Loading...
HomeMy WebLinkAboutSpec Sheets1NDEECO" . _• Calculations for closed top, outdoor tank losses based on NFPA-22 standards for water tanks for private fire protection (2023) (See sheet 2) Inputs CafcufaYed NFPA-22 CALCULATIONS Application information (WORKING PROGRAM, IN DEVELOPMENT) PROJECT: 25-095 Spartan -Silt, CO DATE: 1 10/31/2025 Tank height, ft. 21.31 FT FT FT STEP 1 INPUT Tank diameter, ft. 21.65 Cone height, ft. (use 0 if flat top) 6.37 Ambient °F -10 -F -F -F STEP 2 Set point (427 for NFPA standard) 42 A T S2, Insulation R value (0.5 minimum uninsulated steel) 14 STEP 3 (STEP 4 INPUT) Wind speed (mph) 35 MPH STEP 5 INPUT Wind speed multiplier y4. IUP I IUN 11 Surface area for vertical tank, FLAT nOTTOM AND FLAT TOP (A) FIaL Bottom and Top Surface Area 7 5 89 IF[ 12 SiFP 1 RESUI I Side tank, 1, d h 1,4A8 6u^ FF^7 ft2 (I LAT BOTTOM AND TOP NFuo I - — �� I rA) OP f10 11 [OPTION 21 Surface area for vertical tank, FLAT BOTTOM AND CONE TOP (A) Flat Bottom 367.9.5 FTA2 1 FTA2 FTA2 FTA2 STEP 1 RESULT (OPTION 2) (B) Cone Top 584.47 (C) Side tank, ¶ d h 1,748,6$ Total area, ft2 (FLAT BOTTOM, CONE TOP NFPA STANDARD) 2,401.09 BTU losses Area Used (from above option 1 or 2) 2,401.09 FTA2 OPTION 2 Total area ft2 X AT R 8,918-33 BTU STEP 4 RESULT Add 5%and Wind speed Multiplier Losses in BTU with 5%SF and wind adders 10,768,88 BTU I STEP 5 RESULT Convert to KW and add 10% KW Required Vertical Tank 3.472 KW I STEP 6 RESULT KW Required Horizontal Tank' ;4. KW 39 Max INDEECO Standard Safety Factor is 20% reflecting wattage tolerance +5/-10% and voltage - S% ELECTRIC HEATER SAFETY FACTOR (OUR MANUFACTURER KW Recommended Horizontal Tan 4;542 RECOMMENDATION) (BEYOND NFPA STANDARD CALLS) r` ' Wind speed adjustments range 21 mph to 35 mph INDEECO additional SF is 20% reflecting wattage tolerance +5/-10% and voltage - 5% One inch fiberglass insulation with jacket assumed about R=3.5, 2" insulation about R=7 1 Horizontal tanks, the cone rise is assumed to be on both ends Direct NFPA calculation number (see notes on background page) PERMAFROST AREA ADJUSTMENTS (IF NECESSARY, ENTER EXPECTED GROUND TEMPERATURE) Surface area for vertical tank (ONLY AREA EXPOSED TO AMBIENT) Side tank, $ d h 1445.7 FTA2 STEP 1 RESULT Cone top 584,5 d FTA2 IA/1TLI f11 IT Rr1TTnAA I N m x m m r z --I = m -Ti z -0z v m o LA m m m m K m G n m m z L) r r D In c a z D> W Z [Ti• I N - � f z N p 7 m m N O Z � n m C) = o 0 z X _ m N = = o D Z cn cD o m rn in W O ? c4 O � W O L+ O ? Z O Z W O -P, ° - (n 1 VI U1 In D m m !n L N O !n 2 r m W C N co C Z -I � 4 m r I N 11 I i] I iI I I � v�Z7 R<1� I�T1 M' VO;uL 4�n-1EM�CODOZ mmOMKZWMMDM o Z O a D O O D O m En mg=jm T -m N X �nMM om Z =�ZZCO —I kn � - co l" M o xW5-0 -(A me xx?Dmvco m.— qLn m m�VJz� �D� 3 r-mz om-9mnD D 3o ={�OmOpm � -.iow OZm �m X AMM20mm 0 arm_ m.D AO ;UK 03m xm I t <N D M m � 0 �C> 0= v m 0 I `u 1 T �Nw cn to o = CA 0-0 V• g I 00 ik —77 i I I I O rrl Ln (7 ;q I OZ