HomeMy WebLinkAboutEngineer's OWTS DesignGEO QJU EST. LLC
GEQTECIINICRL ENGINEERING
Leonidas Vallalta
1190 Linda Avenue
Silt, CO 81652
(970) 505-8694
Ieonvillalta2023@gmail.com
(970)318-6784
PO Box 1372
Rifle. CO 81650
geoquestco@pm.me
Geo Quest Project No. 26-141
Date: 5/15/26
RE: On -site Wastewater Treatment System (OWTS) Soil Evaluation
Geo Quest was asked to perform a soil evaluation for a new OWTS at the property located
northwest of Silt in the Silt Mesa area. The property is formally identified as:
e Garfield County Parcel No. 212727200285
e Tract 513 Scutter Ranch Subdivision
This letter presents the evaluation details and USDA soil type encountered at the property on
May 1 and May 4, 2026. This information may be used in OWTS design.
Soil Evaluation
A total of two soil profile test pits were excavated on the western half of the parcel, near the
proposed soil treatment area. The excavations were completed with a mini excavator to maxi-
mum depths of 8.5 feet below ground surface. The approximate locations are shown on the
attached Test Pit Location Map.
Representative soil samples were collected from the material layers encountered in the test
pits. These samples were evaluated and classified using the USDA Soil Texture and Structure
methods. The USDA classifications were applied to the guidance document from Colorado De-
partment of Public Health & Environment, Regulation No. 43, Table 10-1 as presented below.
No limiting layer was encountered within the depths explored.
Table 10-1- Soil Treatment Area Long -Term Acceptance Rates
Soil Structure- Percolation Treatment
Soil Type Soil Texture T e Soil Structure -Grade Rate Level 1
yp _ (MPI)
5 Clay I Platy Strong 121+ I 0.10
GEO CZUEST, LLC
GEOTECHNICAL ENGINEERING
Respectfully submitted,
Geo Quest, LLC
Kevin E. Dye, P.E.
Figures: Approximate Test Pit Location Map, Test Pit Logs
r—VilProperty
Approximate Test Pit Location Map
(970) 318-6784
PO Box 1372
Rifle, CO 81650
geoyuestcoftm.me
r
57139 -
S51pNAL�
G E O EST. LLC
GEOTECHNICAL ENGINEERING
=
Project Number: 26-141
Project Name: Leonidas Villalta, Tract 5B Scutter Ranch
City, State: Silt
County: Garfield
See the Approximate Test Pit Location Map for test pit
location
Garfield County Parcel # 212727200285
Weather Conditions: Pt cld , calm, 50-60
Date: 5/1 /2026
Time: 9:15 am
Excavation Equipment: Excavator
Ground Water
Date:
Time:
[Depth: None
GPS Coordinates: WGS 84
No
01C.
Elevation: feet
Engineer: KD
Test Pit No.: TP-1 north IPage _1_ of 1
Notes:
Depth
(feet)
Sample Type (1)
�
Soil Description & Notes
0
Top
0-12 inches topsoil
1
CL
CLAY, sand, silt, brown, dry
2
3
CL
1CLAY, silt, sand, gray, calcareous, some oxidation, dry
—4-
5
--------
--
---
6
7
Bottom of TP at 8.5 feet
8
_9
10
The "graphic log" column displays the USCS soil classification
G E O CZU E ST, I LC
GEOTECHNICAL ENGINEERING
Project Number: 26-141
Project Name: Leonidas Villalta, Tract 5B Scutter Ranch
City, State: Silt
County: Garfield
See the Approximate Test Pit Location Map for test pit
location
Garfield County Parcel # 212727200285
Weather Conditions: Pt cldy, calm, 50-65
Date: 5/4/2026 Time: 1:30 PM
Excavation Equipment: Excavator
Ground Water
Date:
Time:
Depth: None
GPS Coordinates: WGS 84
No
W°
Elevation: feet
Engineer: KD
Test Pit No.: TP-2 south I Page _1` of T1
Notes:
Depth
(feet)
Sample Type (1)
m o
�
Soil Description & Notes
0
Top
0-12 inches topsoil
1
GC
GRAVEL, clay, sand, silt, dry
2
3
�L
CLAY, silt, sand, gray, calcareous, some oxidation, dry
4
6
7
Virtual bucket refusal at 5 feet
8
_9
10
.— .- — --—
---
---
The "graphic log" column displays the USCS soil classification
'' .t lk a..' `' 12° s: ,i s NOTES _
a • ' -- THIS PIAN SET IS INTENDED TO BE PLOTTED IN
•v, v s ,,'•; 4 `� / t } * 3 `�{^ j a" t SURFACE �'1 / COLOR. FAILURE TO DO SO MAY RESULT IN MISSING
Villoto Tiny Home k
r
r ' s t V A Lr 'C t OATACINFAMATION CRITICAL TO THE PROJECT
County of Garfield,r r e
1 i x
t . SA 4 SI T,
#,t' `• 1. W BROWN, �% State Colorado .'..��' -�::I , F•
t � _4 285 E
L ✓'. �B• "'I '`: 7 > A. o, i !., a £ .-... �.. �.
• arcs' No: 2127 2 00 �
„ r
CALCAREOUS, SOME / �.:
v ,. . 41 dh tt. DI /;/ ; OADA/ION, DRY
ey /
1
i
gr
* \ e lit,
4� / t , ,r i •• l� rJ
; I "�� ' 'I t%' SITE EVALUATION - ',.RfFLE {_•=r ` L/ ,,,:,I.,-�-� - s „rf' ' .
_ � 1. SITE AND SOIL EVALUATIONS WERE PERFORMED BY: a-f . -� � � , '�' �.. � �• �i j� �" € " • _ _ '
70.
r •` `. t {'. `, f k 4 . ,. r DER/CJ WALTER, PE 1(EVIND)$ PE ". � ,_ - 1 !.
a A c 4 BOUNDARIES UNUMITED INC. GEO QUEST Cillity Map
923 COOPER AVE.,STE.201 PO BOX1372 To POLDI.�INte _- I f t To New Castle
i - GLENWOOD SPRINGS, CO 81601 RIFLE, COLORADO 81650
-�i 'K' i y: ,;• - t r {' i,. * �2' ' * 970,945.5252 970.318.6784
>: -., t '4 > r' I _t :� '•` L tom'$ x " ;. tw A . N 'b r SYSTEM DESIGN & CONSTRUCTION NOTES:
`;:v ' „ - „, m , '� • :: ` ;, • 4 : Ir' I„ C \ 7. -;;;' r •w • a►," • ! " 2. EVALUATION DATE(S): MAY 1, 2026. 1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH CDPHE REGULATION 43 ONS(TE WASTEWATER TREATMENT SYSTEM (DINTS) REGULATION, MOST CURRENT
-r .- ,'- a ,# ` �. EDITION AND LOCAL AGENCY REQUIREMENTS WHICH MAY OR MAY NOT SPECIFICALLY BE NOTED ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
F,. f \" 4 . } 31 r} q i7 - + 3. &SOIL WAS CLASSIFIED BY THE GEOTECHNICAL ENGINEER (GEO QUEST (PROJECT #26-141, MAY KNOWING AND CONFORMING r0 SUCH SPECIFIC DETAILS AS ARE REFERRED TO M THE ABOVE MENTIONED REGULATIONS. THIS DRAWING DOES NOT CONSTITUTE AN
z t , / / _: , • , ,;� 4 `+ x '" 1, 2026) AS USDA CLAY; TYPE 2A; WITH AN LTAR OF 0.10 GPD/SF. OWTS PERMIT. A PERMIT MUST BE SUCH
SPECIFIC
CI FROM APPROPRIATE LOCAL AGENCY. THE CONTRACTOR MUST CONTACT THE LOCAL AGENCY HEALTH DEPARTMENT
!�
�,,., , _ a:. : , o Ii] . T ,.I.I '<+: \ " Y . • > a . . 'i f r, ( f . ' .: AND THE PROJECT ENGINEER FOR INSPECTIONS OF THE CONSTRUCTED SYSTEM BEFORE BACKFILL. A REQUEST FOR INSPECTION BY THE PROJECT ENGINEER AND
7. /-��,\`' ,H•SOt , j -{ / „t� « : 7 e ,. a {,. '€+_ --. y b "t f r •F R 4. SETBACK REQUIREMENTS FOR A TREATMENT LEVEL 1 STA TRENCH/BD, UNLINED SAND FILTER THE COUNTY ENVIRONMENTAL HEALTH OFFICER MUST BE MADE AT LEAST 72-HOURS PRIOR TO THE DESIRED TIME OF BACKFlLLING.
�.� ��NS�tpOS10.a •� ,v { ;ct: _'.. - A OR SEEPAGE PIT (PER TABLE 7-1) AND AN ADWF= 150 GPD:
4,c",r. k 'r _
Z. A.A. SPRING, WELL OR POTABLECiSTERN=100'
r', 4.8. POTABLE WATER SUPPLYLINE=25' 2. DEMAND CALCULATIONS (SEC.43.6.A.211)
, a • D5- 4,C. STRUCTUREW/BASEMENT/CRAW4SPACE=20' 2.A. ONE (1)BDROOMTINY HOME <400SFUSING TREATMENT LEVEL 1(TL7).
t [� # + " ' - a '• ' +' t e J 4 E PROPERTY
BASEMENT/CAAWL SPACE-10' 2.B. AVERAGE DAILY WASTEWATER FLOW AD AND ORGANIC LOAD RATE BO
\PP_, l ,y{ $ t 4 `'' ! - 4.. LINE PIPE OR UNED IRRIGATION DITCH=10' ( WF) ( �)
4. 1
It ' ♦`- 2.B.1. TIDYHOME:150gpdc&0.40BODsIbslday(PERTABLE62)
`, _ ro 4.F. INTERMITTENTIRRIGATIONLATERAL,INFILTRATIONSTRUCNRE=25'
4.G. LAKE, WATERCOURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' 2.B.2. ADWF:
I �' °. S y ,.& ' 6 r,, .• ,, ,: _ ` ' .} r t 4.H. DRYGULCH, CUT BANK OR FILL AREA=2S 2.6.2.1. TINY HOME= 150 gpd(MINIMUM PER TABLE 6-2)
+ 1 {t. r 4m ., 4.1. SEPTIC TANK=5' 2.B.2.2. ADWF =150 gpd
- ±4' e K ,' , A 4 - 4 * + r 4.J. RESTRICTIVE LAYER OR GROUNDWATER (VERTICAL): 4' (TREATMENT LEVEL 1, GRAVITY 2.8.3. BOD5 = 0.40lbs/day
- i
r j • 1; F {^< ,�j ,1 \ , •, +� r FEED) BOD5 mg/L = BOD9'1.000,000 = 0.41b5/dav'1,0 ON = 320 mg/L
J t i 1 n ' • #' $ 1 P "�.. „ i f , j t 3. SETBACK REQUIREMENTS FOR THE SEPTIC TANK SHALL BE (PER TABLE 7-1): ADWF'8.34 150 gpd'8.34
\` �- / ` , ? " �. 4 # y t�. r 1t • 1 �' +' ° 3.A. SPRING, WELL OR POTABLE CISTERN=60 2.B.4. CBOD5 = B005' 0.85 = 272 moll.
'-- -1, A t _ 4 ^.' t t.,, IA'..,. y4" 4 _ '+ A ; • - 3.B. POTABLE WATER SUPPLY UNE=10
3.0. STRUCTURE W/ BASEMENT/CRAWL SPACE=5'
T`_ 3. SEPTIC TANK (SEC.43.9.B.2,a):
14
�, t. Ap`...., ,p A- t -, , •, / ter. • 3.D. STRUCNI�WiOBASEMENT/CAAWLSPACE=S'
p c `v '-k� 'A : - `' " } ra < t - &E. PROPERTY LINE, PIPE ORUNDIRRIGATION DITCH =1In 3.A. INSTALL A1,000GALLON TWO -COMPARTMENT SEPTIC TANK WITHEFFLUENT FILTER INTHE OUTLET RISER. (TABLE 9-1)
r ` "
' -I ) � a „ I - `. '' 'I �€' , s 0 � 'fie „' 3.F. INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=10 3.B. THE TANK IS NOT SUBJECT TO BUOYANCY.
3.G. LAKE WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50'
WELL EXISTS ON THE PROPERTY. POTABLE WATER WILL BE HAULED IN i J IF T i "` 3.H. DRY GULCH, CLOT BANK OR FILL AREA=10' 4. ABSORPTION AREA CALCULATIONS:
t -L!D STORED IN A CISTERN LOCATED AT LEAST 100-FEET AWAY FROM THE 4 i' 3J, sra rRENCHBED, UNLINED SAND FILTER OR SEEPAGE P T=s
i * STALLED SOIL TREATMENT SYSTEM (AKA SEPTIC FIELD). THE WATERLINE ' ' ° ro 4.A. THE ABSORPTION AREA SLOPES ARE MODERATELY FROM NORTHWEST TO SOUTHEAST.
5 HALL ALSO BEAT LEAST 25' AWAY FROM THE SOIL TREATMENT SYSTEM. 1 4.0. LONGTERM ACCEPTANCE RATE (LIAR) DA TREATMENT LEVEL 1 (TH) OF 0.10 gpd/SF (SEE SITE & SOILS EVALUATION NOTES/DETAIL).
( •"� y�. ` f1` SITE C SOILS EVALUATION
4C. MINIMUM SOIL TREATMENTAREA,A(PHASEI):
I LILATIONS OF ALL COMPONENTS MAY BE VARIED AS NECESSARY AS T } { Y' > A = ADWF = 150=15M&F.
J c Ac 7L 11P7PAL'SA F STD !CFS �i E n�FS ''EET THOS_-E^I'i9ED+, s,,11e N s
• - _ � >tR,r ♦ A LTAR 0.109Pd/S.F.
T / 4 = _
-,r 4.D. SIZE ADJUSTMENT FACTORS: GAAVITYT N H 1.0' AM8 0.7 A AEC , CHAMBERS (TABLE 10 1A).
a T r •'' ` 4.. " #' # 4.E. A,adj=1500 SF1.0-0.7=1050 SF
MAINTENANCE NOTES 4f, GRAVELLESS CHAMBER TRENCH SYSTEM:
4.F.1. INFILTRATOR QUICK4:1050 SF/ 12 SF/UNR = 88 UNITS. NSTALL 90 UNITS IN THREE(3) TRENCHES CONTAININGTHIRTY(30) UNITSEACH.
41.2. ADS ARC 36:1050 SF / 15 SF/UNIT = 70 UNITS. INSTALL 72 UNRS IN THREE (3) TRENCHES CONTAINING TWENTY --FOUR (24) UNITS EACH.
1. TO ENCOURAGE THE HEALTH AND LONGEVITY OFTHE OWTS SYSTEM, THE OWNER SHALL 5. THIS SYSTEM IS SIZED FOR TYPICAL HOUSEHOLD WASTES ONLY. BACKWASH OR FLUSHING FLOWS FOR REVERSE OSMOSIS UNITS OR WATER SOFTENERS AND/OR
CONSIDER THE FOLLOWING: FILTERS SHOULD NOT BE INTRODUCED INTO THIS SYSTEM. BACKWASH AND FLUSHING FLOWS SHALL BE DISPOSED OF WITHIN A SEPARATE INFILTRATIVE SYSTEM.
1.A. MINIMIZE THE AMOUNT OF WATER THAT GOES DOWN THE DRAIN, THE BETTER YOUR 6. CLEAN OUTS ARE REQUIRED AT THE HOUSE AND AT ALL BENDS GREATER THAN 45• AND AT LEAST EVERY 100-FEET BETWEEN THE HOUSE AND THE SEPTIC TANK.
SYSTEM WILL WORK. I.B. MINIMIZE SOLIDS GOING DOWN THE DRAIN. 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL WATER TIGHT DOMPONENTS THROUGHOUT THE SYSTEM TO PREVENT INFILTRATION.
I.C. ELIMINATE GARBAGE DISPOSALS OR KEEP THE USE OF GARBAGE DISPOSALS TO A 8, INSTALL RISERS AS NECESSARY TO BRING ALL ACCESS PORTS TO FINAL GRADE. PORTS SHALL BE MARKED IF CAPS ARE TO BE BURIED.
MINIMUM. 9. INSTALL 3-INCHES OF BLUEBOARD INSULATION, 3-FEET WIDE, OVER SEWER AND EFFLUENT PIPE WHEREVER DEPTH IS LESS THAN 3-FEET. UNDER NO
I.D. MINIMIZE GREASE AND OILS THAT GO DOWN THE DRAIN, CIRCUMSTANCES SHALL COVER BE LESS THAN 2-FEET.
ey p �J i ® 1.E. USE LINT FILTERS ON LAUNDRY MACHINE DRAINS 10. SITE PLAN INFORMATION FROM OTHERS. LOCATIONS OF ALL COMPONENTS MAY BE VARIED AS NECESSARY AS LONG AS ALL MINIMUM DISTANCES AND SLOPES
clitosomo
1000 Galion Top Seam 2C� a®'+ �ok ®�.S`Ie��u�ton ®oX 1.F. KEEP AVOIDFNDANDDIRT OUTANITAR NAPKINSOF THE PAPENG R PR MEET THOSERDUIRD.
J 1.G. AVOID FLUSHING SANITARY NAPKINS OR PAPEfl PRODUCTS OTHER THAN TOILET PAPER.
T•ZCP Risers and Lid I.H. DO NOT USE LYE-BASDDRAIN UNCLOGGERCHEMICALS SUCH ASDRAINO,OVEN-OFF,
OR OTHER STRONG CLEANING AGENTS.
1.1. DO NOT PUT ANY "ROOT DETERRENTS" DOWN THE DRAIN.
1.J. DO NOT POUR PAINT THINNER, PESTICIDES, PAINTS OR PHOTO LAB CHEMICALS .DOWN
THE DRAIN
,,,• Top UD-BOX 6 & UD43OX B I.K. MINIMIZE USE OF CHLORINE BLEACH AND TOILET ADDITIVES.
DESIGN NOTES ' - ' :'_,::a:`,_` •�,,,.., ,. , . ., ;. • , ....-°
• Design per performance lost per v1eW -_ 2245 D-BOX SEAL 2 THE OWNER SHALL CONTRACT WITH ASEPTIC TANK INSPECTOR TOINS CT THE TANK
ASTM C1227 �''� • �J
PE
Top surface area 46.25 ft'II i �� 1Evsrvoeortoueswim ANNUALLY FOR GREASE AND SEDIMENT D IMENTACCUMULATION. THE INSPECTOR SHALLREMOV
4c O 26 days; concrete = 6,000 PSI 2.�A"n y,. 4SE" AND PROPERLY DISPOSED OF ACCUMULATED GREASE AND SEDIMENT ASNEDEDTOENSURE
Min. 1 I I _ - PROPER FUNCTION OF THE SYSTEM.
Installation:
• Tank to be set on 5' min. sand eon 1 16 CU
T UT OUT
II I
bed or peo grovel i SIDE
CUTO
• Tank to be backfilled uniformly on CALNK� i� �' / �1 I POLYLOK SEAL II I
all sides In lifts less than 24" and D 1 I NO.3001 1 TEAR OUT FOR mechanically compacted r- r C "-_ _.-J , 4"SDR�SOR ATTACH REMOVABLE CAP OR
Excavated material may be used for -JI --------- SCMD-40 12" 50. NYLDPLAST H-20 -.
backfill, provided large stones are ( '��' "•'-'" T �'�.'�"'• SOLIQ COVER ASSEMBLY THREADEDCLEANOUT
MARKER
removed \� l NOT TO SCALE REMOVABLE PVC CAP INSTALL NIARKEA IF CAP IS TO FINISH GARDE
• Excavation should be dewatered and
tonk filled with water prior to being REBURIED.
UD BOX 6" RISER ` , FLUSH WITH SURFACE
put in service for Installation with II � REQUIRED
GENEAALABSORP110NAREANOTES
water table loss than 2' below grade �RlSam toGrade -
Meets C1644-06 for resllient ,•.• s �- ROTO-FLOV� Orr ' L �\ , \��j /\ j \\� 1. INSTALL CHAMBER UNITS IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
connectors
• Inlet and Outlet identified above pipe 1 �" ,'
• Delivered complete with Internal L II- 2. PARALLELING
ABSORPTION TRENCHES SHALL BE 3' WIDE OR LESS AND PARALLEL THE GROUND SURFACE CONTOURS.
piping c ' 29°x24"x6"CONCRETE PARALLELING TRENCHES SHALL BE SEPARATED BY A DISTANCE OF 6' MIN.
• 4' Maximum bury depth Fledbls 7- IN HARDSCAPE 4`0PVC RISER
utyl Rubber ACCESS TO GRADE O � 3. THE BOTTOM OF THE ABSORPTION TRENCHES SHALL BE LEVEL AND THE BOTTOM AND SIDEWALLS MUST
Sealant �_.,- 41 PVC TWO-WAY BE RAKED TO REMOVE ANY SOIL SMEARS INCURRED DURING THE EXCAVATION. FAILURE TO DO SO MAY
REQUIRED } UD-BOX 12" RISER NOT TO SCALE CLEANOUT TEE REQUIRE THE CONTRACTOR TO REPLACE THE ABSORPTION FIELD AT HIS/HER OWN EXPENSE.
t - 5r �' OR 0 4. DRAINAGE SWALES ARE TO BE PROVIDED ABOVE AND AROUND THE FIELD, AS NECESSARY, TO PREVENT
FLOW SURFACE RUNOFF FROM ENTERING ABSORPTION AREA
ALLOWABLE BURY
(Based on Water Table)
WATER TABLE
ALLOWABLE
EARTH FILL
0' - o'
2' - On
t'-Or
X _ W
2'-0"
3'-0"
3'-0•
4'-0"
DRY
4' - Or
tp• 1r • 1 4" PVC TEEMISER REQUIRED
IIr i WITH EFFLUENT POLYLOCK EQUALIZER 4'0 SEWER LINE 5. NO EXCAVATION OF THE ABSORPTION FIELD IS TO BE DONE DURING WET WEATHER AND USE OF RUBBER
° FILTER ON THE ':. - "V-NOTCH' WEPR IN LANDSCAPE TIRE VEHICLES OVER THE ABSORPTION AREA IS STRICTLY PROHIBITED.
4" PVC TEE/RISER 4 is 5 TANK OUTLETAs
/ YyEI� 6. UNSUITABLE MATERIAL EXISTING WITHIN THE FIELD SHALL BE EXCAVATEDAND BACKFILL SHALL CONSIST
UEVELM
OF IMPORTED LOAMY SAND OR SANDY GRAVEL, THE ENGINEER SHALL BE CONTACTED IFBEDROCK OR
'r GROUNDWATER IS ENCOUNTERED IN THE OVER -EXCAVATION.
°
Section �-: RBe PROVIDE F UIPElg-Y'"v TWO-WAY CLEANOUT 7. TOPSOIL COVER MAY BE VARIED (1 -FOOT MINIMUM, 2-FOOT MAXIMUM) TO ALLOW FOR LANDSCAPING.
r FIT ID �\,��
108' View Sale: N.T.S.
20" COVER FOR RISER & D$OX _
NOT TO SCALE
Digging Specs Invert Dimensions- Net Capacity Net Weight"
GASKETED SEAL ON 12" MIN
11' Lonc a 7' Wide Inlet tlet Length Width Height Inlet Side Outlet Total Lid Tank Tct�l 18"MAX CIRCULAR IRRIGATION -STYLE VALVE
9 9 LID&RISER DES 1 MI BOX&COVER - LID COLOR PURPLE
56" below inlet 56" 53" 111" 60" 68" 687 al 323 al 1010 al.2620 Has 9380 Has 12000 Ibs i••
9 9 9 - FILL ORGAEEN- LABEL'SEWEfl"
FINISHED GROUND - MAINTAIN POSITIVE
SLOPE AWAY FROM TOP SURFACE OF STANDARD INSPECTION PORT, TYP. (41
THE CHAMBER TRENCHES. PVC SOLID PIPE CUT TO FIT. LOCATE PER
VALLEY
Phone: 719'395-6764 %PC,,
Phone: 719-395-6764 INFILTRATOR QUICK4,ADVANC D\ 6° 3l AADFILLT READ DCLEANOUTASSEMBLYPLAN VIEW. ATTACH REMOVABLE CAPOR
Y 1'1LLEY Fax: 719-395-3727V�i11L� A Fax: 719-395-3727 DRAINAGE SYSTEMS BIODIFFUSER
WJ /J Website: wvuw.valle StcomI-�' jNebgjte; yyyyyy,ycllle FBCagtCOm (STANDARD), OR ENGINEER 1%MIN
MR"'A- i Inc. ypr LP
RECAST, Inc. yP APPROVED EQUAL. \ _
Buena Vita} C®l®!Sd® En ll: frontdesk@valleyprecastcom 7�Buorado Email: frontdesk@vaileyprecastcarT \ \ E PVC COUPLING FOR SUPPORT
BOTTOM TO BE LEVEL AND FLAT OVER ^ 3•y
ENTIRE AREA TO WITHIN 0.OI (TYP.) 30„MAX
REMOVE ANY ENCOUNTERED
g BOULDERS AND BACKFILL NITH INFLOW PIPE SHALL ENTER
E LOAMY SAND OR SANDY GRAVELS. DO THE UPPER KNOCKOUTS
NOT USE COMPACTED MATERIALS. / ' -. / \ EXCAVATE 6" DEEP. THE
DO NOT WALK ON OR COMPACT - SYSTEM MUST BE
BOTTOM OF TRENCH. 6' (MIN.) / 4"8 PERFORATED PVC PIPE, POSSIBLE TO UTILIZE THE
u EXTEND PIPE TOAESTON INSTALLEDASSHALLOWAS
BOTTOM OF THE BD UPPER LEVEL SANDY CLAYS
GRAVELESS CHAMBER ABSORPTION TRENCH
Scale: N.T.S.
BOUNDARIES
UNLIMITED INC.
CIVIL ENGINEERING,
LAND SURVEYING 6 BEYOND
923 Cooper Avenue, Ste. 201
Glenwood Springs, CO 81601
tele: 970.945,5252
www.bu-inc.com
Engineer or Surveyor Seal
F
SS/0W-����
Client Information:
LEONIDAS VILLALTA
1190 LINDA AVENUE
SILT, CO 81652
970.505-8694
Subsurface Utiliry Engineering (SUE)
Required Project: ND
If "Yes", SUE Certification
Firm: N1A
Job #: NIA
Date: NIA
NORTH
0 60' 120
Scale: 1" = 60
1
Know what's below.
Cali before you dig.
(/5
ly O
ly
H
/..011
E
c
d
oD 0 E
r O r
C3
�- I
o r✓
c r C l`
0
Ji
L
� a
4-anall a�.I
H
N
O
Agency Approval
Agency:
Dept:
By:
Date:
Comments:
Date
Revision
Project No.:
Sheet
26021
Filename
e21-r.Uwg
D
Designer.
Call
DJW
Dmfter:
RTC
Date:
5115126