HomeMy WebLinkAboutHeat Calcs+l* KrHghtroff Load Short Form Entire House For: Kistner Residence Date: Jun 27,2025By: rv!ry!" .' --' ,*:t i/J--. ri l]; :. r- {l ,, ,v r.r..,,i Job: 25260 (lr i: r Project l,nformation Desig,n lnformation clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 lnfiltration Outside db fD lns ide db ('F) Design TD fD Daily range lnside humidity (%) Moisture difference (gr/lb) Method Construction quality Fireplaces Simplified Average 0 HEATING EQUIPMENT COOLING EQUIPMENT $Make Trade Model AHR|ref nla nla nla nla Make nla Trade nla Cond nla Coil nla AHR|ref nla Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat ROOM NAME MAIN AHU LOWER AHU Entire House Other equip loads Equip. @ 1.00 Latent cooling TOTALS nla nla 0 0 0 0 0 0 0 atl s s \ 0 0 0 0 0 Btu Btu Btu cfm Btuh.F cfm h cfm/Btuhcfm/Btuh Hzo/tn h h H2otn nla Clg AVF (cfm) 1633 1 033 RSM 3050 3050500354058413192666 Boldlitatic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Area (tr) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) 1978 3025 29093 19821 27442 13502 1633 1 033 2666500348914 5144 39981 1214 41319 0 tt* rr*ffi Ris hGsuite@ u niversat 2024 24.o.o1 RSU6 1880 202$Sep-02 1 1:03:29 Page 1,&,l€ct ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW * **tghtssfr Load Short Form LOWER AHU Job: 25260 Date: Jun 27,2025 By: MM Project lnformation For: Kistner Residence Design lnformation clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 lnfiltration Outside db CF) lns ide db ('F) Design TD CD Daily range lnside humidity (%) Moisture d ifference (gr/lb) Method Construction quality Fireplaces Simplified Average 0 Efficiency Heating input Heating output Ternperuture rise Actual air flow Air flow factor Static pressure Space thermostat Capacitybalance point = -13 "F Backup: ROOM NAME LOWER ZONE (Unconditioned) Make Trade Model AHRI ref LOWER AHU Other equip loads Equip. @ 1.00 Latent cooling TOTALS 8.2 HSPF2 27400 Btuh @47"F33 "F 1033 cfm 0.052 cfmiBtuh0 in H2O HEATING EQUIPMENT Daikin DAIKIN DH6VSA361OA 215415505 COOLING EQUIPMENT Make DaikinTrade DAIKINCond DHOVSA3610ACoil DFVE36CP13004 AHRI ref 215415505Efficiency 8.7 EER2,16.3 SEER2 Sensible cooling 26350 Btuh Latent cooling 4650 BtuhTuLalcoulirg 31000 Btuh Actual air flow 1033 cfmAirflowfactor 0.077 cfmiBtuh Static pressure 0 in H2O Load sensible heat ratio 1.00 Clg AVF (cfm) RSM 1286 0 1033 1033302522394141521 033 Bolcilitaltc vatues have been manuatly overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Area (tr) Htg load (Btuh) Htg AVF (cfm) Clg load (Btuh) '1978 1047 19821 0 16810 0 I 033 0 3025 19821 2572 1 3502 607 14152 0 1 033 .t*romW RightSuite@ U niversal 2024 24.O.O'l RSU61880 202tsep-02 1 1:03:29 Page 2,&trch ..-R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door fac6s: NW * *tightss'fr Load Short Form MAIN AHU Job: 25260 Date: Jun 27,2025 By: MM Project lnformation For: Kistner Residence Desi lnformation clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 Infiltration Outside db fD lns ide db ('F) Design TD CF) Daily range lnside humidity (%) Moistu re difference (gr/lb) Method Construction quality Fireplaces Simplified Average 0 Make Trade Model AHRIref HEATING EQUIPMENT Daikin DAIKIN DH6VSA6OIOA 215415507 COOLING EQUIPMENT Make DaikinTrade DAIKINCond DH6VSA6010ACoil DFVE60DP1300A AHRI ref 215415507Efficiency 8.0 EER2,16.1 SEER2 Sensible cooling 41650 Btuh Latent cooling 7350 BtuhTotalcooling 49000 Btuh Actual air flow 1633 cfm Air flow factor 0.060 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 1.00 Clg AVF (cfm) Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacitybalance point= -13 'F Backup: ROOM NAME MAIN ZONE MAIN AHU Other equip loads Equip. @ 1.00 Latent cooling RSM TOTALS 8.1 HSPF2 45500 Btuh @47'F 35 'F 1633 cfm 0.056 cfm/Btuh0 in H2O 1764 1633 1633197831665281331633 Boldlitalic values have been manuatly overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Area (tr) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) 1978 29093 29637 1633 1978 29093 2572 27442 607 281 33 0 1633 *t*Y:IIffi*" Right-suite@ u niversal 2024 24.0.u RSU61880 202SSep-02 1 1:03:29 Page 3,&trct\...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW * oHghftsff Load Short Form (Unconditioned) Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 lnfiltration Outside db fD lnside db ("F) Design TD fD Daily range lnside humidity (%) Moisture difference (gr/l b) Method Construction quality Fireplaces Simplified Average 0 HEATING EQUIPMENT GOOLING EQUIPMENT Make Trade Model AHR|ref nla nla nla nla Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat ROOM NAME GARAGE (Unconditioned) Other equip loads Equip. @ 1.00 Latent cooling I(JIALD nla 0 0 0 0 0 Btuh OF cfm Make nla Trade nla Cond nla Coil nla AHRIref nla Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio in nla 0 0 0 0 0 0 0 Btuh Btuh Btuh cfm cfm/Btuhcfm/Btuh H20H20n nla Clg AVF (cfm) 0 0 RSM 1V+ I Boldlitalic vatues have been manually overrtdden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. UuUU Area (tr) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) 1047 0 0 0 1047 0 0 0 0 0 0 0 t**grlm 202$Sep-02 11:03:29 Page 4Right-Suite@ U niversal 2024 24.0.01 RSU61880&...R RESIDENCE MANUAL J AND S ZONES 2025-09,02.rup Calc = MJB Front Door faccs: NW * *rlghtsofr Load Short Form LOWER ZONE Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Design lnformation clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 lnfiltration Outside db CD lnside db ("D Design TD CD Daily range lnside humidity (%) Moisture difference (gr/lb) Method Construction quality Fireplaces Simplified Average 0 HEATING EQUIPMENT COOLING EQUIPMENT Make Trade Model AHRIref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat ROOM NAME FLEX LOWER HALL BED 1 BED 2 BATH 1 AND 2 MECH nla nla nla nla Make nla Trade nla Cond nla Coil nla AHR|ref nla Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 7085 1262 3948 3886 36 593 nla cfm/Btuh nla 0 0 0 0 0 0 0 0 0 0 0 0 Btuh OF cfm Btuh Btuh Btuh cfm cfm/Btuh 20inH H2oln nla Clg AVF (cfm) 624 248 235 264 207 401 7377 1218 2498 3775 1 385 3567 384 63 130 197 72 186 542 97 302 297 3 45 Boldlitalic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed' Htg AVF (cfm) Htg load (Btuh) Clg load (Btuh) Area (tr) ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW 202$Sep-02 l1:03:29 Page 5.& ./EClr LOWER ZONE Other equip loads Equip. @ 1.00 Latent cooling TOTALS RSM 1286 12881 978 19821 16861 1033 Botdlitatic values have been manually overildden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 1 978 19821 0 16810 0 1 6861 0 1033 't*mgg Risht-Suite@ U niversal 2024 24.0.O1 RSU61880 202$Sep-02 11:03:29 Page 6 ^&....R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW * *rlgtrttssftr Load Short Form MAIN ZONE Job: 25260 Date: Jun 27,2025 By: MM lnforrnation For: Kistner Residence Design l,n,formation clg 95 75 20 H 50 -44 Htg -16 70 86 50 73 lnfiltration Outside db CF) lns ide db ('F) Design TD CD Daily range lnside humidity (%) Moisture difference (g r/lb) Method Construction quality Fireplaces Simplified Average 0 HEATING EQUIPMENT COOLING EQUIPMENT Make Trade Model AHR|ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat ROOM NAME PRIMARY BATH PRIMARY BED OFFICE PWDR KITCHEN LAUNDRY MUD PWDR MUD DINING ENTRY GREAT ROOM MAIN HALL nla nla nla nla Make nla Trade nla Cond nla Coil nla AHR|ref nla Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 1412 5265 2696 455 1 160 1265 414 1560 2560 1568 10177 1 105 nla n nla 0 0 0 0 0 0 0 Btuh OF cfm in 0 0 0 0 0 Btuh Btuh Btuh cfm cfm/Btuhcfm/Btuh HzoH2o nla Clg AVF (cfm) 164 298 140 47 145 133 46 141 189 73 397 205 1544 4373 2664 1 136 595 2078 736 2218 2095 1 805 8043 1 805 87 245 150 64 33 117 41 125 118 101 451 101 84 313 160 27 69 75 25 93 152 93 606 66 Boldlitalic values have been manualty overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed Area (tr) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) {* v*{glHn*"2025-Sep-02 1 1:03:29 Page 7Right-Suite@ U niversal 2024 24.0.01 RSU61880.g.ccr,.R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW MAIN ZONE Other equip loads Equip. @ 1.00 Latent cooling TOTALS RSM 1764 1764197829093297261 633 Boltilitatic vatuas have been manually overrtdden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 1978 29093 29637 0 29726 0 1 633 t{"x*snm Right-Suite@ U niversal 2024 24.0.O1 RSU61880 202SSep-02 11:03:29 Page 8,&'...R RESIDENCE MANU^ L J AND S ZONES 2025-09-02.rup Catc . MJ8 Front Door faccs: NW * *HShH{}ft.Building Analysis Entire House Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Conditions Location: Garfield Co Elevation: Latitude: Outdoor: Rgnl, CO, US 8400 ft Cooling 9535 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5 40"N Drybulb ('F) Dailyrange ('D V1,bt bu lb ('F) \Mnd speed (mph) Heating ,16 15.0 Component Btuh/fl3 Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Piping Humidification Ventilation Adjustments Total 3.1 20.7 1.9 1.1 1.8 2.7 12998 16018 482 3480 5305 10631 0 0 0 5144 0 54058 24.0 29.6 0.9 6.4 9.8 19.7 0 0 0 9.5 100.0 GairS Component Btuh/ff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0.3 32.2 0.3 0.4 0 0.3 1067 24937 77 1 335 0 1344 0 1214 11220 0 0 41 196 2.6 60.5 0.2 3.2 0 3.3 0 2.9 27.2 0 100.0 (}rs Latent Cooling Load = 0 Btuh Overall U-wlu-e = 0.054 Btuh/ff-"F, Window/ Floor Area = 15.5o/o Data entries checked. Boldlitalic values have been manuatly overridden 4{* x-.:**lsy*t Ris hr-suire@ u niversat 2024 24.0.o1 RSU6 1880 202+Sep-02 1 1:03:29 Page l,*L.#cr....R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Doorfaces: NW * *aghtsoff Building Analysis LOWER AHU Job: 25260 Date: Jun 27,2025By: MM lnformation For: Kistner Residence ConditionsDes Location: Garfield Co Rgnl, CO, l-JS Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) \A,bt bulb ('F) Wind speed (mph) lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Cor rstl uctiurr quality Fireplaces GoolingHeating 75 20 50 -44. 70 86 50 72.7 5Heating _16 15.0 Cooling 9535 (H ) 59 7.5 Simplified Average 0 Component Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Piping Humidification Ventilation Adjustments Total 2.5 18.7 0 0 1.8 1.8 6462 4236 0 0 5305 381 8 0 0 0 2572 0 22394 28.9 18.9 0 0 23.7 17.1 0 0 0 11.5 100.0 Component Btuh/ff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0.1 35.6 0 0 0 0.2 389 8071 0 0 0 483 0 607 4560 0 0 14110 2.8 57.2 0 0 0 3.4 0 4.3 32.3 0 100.0 (}rs Latent Cooling Load = 0 Btuh Overall U-ralue = 0.049 Btuh/ff-'F, Wndow / Floor Nea = 7.5 o/o Data entries checked. Gairy Botdlitatic values have been manuatly ovenidden q{*- rrrl*rtrcrf't1r*%..aq Rig ht_Suite@ U niversat 2024 24.O.O1 RSU6 1BB0 ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc - MJB Front Door facos: NW 202SSep-02 11:03:29 Page 2,&* t *rlghuofr Building Analysis MAIN AHU Job: 25260 Date: Jun 27,2025 By: MM lnfornration For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, USElevation: 8400 ftLatitude: 40"N Outdoor: Drybulb ('F) Dailyrange ("F) \itbt bulb (" F) Wind speed (mph) Cooling 9535 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) Infiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 5 lin 75 20 50 -44 Coo Heating -16 15.0 Component Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors Infiltration Ducts Piping Humidification Ventilation Adjustments Total 4.3 21.5 24.1 1.7 0 3.6 6536 11782 482 3480 0 681 3 0 0 0 2572 0 31 665 20.6 37.2 1.5 11.0 0 21.5 0 0 0 8.1 100.0 Cdlirgs Cooli Comoonent Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0.4 32.5 3.9 0.7 0 0.4 678 17829 77 1 335 0 862 0 607 6660 0 0 28049 2.4 63.6 0.3 4.8 0 3.1 0 2.2 23.7 0 100.0 (}rs Latent Cooling Load = 0 Btuh Overall U-rlralue = 0.063 Btuh/ff-'F, Window / Floor Aea = 27 .7 o/o WARNING: window to floor area ratio = 27 .7o/o - more than 25o/o. Botdlitalic values have been manualty overridden "g#s. *r'l* vrrkrrrsoftr*=- *.-* - - Right-Suile@ Universal 202424.0.O1 RSU61880 ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Fronl Door faces: NW 202SSep-02 11:03:29 Page 3 * *HgFrH$,fr Building Analysis (Unconditioned) Job: 25260 Date: Jun 27,2025 By: MM Pro lnformation For: Kistner Residence n Conditions Location: Garfield Co Elevation: Latitude: Outdoor:Cooling 9535 (H ) 69 7.5 lndoor: lndoor temperature ("D Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Coo ling 75 20 50 Rgnl, CO, US 8400 ft 40'N Heating _16 15.0 -44.5 Drybulb ('F) Dailyrange ("F) \Arbt bulb ("D Wnd spebd (mph) Heati Component Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Piping Humidification Ventilation Adjustments Total 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Component Btuh/ff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Latent Cooling Load = 0 Btuh Overall U-va lue = 0.053 Btuh/ff-"F, Window / Floor Aea = 2.9 o/o WARNING: window to floor area ratio = 2.9o/o - less than 5% Eoltilitatic vatues have been manually overridden drp urpfshftsgf1'-.r*.*-.*-. Right_Suite@ Universat 2024 24.O.O1 RSU618B0 ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW 2025 Sep-02 I 1:03:29 Page 4,&,&cL * *riglrts$ft'Building Analysis LOWER ZONE Job: 25260 Date: Jun 27,2025By: MM lr,rformation For: Kistner Residence Cond.itions Location: Garfield Co Elevation: Latitude: Outdoor:Cooling 9535 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/l b) Infiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5 Coolin g Rgnl, CO, 8400 ft 40"N US Drybulb ('F) Dailyrange ("F) \A,bt bulb ("F) \Mnd speed (mph) Heating -16 15.0 Heati Component Btuh/ff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Piping Humidification Ventilation Adjustments Total 3.5 21.5 0 0 2.7 3.6 6462 4236 0 0 5305 381 8 0 0 0 0 0 98211 32.6 2 1 .4 0 0 26.8 19.3 0 0 0 0 100.0 CleeirU Component Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0.2 57 .8 0 0 0 0.4 389 11378 0 0 0 483 0 0 4560 0 0 16810 2.3 67. 2. 27. 7 0 0 0I 0 0 1 0 100.0 (Hrs Latent Cooling Load = 0 Btuh Orerall U-ralu-e = 0.045 Btuh/ff-"F, Window / Floor Area = 10.0 o/o Data entries checked. Boldlitalic values have been manuatty overridden 4F lf"ft*I#fl- Ris ht-su ire@ u niversar 2024 24.o.o.t RSU6188o ...R RESIDENCE MANUAL JAND S ZONES 2025-09-02.rup Calc = MJB Front Doorfaces: NW 202$Sep-02 11:03:29 Page 5ib 'lc*. * *uighssft.Building Analysis MAIN ZONE Job: 25260 Date: Jun 27,2025By: MM For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, USElevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) \lvbtbulb ("F) \Mnd speed (mph) lndoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture difference (g r/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5Heating -16 15.0 Cooling 9535 (H ) 59 7.5 Heati Component Btuhrff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Piping Humidification Ventilation Adjustments Total 4 21 24 1 3 5 1 7 0 3.6 6536 11782 482 3480 0 6813 0 0 0 0 0 29093 22.6 40.5 1.7 12.0 0 23.4 0 0 0 0 100.0 irgs CfEr GlairS Comoonent Btuh/ff Btuh % of load Walls Glazing Doors Ceilings Floors lnfiltration Ducts Ventilation lnternal gains Blower Adjustments Total 0.4 36.5 3.9 0.7 0 0,4 2.3 67.6 0.3 4.5 0 2.9 0 0 22.5 0 100.0 678 20025 77 1 335 0 862 0 0 6660 0 0 29637 GHrs Latent Cooling Load = 0 Btuh Overall U-ra lue = 0.063 Btuh/ff-"F, Window / Floor Area = 27 .7 % WARNING: window to floor area ratio = 27.7o/o - more than 25o/o Boldlitalic values have been manually overridden e ,{CCh -d* u'flqnbsft""i- * -e --,- Right-Suite@ Universat 202424.0.O'l RSU6.tBBO ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup catc = MJB Front Door faces: NW 202SSep-02 11:03:29 Page 6 * *rr*hffi&fr Gomponent Gonstructions Entire House Job: 25260 Date: Jun 27,2025 By: MM Pro lnformation For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ft Latitude: 40"N Outdoor: Drybulb ("F) Dailyrange ("F) \A,bt bulb ('F) Wind speed (mph) Gooling 95 35 (H ) 59 7.5 lndoor: lnd oor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44,5Heating -16 15.0 Gonstruction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud 15B19-8wc-8: Bg wall, heavy dry or light damp soil, 2'x4" wood int frm, concrete wall, r-1 0 ins, r-1 I cav ins, 1 2" thk, 112' gypsum board int fnsh Partitions Frm wall, 1/2" gyp.bd ext, r-20 cav ins, 1/2" gypsum board int fnsh 2"x6" wood frm, 16" o.c. stud Windows 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 'll4" thk, clr low-e innr: 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas,1l4" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Door, ovhd mtl, fg core type 0.048 0.048 0.048 0.048 0.048 0.034 0.034 0.034 0.034 0.034 27.0 27.0 27.0 27.O 27.0 27.0 27.0 27.0 27.0 27 -0 2.61 3.86 2.64 2.80 3.03 3.10 2.68 3.10 3.10 3.07 0.29 0.42 0.29 0.31 0.33 0.08 0 0.08 0.08 0.07 Or Area U-value Bfuh/fl3jF lnsul R fl3-" F/Btuhtr Htg HTM Loss Clg HTM Gain Btuh/tr Btuh Btuh/ff ne se sw nw all ne se SW nw all 137 349 20 45 62 48 24 42 48 775 ne SE se se SW SW SW NW nw all ne n all sw 873 817 406 688 2784 160 75 438 528 1200 20.0 2280 3149 1072 1925 8426 495 20'l 1 355 1633 3684 2559 7504 430 968 1 333 1032 516 645 1032 16018 Btuh 249 344 117 210 921 12 0 33 40 85 160 0.065 24 20 44 2't6 5.55 888 0.38 61 0.250 0.250 0.250 0.250 0.250 0.250 0.250 0.250 0.250 0.250 18.7 21.5 21.5 21.5 21.5 21.5 21.5 15.4 21.5 20.7 26.0 36.5 36.5 36.5 36.5 25.5 36.5 21.4 21-0 32.2 0 0 0 0 0 0 0 0 0 0 3567 12730 730 164',! 2262 1226 875 899 1007 24937 0.280 0.280 0.280 0.280 0 24.1 10.9 0 00 482 3.86 482 1.76 00 0 77 77 0 0 0 0 6.3 Botdlitalic values hav6 been manually overridden n{*r;n!ffi 202+Sep-02 1 1:03:29 Page 1Right-Suite@ U niversal 2024 24.o.o1 RSU61880^&.rnCl....RRESIDENCEMANUALJANDSZONES2025-09-02.rup Calc=MJg FrontDoorfaces:NW Geilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors 22D-'lSvpm: Bg floor, heaw dry or light damp soil, full ext ins cov, on grade depth, r-1 5 edge ins, r-5 ins, vinyl flr fnsh 3083 0.020 60.0 1 .13 3480 0.43 1335 25.6 0 16.6 5305 5305 207 113 320 0.298 0.298 0.298 15.0 15.0 15.0 0 0 0 0 0 0 0all Boldlltatlc values hdve been manuatly oveftidden +{} *-rgrr.aat rwr@ffile Right-Suite@ U niversal 2024 24.O.O1 RSU61880 202+Sep-02 11:03:29 Page 2&ffiA ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW # *urgffi*ofr Com ponent Constructions LOWER ZONE Job: 25260 Date: Jun 27,2025 By: MM P lnformation For: Kistner Residence Gonditions Location: Garfield Co Elevation: Latitude: Outdoor: Rgnl, CO, US 8400 ft 40'N lndoor: lndoor temperature ("F) Design TD fD Relative humidity (%) Moisture difference (g r/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 ling 75 20 50 Coo Dry bulb ('F) Dailyrange ("F) \Abt bulb ('F) \Mnd speed (mph) Heating -16 15.0 Cooling 95 35 (H ) 59 7.5 -44.5 Construction descri ptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud 15819-8wc-8: Bg wall, heavy dry or light damp soil, 2'14" wood int frm concrete wall, r-10 ins, r-19 cav ins, 12" thk, 1/2'gypsum board int fnsh Partitions (none) Windows 3 glazing, clr low-e outr, 1i4" gap, insulated vinyl frm mat, clr mid, air gas, 1t4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings (none) Floors 22D-15vpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-15 edge ins, r-5 ins, vinyl flrfnsh Or Area U-value Btuh/fl3-'F 0.048 0.048 0.048 0.048 0.034 0.034 0.034 0.034 0.034 12 120 20 45 197 207 0.298 Bolct/itatic values have been manualty overridden lnsul R Htg HTM Loss Glg HTM Gain fl3-"F/Btuh Btuh/ff Btuh Btuh/ff Btuhft, ne 266 se 338 nw 70 all 673 ne 160 se 75 sw 438 nw 528 all 1200 27.0 27.O 27.0 27.0 27 -0 27.0 27.O 27.0 27.0 4.13 4.13 4.13 4.13 3.10 2.68 3.10 3.10 3.07 1 096 1 393 289 2778 495 201 1 355 1 633 3684 0.45 0.45 0.45 0.45 0.08 0 0.08 0.08 0.07 30.0 36.5 36.5 36.5 36.1 120 152 32 304 't2 0 33 40 85 360 4377 730 1641 7108 ne se se se all 0.250 0.250 0.250 0.250 0.250 21.5 2'1.5 21.5 21.5 21.5 0 0 0 0 0 258 2580 430 968 4236 15.0 25.6 5305 0 0 n{* y:H*mf Risht-suite@ universal 202424 oo't RSU61880 2O2+Sep-O2 11iO3:29 Page 3rg.6Cl\..R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW # wdghms'fr Gom ponent Gonstructions MAIN ZONE Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) V\bt bulb ("F) Wind speed (mph) Cooling 95 35 (H ) 59 7.5 lndoor: lnd oor tempera ture ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 ling 75 20 50 Goo Heating -18 15.0 5-44 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2'x6" wood frm, 16" o.c. stud Partitions Frm wall, 112" gyp.bd ext, r-20 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Windows 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outt,1t4', gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft lread ht Doors Door, wd sc type Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12', thkns, r-60 ceil ins Floors (nonc) Area U-value ff Btuh/f!-'F 0.048 0.048 0.048 0.048 0.048 160 0.065 n 20 0.280 2036 0.020 Boldlitalic values have been manually overridden 287 425 260 396 1 368 27.0 27.0 27.0 27.0 27.0 4.13 4.13 4.13 4.'13 4.13 0.45 0.45 0.45 0.45 0.45 129 192 117 179 617 lnsul R Htg HTM Loss Clg HTM Gain fls-"F/Eltuh Btrh/tr Btuh Eltuh/fi! 1184 1756 1072 1 636 5648 20.0 5.55 888 0.38 61 Btuh Or ne se sw nw all 0 0 0 0 0 0 0 0 ne 107 se 229 sw 62 sw 48 sw 24 nw 30 nw 48 all 548 0.250 0.250 0.250 0.250 0.250 0.250 0.250 0.250 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 2301 4924 1 333 1032 516 645 1032 11782 30.0 36.5 36.5 25.5 36.5 30.0 21.0 32.5 3207 8353 2262 1226 875 899 1007 17829 0 24.1 482 3.86 77 60.0 1 .71 3480 0.66 1335 tl*mW Right-Suite@ Universal 2024 24.O.O1 RSU61880 2025'Sep-02 1 1:03:29 Page 4ArECf\...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW # wurghwafr Gomponent Constructions (Unconditioned) Job: 25260 Date: Jun 27,2025 By: MM l,nformation For: Kistngr Residence Conditions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"NOutdoor: Heating Drybulb ("F) -16 Dailyrange ("F) \Abt bulb ("F) Wind speed (mph) 15.0 lndoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling Cooling 75 20 50 -44.5 95 35 (H ) 59 7.5 Gonstruction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e oulr,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Door, ovhd mtl, fg core type Or Area ne se SW nw all U-value Btuh/f,3-'F 18 0.250 lnsul R ff-"F/Btuhfe Htg HTM Loss Glg HTM Gain Bhrh/fl3 Btuh Btuh/ff3 Btuh 320 54 146 222 743 0.048 0.048 0.048 0.048 0.048 27.0 27.0 27.0 27.0 27.0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ne NW all ne sw 12 30 24 216 o.250 0.250 0.280 0.280 0 6.3 60.0 15.0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors 22D-15vpmi Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-15 edge ins, r-5 ins, vinyl flrfnsh 1047 0.020 1 13 0.298 Boldlitatic values have been manuatly overridden 00 0 ,0 0 0 *{* gw*g*r' Risht-suite@ u niversat 2024 24.o.o1 RSU6 1880 202*Sep-02 11:03:29 Page 5,g.#c!\...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW # *dshtss Component Constructions MAIN AHU Job: 25260 Date: Jun 27,2025 By: MM lnformati,on For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ('F) V1,bt bulb ('F) Wind speed (mph) Cooling 95 35 (H ) 59 7.5 Indoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture difference (gr/l b) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 ling 75 20 50 Coo Heating -16 15.0 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partltlons Frm wall, 1/2" gyp.bd ext, r-20 cav ins, 1/2" gypsum board intfnsh, 2'16" wood frm, 16" o.c. stud Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors (none) Or Area U-value ff9 Btuh/ft'-'F 0.048 0.048 0.048 0.048 0.048 160 0.065 0.280 0.020 Boldlitalic values have been manually oveilidden lnsul R fl3-'F/Btuh Htg HTM $uh/ns Loss Glg HTM Gain Btuh Btuh/ff Btuh ne SE sw nw all 287 425 260 396 't 368 27.0 27 -0 27,0 27.0 27.0 4.13 4.13 4.13 4.13 4.'13 0.45 0.45 0.45 0.45 0.45 129 192 117 179 617 20,0 1't84 1756 1072 1636 5648 2301 4924 1 333 1032 516 645 1032 11782 5.55 888 0.38 61 107 229 62 48 24 30 48 548 20 2036 ne se SW sw sw nw nw all n 0.250 0.250 0.250 0.250 0.250 0.250 0.250 0.250 21.5 21.5 2't.5 21.5 21.5 21.5 21.5 21.5 30.0 36.5 36.5 25.5 36.5 30.0 21.0 32.5 3207 8353 2262 1226 875 899 1 007 17829 0 0 0 0 0 0 0 0 0 24.1 482 3.86 77 60.0 1.71 3480 0.66 1335 ,t* :m:*"Rig ht-Su ite@ U niversal 2024 24.0.O1 RSU6'l 880 202$Sep-02 1 l:03:29 Page 6&nccr,.R RESIDENCE MANUAL J ANO S ZONES 2025-09-02.rup Calc = MJB Front Door laces: NW # *dshecff Component Constructions LOWER AHU Job: Date By: 25260 Jun 27,2025 MM lnformation For: Kistner Residence Condition,s Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"N Outdoor: Drybulb ('F) Dailyrange ('F) \A,bt bulb ("F) Wind speed (mph) lndoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5 lingCoo Heating -1-6 15.0 95 35 (H ) 59 7.5 Cooling Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins,112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud 15819-8wc-8: Bg wall, heavy dry or light damp soil, 2'x4" wood int frm' concrete wall, r-1 0 ins, r-19 cav ins, 12" thk, 112" gypsum board int fnsh Partitions (none) Windows 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas,'114" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Door, ovhd mtl, fg core type 0.250 0.250 0.250 0.250 0.250 0.250 258 2580 430 968 0 4236 12.0 36.5 36.5 36.5 0 31 .3 360 4377 730 1641 0 71 08 Or Area U-value Btrh/ff-'F 0.048 0.048 0.048 0.048 0.048 0.034 0.034 0.034 0.034 0.034 0.280 0.280 lnsul R ff-'F/Btuhfl: Htg HTM Loss Clg HTM Gain Btuh Btuh/ff ne se SW nw all ne se sw nw all ne se se se nw all ne SW 586 392 146 292 1416 160 75 438 528 1200 30 120 20 45 12 227 27.0 27.0 27.0 27.O 27.0 27.0 27 -0 27.0 27.0 27.0 1.87 3.56 0 0.99 1.96 3.10 2.68 3.10 3.10 3.07 8.60 21 .5 21.5 21.5 0 18.7 0 1 096 1 393 0 289 2778 495 20'l '1355 1 633 3684 0.20 0.39 0 0.11 0.21 0.08 0 0.08 0.08 0.07 Bhrh/f,:Btuh 120 152 0 32 304 12 0 33 40 85 0 0 0 0 0 0 24 216 0 6.3 60.0 0 0 0 0 0 0 Ceilings Rficlg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins 1047 0.020 0 0 Floors 22D-15vpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on 207 0'298 grade depth, r-'15 edge ins, r-5 ins, vinyl flrfnsh 113 0'298 all 320 0.298 Botd/ihlic values have been manualty overridden 5305 5305 0 0 0 0 0 0 0 .s,fcr....R RESIDENCE MANUAL J AND S ZONES 2025-09-02 rup Calc = MJ8 Froni Door faces: NW 15.0 15.0 15.0 25.6 0 16.6 Page 7 202+Sep-02 11:03:29 Boldlitalic vatues have been manuatly overridden *{* g'1;p1gryt"Rig ht-Su ite@ U niversal 2024 24.O.O'l RSU6 1 880 202SSep-02 11:03:29 Page B +_ .#c*...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJ8 Front Door faces: NW * unrlehtssft Com ponent Constructions FLEX Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Conditions Location: Garfield Co Elevation: Latitude: Outdoor: Rgnl, CO, US 8400 ft 40'N Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5Heating -16 15.0 95 35 (H ) 59 7.5 Cooling Indoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Drybulb ("F) Dailyrange ("F) Vlbt bulb ('F) Wind speed (mph) Gonstruction descri ptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-O ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e oulr,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings (none) Floors 22D-15vpfi Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-15 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value fl3 Btuh/ff-'F 0.048 0.048 0.048 0.048 12 0.250 0.250 0.250 57 0.298 Botdlitalic values have been manualty ovefiidden Htg HTM Loss Clg HTM Gain Btuh/tr Btuh Btuh/fl: Btuh lnsul R fl3r F/Btuh ne 266 se 150 nw 70 all 486 75 87 ne SE all 27.0 27.0 27.0 27.0 4.13 4.13 4.13 4.13 0.45 0.45 0.45 0.45 1 096 619 289 2004 120 68 32 219 0 0 0 21.5 258 30.0 360 21.5 21.5 161 3 1871 36.5 35.6 2736 3095 015.0 25.6 1467 0 d* *mg*: Risht-suite@ universal 202424 oo1RSU6188o 202+Sep-o2'11i03:29 Page I^&.ffir,...RRESIDENCEMANUALJANDSZONES2025-09-O2.rupCalc=MJBFrontDoorfaces:NW * w*iEhtr$fB Com ponent Constructions MECH Job: 25260 Date: Jun 27,2025 By: MM ect lnformation For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'NOutdoor: Heating Drybulb ("F) -16 Dailyrange ('F) Vlbt bulb ('F) \Mnd speed (mph) 1S.0 Gooling 95 35 (H ) 59 7.5 lndoor: lnd oor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Constructlon quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5 Gonstruction descriptions Walls 15819-Bwc-8: Bg wall, heavy dry or light damp soil, 2'x4" wood int frm, concrete wall, r-10 ins, r-19 cav ins, 12" thk, 112" gypsum board int fnsh Partitions (none) Windows (none) Doors (none) Ceilings (none) Floors 22D-15vpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-1 5 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value te Btuh/flF-"F 56 0.298 Boldlitalic values have been mdnuatly overriddan 160 160 240 560 0.034 0.034 0.034 0.034 27.0 27.0 27.0 27.0 3.10 3.10 3.10 3.'10 495 495 743 1734 0.08 0.08 0.08 0.08 12 12 18 42 lnsul R Htg HTM Loss Clg HTM Gain ff-"F/Eltuh Btuh/fl: Btuh Btrfr/tr Btuh 15.0 25.6 1435 0 0 ne SW nw all *t*#:!m Rightsuite@ U niversal 2024 24.O.O1 RSU61B8O 202$Sep-02 11:03:29 Page 10 Atrch ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW # **qght$ofr Gomponent Gonstructions BATH 1 AND 2 Job: Date By: 25260 Jun27,2025 MM lnformation For: Kistner Residence n Gonditions Location: Garfield Co Rgnl, CO, Elevation: 8400 ft Latitude: 40'N Outdoor: Drybulb ('F) Dailyrange ('F) Vvbt bulb ('D Wnd speed (mPh) ling 75 20 50 Coo US lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/l b) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Heating -16 15.0 Cooling 95 35 (H ) 59 7.5 -44.5 Gonstruction descriptions Walls 15819-8wc-8: Bg wall, heavy dry or light damp soil, 2'x4" wood int frm, nw concrete wall, r-1 0 ins, r-19 cav ins, 12" thk, 112" gypsum board int fnsh Partitions (none) Windows (none) Doors (none) Ceilings (none) Floors 22D-1Svpm: Bg floor, heavy dry or light damp soil, full ext ins cov' on grade depth, r-15 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value Btrh/fl:-"F 218 0.034 22 0.298 Boldlitatic values have bsen manually overridden ftr lnsul R fe-'FlBtuh Htg HTM Btuh/tr 3.10 Loss clg HTM Gain Btuh Eltuh/ff Btuh 673 0.08 1627.0 15.0 25.6 557 0 202+Sep-02 1 l:03:29 Page 11&ffil ...RRESIDENCEMANUALJANDSZoNES2025-09-02'rupcalc=MJSFrontDoorfaces:NW * wrtghBsfr Gom ponent Constructions BED 2 Job: 25260 Date: Jun 27,2025 By: MM Pro I n For: Kistner Residence Design Conditions Locatlon: Garfield Co Rgnl, CO, USElevation: 8400 ftLatitude: 40"N Outdoor: Dry bulb ('F) Dailyrange ('F) \A,bt bulb (" F) \Mnd speed (mph) Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltratlon: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5Heating -16 15.0 Construction descriptions Walls 15819-8wc-8: Bg wall, heavy dry or light damp soil, 2,14" wood int frm, concrete wall, r-10 ins, r-19 cav ins, 12" thk, 112" gypsum board int fnsh Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, ait gas, 114" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings (nonc) Floors 22D-15vpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-1 5 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value Btuh/n:-'F 0.034 0.034 0.034 0.034 se 45 0.250 47 0.298 Boldlitalic values have been manually overridden ft, lnsul R ffr F/Btuh Htg HTM Loss Clg HTM Gain Btuh/ff Btuh Eltuh/ff Btuh se 75 sw 278 nw 70 all 423 27.0 27.0 27.0 27.0 0 0.08 0.08 0.06 0 21 5 26 2.68 3.10 3.10 3.02 201 859 217 1277 0 21.5 968 36.5 1641 15.0 25.6 1 198 0 0 tl*grm.*: Right-Suite@ U niversat 2024 24.O.O1 RSU6lBBO 202$Sep-02 11:03:29 Page 12 Atrc*....R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJ8 Front Door faces: NW * *dghtso#f Gomponent Gonstructions BED 1 Job: 25260 Date: Jun 27,2025 By: MM lnformati,on For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"NOutdoor: Heating Drybulb ('F) -16 Dailyrange ('F) V1,bt bu lb ('F) Wind speed (mph) 15.0 Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5 Coolin g Construction descriptions Walls 'l2F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Geilings (none) Floors 22D-15vpm. Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-1 5 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value fla Btuh/ff'z-'F se 123 0.048 se 45 0.250 17 0.298 Boldlitalic values have been manually overridden Htg HTM Loss Clg HTM Gain Btuh/flr Btuh Btuh/ff Btuh 4.13 506 0.45 55 21 .5 968 36.5 1641 15.0 25.6 429 0 lnsul R ff-'F/Eltuh 27.0 nt* :f*S,l*3tr Rishrsuite@ u niversar 2oz4 24.o.o1RSU6 t88o 202tsep-02 l1:03:29 Page 13,&#cr ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW # *dgheo,ff Component Constructions LOWER HALL Job: 25260 Date: Jun 27,2025 By: MM lnformationP For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"N Outdoor: Drybulb ("F) Dallyrange ("F) Vlbt bulb (" F) Wind speed (mph) Heating -16 15.0 Gooling 95 35 (H ) 59 7,5 Indoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling 75 20 50 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins,1l2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings (none) Floors 22D-1Svpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-15 edge ins, r-5 ins, vinyl flr fnsh Or Area U-value Btuh/tr-"F 0.048se 65 se 20 0.250 9 0.298 Boldlitatic vatues have be6n manually oveilidden Insul R Htg HTM Loss Glg HTM Gain ff3-'F/Btuh Btuh/tr Btuh Btuh/tr Btuh 27.0 4.13 268 0.45 29 0 2'1.5 430 36.5 730 ft 15.0 25.6 218 0 0 ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJ8 Front Door faces: NW 202+Sep-02 1 l:03:29 Page 14e#fr I{* wrightsoft Component Gonstructions PRIMARY BATH Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"N Outdoor: Dry bul b ("F) Dailyrange ("F) V\,bt bu lb (" F) Wind speed (mph) Gooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture d ifference (g r/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5 Coolin g Heating -16 15.0 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Or Area se U-value Biuh/tr-'F 0.048 lnsul R Htg HTM ff:F/Btuh Btuh/fl! Loss Clg HTM Gain Btuh Btuh/ffft, 86 Btuh 39 Ceilings Rflclg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins se 24 0.250 164 0.020 Boldlitalic values have been manualty overridden 27.0 4.13 356 0.45 60.0 0 21 .5 516 36.5 875 1 .71 280 0.66 108 Floors (none) r{p r,s*l*:ty Rishrsuite@ u niversal 2024 24.0.o1RSU61880 202SSep-02 11:03:29 Page 15.s.m-..R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW * *df,hkofts Gom ponent Constructions PRIMARY BED Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F; vubt bulb ("F) Wind speed (mph) Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD CF) Relative humidity (%) Moisture difference (gr/l b) lnfiltration: Method Construction quality Fireplaces CoolngHeati ng -44.5 70 86 50 72.7 Simplified Average 0 75 20 50 Heating -16 15.0 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 112', gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e oulr,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, .l/4', gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12,' thkns, r-60 ceil ins Floors (none) Or Area U-value Bfuh/ffJF 0.250 lnsul R fl3r F/Btuh 60.0 Btuhff Htg HTM Loss Clg HTM Gain Btuh/ff3 Btuh Btuh/ff ne 108 se 92 nw 22 all 222 25 60 85 ne se all 0.048 0.048 0.048 0.048 27.0 27.0 27.0 27.0 4.13 4.'t3 4.13 4.13 0.45 0.45 0.45 0.45 445 381 90 915 49 42 10 100 0 0 0 2't.5 538 30.0 749 0.250 0.250 21.5 21.5 2189 2938 1290 1828 36.5 34.6 316 0.020 Boltllitalic vatues have been manuatly oveffid.ten 1.71 539 0.66 207 ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW 2025-Sop-02 11:03:29 Page 16 Ascl # *dsheoro Gomponent Gonstructions OFFICE Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Conditi,ons Location: Garfield Go Rgnl, CO, US Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ('F) V\bt bulb (" F) Wind speed (mPh) Gooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces ling 75 20 50 GooHeating 70 86 50 72.7 Simplified Average 0 Heating -16 15.0 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Or Area U-value lnsul R Htg HTM Loss Clg HTM Gain Btuh Btuh/ff ne nw all 57 63 120 ft" Btrh/fl:-'F 0.048 0.048 0.048 fti-"F/Eauh Btuh/f 27.0 27.0 27.0 60.0 4.13 4.13 4.13 235 260 495 0.45 0.45 0.45 Btuh 26 28 54 Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins ne 60 0.250 140 0.020 Botdlitalic values have been manuatly oveilid.ten 0 21 .5 1290 30.0 1798 1.71 239 0.66 92 Floors (none) -* H5m-H:ry Ris ht-su ite@ u niversal 2024 24.o.o't Rsuo 1 880 2O2+Sep-O211:03:29 Page 17,&#cl\...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW # *dshffis r Com ponent Constructions PWDR Job: 25260 Date: Jun 27,2025 By: MM ation For: Kistner Residence Conditions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40"N Outdoor: Drybulb ("F) Dailyrange ('F) \Abt bulb ('F) \Mnd speed (mph) Cooling 95 35 (H ) 59 7.5 Indoor: lnd oor temperature ('F) Design TD fD Relative humidity (%) Moistu re difference (gr/lb) Infiltration: Method Construction quality Fireplaces Heati ling 75 20 50 Goong Simplified Average 0 70 86 50 72.7Heating -16 15.0 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud 0.048 0.048 0.048 27.0 27.0 27.0 4.13 4.13 4"13 0.45 0.45 0.45 Htg HTM Loss Clg HTM Gain Bhrh/ff Btuh Btuh/ff Btuh 226 260 486 Or Area U-value Bhh/tr-'F lnsul R ff-'F/Btuhft, sw nw all 55 63 118 25 28 53 Partitions (none) Windows 3 glazing, clr low-e oulr,1l4" gap, insulated vinyl frm mat, clr mid, air sw gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors (none) Boldlitalic values have been manually ovenidden 6 0.250 47 0.020 0 21.5 129 36.5 2't9 60.0 1.71 81 0.66 31 {*:rst*Fjf Right-Suite@ U niversal 2024 24.O.01 RSU61880 2O25-Sep-02 11:O3i29 Page 18 .t,ffi*,-..R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW +f ur*tehEo#r Gomponent Gonstructions KITCHEN Job: Date By: 25260 Jun27,2025 MM lnformationP For: Kistner Residence Design Conditions Location: Garfield Co Elevation: Latitude: Outdoor: Rgnl, CO, US 8400 ft 40'N Gooling 95 35 (H ) 59 7.5 lndoor: lnd oor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5 Goolin g Heating -16Dry bulb ('F) Dailyrange ('F) \Abt bulb ('F) Wind speed (mph)15.0 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins,'112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows (none) Doors (none) Floors (none) Or Area U-value Btuh/fl4-'F NW 0.048 1sl 0.020 Boldlitalic values have been manually overridden lnsul R Htg HTM Loss Clg HTM Gain fFrFlEltuh Btuh/ff Btuh Btuh/ff Btuh 27 .O 4.13 181 0.45 20 60.0 1.7't 258 0.66 99 fl3 44 Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins t{* ystgffi Ris hlsuite@ u niversal 2024 24.o.01 RSU6 1880 202tSep-02 1 1:03:29 Page 19.&,#a ..R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJg Front Door faces: NW * wxshrcuf?Gomponent Constructions LAUNDRY Job: 25260 Date: Jun 27,2025 By: MM lnformationP For: Kistner Residence Design Gonditions Location: Garfield Co Elevation: Latitude: Outdoor:Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ("F) Design TD CD Relative humidity (%) Moisture d ifference (grllb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Gooling Rgnl, CO, US 8400 ft 40'N 75 20 50 -44.5 Dry bulb ("F) Dailyrange ("F) Vl,bt bulb ('F) Wind speed (mph) Heating -16 15.0 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins,'lt2', gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions Frm wall, 1/2" gyp.bd ext, r-20 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air ne gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr,1l4,' gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors (none) Boldlitalic vatues have been manualty overridden Or Area U-value ff Btuh/ft,.'F ne 122 0.048 0.065 0.250 133 0.020 lnsul R fF-'F/Eltuh 27.0 Htg HTM Bfuh/tr 4.13 Loss Clg HTM Btuh Btuh/ff 504 0.45 Gain 65 22 20.0 5.55 362 0.38 0 21.5 473 30.0 Btuh 55 25 659 60.0 1.71 228 0.66 87 +lP *yr.fgrtgorlt* rbw;!i@*.@{%RightSuite@ Universal 2024 24.O.O1 RSU6.l8BO 202$Sep-02 1 1:03:29 Page 20 .+m,.R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJ8 Front Door faces: NW {} wril*htssftr Gomponent Constructions MUD PWDR Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence ConditionsDes Location: Garfield Co Elevation: Latitude: Outdoor: Rgnl, CO, US 8400 ft 40'N Heating 70 86 50 72.7 Simplified Average 0 Gooling 75 20 50 -44.5 Drybulb ('F) Dailyrange ("F) \Abt bulb ('F) Wind speed (mph) Heating -16 15.0 Cooling 95 35 (H ) 59 7.5 lndoor: lnd oor tem perature ('F) Design TD CD Relative humidity (%) Moisture difference (g r/lb) lnfiltration: Method Construction quality Fireplaces Gonstruction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins,2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air sw gas,'1t4" thk, clr low-e innr: 3 glazing, clr low-e oulr,114" gap, insulated vinyl frm mat, clr mid, air gas, 'll4" thk, clr low-e innr; 6'67 ft head ht Doors (none) Area U-value Btuh/ff:-"F 66 0.048 6 0.250 46 0.020 Botctlitalic vatues have been manually overridden fF Or SW lnsul R fe-'F/Btuh 27.0 0 60.0 Htg HTM Btuh/tr 4.13 Loss Glg HTM Gain Btuh Btuh/ff Btuh 272 0.45 30 21.5 129 36.5 219 Ceilings Rflcb c6iling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins 1.71 79 0.66 30 Floors (none) 202$Sep-02 1 l:03:29 Page 21.+,ffi ...R RESIDENCE MANUAL J AND S ZONES 2025-o9-02.rup Calc = MJg Front Doorfaces: NW * *rlghtsotr Com ponent Gonstructions MUD Job: 25260 Date: Jun 27,2025 By: MM For: Kistner Residence Design Gonditions Location: Garfield Co Elevation: Latitude: Outdoor: Drybulb ("F) Indoor: lnd oor temperature ("F) Design TD fD Relative humidity (%) Moisture difference (gr/l b) Infiltration: Method Construction quality Fireplaces ngCoolHeating Rgnl, CO, US 8400 ft 40'N 70 86 50 72.7 Simplified Average 0 75 20 50 -44.5Heating -16 15.0 95 35 (H ) 59 7.5 Cooling Dailyrange ('F) V1,bt bulb ('F) Wind speed (mph) Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions Frm wall, 1/2" gyp.bd ext, r-20 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Windows 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4', gap, insulated vinyl frm mat, clr mid, air gas, 'l14" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Geilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8,'gypsum board int fnsh, 12" thkn8, r 60 ceil ins Floors (none) Or Area U-value Btuh/ff3-'F 0.048sw 48 0.065 sw 0.250 n 20 0.280 141 0.020 Boldlitatic values have been manually overridden 0 24.1 482 3.86 77 60.0 1.71 241 0.66 92 lnsul R ff-'F/Btuh 27.0 20.0 Htg HTM Bfuh/tr 4.13 Loss Glg HTM Btuh Btuh/ns 198 0.45 Gain fls Btuh 22 36 875 95 24 0 5.55 526 0.38 21 .5 516 36.5 tl*x:!ffi Right-Suite@ U niversal 2024 24.O.Oj RSU61880 202$Sep-02 11 :03:29 Page 22 A,frch ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02_rup Catc = MJB Front Door facas: NW * wdsht*otts Gomponent Constructions DINING Job: 25260 Date: Jun 27,2025 By: MM lnforrnati,on For: Kistner Residence Design Cond,itions Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'NOutdoor: Heating Drybulb ('F) -16 Dailyrange ('F) \A,bt bulb ('F) Wind speed (mph) 15.0 Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD fD Relative humidity (%) Moisture d ifference (grll b) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72,7 Simplified Average 0 Cooling 75 20 50 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins,112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Or Area U-value Btuh/fl3-"F 0.048se 130 se 30 0.250 200 0.020 Bold/italic values have been manuatly overridden Htg HTM Loss Clg HTM Gain Btuh/tr Btuh Btuh/ff Btuh 4.13 538 0.45 59 0 21 .5 645 36.5 1094 ff lnsul R fF-" F/Eltuh 27.0 Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns. r-60 ceil ins 60.0 't .71 342 0.66 131 Floors (none) 202aSep-02 1 1:03:29 Page 23.&rmh ...R RESIDENCE MANUAL J AND S ZONES 2o25-09-O2.rup Calc = MJB Front Doorfaces: NW # wdshtsotr Com ponent Constructions ENTRY Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Location: Garfield Co Rgnl, CO, US Elevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) V1btbulb('D \Mnd speed (mph) Gooling 95 35 (H ) 59 7.5 lndoor: lndoor temperafure ('F) Design TD fD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cool ng -44.5 75 20 50 Heating -16 15.0 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors (none) Or Area U-value Btuh/tr-'F nw 0.048 6 0.250 0.250 0.250 73 0.020 Botdlitaltc valuas havc been manuatly ovenidden lnsul R Htg HTM Loss Clg HTM fi:-"F/Btuh Btuh/tr Btuh Btuh/ff 0.4527.0 4"'t3 176 21 .5 129 30.0 t 80 Gain BtuhfF 43 19 0 0 0 21 2'l 48 54 nw NW all 5 5 1032 1161 21.0 22.0 1 007 1't87 60.0 1.71 124 0.66 48 *l*m**:gf Risht-Suite@ U niversal 2024 24.0.01 RSU61880 2O2USep-O2 11:03:29 Page 24sffi...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJg Front Door faces: NW '{* wrlehrcoff Com ponent Gonstructions GREAT ROOM Job: 25260 Date: Jun 27,2025 By: MM P l,nformation For: Kistner Residence Gonditions Location: Garfield Co Rgnl, CO, Elevation: 8400 ft Latitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("D \Abt bulb (" F) \Mnd speed (mph) lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Cooling US 5 75 20 50 -44.Heating -16 Cooling 95 35 (H ) 59 7.515.0 Gonstruction descri ptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 1/2" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c' stud Partitions (none) Windows 3 glazing, clr low-e oult,114" gap, insulated vinyl frm mat, clr mid, air gas, 1t4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors (none) Or Area U-value Btuh/fl'?-"F 115 50 48 213 421 0.020 Botdlitalic vatues have been manually overfidden Htg HTM Loss Clg HTM Gain Btrh/f,i Btuh Bluh/ff Btuhf1c lnsul R ff-'F/Eltuh 117 91 51 259 se sw nw all se sw sw all 0.048 0.048 0.048 0.048 27.O 27.0 27.0 27.0 4.13 4.13 4.'.!3 4.13 0.45 0.45 0.45 0.45 481 376 2't'l 1067 2473 1075 1032 4580 53 41 23 117 4195 1824 1226 7244 0.250 0.250 0.250 o.250 21.5 21.5 21.5 21.5 36.5 36.5 25.5 34.0 0 0 0 0 Ceilings Rflclg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins 60.0 1.71 715 0.66 276 Floors (none) *l* mr*:ggr:: Ris ht-suite@ u niversar 2024 24.o.01 RSU6 1880 202$Sep-02 1 l:03:29 Page 255- f,a ...RRESIDENCEMANUALJANDSZONES2O2S-09-o2rupCalc=MJSFrontDoorfaces:NW * *gnhes,ff Gom ponent Constructions MAIN HALL Job: 25280 Date: Jun 27,2025 By: MM Pro For: Kistner Residence Design Conditiorrs Location: Garfield Co Rgnl, CO, USElevation: 8400 ftLatitude: 40'N Outdoor: Drybulb ("F) Dailyrange ("F) \Abt bulb ('F) \Mnd speed (mph) Cooling 95 35 (H ) 59 7.5 lndoor: lndoortemperafure ('F) Design TD fD Relative humidity (%) Moisture difference (grllb) lnfiltration: Method Construction quality Fireplaces eatiH ling 75 20 50 Coong Simplified Average 0 70 86 50 72.7Heating -16 15.0 -44.5 Gonstruction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, 112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Or Area NW 111 U-value Btuh/tr-'F 0.048 lnsul R ff-"F/Btuh Htg HTM Loss Clg HTM Gain Btuh/fr3 Btuh 50 ft,Btuh 458 Btuh/ff 0.45 Partitions (none) Windows 3 glazing, clr low-e outr,1l4" gap, insulated vinyl frm mat, clr mid, air nw gas, '114" thk, clr low-e innr: 3 glazing, clr low-e outr,1t4', gap, insulated vinyl frm mat, clr mid, air gas, 'l14" thk, clr low-e innr; 6.67 ft head ht Doors (none) Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12,' thkns, r-60 ceil ins Floors (none) Bokilitalic values have been manuatly ovenidden 24 0.250 205 0.020 27.0 4.13 0 21 .5 516 30.0 719 60.0 1.71 350 0.66 134 f wr6frt*o,ft Rig ht-Su ite@ U niv ersal 2024 24.O.O't RSU6 1 BB0 202$Sep-02 11:03:29 Page 26 A,/Ea ..R RESIDENCE MANUAL J AND S ZONES 2o25-09-02.rup Catc = MJ8 Front Door faces: NW # *,*ghtsoff Com ponent Constructions GARAGE Job: 25260 Date: Jun 27,2025 By: MM lnforr,nati,on For: Kistner Residence Conditions Location: Garfield Co Elevation: Latitude: Outdoor: ling 75 20 50 Coo Rgnl, CO, US 8400 ft 40"N Cooling 95 35 (H ) 59 7.5 lndoor: lndoor temperature ('F) Design TD CD Relative humidity (%) Moisture difference (gr/lb) lnfiltration: Method Construction quality Fireplaces Heating 70 86 50 72.7 Simplified Average 0 Drybulb ("F) Dailyrange ("F) \Abt bulb (" F) Wind speed (mph) Heating -16 15.0 -44.5 Construction descriptions Walls 12F-6sw: Frm wall, stucco ext, r-30 cav ins, '112" gypsum board int fnsh, r-6 ext bd ins, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 3 glazing, clr low-e outt,114" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr: 3 glazing, clr low-e outr, 1/4" gap, insulated vinyl frm mat, clr mid, air gas, 1/4" thk, clr low-e innr; 6.67 ft head ht Doors Door, wd sc type Door, ovhd mtl, fg core type Or Area U-value Btuh/tr-'F 0.250 0.250 0.280 0.280 lnsul R fl3-'F/Eltuh 0 6.3 60.0 15.0 ft, Htg HTM Loss Clg HTM Gain Btuh/fl3 Btuh Btuh/ff Btuh 320 54 146 222 743 ne se sw nw all 0.048 0.048 0.048 0.048 0.048 27.0 27.0 27.0 27.0 27.O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ne 18 0.250 0 0 0 0 0 n 0 0 0 0 0 0 0 0 nw 12 30 ne sw 24 216 0 0 0 0 0 0 0 0 Ceilings Rf/clg ceiling, mtl roof mat, frm cons, 5/8" gypsum board int fnsh, 12" thkns, r-60 ceil ins Floors 22D-15vpm: Bg floor, heavy dry or light damp soil, full ext ins cov, on grade depth, r-15 edge ins, r-5 ins, vinyl flr fnsh 1047 0.020 113 0.298 Boldlitalic values have been manually ovenidden 0 0 00 00 0 0 d* stg:'Hg#202SSep-02 1 1 :03:29 Page 27Rig ht-Suite@ U niversal 2024 24.o.o1 RSU61880.&,mct .-.R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW +{* *,qghtssff H?1,:"b:;S'"" Job: 25260 Date: Jun 27,2025By: MM lnformation For: Kistner Residence Notes:All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. Weather: Winter Design Gonditions Outside db lnside db Design TD VentilationMethod ASHRAE62.2-2019 Heating Summary Structure Ducts Central vent (149 cfm) Humidification Pioino E{uiPYment load lnfiltration Garfield Co Rgnl, CO, US ,16'F 70 'F 86 "F Outside db lnside db Desiqn TD Daily-range Relative humiditv Moisture differerice Summer Design Gonditions 95 'F Sensible Gooling Equipment Load Sizing 75 "F20 "F H 50 o/o -44 grllb Structure Ducts Centralvent (149 cfm) Blower Use manufacturer's data 39981 Btuh0 Btuh 1214 Btuh 0 Btuh n 1.00 41319 Btuh 0 Btuh 41319 Btuh 4.1 ton 0 Btuh0 Btuh 54058 Btuh Simplified Averane Heatinq Coolinq395d 3956' 48914 Btuh0 Btuh 5144 Btuh Method Construction quality Frreplaces Area (ftJ Volume (ff) Air chan!e's/hour Equiv. AVF (cfm) Heating Equipment Summary Make nlaTrade nlaModel nlaAHR|ref nla Efficiency nla Heatino inout lJootinX nrilnr rl fl Fl*r rlqv utgt I Temperature rise 0 'F Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat nla Rate/swino multiolier Equipmenf sensible load Latent Gooling Equipment Load Sizing Structure -1020 BtuhDucts 0 Btuh Centralvent (149 cfm) -1644 Btuh Equipment latent load Equipment Total Load (Sen+Lat) Req. total capacity at 0.85 SHR Gooling Equipment Summary Make nlaTrade nlaCond nlaCoil nlaAHR|ref nla Efficiency Sensible coolinoI -r^,-r -^^t;,-- -Lqtgt rt 9vvilr rg Total coolino Actual air flo'w Air flow factor Static pressure Load sensible heat ratio 32922 0.28 154 32922 0.15 82 in nla 0 0 0 0 0 0 BtuhDa..l*Dtut r Btuh cfm H20 cfm/Btuh Boldlitatic vdlues have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. {tl+ rnrrlg}rboft*' ,,;,,,",..o-il..,"";i.!s -.--, Right-Suite@Universat 202424.0.01 RSU61BB0 202$Sep-02 l 1:03:29 Page 1&,...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW # *'ishrsofr iHfrE|Summary AHU Job: Date By: 25260 Jun 27,2025 MM For: Kistner Residence Notes All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. Des Weather: Winter Design Gonditions Outside db lnside db Design TD VentilationMethod ASHRAE62.2-2019 Heating Summary Garfield Co Rgnl, CO, US Summer Design Gonditions -16 "F70 "F 86 'F Outside db lnside db Desion TD Daily"range Relative humidity Moisture difference 95 "F75 "F 20 "F H 50%-44 grllb n 1.00 14152 Btuh 14152 Btuh 1.4 ton Structure Ducts Central vent (SER=50% 7 4 cfm) Enerov recoverv Humidification ' Pioino EtiuiPiment load lnfiltration Method Construction quality Fireplaces Sensible Gooling Equipment Load Sizing Structure 13502 BtuhDucts 0 Btuh Centralvent (SER=50%74 cfm) 607 Btuh Enerov recovervBlow6i ' o Btuh Use manufacturer's data Rate/swino multiolier Equipmenl sensible load Latent Cooling Equipment Load Sizing Structure -254 BtuhDucts 0 Btuh Central vent (LER=SOo6 74 cfm) -822 Btuh Enerov recovery Equidfrrent latefit load 0 Btuh Equipment Total Load (Sen+Lat) Req. total capacity at 0.85 SHR Gooling Equipment Summary Make DaikinTrade DAIKINCond DHOVSA3610ACoil DFVE36CP13004 AHRI ref 215415505Efficiency 8.7 EER2,16.3 SEER2 Sensible cooling 26350 Btuh Latent cooling - 4650 Btuh Total coolino 31000 Btuh Actual air flo:w 1033 cfm Air flow factor 0.077 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 1.00 19821 0 2572 0 0 22394 Btuh Btuh Btuh Btuh Btuh Btuh Simplified Average Heatino Coolinq Area (ftJ 197{ 197{ Volume (ff) 12808 12808 Air chanle's/hour 0.26 0.14 Equiv. AVF (cfm) 55 30 Heating Equipment Summary Make DaikinTrade DAIKINModel DH6VSA3610AAHR|ref 2'15415505 Efficiency Heating input Heating output Temoerature rise Actubl air flow Air flow factor Static pressure Soace thermostat Capacitybalance point = -13 "F Backuo: lnput = 0 Btuh, Output = 0 Btuh, 80 AFUE Boldlitalic values have been manualty overridden 8.2 HSPF2 27400 Bluh@47"F 33 "F 1033 cfm 0.052 cfm/Btuh0 in H2O Calculations approved by ACCA to meet all requirements of Manual J 8th Ed +l+ wrrgttc.plt' ^ 202SSep-02 11:03:29 Page 2rS ,4cc*-...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW * *'isfttssff rrf/,iff,ymmary Job: 25260 Date: Jun 27,2025By: MM For: Kistner Residence Notes All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. lnformation Outside db lnside db Design TD Make Trade Model AHR|ref Weather: Winter Design Conditions Garfield Co Rgnl, CO, US Summer Design Conditions Outside db lnside db Desion TD Daily"range Relative humiditv Moisture differedce -16 "F 70 "F 86 'F Simplified 8.1 HSPF2 , ctnn Dr. . r- a ata -auuvv ptuilt.lg,at f 35 'F 1633 cfm 0.056 cfm/Btuh0 in H2O 95 75 20 H 50 -44 "F OF .F VentilationMethod ASHRAE62.2-2019 Heating Summary Structure 29093Ducts 0 Centralvent (SER=SA%74 cfim) 2572 Enerov recoverv Humidification ' Pioino E<iuipYment load lnfiltration Method Construction quality Frreplaces Sensible Cooling Equipment Load Sizing Structure 27442 BtuhDucts 0 Btuh Central vent (SER=Slo/o 74 cfm) 607 Btuh Enerov recovervBlow6i ' o Btuh Use manufactureis data Btuh Btuh Btuh o/o gr/lb n 1.00 28133 Btuh -767 Btuh0 Btuh -822 Bluh 0 Btuh 0 Btuh0 Btuh 31665 Btuh Averaoeb Heatinq Coolino Aea (ft') 197{ 197{ Volume (ff) 20114 20114 Air change's/hour O.29 0.16 Equiv. AVF (cfm) 98 53 Heating Equipment Summary Rate/swino multiolier EquipmenT sensible load Latent Cooling Equipment Load Sizing Structure Ducts Central vent (LER=S0o/o 74 cfm) Enerov recovery Equiffrrent lateit load Equipment Total Load (Sen+Lat) 28133 Btuh Req. total capacity at 0.85 SHR 2.8 ton Gooling Equipment Summary Daikin DAIKIN DH6VSA6O1OA 215415507 Make Trade Cond Coil Daikin DAIKIN DH6VSA6O DFVE6ODP Efficiency Heating input I lrrliqr rll*' 'ar r9qril rY vulPu( Temperature rise Actual air flow Air flow factor Static pressure Soace thermostat Cbpacitybalance point = -13 "F AHR|ref 215415507 Efficiency Sensible coolinot -,r^---r ------t:-,-- t LdlEil[ uuullilg Total coolino Actual air flo:w Air flow factor Static pressure Load sensible heat ratio 10A 1300A 8.0 EER2,16.1 SEER2 41650 Btuh?nEn hr..L/oou Dtuil 49000 Btuh 1633 cfm 0.060 cfm/Btuh0 in H2O 1.00 Backuo: lnput = 0 Btuh, Output = 0 Btuh, 80 AFUE Bokllltalic values have been manualty ovenidden Calculations approved bv ACCA to meet all requirements of Manual J 8th Ed -t{* vvrlqtrtcofr-i;202$Sep-02 '11:03:29 Page 3.jE"/cc$...-R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW f wrightsofts Project Summary (Unconditioned) Job: 25260 Date: Jun 27,2025By: MM For: Kistner Residence Notes:All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. Weather: Winter Design Gonditions Garfield Co Rgnl, CO, US Summer Design Gonditions Outside db lnside db Design TD Make Trade Model AHRI -16 "F70 'F 86 'F Outside db lnside db Desion TD Daily-range Relative humiditv Moisture differerice 95 "F o gr/lb 0 Btuh n 1.000 Btuh 0 Btuh 0 Btuh0 ton .F OF 75 20 H 50 -44VentilationMethod ASHRAE62.2-2019 Heating Summary Structure 0Ducts 0 Central vent (0 cfm) 0 Humidification 0Pioino 0 E{uiPYment load 0 lnfiltration Method Construction quality Fireplaces Sensible Gooling Equipment Load Sizing Structure 0 BtuhDucts 0 Btuh Centralvent (0 cfm) 0 Btuh Blower Use manufacturer's data Rate/swino multiolier Equipmenl sensible load Latent Cooling Equipment Load Sizing Structure 0 BtuhDucts 0 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load Equipment Total Load (Sen+Lat) Req. total capacity at 0.70 SHR Gooling Equipment Summary Make nlaTrade nlaCond nlaCoil nlaAHR|ref nla Efficiency Sensible cooling Latent cooling Total coolino Actual air flow Air flow factor Static pressure Load sensible heat ratio Btuh Btuh Btuh Btuh Btuh Btuh Simplified AveraO; Aea (ft1 Volume (ff) Air chan!e's/hour Equiv. AVF (cfm) ing 0 0 0 0 Coolts 0 0 0 Heati nla Btuh OF cfm Heating Equipment Summary nla nla nlaref nla Efficiency Heating input Heating output Temoerature rise Actubl air flow Air flow factor Static pressure Space thermostat 0 0 0 0 0 cfm/Btuh Hzotn nla 0 0 0 0 0 0 0 Btuh Btuh Btuh cfm cfm/Btuh in H2O nla Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed q{r" :gf :k=f Ris ht-suite@ u niversat 2oz4 24.o.o1 RSU6 1B8o 2025Sep-02 11:03:29 Page 4,&.,rccL ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW * *'igrrtsorr illltfl Summary ZONE Job: 25260 Date: Jun 27,2025By: MM For: Kistner Residence Notes All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. lnformation Weather: Winter Design Gonditions Outside db lnside db Design TD VentilationMethod ASHRAE62.2-2019 Heating Summary Structure Ducts Centralvent (74 cfm) Humidification Pioino EquipYment load lnfiltration Method Construction quality Frreplaces Garfield Co Rgnl, CO, US Summer Design Conditions 95 75 20 H 50 -44 -16 "F 70 "F 86 "F Outside db lnside db Desion TD Daily"range Relative humiditv Moisture differedce Rate/swino multiolier Equipmenl sensible load F F F % gr/lb Sensible Gooling Equipment Load Sizing 19821 Btu Btu Btu Btu Btu Btu h h h h h h Structure Ducts Centralvent (74 cfm) Blower Use manufacturer's data 16810 Btuh0 Btuh0 Btuh 0 Btuh n 1.00 16861 9821 1 0 0 0 0 0 0 0 0 0 Heating Equipment Summary Btuh Latent Gooling Equipment Load Sizing Structure Ducts Centralvent (74 cfm) Equipment latent load Equipment Total Load (Sen+Lat) Req. total capacity at 0.70 SHR Cooling Equipment Summary Make nlaTrade nlaCond nlaCoil nlaAHR|ref nlaEfficiency nla Sensible cooling 0 BtuhI ^t^..+ ^.-.^li.--. n Dr,.LLArEr I UUUI| rV \J Dt Ut I Total cooling 0 Btuh Actual air flow 0 cfmAirflowfactor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Simplified Heatino 197{ 12808 0.26 55 nla Goolino 1e7{ 12808 0.14 30 AveraO; -254 Btuh0 Btuh0 Btuh 0 Btuh 16861 Btuh 2.0 ton Aea (ft) Volume (ff) Air changes/hour Equiv. AVF (cfm) Make nlaTrade nlaModel nla AHRI ref nla Efficiency Heating input tlaofinn nr rlnr rt, ,vsu,,v vsryur Temperature rise Actual air flow Air flow factor Static pressure Space thermostat nla Boldlitalic varues have been manually overridden E}r.,lnutut I OF cfm cfm/Btuh HzAtn Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. +{* rrrlrr}rtryrft*' .*- --*;- *-; Rightsuite@ Universal 202424.O.O1 RSU61880 202+Sep-02 I1:03:29 Page 5&dcch....R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJB Front Door faces: NW +{F wrrEhrsorr frftiir9^yfl mary Job: 25260 Date: Jun 27,2025By: MM For: Kistner Residence Notes:All windows assumed purpose-built daylight windows. (# of occupants=# of bedrooms+1) used for internal loads. Weather: Winter Design Conditions Garfield Co Rgnl, CO, US Outside db lnside db Design TD Area (ftz) Volume (ff) Air changes/hour Equiv. AVF (cfm) VentilationMethod ASHRAE62.2-2019 Heating Summary Structure 29093 BtuhDucts 0 Btuh Centralvent (74 cfm) 0 Btuh Humidification 0 BtuhPioino 0 Btuh Equipiment load 29093 Btuh lnfiltration Method SimPlified Construction quality AverageFrreplaces u Summer Design Gonditions 95 'F75 'F 20 "F H 50 o/o -44 grllb Sensible Gooling Equipment Load Sizing Structure 29637 BtuhDucts 0 Btuh Centralvent (74 cfm) 0 Btuh Blower 0 Btuh nUse manufacturer's data 1.00 29726 Bluh Latent Gooling Equipment Load Sizing Structure -767 BtuhDucts 0 Btuh Centralvent (74 cfm) 0 Btuh Equipment latent load Equipment Total Load (Sen+Lat) Req. total capacity at 0.70 SHR 0 Btuh Gooling Equipment Summary Make nlaTrade nlaCond nlaCoil nlaAHR|ref nla Efficiency Sensible cooling Latent cooling Total coolino Actual air floYw Air flow factor Static pressure Load sensible heat ratio -15 "F70 "F 86 "F Outside db lnside db Desion TD Daily'range Relative humidity Moisture difference Rate/swino multiolier Equipmenf sensible load Heatino 197{ 20114 0.29 98 Goolinq 1978' 20114 0.16 53 nla 29726 Bluh 3.5 ton Make Trade Model AHRI ref Heating Equipment Summary nla nla nla nla Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 0 Btuh0"F0 cfm0 cfm/Btuh0 in H2O ln nla 0 0 0 0 0 0 0 Btuh Btuh Btuh cfm H20 cfm/Btuh nla Boldlitalic vatues have been manuatly overridden Calculations approved bv ACCA to meet all requirements of Manual J 8th Ed 2O2+Sep-02 1'l:03:29 Page 6A,cc*....R RESIDENCE MANUAL J AND S ZONES 2025-o9-o2.tup Calc = MJB Front Door faces: NW * toright*ofts Manual S Gompliance Report LOWER AHU Job: 25260 Date: Jun 27,2025 By: MM lnformation For: Kistner Residence Equipmentc Design Gonditions Outdoor design DB: Outdoor design WB: lndoor design DB: lndoor RH: 95.3"F 59.0'F 75.0'F 50o/o Sensible gain: Latent gain: Total gain: Estimated airflow: 14110 0 14110 1033 Btuh Btuh Btuh cfm 75,TF 61.1"F Entering coil DB: Entering coilWB Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Daikin Actual airflow: 1033 cfm Sensible capacity: 20026 Btuh Latent capacity: 3534 Btuh Total capacity: 23560 Btuh Model: DHOVSA361 0A+DFVE36CP1 3004 142o/o of lsad 0% of load 167% of load SHR: 85% Heating Equipment Design Gonditions Outdoor design DB: lndoor design DB: -16'F 70.0"F Manufacturer's Performance Data at Actual Design Gonditions Heat loss:22394 Btuh Model: DHOVSA361 0A+DFVE36CP1 300A Entering coil DB: 66.9'F Equipment type: Split ASHP Manufacturer: DaikinActualairflow: 1033 cfm Output capacity: 20824 Btuh Supplemental heat required: 1570 93% of load Btuh Capacity balance: Economic balance: -13 "F -99 "F Backup equipment gpe: Manufacturer: ,Actual airflow: 1033 Output capacity: 0 trlec boiler cfm Model 0% of loadBtuh Mccts all rcquircments of ACGA Manual S *xrffi Right-Suite@ U niversal 2024 24.O.O1 RSU61880 202$Sep-02 l1:03:30 Page 1,g,cch ...R RESIDENCE MANUAL J AND S ZONES 2025-09-02.rup Catc = MJB Front Door faces: NW * *tightsoft Manual S Compliance Report MAIN AHU Job: 25260 Date: Jun 27,2025 By: MM Project lnformation For: Kistner Residence Equipment Design Gonditions Outdoor design DB: Outdoor design WB: lndoor design DB: lndoor RH: 95.3'F 59.0"F 75.0"F 50% Sensible gain: Latent gain: Total gain: Estimated airflow: 28049 0 28049 1633 Btuh Btuh Btuh cfm 75.5'F 61.TF Entering coilDB: Entering coilWB Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Daikin Actualairflow: 1633 cfm Sensible capacity: 31654 Btuh Latent capacity: 5586 Btuh Totalcapacity: 37240 Btuh MOdEI: DH6VSA6O1 OA+DFVEoODPl 3OOA 113l/o of load 0% of load 133% of load SHR: 85o/o Design Conditions Outdoor design DB: lndoor design DB: -16"F 70.0'F Equipment type: Split ASHP Manufacturer: Daikin Actualairflow: 1633 cfm Output capacity: 34580 Btuh Supplemental heat required : Heat loss 31665 Btuh Model: DH6VSA601 0A+DFVE60DP 1 3004 Entering coil DB: 68.0"F Capacity balance: -13 "F Economic balance: -99 "F Manufacturer's Performance Data at Actual Design Conditions 109% of load 0 Btuh Backup equipment type: Manufacturer:Actualairflow: 1633 Output capacity: 0 Elec boiler Btuh Meets all requirements of ACCA Manual S cfm Model: 0% of load {* *q-ll*t*gff Ris ht-su ite@ u niv ersat 2024 24.o.o1 RSU6'l 880 202$Sep-02 1 1:03:30 Page 2.&Jlcch ..R RESIDENGE MANUAL J AND S ZONES 2025-09-02.rup Calc = MJ8 Front Door faces: NW