HomeMy WebLinkAboutGeotechnical Investigation 06.06.2024Qecakuy' 4-/p*26 Huddleston-Berry Engineering & Testing, LLC 2789 Riverside Parkway Grand Junction, Colorado 81501 Phone: 970-255-8005 Info@huddlestonberry. com June 6,2024 Project#02038-001 1 MIB Construction 789 25 Road Grand Junction, Colorado 81505 Affention: Mr. Micah Berg Subject Geotechnical Investigation Parcel 217534300219 Rulison, Colorado Dear Mr. Berg, This letter presents the results of a geotechnical investigation conducted by Huddleston-Berry Engineering & Testing,LLC (HBET) at Parcel 217534300219 in Rulison, Colorado. The site location is shown on Figure 1. The proposed construction is anticipated to consist of a new single-family residence. The scope of our investigation included evaluating the subsurface conditions at the site to aid in developing foundation recommendations for the proposed construction. Site Conditions At the time of the investigation, the eastem portion of the site was occupied by an active natural gas well. The remainder of the site was open and contained slight to moderate slopes down to the north, east, and south, away from the investigated arca. The site was bordered to the north, west, and east by rural residential properties, and to the south by federal land. Subsurface nvesfioafion The subsurface investigation included three test pits as shown on Figure 2 - Site Plan. The test pits were excavated to depths of 6.0 and 7.0 feet below the existing ground surface. Typed test pit logs are included in Appendix A. As indicated on the logs, the subsurface conditions encountered at the site were fairly consistent. The test pits encountered 0.5 feet of topsoil above tano moist, medium stiff sandy lean clay soils to depths of between 2.0 and 6.5 feet below the existing ground surface. The clay soils were underlain by tan to brown, moist, medium stiff to stiff sandy lean clay soils with trace gravel and cobbles to the bottoms of the excavations. Groundwater was not encountered in the subsurface at the time of the investigation. Laboratorv Testing Laboratory testing was conducted on samples of the native soils encountered in the test pits. The testing included grain size analysis, Atterberg limits determination, natural moisture content determination, and maximum dry density and optimum moisture content (Proctor) determination. The laboratory testing results are included in Appendix B. $tt A\ N N Parcel 217534300219 #02038-001 I 06106/24 Iladdlesto&Bery Engln..tug& tiii.g. ll.C The laboratory testing results indicated that the netive clay soils are moderately plastic. In general, based upon the Atterberg limits and our experience with similar soils in the vicinity of the subject site, the native clay soils are anticipated to be slightly expansive. Foundation Recommendations Based upon the results of the subsurface investigation and nature of the proposed construction, shallow foundations are recommended. Spread footings and monolithic (turndown) structural slabs are both appropriate foundation alternatives. However, as discussed previously, the native soils are anticipated to be slightly expansive. Therefore, in order to provide a stable bearing stratum and limit the potential for excessive differential movements, it is recommended that the foundations be constructed above a minimum of 24-inches of structural fill. If a basement is proposed, HBET should be contacted to evaluate the subsurface conditions below the basement foundation elevation. Due to their plasticity, the native soils are not suitable for reuse as structural fill. Imported structural fill should consist of a granularo non-expansive, non-free druining material with greater than l0o/o passing the #20Q sieve and Liquid Limit of less than 30. However, all proposed imported structural fill materials should be approved by HBET. For spread footing foundations, the footing areas may be trenched. However, for monolithic slab foundations, the structural fill should extend across the entire building pad area to a depth of 24- inches below the turndown edges. Structural fill should extend laterally beyond the edges of the foundation a distance equal to the thickness of struotural fill. Prior to placement of structural fill. it is recommended that the bottom of the foundation excavation be scarified to a depth of 6 to 9 inches, moisture conditioned, and compacted to a minimum of 95o/o of the standard Proctor maximum dry density, within + 2oA of the optimum moisture content as determined in accordance with ASTM D698. Structural fill should be moisture conditioned, placed in maximum 8-inch loose lifts, and compacted to a minimum of 95Yo of the standard Proctor maximum dry density for fine grained soils and 90%o of the modified Proctor maximum dry density for coarse grained soils, within + 2Yo of the optimum moisture content as determined in accordance with ASTM D698 and D1557, respectively. Structural fill should be extended to within O.l-feet of the bottom of the foundation. No more than O.l-feet of gravel should be placed below the footings or turndown edge as a leveling course. For structural fill consistiug of approved imported granular materials and foundation building pad preparation as recommended, a maximum allowable bearing capacity ofJdQ0 g$.rqay be used. In addition, a modulus of 200 pci may be used for approved imported structural fill materials.Foundationssubjecttofrostshouldbeatleastalru::thefinishedgrade. Any stemwalls or retaining walls should be designed to resist lateral earth pressures. For backfill consisting of the native soils or imported granular, non-free draining, non-expansive material, we recommend that the walls be designed for an active equivalent fluid unit weight of 55 pcf in areas where no surcharge loads are present. An at-rest equivalent fluid unit weight of 75 pcf is recommended for braced walls. Laterul earth pressures should be increased as necessary to reflect any surcharge loading behind the walls. Z:V008 ALL PROJECTS\02038 - MIB\02038-00 I I Prcel 21753430021 9\200 - Geo\02038.001 I LR060624.doc 2 Parce1217534300219 7@1 #02038-oor t {ilB$)ilf**"*f"Pff06t06t24 \4Z Water soluble sulfates are common to the soils in Western Colorado. Therefore, at a minimum, Type I-II sulfate resistant cement is recommended for construction at this site. Non-Structural Floor Slab and Exterior Flatwork Recommendations In order to reduce the potential for excessive differential movements, it is recommended that non-structural floating floor slabs be constructed above a minimum of 24-inches of structural fill with subgrade preparation, structural fill materials, and fill placement be in accordance with the Foundation Recommendations section of this report. It is recommended that exterior flatwork be constructed above a minimum of l2-inches of structural fill. Drainage Recommendations Gradine and drainage are critical for the lons-term performunce of the structure and grading around the structure should be designed to carry precipitation and runoff away from the structure. It is recommended that the finished ground surface drop at least twelve inches within the first ten feet away from the structure. It is also recommended that landscaping within five feet of the structure include primarily desert plants with low water requirements. In addition, it is recommended that irrigation, including drip lines, within ten feet of foundations be minimized. HBET recommends that downspout extensions be used which discharge a minimum of 15 feet from the structure or beyond the backfill zone, whichever is greater. However, if subsurface downspout drains are utilized, they should be carefully constructed of solid-wall PVC and should daylight a minimum of 15 feet from the structure. [n addition, an impermeable membrane is recommended below subsurface downspout drain lines. Dry wells should not be used. In order to limit the potential for surface moisture to adversely impact the structure, a perimeter foundation drain is recommended. In general, the perimeter foundation drain should consist of prefabricated drain materials or perforated pipe and gravel with the flowline of the drain at the bottom of the foundation (at the highest point). The prefabricated drain materials or gravel should extend along basement walls to within 36-inches of the finished grade. The perimeter drain should slope at a minimum of I .0o/o to daylight or to a sump with pump. The drain should also include an impermeable membrane at the base to limit the potential for moisture to infiltrate vertically down below the foundations. General Notes The recommendations included above are based upon the results of the subsurface investigation and on our local experience. These conclusions and recommendations are valid only for the proposed construction. As discussed previously, the subsurface conditions encountered in the test pits were fairly consistent. However, the precise nature and extent of any subsurface variability may not become evident until construction. As a result, it is recommended that HBET provide construction materials testing and engineering oversight during the entire construction process. In addition, the homeowner and any subcontractors working on the project should be provided a copy of this report and informed of the issues associated with the presence of moisture sensitive subgrade materials at this site. aJz12008 ALL PROJECTS\02038 - MIB\02038-0011 Pxcel217534300219V00 - Geo\02038-0011 LR060624.doc Parcel 217 534300219 #02038-001 1 06/06/24 @ Iludane.sa@-Bsrry [n8bc.dng& t irbg. tlc It is important to note that the recommendations herein are intended to reduce the risk of structursl movement and/or damsge. to varving degrees, associated with volume chqnge of the native soils. However, HBET cannot predict lone-term chanses in subsurface moisture t:rttttlilittrts tlrttlhtr'flt,p. nret:ise masnilude or pxteilt of volune dtailse ln the nntivp sttils.IYhere significant increases in suhsurface moisture. nccur due,lo nonr gradine, imnrone.r stormutate,r management, utilitv line failure, excess irrieation, or other cause, either during construction or the result of actions of the propertv owner, severul inches of movement are possible. I! addition, anv failure to comnlv with the recommendations in this report releases Huddleston- Berrv Ensineerins & Testins, LLC of anv liabilitv h,ith resard to the structure performance. We are pleased to be of service to your project. Please contact us if you have any questions or comments regarding the contents of this report. Respectfully Submitted: Huddleston-Berry Engineering and Testing, LLC Michael A. Berry, P.E. Vice President of Engineering 4Z:\2008 ALL PROJECTS\02038 - MIB\02038-001 I Prccl 2175343002 l9\200 - Ceo\02038-001 I LR060624.doc FIGURES +tqPublic,net ' Garfield Countir, CO Date created: 5/ IO/2024 Ldr! udLd vPrucuru. rt lvt.wzt z.+r.ot Atvl FIGURE I Site Location Map FIGIIRF] i Site Location Map Deve I o pe d ry*) Fsbg"q',4 si Glqfublistet* Garfield County, CO FIGURE 2 Site PlanDate created: 5/ LO/2O24 Last Data Uploaded: 5/ !O/2O24 2:43:37 AM oeveronedbv()*llgFjdff APPENDIX A Typed Test Pit Logs 1 PARCEL2175343OO219.GPJ GINT US LAB,GDT 6/5/24 A P q zc3 H7 otr lTtz{ @ oo o o =.o \o{ N) oo o o 6 F d o ln 0e 6o 0c &Jo' oa t-<-o !vI mo 5o -.16z n _g-ao 'c) o !v P mo z =m ! OJ o(D;{(,l(r)5o)ooN (o {m U'{ !+zc =T[D>m i',4n -{qP AI zo{m(t t-ooomo E =o mxo Ioz =mI+oo -t o'o f (! q)ox oo mxo j oz ooz{1 o ov Io o -{mo-{ vI mo (,l o Ns o+ moxmo @ qt oo3!|.mImc, (t o N5 Im7 mxo oz I -{ mzoo'fl mxo -loz g e ono>,-lo #f 9S $fi {i?6z a ? ovoczo mt-m Ioz -{mU'{ ! -.1 LNm Io DEPTH (ft) GRAPHIC LOG -{m7 t-0 maov 1'Ioz SAMPLE ryPE NUMBER RECOVERY % (ROD) BLOW COUNTS (N VALUE) POCKET PEN. (tsD DRY UNITWT (pcf) MOISTURE CoNTENT (%) -l =E -{ tD@mno FINES CONTENT {lo) LIQUID LIMIT PLASTIC LIMIT PLASTICIry INDEX l\)(,l r\--.t'j. .t-f'..''s. a o)ao. a 9) 5.:' o (ct !)f6'(t -{o-oaIt- o TD I;: t- 0)d c)doo o a!): CL t-o A' ot ot-v 0) 3 9.on 3os 3 cn+. (F -oTD @ (^)5 N' N N (Jr (,r o (tt:s =a-J r< =6oo6'=io;lo-< 5= -JA;'dg 4o+il oa !t o. ooqq oa c.9 of o @o o 3 o otn E=q) )to (Do:+ N e- @ Fo q. mI @l Fz6 Ioo Noo s ts N JUotr c o9 @ oNo az fJoo I6 IouFoUo Huddleston-Berry Engineering & Testing, LLC TEST PIT NUMBER TP.2 PAGE 1 OF 1789 Riverside Parkway Junction, CO 81501 970-255-8005 CLIENT MIB Construction PROJECT MME Parcel 217534300219 PROJECT NUMBER 02038-001 1 PROJECT LOCATION Rulison. CO DATE STARTED 5I1OI24 COMPLETED 5/10/24 GROUND ELEVATION TEST PIT SIZE EXCAVATION CONTRACTOR Client GROUND WATER LEVELS: AT I'IME OF EXCAVATION AT END OF EXCAVATION AFTER EXCAVATION ._ EXCAVATION METHOD Trackh/Backhoe Drv LOGGED BY WDA CHECKEDBY MAB Drv NOTES IF(L IUo 00 C) I rn TEt-(9 MATERIAL DESCRIPTION IJJ(L>&FLU 5gO-->= a s t^ lIJ !J>(J 8s H @u =FlYr<60>oz z uJ(L FGup Oo 0- I 705-o to G'Ltl o\t- t ltl Oz>o() ATTERBERG LIMITS Fz lrJFzOG U)ulztr 9+ a=)- oEF 3=(L F0t 42 o_ 25 !,',. .! itja Sandy Clay with Organics (TOPSOIL) Sandy Lean CLAY (cl), tan, moist, medium stiff Sandy Lean CLAY with Trace Gravels and Cobbles (clg), tan to brown, moist, medium stiff to stiff Bottom of test pit at 6.0 feet. Tvo(- mo -.1zc3t!mn oNo(t @oo otrmz-{ =@ oo5(n Eo4o \o{ N) 00 o o IJ oo o ot ,l s o o o Lrl oc oo 0a ts,lo 0c r<|-o !vo(- mo-{ 5o{ 6z v =@o bo !v P mo-{z =m ! A' oo*{(t(/)so)ooN) (o {ma{ T {zc =-E>mi''lV-{qP -Gt zo m an t-ooomo mxo 6z 3m-{+oo mxo -{6zooz a C)+on tr' -{m u, v mct ('r o N5-l do-f, IFqto- oo Iof o+ mox 1IIq @ @ oo =!rm mI ('l o N)s Tm7 mxo -{6z I -{ mz0o.T mx c) -{6z g ? ovo>= *; 9S HH Ei? oz o ? ovoczo m|-m Ioz -{m @{!-l LNm o DEPTH (ft) GRAPHIC LOG -{mn ro maon!-toz SAMPLE TYPE NUMBER RECOVERY % (ROD) BLOW COUNTS (N VALUE) POCKET PEN. (ts0 DRY UNITWT (pc0 MOISTURE CoNTENT (%) -lr --{ =[-l@.r')fnvo FINES CONTENT (T") LIQUID LIMIT PLASTIC LIMIT PLASTICITY INDEX , r:. 1.- .-. rr'..1*: a!) o. a o) E. (ao 6'@ -lo1laIr- a> 0) o. roq) ot- ov A) 3o 6F 3osc 3 CD4 cfa: ril so..J \< =5'oo @)io6>cL< E=. J= a' -o6',9 9.a+ts oo q) CL C)oqtto U' a.(ov 0)f o (Do o 3 oo p. o, Io (Do APPENDIX B Laboratory Testing Results N @ NJU t I oc@ oNo Huddleston-Berry Engineering & Testing, LLC GRAIN SIZE DISTRIBUTION 789 Riverside Parkway Junction, CO 81501 970-255-8005 CLIENT MIB Construction PROJECT MME Parcel 217534300219 PROJECT NUMBER 02038-0011 PROJECT LOCATION Rulison, CO U,S. SIEVE OPENING IN INCHES I6 4 3 21.5 1314 112318 3 4 6 U.S. SIEVE NUMBERS HYDROMETER FIoil =m E. UJztr Fzul Otrtrl IL '100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 100 1 GRAIN SIZE IN MILLIMETERS 0.1 0.01 1 'lY IIIIIT I I\t \ t: \ t: t: COBBLES GRAVEL SAND SILT OR CLAY coarse fine coarse medium fine Specimen ldentification Classification LL PL PI Cc Cu o TP-1, GB-l 5/10 SANDY LEAN GLAY(CL)u 22 12 Specimen ldentification D100 D60 D30 D10 %Gravel %Sand %sitt o TP-1, GB-l 5110 2.36 0.088 0.0 4.7 55.3 Huddleston-Berry Engineering & Testing, LLC ATTERBERG LIMITS' RESULTS I 970-25s-800s CLIENT MIB Construction PRo.JECT MME Parcel 217534300219 PROJECT NUMBER 02038-001 1 PROJECT LOCATION Rulison. CO (e)(s) P L A s T I c I T I N D E X 50 40 30 20 10 o CL-ML @ @ 0 4 00 LIQUID LIMIT Specimen ldentification LL PL PI #200 Classification a TP.l, GB.1 5110 u 22 12 55 SANDY LEAN CLAY(CL) N PROJECT I{AME I CLIENT & Testing, LLC ?1 MO ry RE LA TIONS H IP PROJECT NUMBER PROJECT LOCATION 970-255-8005 Sample Date: Sample No.: Source of Material: Description of Material: 5t10t2024 145 24-0306 TP.1 GB-1 LEAN crA 140 Test Method (manual)ASTM D698A 135 TEST RESULTS Maximum Dry Density IOO.S pCF Optimum Water Content - nn- n130 GMDATTON RESULTS (% PASSTNG) #200 #4 100 314" 100 25 55 o o_tF6zt!o 20 ATTERBERG LIMITS E.o LL PL PIu22 12 Curves of 100o/o Saturation for Specific Gravity Equalto: 115 110 2.80 2.70 2.60 105 100 95 90 5 15 0 10 WATER CONTENT , o/o 20 25 30