Loading...
HomeMy WebLinkAboutManual JBold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 1 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Project Summary Sep 03, 2025Date:Entire House MTBy: Project Information Lawler RanchFor: Assume all purpose built daylight windows, no internal shading. Occupancy 4. Manual J.Notes: Design Information Garfield Co Rgnl, CO, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F2 Outside db °F95Inside db °F70 Inside db °F75 Design TD °F68 Design TD °F20Daily range H Relative humidity %50Ventilation Method Moisture difference gr/lb-45 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh41692 Structure Btuh28547 Ducts (R-8.0)Btuh7664 Ducts (R-8.0)Btuh3179Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh49356 Use manufacturer's data n Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh31821 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-918 Ducts Btuh-426Central vent (0 cfm)Btuh0 CoolingHeating24692469Area (ft²)Equipment latent load Btuh0 2709627096Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh31821 Equiv. AVF (cfm)72145 Req. total capacity at 0.70 SHR ton3.8 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 2 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Project Summary Sep 03, 2025Date:(Unconditioned)MTBy: Project Information Lawler RanchFor: Assume all purpose built daylight windows, no internal shading. Occupancy 4. Manual J.Notes: Design Information Garfield Co Rgnl, CO, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F2 Outside db °F95Inside db °F70 Inside db °F75 Design TD °F68 Design TD °F20Daily range H Relative humidity %50Ventilation Method MJ8 Moisture difference gr/lb-45 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh0 Structure Btuh0 Ducts (R-8.0)Btuh0 Ducts (R-8.0)Btuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh0 Use manufacturer's data n Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh0 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh0 Ducts Btuh0Central vent (0 cfm)Btuh0 CoolingHeating00Area (ft²)Equipment latent load Btuh0 00Volume (ft³)Air changes/hour 00 Equipment Total Load (Sen+Lat)Btuh0 Equiv. AVF (cfm)00 Req. total capacity at 0.70 SHR ton0 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Btuh0 Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat Load sensible heat ratio 0.70 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 3 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Project Summary Sep 03, 2025Date:AHU1 MTBy: Project Information Lawler RanchFor: Assume all purpose built daylight windows, no internal shading. Occupancy 4. Manual J.Notes: Design Information Garfield Co Rgnl, CO, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F2 Outside db °F95Inside db °F70 Inside db °F75 Design TD °F68 Design TD °F20Daily range H Relative humidity %50Ventilation Method MJ8 Moisture difference gr/lb-45 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh41692 Structure Btuh28547 Ducts (R-8.0)Btuh7664 Ducts (R-8.0)Btuh3179Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh49356 Use manufacturer's data n Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh31821 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-918 Ducts Btuh-426Central vent (0 cfm)Btuh0 CoolingHeating24692469Area (ft²)Equipment latent load Btuh0 2709627096Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh31821 Equiv. AVF (cfm)72145 Req. total capacity at 0.70 SHR ton3.8 Heating Equipment Summary Cooling Equipment Summary Make MakeTradeTrade Model CondAHRI ref Coil AHRI refEfficiency80 AFUE Efficiency 0 SEER Heating input Btuh0 Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm1930 Actual air flow cfm1930 Air flow factor cfm/Btuh0.039 Air flow factor cfm/Btuh0.061Static pressure in H2O0 Static pressure in H2O0 Space thermostat Load sensible heat ratio 1.00 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 1 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:Entire House MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 3290.3622362.4226.00.050923n 3450.3523472.3926.00.050981e 2780.4218902.8626.00.050661s 3500.4423783.0126.00.050791w 13020.3988512.6426.00.0503355all Partitions 12F-0sw: Frm wall, 5/8" gyp.bd ext, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 570.323441.9521.00.065176 Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 167513.4237219.000.280125n 312735.4137015.500.28088e 238121.9207119.000.280109s 279643.5122519.000.28064w 997925.8703818.200.280386all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 4.5 ft overhang (8.5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 26713.437819.000.28020n 34313.448619.000.28026n 60913.486319.000.28045all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 3.5 ft overhang (8.5 ft window ht, 0.5 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 68613.497119.000.28051s 137113.4194219.000.280102all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 5 ft overhang (8.5 ft window ht, 0 ft sep.); 6.67 ft head ht 66713.494419.000.28050s 83813.4118719.000.28062s 171413.4242819.000.280128s 321813.4455819.000.280239all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 10.5 ft overhang (8.5 ft window ht, 0.25 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 82813.4117319.000.28062s 151413.4214419.000.280113all Doors 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 2 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N Door, wd sc type 000000.300153w 361.502169.0000.30024n 360.202161.2200.300177all Ceilings Attic ceiling, mtl roof mat, r-49 ceil ins, 5/8" gypsum board int fnsh 0049.00.021587 00 Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 20590.8242421.6849.00.0252521 Floors 22B-10tpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins 000010.00.35582 Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 7010.3823491.2753.00.0291856 Flr floor, frm flr, 12" thkns, r-38 cav ins, leaky crwl ovr, r-15 wall insul 000053.00.02952 Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 2320.387761.2753.00.029613 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 3 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:AHU1 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 3290.5022363.4026.00.050658n 3450.5023473.4026.00.050690e 2780.5018903.4026.00.050556s 3500.5023783.4026.00.050700w 13020.5088513.4026.00.0502603all Partitions 12F-0sw: Frm wall, 5/8" gyp.bd ext, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 570.323441.9521.00.065176 Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 167513.4237219.000.280125n 312743.5137019.000.28072e 238121.9207119.000.280109s 279643.5122519.000.28064w 997927.0703819.000.280370all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 4.5 ft overhang (8.5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 26713.437819.000.28020n 34313.448619.000.28026n 60913.486319.000.28045all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 3.5 ft overhang (8.5 ft window ht, 0.5 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 68613.497119.000.28051s 137113.4194219.000.280102all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 5 ft overhang (8.5 ft window ht, 0 ft sep.); 6.67 ft head ht 66713.494419.000.28050s 83813.4118719.000.28062s 171413.4242819.000.280128s 321813.4455819.000.280239all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 10.5 ft overhang (8.5 ft window ht, 0.25 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 82813.4117319.000.28062s 151413.4214419.000.280113all Doors 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 4 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N Door, wd sc type 361.502169.0000.30024n Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 20590.8342421.7249.00.0252469 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 7010.3823491.2753.00.0291856 Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 2320.387761.2753.00.029613 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 5 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:(Unconditioned)MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 000026.00.050265n 000026.00.050291e 000026.00.050105s 000026.00.05091w 000026.00.050752all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 000000.28016e Doors Door, wd sc type 000000.300153w Ceilings Attic ceiling, mtl roof mat, r-49 ceil ins, 5/8" gypsum board int fnsh 0049.00.021587 00 Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 000049.00.02552 Floors 22B-10tpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins 000010.00.35582 Flr floor, frm flr, 12" thkns, r-38 cav ins, leaky crwl ovr, r-15 wall insul 000053.00.02952 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 6 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:GARAGE MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 000026.00.050265n 000026.00.050228e 000026.00.050105s 000026.00.05091w 000026.00.050689all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 000000.28016e Doors Door, wd sc type 000000.300153w Ceilings Attic ceiling, mtl roof mat, r-49 ceil ins, 5/8" gypsum board int fnsh 0049.00.021587 00 Floors 22B-10tpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins 000010.00.35582 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 7 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:MECH MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 000026.00.05063e Partitions (none) Windows (none) Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 000049.00.02552 Floors Flr floor, frm flr, 12" thkns, r-38 cav ins, leaky crwl ovr, r-15 wall insul 000053.00.02952 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 8 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:MUD MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 450.503033.4026.00.05089w Partitions 12F-0sw: Frm wall, 5/8" gyp.bd ext, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 350.322121.9521.00.065109 Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 52243.522819.000.28012w Doors Door, wd sc type 361.502169.0000.30024n Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 730.831501.7249.00.02587 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 330.381101.2753.00.02987 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 9 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:LAUNDRY MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 90.50613.4026.00.05018n 400.502743.4026.00.05080w 490.503353.4026.00.05098all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 21743.59519.000.2805w Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 770.831591.7249.00.02593 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 350.381171.2753.00.02993 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 10 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:E. HALL MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions (none) Windows (none) Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 370.83771.7249.00.02545 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 170.38561.2753.00.02945 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 11 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:PANTRY MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 280.501913.4026.00.05056s Partitions (none) Windows (none) Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 290.83591.7249.00.02534 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 130.38441.2753.00.02934 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 12 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:KITCHEN MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 670.504563.4026.00.050134n 670.504533.4026.00.050133e 400.502713.4026.00.05080s 1730.5011793.4026.00.050347all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 64513.491419.000.28048n 57421.950019.000.28026s 122016.4141419.000.28074all 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 5 ft overhang (8.5 ft window ht, 0 ft sep.); 6.67 ft head ht 66713.494419.000.28050s 83813.4118719.000.28062s 150413.4213119.000.280112all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 2790.835761.7249.00.025335 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 1270.384241.2753.00.029335 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 13 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:GREAT ROOM MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 550.503723.4026.00.050110s 500.503433.4026.00.050101w 1050.507153.4026.00.050210all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 57421.950019.000.28026s 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 5 ft overhang (8.5 ft window ht, 0 ft sep.); 6.67 ft head ht 171413.4242819.000.280128s Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 3130.836451.7249.00.025376 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 1420.384751.2753.00.029376 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 14 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:ENTRY MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 340.502283.4026.00.05067n 290.501993.4026.00.05058e 630.504273.4026.00.050126all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 4.5 ft overhang (8.5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 26713.437819.000.28020n 34313.448619.000.28026n 60913.486319.000.28045all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 680.831401.7249.00.02581 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 310.381031.2753.00.02981 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 15 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:PWDR MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 220.501493.4026.00.05044n 290.501993.4026.00.05058w 510.503483.4026.00.050102all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 10813.415219.000.2808n Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 310.83641.7249.00.02537 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 140.38471.2753.00.02937 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 16 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:W. HALL MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 310.502083.4026.00.05061n Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 29613.441919.000.28022n Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 560.831161.7249.00.02568 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 260.38861.2753.00.02968 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 17 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:OFFICE MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 90.50593.4026.00.05017s Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 110121.995819.000.28050s Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 580.831201.7249.00.02570 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 260.38891.2753.00.02970 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 18 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:PRIMARY BED MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 730.504973.4026.00.050146e 870.505953.4026.00.050175s 360.502443.4026.00.05072w 1960.5013353.4026.00.050393all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 127543.555919.000.28029e 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 10.5 ft overhang (8.5 ft window ht, 0.25 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 82813.4117319.000.28062s 151413.4214419.000.280113all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 2580.835331.7249.00.025310 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 1170.383921.2753.00.029310 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 19 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:PRIME BATH MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 700.504743.4026.00.050140n 320.502203.4026.00.05065e 1020.506943.4026.00.050204all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 15113.421419.000.28011n 119543.552419.000.28028e 134634.773819.000.28039all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 1430.832951.7249.00.025172 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 650.382171.2753.00.029172 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 20 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:WIC MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 190.501303.4026.00.05038e Partitions 12F-0sw: Frm wall, 5/8" gyp.bd ext, r-21 cav ins, 5/8" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 220.321321.9521.00.06568 Windows (none) Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 950.831961.7249.00.025114 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 430.381441.2753.00.029114 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 21 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:BED 2 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 580.503913.4026.00.050115e 350.502403.4026.00.05070s 340.502343.4026.00.05069w 1270.508643.4026.00.050254all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 63743.527919.000.28015w 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 3.5 ft overhang (8.5 ft window ht, 0.5 ft sep.); 6.67 ft head ht 68613.497119.000.28051s 68613.497119.000.28051s 137113.4194219.000.280102all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 2280.834691.7249.00.025273 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 1030.383461.2753.00.029273 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 22 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:BATH 2 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 240.501633.4026.00.05048s 480.503293.4026.00.05097w 720.504923.4026.00.050145all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 13121.911419.000.2806s 39143.517119.000.2809w 52234.828619.000.28015all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 590.831211.7249.00.02570 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 270.38891.2753.00.02970 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 23 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:BED 3 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 730.504973.4026.00.050146n 670.504573.4026.00.050134e 170.501163.4026.00.05034w 1570.5010703.4026.00.050315all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 39413.455919.000.28029n 65743.528819.000.28015e 63743.527919.000.28015w 168928.6112619.000.28059all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 1930.833981.7249.00.025232 Floors Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 870.382931.2753.00.029232 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 24 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Component Constructions Sep 03, 2025Date:BATH 3 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-5sw: Frm wall, vnl ext, 5/8" wood shth, r-21 cav ins, 5/8" gypsum board int fnsh, r-5 ext bd ins, 2"x6" wood frm, 16" o.c. stud 240.501633.4026.00.05048n 500.503373.4026.00.05099w 740.505003.4026.00.050147all Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr: 3 glazing, clr low-e outr, 1/4" gap, vnl frm mat, clr low-e mid, air gas, 1/8" thk, clr innr; 6.67 ft head ht 8113.411419.000.2806n 39143.517119.000.2809w 47231.528619.000.28015all Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 8" thkns, r-49 ceil ins 600.831241.7249.00.02572 Floors Flr floor, frm flr, 12" thkns, tile flr fnsh, r-38 cav ins, leaky crwl ovr, r-15 wall insul 270.38911.2753.00.02972 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 1 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Load Short Form Sep 03, 2025Date:Entire House MTBy: Project Information Lawler RanchFor: Design Information InfiltrationClgHtg SimplifiedMethod952Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2068Design TD (°F) H-Daily range 5050Inside humidity (%) -4565Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) AHU1 2469 49356 31726 1930 1930 (Unconditioned)640 0 0 0 0 Entire House 3108 49356 31726 1930 1930 Other equip loads 0 0 Equip. @ 1.00 RSM 31821 Latent cooling 0 TOTALS 3108 49356 31821 1930 1930 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 2 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Load Short Form Sep 03, 2025Date:(Unconditioned)MTBy: Project Information Lawler RanchFor: Design Information InfiltrationClgHtg SimplifiedMethod952Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2068Design TD (°F) H-Daily range 5050Inside humidity (%) -4565Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Btuh0 Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat Load sensible heat ratio 0.70 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) GARAGE 587 0 0 0 0 MECH 52 0 0 0 0 (Unconditioned)640 0 0 0 0 Other equip loads 0 0 Equip. @ 1.00 RSM 0 Latent cooling 0 TOTALS 640 0 0 0 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 3 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Load Short Form Sep 03, 2025Date:AHU1 MTBy: Project Information Lawler RanchFor: Design Information InfiltrationClgHtg SimplifiedMethod952Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2068Design TD (°F) H-Daily range 5050Inside humidity (%) -4565Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Trade Trade Model Cond AHRI ref Coil AHRI ref Efficiency 80 AFUE Efficiency 0 SEER Heating input Btuh0 Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm1930 Actual air flow cfm1930 Air flow factor cfm/Btuh0.039 Air flow factor cfm/Btuh0.061 Static pressure in H2O0 Static pressure in H2O0 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) MUD 87 1733 1127 68 69 LAUNDRY 93 1132 1101 44 67 E. HALL 45 158 58 6 4 PANTRY 34 508 96 20 6 KITCHEN 335 8296 5017 324 305 GREAT ROOM 376 6677 5107 261 311 ENTRY 81 2303 889 90 54 PWDR 37 1038 260 41 16 W. HALL 68 1219 468 48 28 OFFICE 70 1643 2587 64 157 PRIMARY BED 310 7401 5250 289 319 PRIME BATH 172 2995 1984 117 121 WIC 114 822 206 32 13 BED 2 273 5676 3024 222 184 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 4 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N BATH 2 70 1626 949 64 58 BED 3 232 4483 2662 175 162 BATH 3 72 1646 940 64 57 AHU1 2469 49356 31726 1930 1930 Other equip loads 0 0 Equip. @ 1.00 RSM 31821 Latent cooling 0 TOTALS 2469 49356 31821 1930 1930 Bold/italic values have been manually overridden 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 1 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Building Analysis Sep 03, 2025Date:Entire House MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 18.691952.6Walls 33.51654618.7Glazing 0.42161.2Doors 8.642421.4Ceilings 6.331251.01.0Floors 17.083681.9Infiltration 15.57664Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.049356Total Cooling Walls Glazing OtherCeilings Floors Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 4.313590.4Walls 52.61669218.8Glazing 0.1360.2Doors 6.520590.7Ceilings 2.99330.3Floors 3.912490.3Infiltration 10.03179Ducts 00Ventilation 19.66220Internal gains 00Blower 0Adjustments 100.031726Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 61 Btuh/ft²-°F, Windo w / Floor Area = 28 .5 % WARNING: window to floor area ratio = 28.5% - more than 25%. Bold/italic values have been manually overridden 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 2 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Building Analysis Sep 03, 2025Date:(Unconditioned)MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating % of loadBtuhBtuh/ft²Component 000Walls 000Glazing 000Doors 000Ceilings 0000Floors 000Infiltration 00Ducts 00Piping 00Humidification 00Ventilation0Adjustments 00Total Cooling % of loadBtuhBtuh/ft²Component 000Walls 000Glazing 000Doors 000Ceilings 000Floors 000Infiltration 00Ducts 00Ventilation 00Internal gains 00Blower 0Adjustments 00Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 60 Btuh/ft²-°F, Windo w / Floor Area = 2.6 % WARNING: window to floor area ratio = 2.6% - less than 5%. Bold/italic values have been manually overridden 2025-Sep-03 14:26:40 Rig ht-Su ite® U niv er sal 20 25 25 .0.01 RSU5 6562 Page 3 ...Mechanical\25-362 - Lawler Ranch - Manual J.rup Calc = MJ8 Front Door faces: N 25-362Job:Building Analysis Sep 03, 2025Date:AHU1 MTBy: Project Information Lawler RanchFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Garfield Co Rgnl, CO, US 2068Design TD (°F)ft6914Elevation: 5050Relative humidity (%)°N40Latitude: Outdoor:-45.264.7Moisture difference (gr/lb)CoolingHeating Infiltration:952Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality59-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 18.691953.3Walls 33.51654619.0Glazing 0.42169.0Doors 8.642421.7Ceilings 6.331251.31.3Floors 17.083682.4Infiltration 15.57664Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.049356Total Cooling Walls Glazing OtherCeilings Floors Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 4.313590.5Walls 52.61669219.2Glazing 0.1361.5Doors 6.520590.8Ceilings 2.99330.4Floors 3.912490.4Infiltration 10.03179Ducts 00Ventilation 19.66220Internal gains 00Blower 0Adjustments 100.031726Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 61 Btuh/ft²-°F, Windo w / Floor Area = 35 .2 % WARNING: window to floor area ratio = 35.2% - more than 25%.