HomeMy WebLinkAboutEngineer's OWTS Design PlanGEO QUEST. LLC GEOTECHNICAL ENGINEERING Steven Mancini President/CEO Ric -Man Construction, Inc. 41500 Mound Road Sterling Heights, MI 48314 smancini@ric-man.com (586) 739-5210 RE: Onsite Wastewater Treatment System (OWTS) Soil Evaluation (970) 318-6784 PO Box 1372 Rifle, CO 81650 geoquestco%Pm-me Geo Quest Project No. 26-142 Date:5/18/26 Geo Quest was asked to perform a soil evaluation for a new OWTS at the property on Coffee Pot Road described as: ■ Garfield County Parcel No. 193333400009 ■ Section 33, Township 4, Range 87 and the portion of Tract 43 and 44 described in War- ranty Deed Rec. 869687 This memo presents the soil evaluation details and USDA soil type encountered at the property on May 14, 2026. This information may be used in OWTS design. Soil Evaluation Three soil profile test pits were excavated near potential OWTS locations and are identified as Test Pit 1 (TP-1), TP-2 and TP-3. Excavations were completed with a Caterpillar excavator to max- imum depths of 9.5 feet below ground surface and approximate locations are shown on the attached map. Representative soil samples were collected from the material layers encountered in the test pits. These samples were evaluated and classified using the USDA Soil Texture and Structure methods. The USDA classifications were applied to the guidance document from Colorado De- partment of Public Health & Environment, Regulation No. 43, Table 10-1 as presented below. A limiting layer was not encountered within the depths explored. Table 10-1- Soil Treatment Area Long -Term Acceptance Rates Soil Soil Structure- Soil Structure- Percolation Type Soil Texture Type Grade Rate (MPI) 3A Sandy Clay 1 Blocky Weak —761-75 Loam (970) 318-6784 GEO QUEST, LLC PO Box1372 GEOTECHNICAL ENc,[NEERING Rlfte CO 81650 geoquestcoC•spm.me Respectfully submitted, a�pDD LIC�� Geo Quest, LLC 0 yr 5/28/25 r" 57139 z Kevin E. Dye, P.E. SSic NAI. Attachments: Approximate Test Pit Location Map, Test Pit Logs WU R083846 'P,063977 -•,; 193333300012. ���� � t � � 1933331 0000,1 R083678 1933333000 �f •�• 541 ft a; jt - - -� �-• R483fi12 -. 193333 00009 jp_1 n%z=►" Sri • 7. .ep. _ ' € : ti: w ,a ' t L1 : 193322100953'. •. . • , �U JJDLr�� • Y= - I .� n .4.. � � f at Approximate Test Pit Location map GEQZ'ECHNICAL ENGINEERING 0 GECH QUEST, LLC Project Number: 26-142 Project Name: Mancini OWTS City, State: Gypsum County: Garfield See the Approximate Site and Test Pit Location Map for test pit location Garfield County Parcel No. 193333400009 Weather Conditions: clear, calm, 60 Date: 5/14/2026 Time: 12:40 pm Excavator: Client Excavation Equipment: Caterpillar 312B Ground Water Date: Time: Depth: none GPS Coordinates: WGS 84 No W° Elevation: feet Engineer: KD Test Pit No.: TP-1 Page 1 of 1 Notes: Depth (feet) Sample Type (1) a `O J C7 Soil Description & Notes I� 0 0-36 inches topsoil 1 2 3 sandy clay loam SAND, clay, gravel, brown, moist, few cobbles 4.4.. 5 --- •-- 6 7 8 _9 10� - Bottom at 9.5 ft GEOTECHNICAL ENGINEERING im G E OQUEST LLC Project Number: 26-142 Project Name: Mancini OWTS City, State: Gypsum County: Garfield See the Approximate Site and Test Pit Location Map for test pit location Garfield County Parcel No. 193333400009 Weather Conditions: clear, calm, 60 Date: 5/14/2026 Time: 12:15 pm Excavator: Client Excavation Equipment: Caterpillar 312B Ground Water Date: Time: Depth: none GPS Coordinates: WGS 84 No W° Elevation: feet Engineer: KD Test Pit No.: TP-2 Page 1 of 1 Notes: Depth (feet) Sample Type (1) a J Soil Description &Notes 0 0-24 inches topsoil 1 2 sandy clay loam 3 SAND, clay, gravel, brown, moist, few cobbles _4. 5 gravel band 3-4ft 6 7 8 _9 10 _ Bottom at 8.5 ft LLC N GEOTECHNICAL ENGINEERING 0 GEO QUESTProject Project Number: 26-142 Name: Mancini OWTS City, State: Gypsum County: Garfield See the Approximate Site and Test Pit Location Map for test pit location Garfield County Parcel No. 193333400009 Weather Conditions: clear, calm, 60 Date: 5/14/2026 Time: 11:50 am Excavator: Client Excavation Equipment: Caterpillar 312B Ground Water Date: Time: Depth: none GPS Coordinates: WGS 84 No W° Elevation: feet Engineer: KD Test Pit No.: TP-3 Page 1 of 1 Notes: Depth (feet) Sample Type (1) n J Soil Description & Notes 0 0-18 inches topsoil 1 sandy clay loam 2 3 5 SAND, clay, gravel, brown, moist, few cobbles 6 7 Increasing gravel content below 7 ft 8 _9 10 Bottom at 8.0 ft NOTES: 1. THIS PLAN SET IS INTENDED TO BE PLOTTED IN COLOR. FAILURET MAY 0 D 0 SO M RESULT 7. PRIOR TO ANY EXCAVATION, CTOR SHALL CONTACT ALL APPROPRIATE UTILITY 1 H N IN MISSING DATA& INFORMATION CRITICAL TO THE PROJECT. CONTRA U 1 THE CONTRACTOR SHALL ENSURE DRAINAGE AWAY FROM ALL STRUCTURES IN ALL 15. THE CONTRACTOR SHALL NOT SCALE DRAWINGS FOR CONSTRUCTION PURPOSES. ANY COMPANIES FOR LINE LOCATIONS. CONTRACTOR SHALL NOTIFY PROJECT ENGINEER OF DIRECTIONS. D 0 C 0 NOT ALLOW WATER TO POND ON SITE. PROVIDE SWALES TO MISSING DIMENSIONS OR DISCREPANCIES IN PLANS, FIELD STAKING, OR PHYSICAL ANY POTENTIAL CONFLICTS PRIOR TO U11UTY CONSTRUCTION SO THAT LINE OR GRADE DRAINAGE STRUCTURES AND RUNOUT. SHALLOW DRAINAGE SWALES HAVE A FEATURES SHALL BE BROUGHT TO THE ATTENTION OF THE PROJECT ENGINEER. IF THE 2. SURVEY INFORMATION PROVIDED BY OTHERS. TOPOGRAPHY BASED ON THE USGS CHANGES CAN BE MADE TO AVOID A CONFLICT WITH ANY EXISTING UTILITY. THE TENDENCY OVER TIME TO FILL IN & BECOME LESS EFFECTIVE. PERIODIC MAINTENANCE, CONTRACTOR PROCEEDS WITH THE WORK WITHOUT NOTIFYING THE ENGINEER, HE LIDAR, CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES FROM DAMAGE DURING AT LEAST TWICE A YEAR, IS NECESSARY TO CHECK THE INTEGRITY OF THE SWALE & DOES SO AT HIS OWN RISK. CONSTRUCTION AND, AT NO EXPENSE TO THE CLIENT OR PROJECT ENGINEER, REPAIR MAINTAIN DRAINAGE CHARACTERISTICS. 3. SEE ARCHITECTURAL, LANDSCAPING AND AND STRUCTURAL ENGINEERING PLANS FOR ANY DAMAGED UTILITIES. 16. DISPOSAL OF TRASH, ASPHALT, CONCRETE AND CONSTRUCTION DEBRIS IS THE ADDITIONAL BUILDING AND LANDSCAPE INFORMATION. 12. THE CONTRACTOR SHALL AT ALL TIMES KEEP TWO FULL SETS OF CONTRACT DRAWINGS CONTRACTORS RESPONSIBILITY AND SHALL BE CONSIDERED PART OF THE WORK. 8. ALL EXCAVATIONS FOR UTILITY LINES, RETAINING WALLS, ROADWAYS, BUILDING MARKED UP TO INDICATE THE AS -BUILT CONDITIONS. THE DRAWINGS SHALL BE 4. SEE ADDITIONAL NOTES ON REMAINING PLAN SHEETS. STRUCTURES, DRAINAGE FACILITIES AND TRENCHES, ALONG WITH WORK IN GENERAL, PROVIDED TO THE OWNER AND THE ENGINEER UPON COMPLETION OF THE WORK. 17. ALL PRODUCT INFORMATION SHOWN IS AS PROVIDED BY THE MANUFACTURER. THE SHALL MEET THE REQUIREMENTS OF THE OCCUPATIONAL SAFETY AND HEALTH WHERE PRACTICAL, THE CONTRACTOR IS TO PROVIDE AT LEAST TWO TIES FROM CONTRACTOR IS RESPONSIBLE FOR REVIEWING AND COMPLYING WITH THE 5. ALL DEMOLITION AND CONSTRUCTION HALL MEET TOR EXCEED THE CURRENT ADMINISTRATION (OSHA), COLORADO INDUSTRIAL COMMISSION, OR THE COLORADO PHYSICAL MONUMENTS TO ALL FITTINGS, VALVES, MANHOLES, AND THE END OF ALL MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS FOR THE INSTALLATION CONSTRUCTION AND DESIGN STANDARDS ESTABLISHED BY THE COUNTY AND BE DIVISION OF MINES, WHICH EVER APPLIES. SAFETY IS THE CONTRACTORS SERVICE LINES. OF ALL MATERIALS WITH SPECIAL ATTENTION TO PROPER SEALING OF MATING SUBJECT TO OBSERVATION BY THE COUNTY AND THE PROJECT ENGINEER. RESPONSIBILITY. NO OTHER PARTIES ARE RESPONSIBLE FOR SAFETY IN, ON OR ABOUT SURFACES. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE ENGINEER IF ANY THE SITE, NOR FOR COMPLIANCE BY THE APPROPRIATE PARTY WITH ANY REGULATIONS 13. ON -SITE OBSERVATIONS AND REVIEW CONDUCTED BY THE CITY/COUNTY OR THE DISCREPANCIES ARE FOUND BETWEEN THE DELIVERED PRODUCTS AND THOSE SHOWN 6. THIS DESIGN WAS PREPARED WITHOUT THE BENEFIT OF A SUBSURFACE UTILITY RELATING HERETO, PROJECT ENGINEER OF CONSTRUCTION WORK IN PROGRESS ARE NOT TO BE ON THIS PLAN. ENGINEERING (SUE) STUDY OR MAP. THIS DESIGN HAS BEEN PREPARED FOR A PRIVATE CONSTRUED AS A GUARANTEE OR WARRANTY BY THE COUNTY OR THE PROJECT DEVELOPMENT USING EXISTING UTILITY INFORMATION M TION PROVIDED BY OTHERS. EXISTING g. COMPACTION SHALL MEET OR EXCEED COUNTY AND UTILITY PROVIDER REGULATIONS. ENGINEER OF THE COMPLETED WORK AND THE CONTRACTOR'S RESPONSIBILITIES. 18. FOUNDATION DESIGNS AND SUBSURFACE DRAINAGE, IF APPLICABLE TO BE OBTAINED UTILITIES ARE SHOWN AS THEY ARE BELIEVED TO EXIST BUT Y U MAY NOT REPRESENT THE MINIMUM COMPACTION STANDARD SHALL BE 95%STANDARD PROCTOR UNLESS FROM THE PROJECT STRUCTURAL ENGINEER. ACTUAL FIELD CONDITIONS. BOUNDARIES UNLIMITED INC. DID NOT CONFIRM ANY DATA OTHERWISE SPECIFIED IN THE PLANS OR BY A GEOTECHNICAL ENGINEER. 14. THE CONTRACTOR SHALL TAKE ALL APPROPRIATE PRECAUTIONS TO SIGNIFICANTLY PROVIDED OR PERFORM ANY ADDITIONAL RESEARCH OR NOTIFICATION TO ELEVATE REDUCE ANY POTENTIAL POLLUTION CAUSED BY HIS ACTIVITIES, INCLUDING VEHICLE 19. ANY STORM DRAIN PIPES SHALL BE INSTALLED WITH 1% MINIMUM SLOPE TO THE THESE PLANS TO SENATE BILL 18 167 STANDARDS, AS SUCH, BOUNDARIES UNLIMITED 10. THE CONTRACTOR SHALL CONTAIN HIS CONSTRUCTION ACTIVITIES TO THE AREA WITHIN FUELING, STORAGE OF FERTILIZERS OR CHEMICALS, ETC. THE CONTRACTOR SHALL OUTFALL POINTS. HEAT TAPE IS RECOMMENDED IN ALL EXTERIOR ROOF GUTTERS, INC. MAKES NO GUARANTY EXPRESSED OR IMPLIED FOR THE LOCATION OF THE STREET RIGHT OF WAY AND PROPERTY OWNED, OR EASEMENTS PROVIDED TO HAVE IDENTIFIED PROCEDURES FOR HANDLING POTENTIAL POLLUTANTS AND DRAIN PIPES, AREA DRAINS, TRENCH DRAINS AND GRATED STRUCTURES: SUBSURFACE UTILITIES CONTAINED WITHIN THIS PLAN SET. IF THE CLIENT AND/OR OWNER. THE CONTRACTOR SHALL NOT OPERATE OUTSIDE THIS AREA WITHOUT THE IDENTIFIED SPILL PREVENTION AND RESPONSE PROCEDURES PRIOR TO ANY ACTIVITIES CONTRACTOR REQUIRES A SUBSURFACE UTILITY ENGINEERING STUDY OR MAP FOR PRIOR CONSENT OF THE PROPERTY OWNER INVOLVED. ANY DAMAGE TO PRIVATE AT THE PROJECT SITE. 20. ACCUMULATED SNOWFALL SHALL BE REMOVED TO GRASS AREA TO ENSURE THAT FULL COMPLIANCE WITH SENATE BILL 18-167, THEN A MORE EXHAUSTIVE PROPERTY BY THE CONTRACTOR OUTSIDE THESE LIMITS WITHOUT THE PERMISSION OF PROPER DRAINAGE AWAY FROM THE BUILDING IS MAINTAINED THE PRIVATE PROPERTY OWNER WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 21. ALL PIPES SHALL BE INSTALLED WITH WATERTIGHT CONNECTIONS. x / � ,p� I / \ \ {z / 7 P i t i I x \ 1 i / I ?au 9460 9450 9440 9430 9420 9410 9400 FAGNOTES: TBD Coffee Pot Road 1 O CONSTRUCT GRAVEL DRIVEWAY SEE DETAIL County of Garfield, O CATCH SLOPE AT 3:1 TYPICAL, 2:1 MAX. SEED DISTURBED AREAS WITH A REGIONAL HIGH ALTITUDE NATIVE GRASS SEED MIXTURE. State of Colorado Q3 CONSTRUCT I2"DEEP DRAINAGE SWALE,MIN.,3:1 MAX SIDE SLOPES. Parcel No. 1933-334-00-009 BURIED PROPANE TANKS, MAINTAIN COVER & CLEARANCES BETWEEWOVER NEW SERVICES PER CURRENT INTERNATIONAL CODES AND/OR UTILITY PROVIDER REQUIREMENTS. Q5 PROPOSED POTABLE WATER WELL/SERVICE, INSTALL A NEW 2"0 WATER SERVICE USING AWWA PURECORE (200 PSI) AND EXTEND TO THE MECHANICAL ROOM. s o SEPTIC TANK P SEE OWTS LA ( SITE M . 0 INSTALL 40 LF 18"0 ADS N-12-WT CULVERT WITH FLARED END SECTIONS; INV. IN=9417.0'; INV. OUr=9416.6'. INSTALL 6k12OF 9'0 NOMINAL RIPRAP BELOW THE OUTLET, ® INSTALL TEMPORARY EROSION LOGS IN SWALES/DITCHES EVERY 40 LF, TYP. (SEE DETAIL) O9 INSTALL TEMPORARY SEDIMENT CONTROL FENCING ALONG THE LOWER OMITS OF ALL DISTURBANCES (SEE DETAIL). 1D CONCRETE DRIVEWAY APRON (6" THICKx 1GWx 32L. SLOPE AT 4%AWAY FROM THE STRUCTURE). 11 SLOPE THE HARDSCAPE AT 2%MIN. AWAY FROM THE STRUCTURE. 1© GRADE AROUND (SLOPE DOWN) THE PERIMETER OF BUILDING AS NECESSARY AT 5% FOR 10-FEET-MIN. IN UNPAVED - 1" "4'* AREAS TO ENSURE PROPER DRAINAGE AWAY FROM THE FOUNDATION. FOLLOW ALL RECOMMENDATIONS OF THE GEOTECHNICAL REPORT. SLOPE AT 2% MIN. BEYOND 10'. To Glenwood Springs LEGEND PROPOSED CONCRETE EXISTING/PROPOSED GRAVEL LINE ALL SWALES WITH FLOWUNE GRADES EXCEEDING 5544 -- — EXISTING CONTOUR 5%WITH 9"0 NOMINAL ANGULAR ROCK RIPRAP OR A PROPOSED CONTOUR PERMANENT EROSION CONTROL FABRIC (NORTH — —. — — PROPERTY ONE AMERICAN GREEN VMAX S200 OR EQUAL) INSTALLED SETBACK/ENVELOPE GRADE PER MANUFACTURER'S RECOMMENDATIONS — — — — — — — — — — — — — — — — EASEMENT ..-- ---x - x---- x ---- EXISTING FENCE <, 9, SCP—SCF— PROPOSED SEDIMENT CONTROL FENCING — W— — — —W— -BC1-- —ti'— EXISTING WATER MAINNALVE EXISTING/PROPOSED WATER SERVICE/SHUTOFF/METER V — — ——stEXISTING/PROPOSED SEWER SERVICE/CLEANOUT —E--^ E— EXISTING/PROPOSED ELECTRIC -----T—f---T EXISTING/PROPOSED TELECOMMUNICATIONS . ' SIDE SLOPES t�c EXISTING/PROPOSED GAS @ 3:1 TYP., 2:1. MAX EXISTING/PROPOSED CULVERT/STORM PIPE & SIZE DRAINAGE SWALE —>—>--->--->--- PROPOSED SWALEIDITCH FLOWLINE SCale. ', -,S. ® ® ® EXISTING/PROPOSED UTILITY PEDESTALS &METERS GENERAL DIRECTION OF FLOW DS PROPOSED DOWNSPOUT/RAIN CHAIN 11 FLAGNOTE -ftkI II ROCK SOCK OR EROSION LOG SITE DISTURBANCE i ✓ � ' _ ,—_.—: ! I 1 � ` ` �\ ,` \ \ 1 , 1 � / DRIVEWAY & HOUSE: 18,400SF + / OWTS: 12,500 SF TOTAL: 30,900 SF 9 z+ 1 ( 1 1 1 12 Rib i I 4 7 ti ` 1 R10' 1 x� 1 PROPERTY UNE ,l PVI STA: 1+50.00 1+00 2+00 Profile: CL Drive, Sta:1+00 to Sta:3+91 3+00 3+91 Scale: Vert.=20', Horiz.=20' 9460 9450 9440 9430 9420 9410 9400 6" CLASS 6AGGREGATE BASE COURSE. CONTRACTOR TO PLACE 4" LIFT AT THE BEGINNING OF CONSTRUCTION AND THEN REGRADE AND PLACE ANOTHER 2" JUST PRIOR TO PROJECT CLOSEOUT. DRIVEWAY 16 CL 3 —y 1' 2 MAX � 1.5 _ % 1 � LINE THE DITCH WITH 9"0 NOMINAL ANGULAR RIPRAP DRIVEWAY SECTION Scale: N.T.S. SCARIFY THE SUBGRADE AND RECOMPACT TO 95% STANDARD PROCTOR AREA DRAIN 1CIU ;' E` ION LOG �p0,� Fp9p `" �S 9Cy THx TO FEATURE THI NEEDS PROTECTION ENTRENCH S"_-� SECTIONgg��pA-A 0 CONTINUOIRSMYPoRLPRI FLOW I `�' POINT B D U U POINT �'- - POINT o H o - 0 EROSION LOG PLAN VIEW EROSION LOG D D POINT A USE 2 PINE STAKES 11/2" x 1 POINTA 1/2"x1T'ATALL EROSION LOG �y.. ENDS OR JOINTS, OTHERWISE PCINTB USE A STAKE EVERY 24 IN AND ' CONTINUE TO ALTERNATE ENTRENCH 3" ORIENTATION THROUGHOUT THE LENGTH OF THE EROSION LOG. PObVTS A MAST BE HIGHER -HAN POINT S PLAN VIEW SECTION D-D TEMPORARY EROSION CONTROL LOGS Scale. N.T.S. EROSION CONTROL NOTES: 1. IMPLEMENTATION OF THE EROSION AND SEDIMENT CONTROL MEASURES SHALL PRECEDE STRIPPING OF NATIVE VEGETATIVE COVER AND AS GRADING PROGRESSES. 2. ALL TEMPORARY AND PERMANENT SOIL EROSION AND SEDIMENT CONTROL PRACTICES SHALL BE MAINTAINED AND REPAIRED AS NEEDED TO ASSURE CONTINUED PERFORMANCE OF THEIR INTENDED FUNCTION. STRAW BALE DIKES OR SILT FENCING MAY REQUIRE PERIODIC REPLACEMENT. SEDIMENT TRAPS WILL REQUIRE PERIODIC SEDIMENT REMOVAL. - 10, POST (2" X 2" NOMINAL) ANCHORED IN TRENCH AND 1 1 , ; 24" iFIRMLY ATTACHED SILT FENCE SILT FABRIC STAPLED 1 n MIN. FABRIC TO POST TO POSTS 1,1 6"x6"TRENCH MIN. � FLOW irT �i 42 T COMPACTED MIN.'� BACKFILL Mat-420* Ili l J� SILT FENCE FABRIC ANCHORED IN W" TRENCH AND ATTACHED FIRMLY TO POST /`� TEMPORARY SEDIMENT CONTROL FENCE Scale: N.T.S. IN FBNDABLE ITED INC. RING, NG & BEYOND nue, Ste.201 Glenwood Springs, CO 81601 tele:970.945.5252 www.bu•inc.com Engineer or Surveyor Seal D P I L C O. .F V rA to�Q 5/26/26 37110 ss/ONALE� Client Information: Steven Mancini 41500 Mound Road Sterling Heights, MI48314 586J39.5210 Subsurface Utility Engineering (SUE) Required Project: No If 'Yes" SUE Certification by: Firm: NIA Job #: NIA Date: NIA NORTH 0 20 40' Scale: 1" = 20AdEFAI Know what's below. Call before you dig. O C 0 ex ®. o O CL) V CU C `••b— O 1114-- 'y a Co o a V LJ U -O � i C s CL) C o � 3 c CL) 1S? a �y G C •� O 1C > D C a' y � Agency Approval Agency: Dept: Date: Continents: Date Revision Project No.: Sheet 25032 Filename: dwg Designer:ner: Designer: tl(w C01 Drafter: d1w Date: 5126126 we. 0 NOTES: \ \ \ \ \ \ 1 / ) ` ' ~ ' - - - - SURFACE (+ F n (� NI \ \ V 1 1 ' 1 \ ` \ / / / :. \ \ \�."� \ -\ _ \ \ 2 TBU l.Uflee 1'Ut KoO� l,. I,., ,�;, ' >'' DOLOR FAILURE To 00SO NAY RESUL�N MISSMIIN v L� v-- \ I�- \ \ / 1 ` It ' r \\ I t\ N IN IN,1 \ v v v v v\ \ \,\\ \, \ '\\. \ \\\ \ _ \\ \, \\ \ �( \ CONSTRUCT SWALE (/ �. '/.. >\ APPROk. TEST PITS�M - r i , , L \ `\ \ \ `\ \ \ N. \\ \ , ,` \ % ��_-• 7 \ \ ABOVE AND AROUND THE 7 LOCATION, TYP. , V A V A A \ A ' 1\ t 1\\ V y1 VA \ VA v A v v l A i A STAFIELD(SEEDETAIL} \, m '\ I� v A \ v A A lX� , v , I \, IN I,', \ A ` V IN `.\+t,\\\,\\\1111\ \\\\\\\\ \\\\\`\\'\\\\ �) \ s\\ -_- \\�J\ / , i\ 1' •�`� _��` l\ `vi-.._ IN,\ V I v A 1 1 I I A A y\` �' A V v V A\ V A `, v( v A SOIL TREATMENT AREA (STA) V\ B \ t \\ \l } 1 \ \ \ \ \ ` \ \ \ \` ! \ \ }\ \ ) ` 90 QUICK 4 INFILTRATOR (6 x 15j \ \ ` \ \ \ \ \\ \ \ \ \ \ OR72ADS ARC36UNITS 6x12 \ IIN 1 III, ; \ \ \ \ \ \ y \\ \ \ \ \ \ \\ \ IN A TRENCH CONFIGURATION \ \ \\ \\ INSPECTION PORT A ACH ti ` \ \ \ ( \ \ \ SEE DETAIL AND SETBACK NOTES � \ �vvv A TOIA. v� V V` AV A A A +I j] SANDY CLAY LOAM SAND, CLAY, GRAVEL, -- BROWN, MO FEW 0 B \ \ \ \ \ \ \ \ ( ) 6 MIN. TYP, \ \. 1`\ \ \ '\ \ \ N. \ \ \ \ \ \ \ \ \ \ , \ END OF EACH TRENCH, TYP.` ` \` ` \ \ J 1 11 \ \ \ \ \ \ \ \ \\ \ \\ \ \ \ \ \ \\ \ \ \ l OIS�RIBUTION DOk / \, \ SITE EVALUATION:; \ \ \ i \(SEE DETAIL ` \\ =\ \ \ \ \ , \ \ \ \ i �., 1. SITE AND SOIL EVALUATIONS WERE PERFORMED BY: r' 1 , ll ` i I I , * \ \ \ \ \ `\ \ \` \\ \ \ \ \ I: / \� I� \ ` \ \\\ \ ; r \ `\ DERIC J. WALTER, PE !(EVIN DYE, PE „ ,.✓ } , \ \ \ \ \\ . \\ , \ , } ,\y \ \ \ \ \ \ \ �� \•\ \\�� ` s ! \�� \ ` BOUNDARIES UNLIMITED INC. BED QUEST �Y s 1 I \ \ \ \ \ \ i t ` \ , , \ \ \ \ \ \ \ \ .Q> \ , \ �\-932 - Y- ,93 /\ t3'.., o- s i r \ , , �, \ \ \ ` -� , \ \ \ \ `\ \�"-- 0\ \ > �"'� 923 COOPERAVE, STE.201 PO 1372 A A A y A\ v v V \ y A\ v A v A v ` > /" , A V ` v`` v A V 1 GLENWOOD SPRINGS, CO81601 RIFLE, COLORADO 81650 .I I -- pI \ „\\ \ \ \ \ \ \ \ \ ,t� -� , 9709455252 9703186784 \ \ \ \ �\ \ \ _ \ \ 9� : \\ \ \, To Glenwood Springs', ViClnity Map VP p . \ J ` \ \ \ To Gypsum r ' i, \, \ \ \\ \\ \ \ \ \ \ \ \ \ \ `\ ` \ \�\\ \ \ \�\\ I / 2. EVALUATION DATES): 5/18/26. 0 \ l 1 , \ \ \ \ \ \ \ \ \\ \ \ \� \ \ \ \ ` a i \ \ \ \�`,\\ `` \ / SYSTEM DESIGN &CONSTRUCTION NOTES: \ \ / \ \ \ \ \ _ \ \ \ \ ( J 3. SOIL WAS CLASSIFIED BY THE GEOTECHNICAL ENGINEER (GEO QUEST (PROJECT #26-142, May 18, 1 ALL CONSTRUCTION SHALL BEJNACCORDANCE WITH CONE REGULATION 43 ONSITE WASTEWATER TREATMENT SYSTEM (OWTSI REGULATION, MOST CURRENT EDITION \ \\ \ \ \\\� \ \\ \ \ \ \ \ \ \ \ \ `\ ,+ 1 1 \ \ i \ \ \ ` \\\\\\\\ \ `,- ^ \ \ \ \ _ - 2026) AS USDA SANDY CLAY LOAM; TYPE 3A; WITH AN LIAR OF 0.30 GPD/SF. AND LOCAL AGENCY REQUIREMENTS WHICH MAYOR. MAY NOT SPECIFICALLY BE NOTED ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR KNOWING \ \ \ \ \ \ \ -��\ , \ ,. 1 \ .m r. \ + , \ , \)) \ 1 • - X \ AND CONFORMING TO SUCH SPECIFIC DETAILS AS ARE REFERRED TO IN THE ABOVE MENTIONED REGULATIONS, THIS DRAWING DOES NOT CONSTITUTE AN OWTS \ \ \ \ \ \ \ r �"�-\^��\l^ J� 1 t, \ \\ \ V �,.�";\� \\ I 4. SETBACK REQUIREMENTS FOR A TREATMENT LEVEL 1 STA TRENCH/BED, UNLINED SAND FILTER OR PERMIT, A PERMIT MUST BE OBTAINED FROM APPROPRIATE LOCAL AGENCY, THE CONTRACTOR MUST CONTACT THE LOCAL AGENCY HEALTH DEPARTMENT AND THE a r' I � 1 \ \ \ \ \ \ \:\ \\ \ I / \ I. , t •� ,\\� \,,,� �`i \ \ \ ( c SEEPAGE PIT (PERTABLE 7-1) AND ANERN=10 50 GPD: PROJECT ENGINEER FOR INSPECTIONS OF THE CONS RUCTED SYSTEM BEFORE BACKFILL. A REQUEST FOR INSPECTION BY THE PROJECT ENGINEER AND THE COUNTY fD \ \ , \ \ \\\ \ \ \ \ \ \ 1 \ \ \ _ _ \ _ 4.A. SPRING, WELL OR POTABLE CISTERN=100 �y� \ \\ \ \ \\ �\ \ \` \ \ \ \\� ,\\� t\\ \ \\\ \\ \ \ \ I \ \ \ +\ 1 \ \ } `,\ '\ t l \ V 1 ) / �- I \ \ ` �_ = _ _ `; \i\ \ \ \ `t t ` T ^ �,� 4.6. POTABLE WATER SUPPLY DNE=25' _ ENVIRONMENTAL HEALTH OFFICER MUST BE MADE AT LEAST 72-HOURS PRIOR TO THE DESIRED TIME OF BACKfiLLING. \ \ \ • \ \\\\\ \\ \\ \ \I\\ \ \ - \ ` \ 1 - �'= r'. ( y ��_ - _ -- -\ \ I it 1`! `1(.l \ 1 J i, 4.0 STRUCTURE W/ BASEMENTICRAWL SPACE-20' n0 I \ \ 1 \ \ ' \ \ \ \ \y \ \ \ \ \ \ 1 \ I @ \ _ 1 , \ IN \` ' /-" 4.D. STRUCTURE. W/O BASEMENT/CRAWL SPACE=10 2. DEMAND CALCULATIONS (SEC.43.6.A.2.h) \ \ \ \ \ \ \\ \ \ \I 1 \ \ \ \ I 1 , \ ,` \, > I / : \ 1 - '--\ \ \\ \ 1 ,` ', \ \, \ \!\,\,f/`-' / 4E, PROPERTY LINE, PIPE OR LINED IRRIGATION DITCH=10' 2A, THREE 3 BEDROOM PRIMARY RESIDENCE USING TREATMENT LEVEL 1 TL1 Ql I i , \ , 1 \ \ \ 1 \ ' \ I 4.P, INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=25' l) ( )' / \ \ 1 I, \ \ \`� �\ \. \\ �,\\\\ \ \ \ ` 1 \ \\ \ \ ` \ \ \ 1 +, \ \ I 7, '' / --- -\ \ \ , t I \ \\ \\ \\\\\` ( 2.B. AVERAGE DAILY WASTEWATER .FLOW (ADWF) AND ORGANIC LOAD RATE(BODS): (\ , IN, , \ 1 4.G. LAKE, WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' \ \ \ ` \ \ \ ( t l \ } \ 1 \ / t / \ \ ,_ _ _ 1 ` \ \ \ \� ` \"\ r 2.B.f. SINGLE FAMILY DWELLING: I5 tic & 0.20 80D.Ihs/tla }' \ ', \ \ \ -\ \ ` \ \ \ \ 4.H. DAY GULCH, CUT BANK OR FILL AREA=25' 9P Y 1 I 4.1. SEPTIC TANK=5' 2.8.2. ADWF: \ \ 4.J. RESTRICTIVE LAYER OR GROUNDWATER (VERTICAL): 4' (TREATMENT LEVEL 1, GRAVITY FEED) 2.B.2,t PRIMARY RESIDENCE (3 BEDROOM) = 450gpd (MINIMUM PER TABLE 6-1) 1 \ \ 'I. I , t , , , \ \ I I ( �/ _ i 1 \ \ \ N \ ` \\ \ N. \\ 2.B.2.2. ADWF = 450 gpd 1 1 \ 1,1 , 1 t ', \ \\ I ) i \ , \ , 1 1. }. \I 1 ) t \ \ \ \ �\ `\ n , -"\ ( I `\ '`. '\ ` \\`\ 3. SETBACK REQUIREMENTS FOR THE SEPTIC TANK SHALL BE (PEA TABLE 7-1): i 2 r I \ , I I \ j } { I \ 1 \ \ \ ` \ \� \ 2.B.3. BOOS = 020165/tlay * 6 PERSONS = 1.201bs/tlay ± ( 1 \ I I I ( \ \ \ \ \. 1 1 , + I / \ > 1 I \ \ \ \ 3.A. SPRING, WELL DR POTABLE CISTERN=50' < r r r �- ( \ \ , \ \\ BOOS mg/L = BODs 1,000,000 = 1.201hs/dav*t,000,000 = 320 mg/L \ \ � I I \ l --,�-- ` � I 1 \ ` 1. ,\ \\, \ \\ 3.8. POTABLE WATER SUPPLY LINE-1O \ 1 } \ \ r , / \'�-��- - /- Y i 1\\ \\\ ` 3.0, STRUCTURE W/BASEMENT/CRAWL SPACE 5' ADWF*8.34 4W d 834 \ `-i ✓ 3.D. STRUCTURE W/O BASEMENT/CRAWL SPACE=5' \, I I I I t \ \ \ 2.B.4. CBOD - BOD * 0.85 = 272 m /1- � � T I 1 I \� �� s i � r r � 1\+� 1}) I I I 3,E. PROPERTY LINE, PIPE DR LINED IRRIGATION DITCH=10' 6- ° M l ( j 1 1 V A ) ) _�� / i l l l I A/v V / / i/ 11 3.F. INTERMITTENT IRflIGAl10NLATERAL, INFILTRATION STRUCTURE=10' 3,G. LAKE WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' 3. SEPTIC TANK (SEC.43.9.B.2.aI: 3.H. DRY GULCH, .CUT BANK OR FILLAAEA=10' 3.A. INSTALL A 1,000 GALLON TWO -COMPARTMENT SEPTIC TANK WITH EFFLUENT FILTER IN THE OUTLET RISER. (TABLE 9-1) V A i,1\ I m �� ✓ , I I 1 m i 1 / / * .-v / ��/f"/ / / / �„ , / / / / ) r j 3.1. STA TRENCH/BED, UNLINED SAND FLIER OR SEEPAGE PIT=5' 3.6. THE TANK IS NOT SUBJECT TO BUOYANCY. x NOTES: SITE SOILS EVALUATION I I I I . r , , v1\\� 4. SOIL TREATMENT AREA(STA) CALCULATIONS: PROPERTY LINES MAY BE BEYOND THE 4,A. THE STA AREA SLOPES GENTLE TO MODERATE. I I - / + Scale: N.T.S. ) I j! r I r / l ' MAPPED AREA. 1 l 1 ,V ( (, A < <V < <� 1 4.B. LONG TERM ACCEPTANCE RATE (LTAR) FOR TREATMENT LEVEL 1 (TL1) OF 0.30 gpolSF (SEE SITE & SOILS EVALUATION NOTES/DETAIL). - 4.C. MINIMUM SOIL TREATMENT AREA, A(PHASE I): h 1 v,I 1 INSTALL TWO-WAY �LIJAt OUTs t I) I� 1 'I ( h 4 ) I LOCATIONS OF ALL COMPONENTS MAY BE A y y v , v A I v A = ADWF = 450 =1500 S.F. / EVERY 100 LF MIN. (SEE DETAIL)", 1 ; I + I ' I ' _ I I I VARIED AS NECESSARY AS LONG AS ALL v vv\vv v�V� LIAR 0.30 9PNS.F. (CO 1 I I I/U / 1 I r 1 1�MINIMUM DISTANCES AND SLOPES MEET \ �\ 4.D. SIZE ADJUSTMENT FACTORS: GRAVITY TRENCH=1.0;CHAMBERS=0.7(TABLEIO-1A). l I / / ri f li _ \ �;: THOSE REQUIRED. \ < ; \ MAINTENANCE NOTES 1 + I F I \ \ 1' t I I i r `\ \/\� \` 4.E. A,alGRA LLESS SF* 1.ER0.7 = 10505E \, 4" 0 SCH.40 PVC SEWER,Nt� ; I r r I r y , I 1 ( ( } \ 4.F. GRAVELLESS CHAMBER TRENCH SYSTEM: 1 - 2% MIN. SLOPE W( 3:5'' ! 1 a)O " ' I i \ \ \ \ \ \ \ \ `l 1. TO ENCOURAGE THE HEALTH AND LONGEVITY OF THE OWTS SYSTEM, THE OWNER SHALL 4F.1. INFILTRATOR 0UICK4: 1050 SF/ 12 SFNNIT = 88 UNITS. INSTALL 90 UNITS 1N SIX (6) TRENCHES CONTAINING FIFTEEN (15) UNITS EACH. ' (\ @ MIN. COVER AND PIPE 1 11 I 111I II'� �I �-' _ \ \ CONSIDER THE FOLLOWING:INSULATION SEEDETAIL„p I I I \ L - 4.F.2.ADS ARC36:1050SF/15SF/UNIT=70UNITSJNSTALL72UNIlSINSIX(IgTRENCHESCONTA/NING1WEClE(12)UNfTSEACH. ( ) 1 \ } I III I I I I. I ) ( r �s ,� `` �.- \ ` J �. \ \ \ \ \ \ 1.A. MINIMIZE THEAMOUNT OFWATER THAT GOES DOWN THE DRAIN, THE BETTER YOUR 5. THIS SYSTEM IS SIZED FOR TYPICAL HOUSEHOLD WASTES ONLY, BACKWASH OR FLUSHING FLOWS FOR REVERSE OSMOSIS UNITS OR WATER SOFTENERS AND/OR l ' I I \ ' G \ - \ \ \ \ \ , SYSTEM WILL WORK 1.B. MINIMIZE SOLIDS GOING DOWN THE DRAIN. FILTERS SHOULD NOT BE INTRODUCED INTO THIS SYSTEM. BACKWASH AND FLUSHING FLOWS SHALL BE DISPOSED OF WITHIN A SEPARATE INFILTRATIVE SYSTEM. 6. CLEAN OUTS ARE REQUIRED AT THE HOUSE AND AT ALL BENDS GREATER THAN 45'AND AT LEAST EVERY 100 FEET BETWEEN THE HOUSE AND THE SEPTIC TANK f.C. ELIMINATE GARBAGE DISPOSALS OR KEEP THE USE OF GARBAGE DISPOSALS TO A I ' 1 °�, i 1+ \I \ \ \, II 1 }, II `, I I j / '+, '\ \I \ \ ) �\ `\\ \\ \` \ \ ` _ - _ _ _ �.,- \ \ `t 1 , } MINIMUM, 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL WATER TIGHT COMPONENTS THROUGHOUT THE SYSTEM TO PREVENT INFILTRATION. / INSTALL 1000-GALLON T�JO-CbMPARTMENT I + 1� ° \ 1 \ - '-'\ \ j 1.D. MINIMIZE GREASE AND OILS THAT GO DOWN THE DRAIN. 8. INSTALL RISERS AS NECESSARY TO BRING ALL ACCESS PORTS TO FINAL GRADE, PORTS SHALL BE MARKED IF CAPS ARE TO BE BURIED. laosd SEPTIC TANK WITH AN EFFLUENT FILTER IN THE I ; S 1 1 , 1 \ \ +I \\ `\ \ - \ \ I \ t 1.E. USE LINT FILTERS ON LAUNDRY MACHINE DRAINS. 9. INSTALL 3-INCHES OF BLUEBOARD INSULATION, 3-FEET WIDE, OVER SEWER AND EFFLUENT PIPE WHEREVER DEPTH IS LESS THAN 3-FEET. UNDER NO CIRCUMSTANCES ( I � OUTLET RISER (SEE DETAIL & SETBACK NOTES) ,I '( \ , �1 1 1 1 I 1 \ \-, \ \ \ I \ ,I 1.F. KEEP SAND AND DIRT OUT OF THE BUILDING DRAIN. SHALL COVER BE LESS THAN 2-FEET. ` \ ��0 I.G. AVOID FLUSHING SANITARY NAPKINS OR PAPER PRODUCTS OTHER THAN TOILET PAPER. 10. SITE PLAN INFORMATION FROM OTHERS. LOCATIONS OF ALL COMPONENTS MAY BE VARIED AS NECESSARY AS LONG AS ALL MINIMUM DISTANCES AND SLOPES MEET �. o /OQ��CQ I INSTALL A TVJO-44AY ) 1 ,I i I l i \ \ \ o \ } I \ \ ` \ ! \ \ 1:H. DO NOT USE LYE -BASED DRAIN UNCLOGGER CHEMICALS SUCH AS DRAINO, OVEN -OFF, THOSE REQUIRED. \`�� CLEANOUTOUTSIDETHE It IL 1 i ('1 \ \\\\ \ \ 11 1 ,I 11 \ \\ \ \ \ \ \ DnomeaSTRONG CLEANING AGENTS. i CIS ! BUILDING (SEE DETAIL) I , 1 I \ \ \ 1 ( i \ ` DO NOT RUT ANY "HOOT DETERRENTS"DOWN THE DRAIN. I I I l 1 , 1 \ \ \ \ \ \ \I t -, I I, i \ \ \ \ \ \ + \ ( 1 + '} I.J. DO NOT POUR PAINT THINNER, PESTICIDES, PAINTS OR PHOTO LAB CHEMICALS DOWN ,lY `9 ` I \ \ __ `\ I \ i ' I , THE DRAIN � , A \ �l ( \ I t i00' SETBACK I w' 11 \\a \\ ; \\ \ \ \ \ \ \\ I \ \ \ \ ' , \ _ , \ ` I.K. MINIMIZE USE OF CHLORINE BLEACH AND TOILET ADDITMES. 4" DUPOM STYROFOAM BRAND FROM WELL o +i I I eOo , \ \ \ \ \ \ �I, I, I \ \ \ - - \ I HIGHLOAD 6D XPS INSULATION IN \ \ ,� ,�. \ \ L \ ` I I 2. THE OWNER SHALL CONTRACT WITH A SEPTIC TANK INSPECTOR TO INSPECT THE TANK / ( I ) d \ \ \ \, \ \ \ ,+` � \ \ \ \ \ _ ANNUALLY FOR GREASE AND SEDIMENT ACCUMULATION. THE INSPECTOR SHALL REMOVED I, } 1 \\ \,\ \\ \\`\ \ \ 1, \ `, 1 I < \ AND PROPERLY DISPOSED OF ACCUMULATED GREASE AND SEDIMENT AS NEEDED TO ENSURE -. tLL &WATERLINE- 1 `r, "��1 �'L - -j'- �-^ l�k '-r--> y - �-- 1 \ -1 - - <� \ I l (\ - PROPER FUNCTION oFTHESYSTEM. 1/2" MINUS ONSfTE �x _ 25' $E K SELECT MATERIAL '�� 10 gallon Top Seam se 2CP Pol lok Distribution Box its Tl Misers and Lid PIPE INSULATION 12" SD. NYLOPLASi H-2D ATTACH REMOVABLE CAP OR SOLID COVER ASSEMBLY THREADED CLEANOUT ASSEMBLY. REMOVABLE PVC CAP INSTALL MARKER IF CAP IS TO FINISH GRADE Scale: N.T.S. FLUSH WITH SURFACE 8E BURIED. 111 UD$OX 6 & UD-BOX 8 , DESIGN NOTES �;_•�_.:•-_ .. r Top -: q.A�. �VA�.A- / vA� • Design per performance test per `, �Q= ' ^ T" ASTM C1227 �`'"� • �•� View __ ) D-BOX SEAL • Top surface area 46.25 ft' __.-) _ -__ - _ �� / tevea' 4DeBE W1111 24'k24'kfi'CONCRETE LINE ALL SWALES WITH FLOWLINE GRADES EXCEEDING • tdn028 days; concrete - 6,000 PSI ;Y Cbw'Acew' �. " I I �,,--\ IN HOROSCOPE 4"HPVC RISER 5% WITH 9'0NOMINALANGULAR RDCKRIPRAPORA installation, a " ,C PERMANENT EROSION CONTROL FABRIC (NORTH �: • Tank to be set on 5" min. sand is ! SIDE CUTOUT I v 4"flPVC TWO-WAY AMERICAN GREEN VMAX S200 OR EQUAL). INSTALLED bed or pea gravel TO ACCEPT �; - PER MANUFACTURER'S RECOMMENDATIONS. (- ' CLEANOUT TEE ADJACENT GRADE • Tank to be backfliled uniformly on IL-TAt1C POLYLOK SEAL °a all sides in lifts less than 24" and NO.3001 - ,\ I TEAR OUT FOR mechanically compacted Ir r 4" SDR-35 OR FLOW I �I '� \ SCHD-40 ,\ • Excavated material may be used for ; �� »>lll LLL.,... _... ..�°' - \L , \ bockfill, provided large stones are ` ?` NOT TO SCALE \'\\ \ \`- removed • tankExcavation filled with water be driortered to being __ 4"BSEWEALINE p g �D•$oXe'wsER 'IP.� • �y IN LANDSCAPE water table less put in service o than 2'abeow tion ig grade tO Grade € If - -��- I IAR R(YT"LI11111M AN connectors T V�-�� • Inlet and Outlet identified above pipe 1 1l'i8" I, s --- - _ - ---- - '/ \1 �] - - SLOE SLOPES 3:1 MIN. • Delivered complete with Internal .4 i I 1 111i, i yy i7�--�-�� �(� 1-1. - it ---4 tC// �\ Twn_wnv rl Ming piping • 4' Maximum bury depth Fle)Qde Rubber ---- a '� �] '••" ••"' wi-i "' Scale: N.T.S. URAINAU.NWALt tltyl h�0�!/1 O Sealant ACCESS TO GRADE -_ Scale: N.T.S. REQUIRED UD-BOX12"RMiER norroSCALE GENERAL ABSORPTION AREA NOTES M El OR 1 • 1 1. 4" PVC TEE/RISER �' Ii.I (I tl, �'1 '!'I/ REQUIRED TMIN CIRCULAR IRRIGATION -STYLE VALVE 111 WITH EFFLUENT iii it + 1.. �� r POLYLOCK EQUALZER E GRADE 2 MAX BOX L COVER -LID COLOR PURPLE /. INSTALL CHAMBER UNITS IN ACCORDANCE WITH MANUFACTURER'S " FILTER ON THE 1 " NNOTCH"WEIR �� 5%-^ 1%MIN RECOMMENDATIONS. 4 TANK OUTLET OR GREEN q wElR swwEIS ;; FILL *'PVC TEE/RISER 5 " I, �! 1 % SELF WEIR d 1 2. ABSORPTION TRENCHES SHALL BE 3' WIDE OR LESS AND PARALLEL THE GROUND i FINISHED GROUND- MAINTAIN POSITIVE SURFACE CONTOURS. PARALLELING TRENCHES SHALL BE SEPARATED BY A DISTANCE SLOPE AWAY FROM TOP SURFACE OF STANDARD INSPECTION PORT, TYP. (4"0 OF 6' MIN. s _ THE CHAMBER TRENCHES. PVC SOLID PIPE CLOT TO FIT. LOCATE PER. Section FUSS PROME Fre 3: PLAN VIEW. ATTACH REMOVABLE CAP DA FIT FORAu4•f4PE ID ' GRAVELLESS CHAMBER SYSTEM -� /, 7 3. THE BOTTOM OF THE ABSORPTION TRENCHES SHALL BE LEVEL AND THE BOTTOM AND THREADED CLEANOUT ASSEMBLY 106" View " k�"� INFILTRATOR QUICK 4, ADVANCED ,\ \ d BggOf FILL SIDEWALLS MUST BE RAKED TO REMOVE ANY SOIL SMEARS INCURRED DURING THE 20 COVER FOR RISER 6 D$OX DRAINAGE SYSTEMS BIODIFFUSER " j /i\ / EXCAVATION. FAILURE TO DO SO MAY REQUIRE THE CONTRACTOR TO REPLACE THE (STANDARD), OR ENGINEER NOT TO SCALE APPROVED EQUAL ` ;\\\\> V� /:\\\<�\%�\\\'\�\�;�„� �\ 1%MIN ABSORPTION FIELD AT HIS/HER OWN IXPENSE. '`':\\�\� \//��\\\\\';/\\i/\\/\_/_��/`\/\\/�\//\\//\\lam\\\�\",\ v- X;S` ';1% PVC COUPLING FOR SUPPORT 4. DRAINAGE SWALES ARE TO BE PROVIDED ABOVE AND AROUND THE FIELD, AS S�j\/\/�/',/\ 'i\, �D� NECESSARY, TO PREVENT SURFACE RUNOFF FROM ENTERING ABSORPTION AREA. Digging Specs Invert Dimensions Net Capacity Net Weight BOTTOM TO BE LEVEL AND FLAT OVER\. \.37 �- GASKETED SEAL ON ENTIRE AREA TO WITHINO.D5' . TYP.) 36'MAX \' /i;\\j \// j /jl`; Yj /i`%\/j'✓\Y/\%%` �// ; ` `` G 'QI' 5. NO EXCAVATION OF THE ABSORPTION FIELD IS TO BE GONE DURING NET WEATHER AND 11' Long x T Wide Inlet !Outlet '_; ,ength Width Height Ill Side Outlet Total Lid Tank Total ! '' LID &RISER \'\\\'\\/\\S\\'\\- \T \/�\;\\���\\���\�', ✓ i;;j \ ,4. h �;', 'ODE USE OFAUBBEATIAEVEHICLESOVERTHEABSORPTIONAREAISSTAICTLVPROHIBITED. - ---- - - REMOVE ANY ENCOUNTERED i.,,jv, /,/,yv/ / , / /Av/% /iv ivy/ i , Vic, , INFLOW PIPE SHALL ENTER 6 MIN. - _A` ; •, ,. 56" below inlet 56" 53" 111' 60" 68" 687 gal 323 gal 1D70 gai 2620 Ibs 9380 Ibs 12000 Ibs - SANDORSAND GRAVELS. DO - ( , )rA vi / THE UPPER KNOCKOUTS `/' ' � ��%/ � i v// %�/'v// v/� I �..i - - . 6. UNSUITABLE MATERIAL EXISTING WITHIN THE FIELD SHALL BE EXCAVATED AND ��.- ._--- -- __._- ---- LOAMY COMPACTED .,. A/v yy;vA,A.� r v�v NOT USE COMPACTED MATERIALS. �'� �i ,i', /i vi/ / ii / �i i , i - BACKFILL SHALL CONSIST OF IMPORTED LOAMY SAND OR SANDY GRAVEL. THE DO NOT WALK ON OR COMPACT ivA/`iA /v���A ER'k0ATED PVC PIPE. ENGINEER SHALL BE CONTACTED IF BEDROCK OR GROUNDWATER IS ENCOUNTERED IN �<vAw NO PIPE TO REST ON .. z• `'' BOTTOM OF TRENCH. - "\\��� \ \ THEOVER-EXCAVATION. ""BOTTOM OF THE BED ' Phone: 719.395.6764 Phone: 719�395�764 7. TOPSOIL COVER MAYBE VARIED (1-FOOT MINIMUM, 2-FOOT MAXIMUM) TO ALLOW FOR � o =LEYVALLEY Fax: 719-395-3727 o VALEY Fax: 7'19-395-3727 LANDSCAPING' 0 CAST, Inc. webeille: www.WTalleyprecastoom ❑ PRECAST, Inc. websille: wwwmalleyprecastcom GRAVELLESS CHAMBER ABSORPTION TRENCH Bueaa Vista, Colorado Email: fronWeSINIQaalleyprecast Buena Vista, Colorado E111i irordIdesk@valleyprecaste:om Scale: NTS, ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0' - 0" 2' - 0' 2•- 0' 3' 0' 3'- 0' 4' 0. DRY V a' BOUNDARIES UNLIMITED INC CIVIL ENGINEERING, LAND SURVEYING E BEYOND 923 Cooper Avenue, Ste.201 Glenwood Springs, CD 81601 tele:970.945.5252 www.hu-inc.com or �'p,D011�F� 0%\GjONWq! U V 2oQ 5/25/26 y'• O 37110 L Steven Mancini 41500 Mound Road Sterling Heights, MI4B Subsurface Utility Engineering (SUE) Required Project: NO If 'Yee, SUE Certification by: Firm: NIA Job #: NIA Date: ILIA NORTH Know what's below. Call before you Ill Agency Approval Agency: Dept: Bi Date: Comments: No.: Sheet Ce2