Loading...
HomeMy WebLinkAboutBlower Door Test Page 1 of 1 9/12/2025 P.O. Box 1434, Edwards, CO 81632 | www.north39energy.com | 970.306.4237 Murillo Residence Air Infiltration Report Background The project goal is to undergo testing at the final point in construction to determine if the unit meets the IECC requirements for infiltration. North 39 Energy was contracted to perform a final blower door test to determine total air infiltration. The blower door testing must show a tested value of 3.0 ACH50 or lower in order to comply with the IECC. Site Observations Construction of the building envelope was complete. All exterior openings were shut and locked and interior doors were open. The pressure probe was placed outside. Blower Door Test The unit was depressurized, utilizing blower door testing equipment to a pressure of -50 Pa. At the test pressure, the CFM50 was recorded, in order to determine the ACH50. The blower door air leakage resulted in the following measurements: 2.7ACH50 Please call with any questions or concerns. Jason Weingast HERS Rater& IECC/HERS Compliance Specialist North 39 Energy Expert Energy Consulting & Verification Services Test Date: Builder: Contact: Site Address: Site Visit By: September 11th, 2025 Monico Murillo Monico Murillo 1127 Scutter Lane, Silt, CO Jason Weingast