HomeMy WebLinkAboutOWTS Installation ObservationCBO Inc.
129 Cains Lane
Carbondale, CO 81623
970.309.5259
carla.ostberg@gmail.com
October 14, 2025 Project No. C1674
Chris Hjorth
norskbuilders@gmail.com
Onsite Wastewater Treatment System (OWTS) Installation Observations
Lot 23, Stirling Ranch
Garfield County, Colorado
Permit SEPT-8286
Chris,
CBO Inc. observed the installation of the onsite wastewater treatment system (OWTS) on August 4 and
August 22, 2025 for the subject property. Norsk Builders (you, the property owner) installed the system.
The OWTS design is based on 6-bedrooms in the Main Residence and 2-bedrooms in a detached
accessory dwelling unit (ADU(. An average daily wastewater flow of 975 GPD was used.
The sewer lines exiting the ADU and Main Residence have 4-inch diameter SDR-35 sewer lines with
double-sweep clean outs and a minimum 2% grade to the septic tanks.
The system installation includes a 1000-gallon, two-compartment Infiltrator® poly septic tank with an
Orenco® Biotube Effluent filter on the outlet to serve the ADU. A 2000-gallon, two-compartment Valley
Precast concrete septic tank with an Orenco Biotube Effluent filter was installed to serve the Main
Residence. A 500-gallon, single-compartment Infiltrator® poly pump chamber was installed with an
Orenco® Pump Vault and an Orenco® PF3005 pump. The floats are set to dose 75 gallons each pump
cycle. The control panel for the pump is located within line of sight of the septic tank. The filters in these
septic tanks must be cleaned annually, or as needed. Valley Precast performed start up of the pumping
system. We performed a squirt test, tested the pump and alarm floats, and cycled the ADV at the time of our
August 22, 2025 visit.
Effluent is pumped through a 1.5-inch diameter pump line from the pump chamber to an Orenco®
automatic distributing valve (ADV), model 6404. This pump line has a 1% grade for proper drain back into
the tank after each pump cycle. The ADV is placed at a high point in the system in an insulated riser with
access from grade.
Effluent is pressure dosed through 1.5-inch diameter pipes to four gravelless chamber trenches, each
with 19 ‘Quick 4’ Plus Standard Infiltrator® chambers, for a total of 76 chambers and 912 square feet of
infiltrative area. There was at least 4-feet of undisturbed soil between each trench.
Effluent is pressure dosed to 1.5-inch diameter laterals, which are hung with zip ties from the underside
of the chambers. Laterals have 5/32-inch diameter orifices facing up, with the exception of the first and
last orifices facing down for drainage. The orifices are placed 3-feet on center. Each lateral has a 90
degree ell facing up with a ball valve for flushing. Valves are placed in a valve box, accessible from
grade, for access. Inspection ports are placed at the beginning and end of each trench. Ports are cut to
grade and covered with a valve box for access.
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. CBO Inc. should be notified if changes are made to the OWTS
in the future. Any additional OWTS construction must be according to the county regulations.
LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent on the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
CBO Inc.
Carla Ostberg, MPH, REHS
Pump Selection for a Pressurized System - Single Family Residence Project
Hjorth 7 29 25
Parameters
Discharge Assembly Size
Transport Length Before Valve
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Transport Length After Valve
Transport Pipe Class
Transport Pipe Size
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
1.25
100
40
1.50
6404
35
40
2.00
8
0
40
1.50
4
76
40
1.50
5/32
3
5
None
0
inches
feet
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity Before Valve
Transport Velocity After Valve
0.68
26
17.8
1
4.9
2.8
1.7
gpm
gpm
%
fps
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport Before Valve
Loss through Valve
Loss in Transport after Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
2.2
1.9
3.7
0.2
0.0
0.6
0.0
0.0
feet
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line Before Valve
Vol of Transport Line After Valve
Vol of Manifold
Vol of Laterals per Zone
Total Vol Before Valve
Total Vol After Valve
10.6
6.1
0.0
8.0
10.6
14.1
gals
gals
gals
gals
gals
gals
17.8
21.7
gpm
feet
0 5 10 15 20 25 30 35 40
0
50
100
150
200
250
300
Net Discharge (gpm)
PumpData
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
115/230V 1Ø 60Hz, 200V 3Ø 60Hz
PF3007 High Head Effluent Pump
30 GPM, 3/4HP
230V 1Ø 60Hz, 200/460V 3Ø 60Hz
PF3010 High Head Effluent Pump
30 GPM, 1HP
230V 1Ø 60Hz, 200/460V 3Ø 60Hz
PF3015 High Head Effluent Pump
30 GPM, 1-1/2HP
230V 1Ø 60Hz, 200/230/460V 3Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point:
Garfield County Public Health
2014 Blake Ave.
Glenwood Springs, CO 81601
Phone: (970) 945-6614 ext. 8150
For inspections, call: 970-945-6614 ext. 8150 and call the Design Engineer, if applicable
Project Address: 0 Skipper Dr Carbondale, CO _ Parcel No.: _239129205023
Owner Name: Chris Hjorth Owner Phone: (970)-445-0777
Designed By: CBO Septic Consulting, Inc. Designer Phone: (970) 309-5259
Number of Bedrooms: _8_ Minimum Tank Capacity: 3,000-gallon Minimum Absorption: 910 ft 2
OWTS PERMIT
KEEP AVAILABLE AT PROJECT SITE
Permit Number _SEPT-8286_______________________________
Permit Type X New X Repair X Remodel/addition X Tank only
Issue Date _10/04/2023____________________ Expiration Date_10/04/2024_________________
Permit Conditions:
This OWTS Permit is approved on the condition of compliance with the report and design as
submitted by CBO Septic Consulting, Inc. dated November 27, 2022. Changes to the design and
permit must be approved by Garfield County Public Health and the designer prior to construction.
The new OWTS will serve a new six-bedroom residence and a two-bedroom ADU. The system will
consist of a new, two-compartment 2,000-gallon septic tank for the residence and a 1,000 gallon
tank for the ADU set level with access to grade followed by a 500-gallon single-chamber pump
chamber set level with access to grade and a high-head pump in the pump chamber. Effluent will be
pumped to an automatic distributing valve set at the high point of the system that will distribute
effluent to 912 ft2 of STA. The new STA will consist of four gravelless chamber trenches, each trench
consisting of 19 chambers per trench (76 chambers total). Distribution laterals are to be 1 ½ inch
Schedule 40 PVC, with 5/32-inch orifices 3-feet on center and the laterals ending in flushing valves at
the distal end of the laterals. Laterals are to be hung from the underside of the chambers with zip-
ties. The orifices are to be facing upward, except for the first and last orifice (which shall face
downward for drainage purposes). Inspection ports are to be installed at each end of each trench.
Maintain all setbacks and elevations as designed.
Contact the designer and Garfield County Public Health at least 48 hours prior to requesting final
inspection of the installed system prior to backfill.
Agreement
All installations must comply with all requirements of the Garfield County OWTS regulations
including but not limited to the conditions specified above.
In consideration of the issuance of the permit, the applicant hereby agrees to comply with all
laws and regulations related to the zoning, location, construction, and erection of the proposed
OWTS and associated structures for which this permit is granted. The applicant further agrees
that if the above said regulations are not fully complied with in the zoning, location, erection,
and construction of the above described OWTS and structure, the permit may then be revoked
by notice from the Health Department and immediately become null and void.
The issuance of a permit and specifications of terms and conditions therein will not constitute
assumption of liability, nor create presumption that the local public health agency or its
employees may be liable for the failure or malfunctioning of any system. Permit issuance will
not constitute a certification that the system, the equipment used in the system, or any
component used for system operation will ensure continuous compliance with the provision of
the OWTS Act, the regulations adopted thereunder, or any terms and conditions of a permit.
Permit Approval
Plans and specifications for the proposed OWTS have been reviewed and are considered
satisfactory. Permission is hereby given to the property owner(s) to perform the work indicated
in accordance with the Garfield County OWTS Regulation. This Permit will expire 1 year from
the date of issuance unless construction on the system has commenced. An "as-built" drawing
must be submitted and inspection of the system must be completed by GCPH before final
approval of the system will be issued.
10/04/2022
Issued By: Garfield County Environmental Health
Department
Date
832‐R‐13‐002