HomeMy WebLinkAboutState Rough Electrical Inspection ReportYou don't often get email from darrenrb7@hotmail.com. Learn why this is important
From:John Hendricks
To:Brooke Winschell; Teresa Bianco
Subject:FW: Alta Mesa Electrical: Inspection Report for Permit: 1034249
Date:Thursday, September 11, 2025 7:54:08 AM
Attachments:image001.png
Rough elec Permit #9272
John Hendricks
Building Inspector
Community Development Department
Jhendricks@garfieldcountyco.gov
Phone- 970-945-1377 ext. 1461
108 8th St, Suite 401 | Glenwood Springs, CO 81601
From: Darren Byman <darrenrb7@hotmail.com>
Sent: Thursday, September 11, 2025 7:21 AM
To: John Hendricks <jhendricks@garfieldcountyco.gov>
Subject: Fw: Alta Mesa Electrical: Inspection Report for Permit: 1034249
From: steven garza <stevengarza1991@outlook.com>
Sent: Thursday, September 11, 2025 7:13:40 AM
To: Darren Byman <darrenrb7@hotmail.com>
Subject: Alta Mesa Electrical: Inspection Report for Permit: 1034249
COLORADO STATE ELECTRICAL BOARD
1560 Broadway, Suite 1350
Denver, Colorado 80202
Automatic email - Do not reply to this email.
Inspection Report
Permit #:1034249 Date Inspected:10-SEP-25
Permit
Holder:SSteven Garza
1639 E 17th Cir Rifle 816508581
Phone: (970) 948-5826 Fax:
Email: stevengarza1991@outlook.com
Site:295 S Alta Mesa Silt County: Garfield
Owner:Casey Sheets
Byman ADU Phone:(970) 948-5826
Status:PARTIAL
Inspection Type: Rough In Trim Permit:N
Constuction Type: NEW Building Type: RESIDENTIAL
Inspector:Ryan Derouen 970-420-0635
Corrections:110.3(B) Lugs in panels listed for up to 300 kcmill, strand cut on 350's to fit
Comments:Walls and ceilings ok to cover excluding bathroom CEE in bedroom U/G service laterals and 350 URD
feeders ok to cover "S" loops in URD present for mitigation of earth movement per 300.5 Underslab rough
accepted via photos