLS
IC
THE APPUCANT SHALL NOTIFY THE COUNTY AND THE ENGINEER NO LESS THAN
TWO BUSINESS DAYS IN ADVANCE TO SCHEDULE A FINAL FIELD INSPECTION OF THE SYSTEM,
PRIOR TO BAC(FIWNG THE SYSTEM.
15,
THE APPUCANT OR LICENSED INSTALLER SHALL PROVIDE AN AS -BUILT CRANING OF THE
SYSTEM TO THE COUNTY AND ENGINEER, UPON COMPLETION.
16.
PLACE 27 BODE BOARD INSULATION ABOVE ALL PIPES WHENEVER DEPTH IS LESS THAN
MOST DEPTH.
17.
ALL SEWER LINES SHALL BE 4-INCH DIAMETER PCLYMNYL CHLORIDE (PVC) SCHEDULE 40.
AND SHALL BE INSTAUED WITH MINIMUM SLOPES NO LESS THAN 2X
15.
THE PROPERTY UNES AND EXISTING IMPROVEMENTS SHOWN HEREON WERE OBTAINED FROM
THE'RUIZ SOUTH MINOR SUBDIVISION' AS PREPARED BY BOOKCUFF SURVEY SERVICES IND,
DATED: S/9/19 AND 2/18/20. PROPOSED IMPROVEMENTS SHOWN HEREON WERE OBTAINED
FROM THE 'SITE PLAN' AS PREPARED BY SOCKCUFF SURVEY SERVICES DATED: 6/9/22.
19.
ARCHITECIURAL INFORMATION WAS OBTAINED FROM THE'ELR RESIDENCE' AS PREPARED BYi
DESIGN FORUM " DATED: SA4122 AND THE 'ELR SMALL RESIDENCE' AS PREPARED BY:
B
DESIGN FORUM LLC, DATED: 1/23/23.
ABSORPTION TRENCH NOTES
GRAPHIC SCALE I.
ABSORPTION TRENCH LATERALS SHALL NOT EXCEED 100 FEET IN LENGTH.
a0 D to Aa Z
THE BOTTOM OF THE ABSORPTION TRENCHES SHALL BE LEVEL
3.
DRAINAGE DITCHES SHALL PROVIDED ABOVE AND AROUND TRENCHES, AS
NECESSARY, TO PREVENT SURFACE RUNOFF FROM ENTERING ABSORPTION AREA.
4.
ABSORPTION TRENCH BOTTOM AND SIDEWALLS MUST BE RAKED TO REMOVE SOIL
( IN FE7.T)
SMEARS INCURRED DURING EXCAVATION.
1 imah = 30 ft. 5.
NO EXCAVATION OF ABSORPTION FIELD IS TO BE DONE DURING WET WEATHER
AND USE OF RUBBER IRE VEHICLES OVER TRENCH AREA IS PROHIBITED TO
MAINTAIN GDOD SOIL STRUCTURE.
&
UNSUITABLE MATERIAL EXISTNG WITHIN THE TRENCH SHALL BE EXCAVATED AND
BACKFlLL SHALL CONSIST OF ONSITE SELECT OR PIT -RUN MATERIAL
7.
CONTRACTOR SHALL INSTALL 4 INCH DIAMETER SCHEDULE 40 PVC INSPECTION
PORTS AND CAPS AT BOTH ENDS OF EACH ROW OF CHAMBERS, IN ACCORDANCE
WITH THE MANUFACTURER'S INSTALLATION GUIDEUNES
&
CONTRACTOR SHALL SNAP OFF THE MOLDED SPLASH PLATES LOCATED AT
THE BOTTOM OF THE END CAPS, AND INSTALL THE SPLASH PLATES AT
THE APPROPRIATE SLOTS BELOW THE INLETS IN ACCORDANCE WITH THE
MANUFACTURER'S INSTALLATION GUIDELINES
9.
CONTRACTOR SHALL ALIGN THE CHAMBER ROWS PARAIIM WITH THE
THE CONTOURS OF THE EXISTING TERRAIN. THE CONTRACTOR MAY CURVE
THE AUGNMENT OF THE CHAMBER ROW, AS NECESSARY. IN ACCORDANCE
WITH THE MANUFACTURER'S INSTALLATION GUIDELINES.
10.
CONTRACTOR SHALL PROVIDE AND VERIFY A MINIMUM 4 FRET OF DEPTH, OR
GREATER FROM THE BOTTOMS OF INSTALLED CHAMBERS TO CONFINING BEDROCK.
11.
CONTRACTOR SHALL PROVIDE AND VERIFY A MINIMUM 12 INCHES OF COVER, OR
GREATER FROM T1E TOPS OF INSTALLED CHAMBERS TO FINISH GRADE.
12.
CONTRACTOR SHALL CONNECT THE 4 INCH DIAMETER PVC THE DISTRIBUTION
LATERAL PIPES AT THE MOLDED CIRCULAR BLOCK OUTS. NNICH ARE SITUATED
B INCHES ABOVE THE BOTTOMS OF THE STANDARD QUICK 4 POPS CHAMBER
END CAPS, IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION GODEUNES.
54A6
O-1473 PIND-2 5448
5134
5434
a3
F1n'Sg32k
FX-H
9447
5447
6433
6433
G
544a
5444
5432
5432
aw
15M5
,
5431
wi
s=
54H
5,44
543D
5430
5143
SF43
942a
SF2H
M42
Sff2
3428
SOB
a441
9441
g
5427
5427
SNO
5M0
S426
SINI
5439
5439
5a25
5125
5N35
S4Se
5424
W4
LEGEND: ®TOP
SOIL: USDA S01 TYPE 3 SILTY (LAY LRAM
®
USDA SOIL TYPE TJ, SILT CLAY LOAM
NOTES: 1. P UE PITS WERE EXCAVATED BY OWNER DURING FTBfiIMtY,
2020 AND MAY,
=3 .
Z NO ITFE WATER WAS ENCOUNTERED IN TTE PITS AT THE IME
OF THE SOILS EVALVAIOH.
I SOIL SAMPLES WERE FIELD EVALUATED AND CLASSIFIED BY DDLAIMY ENDNEERINO INC. ON FEIy2VARY 22.
MW MHD MAY e. 2023. In,, WSUAL
AND TACTILE METHODS ESTAEUSH BY THE U.S. DEPARTIENT O AGRICULTURE AND THE NAT)RAL PF AWE CONSFRVATIDN - FR
VITA
FINAL
B-25-23
w
z z
oo�o
go
000 NE
zLLNZ
0M60
J5� GD v$v
¢U �p
V O
V
Z
N
Z H
O_Q
W Lv 4D - i
Z01)
us
20LL Z
Z MM3m m
W aan U
WU)w x
goa n
�ZH IN
..A U tU
U ^0Z
2
i
0
LLI ° U)
U U) IL
z
00Fh W_O o
WU 00Z f3
W j
N a
Q
(D 0
U) 0
PROJECT NO.
2231006.00
OWTS-01
C1