HomeMy WebLinkAboutStamped Plans 02.02.26 rev4PLAN NOTES O1 TERMINATE EF-2 EXHAUST DUCT WITH PAINTABLE WALL CAP. l 2 RE: ELECTRICAL POWER PLANS FOR BB-1 / BB-2 CONTROL REQUIREMENTS. MAIN LEVEL MECHANICAL FLOOR PLAN SCALE: 1/8" = 1'-0" MECHANICAL EQUIPMENT LIST AIR DEVICES BB-1 ELECTRIC BASEBOARD RUNTAL MODEL E133-72-120D 879 WATTS, 3000 BTUH 120 VOLT BB-2 ELECTRIC BASEBOARD RUNTAL MMODEL EB-120-120D 1466 WATTS, 5000 BTUH 120 VOLT EF-1 ADMINISTRATION EXHAUST FAN COOK MODEL SQN-D 100SQN 700 CFM, 0.5" S.P. 1/3 HP, 120 VOLT EF-2 RESTROOM EXHAUST FAN PANASONIC MODEL FV 0511 VF1 80 CFM, 0.25 E.S.P. Q d WATTC 190 \/Ol TC EF-3 CRAWLSPACE VENTILATION FAN FANTECH MODEL FG 8 300 CFM, 0.25" S.P. 1.2 AMPS, 120 VOLTS PROVIDE COMPLETE WITH SOLID STATE SPEED CONTROLLER RATED FOR 5.0 AMPS AND LINE VOLTAGE HUMIDISTAT (START ON HUMIDITY RISE). HUMIDISTAT SHALL BE INSTALLED WITH -IN 3' OF CENTER OF NORTHEAST CRAWLSPACE WALL. limmyp1ri►[ewile1r1e VENTILATION FAN HAS BEEN SELECTED BASED ON 2 ACH VENTILATION RATE OVER 1500 S.F. AREA x 5' MAX. HEIGHT. FC-1 FAN COIL UNIT - SERVICE TO ADMINISTRATION ARMSTRONG MODEL 77 AH 2 A E 60 P X-71 1700 CFM, 700 CFM 0/A, 0.5" S.P. 36.2 MBH SENS. CLG, 42.6 MBH TOTAL CLG 49.0 MBH HEATING (HEAT PUMP) 12.5 KW ELECTRIC HEAT (AUXILIARY) 1 HP BLOWER MOTOR 66 MCA, 70 MFS 208 VOLT, 1 PHASE - SINGLE POINT CONNECTION PROVIDE COMPLETE WITH 2" MERV 13 PLEATED MEDIA FILTER FC-2 NOT USED HP-1 HEAT PUMP - ASSOCIATED WITH FC-1 ARMSTRONG MODEL 4 SHP 17 LE 1 60 P - 51 A NOMINAL 5-TON HEATING / COOLING CAPACITY 26.5 FLA, 32.5 MCA, 50 MCA 208 VOLT, 1 PHASE PROVIDE COMPLETE WITH 1-1/8" x 3/8" REFRIGERANT LINE SET 171��►Ce>tt1L���7 RT-1 EXISTING ELECTRIC / GAS ROOFTOP HVAC UNIT TRANE MODEL YCD 360 B E P 2 30 TON COOLING - NOMINAL CAPACITY 600,000 BTUH HEATING, 355,200 BTUH OUTPUT, 6,500 FT. ELEV. 12,000 CFM NOMINAL S/A, BALANCE TO 4100 CFM MINIMUM O/A 150.4 FLA, 185 MCA, 225 MOP 208 VOLT, 3 PHASE SEE RE -COMMISSIONING REQUIREMENTS - DRAWING M-2 - FOR START-UP / COMMISSIONING UH-1 GAS FIRED UNIT HEATER REZNOR MODEL UDAS 100 100 MBH INPUT, NATURAL GAS 64.1 MBH OUTPUT, 6,600 FT. ELEV. 3.9 AMPS, 120 VOLTS TYPICAL OF TWO UNITS LV-1 ADMINISTRATION OFFICE OUTSIDE AIR RUSKIN ELF 375 DX 24" x 12" TALL LV-2 ADMINISTRATION OFFICE EXHAUST RUSKIN ELF 375 DX 24" x 12" TALL SA-1 SUPPLY AIR REGISTER KRUEGER MODEL 5880 - DOUBLE DEFLECTION 14" x 6" W/ HORIZONTAL FRONT BLADES PROVIDE WITH OPPOSED BLADE BALANCING DAMPER AND FRAME FOR GYPBOARD WALL MOUNTING SA-2 IS SIMILAR EXCEPT PROVIDE FRAME FOR SHEET METAL MOUNTING SA-3 CEILING DIFFUSER KRUEDGER 1400 SERIES 4-CONE WITH FRAME FOR GRID CEILING INSTALLATION 01141:00111 FA9W: _l04iA01[I :N:i1P►MilljM1lll819 1111•yp0 RA-1 RETURN AIR GRILLE KRUEGER S580 - 35° BLADE DEFLECTION 30" x 12" TALL PROVIDE WITH FRAME FOR GYPBOARD WALL MOUNTING EA-1 EXHAAUST AIR GRILLE KRUEGER S80P 10" x 10" PROVIDE WITH FRAME FOR GYPBOARD CEILING MOUNTING AND OPPOSED BLADE BALANCING DAMPER. EA-2 EXHAUST AIR GRILLE KRUEGER S580 - 35° BLADE DEFLECTION 18" x 10" TALL PROVIDE WITH FRAME FOR GYPBOARD WALL MOUNTING AND OPPOSED BLADE BALANCING DAMPER. TCHES SHALL BE E-1 . S/A TRUNK DUCT. ONNECTION TO SA-4. AIIV, iil>ilCi1PI:aD11[It 8 RIFY MINIMUM FIELD FABRICATE % FREE AREA TO COVER 10 OODINATE WITH G.C. AS REQUI D TO PROVID 1" DOOR UNDE -CU . 11 SUPPLY AIR DUCT SHALL BE COVERED WITH A HORIZONTAL CHASE / SOFFIT INSTALLED ON BACK WALL OF OFFICE AREA. FIELD COORDINATE DUCTWORK INSTALLATION AS REQUIRED. INSTALL EF-3 (CRAWLSPACE VENTILATION FAN) IN CRAWLSPACE. FIELD COORDINATE FLOOR ACCESS PANEL WITH G.C. 13 EXTEND 8"0 E/A DUCT FROM EF-3 TO BUILDING EXTERIOR. FIELD COORDINATE TERMINATION WITH G.C. AS REQUIRED TO INSTALL APPROX. 18" ABOVE FINISHED GRADE TO BOTTOM. TERMINATE WITH PAINTABLE METAL WALL CAP. 14 INSTALL 8"0 PAINTABLE METAL WALL CAP WITH INSECT SCREEN MINIMUM 5'-0" FROM EF-3 TERMINATION AND MINIMUM 18" ABOVE FINISHED GRADE FOR CRAWLSPACE MAKE-UP AIR. EXTEND DUCT DOWN INTO CRAWLSPACE AND TERMINATE WITHIN 12" OF CRAWLSPACE FLOOR. 15 EXTEND EF-3 EXHAUST DUCT TO WITHIN 24" OF SOUTHEAST WALL OF CRAWL SPACE. GENERAL NOTES 1. PROVIDE LABOR AND MATERIALS REQUIRED FOR COMPLETE AND OPERATIONAL MECHANICAL (HVAC) SYSTEMS. 2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE GOVERNING CODE AUTHORITIES. 3. ALL WORK SHALL COMPLY WITH AND BE COORDINATED WITH REQUIREMENTS OF ARCHITECTURAL PLANS AND EXISTING CONSTRUCTION AT THE TIME OF INSTALLATION. 4. WHERE DESIGN INFORMATION IS IN -ADEQUATE OR INCOMPLETE WITH REGARD TO PROJECT SCOPE OR CODE / ORDINANCE COMPLIANCE IN ORDER TO PROVIDE A COMPLETE PROJECT BID OR PRICE, THE MECHANICAL AND / OR PLUMBING SUB -CONTRACTORS) SHALL BRING SUCH TO THE ATTENTION OF THE ARCHITECT OR ENGINEER PRIOR TO BIDDING OR PRICING THE PROJECT. IMPLICIT IN SUBMISSION OF A BID OR PRICE TO DO THE WORK IS THE STATEMENT THAT THE PROJECT SCOPE AS SHOWN ON THE PLANS WILL BE INSTALLED COMPLETE, OPERATIONAL, AND IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. 5. INSTALL EQUIPMENT TO BE READILY ACCESSIBLE FOR SERVICE AND MAINTENANCE. REVIEW PROPOSED INSTALLATION WITH OWNER AND ARCHITECT PRIOR TO STARTING WORK. 6. OBTAIN WRITTEN APPROVAL FROM THE ARCHITECT OR STRUCTURAL ENGINEER BEFORE NOTCHING, CHIPPING, BURNING, DRILLING OR WELDING OF STRUCTURAL MEMBERS. 7. MAKE ALL DUCT CONNECTIONS TO FAN COIL UNITS, MAKE-UP AIR UNIT, AND EXHAUST FANS WITH FLEXIBLE CONNECTIONS. 8. COORDINATE FINAL CEILING GRILLE AND EXHAUST FAN LOCATIONS WITH GENERAL CONTRACTOR AND LIGHTING LAYOUT PRIOR TO ROUGH -IN. 9. SEAL ALL DUCT JOINTS AND CONNECTIONS TO EQUIPMENT AIR TIGHT. 10. NOT ALL DUCTWORK OFFSETS AND TRANSITIONS REQUIRED TO INSTALL THE WORK IN THE AVAILABLE SPACE ARE SHOWN ON THIS DRAWING. FIELD MEASURE FOR EXACT REQUIREMENTS AND INSTALL ACCORDINGLY. 11. UNLESS OTHERWISE NOTED, ALL DIFFUSER RUN -OUT DUCTS IN ACCESSIBLE LOCATIONS SHALL BE INSTALLED WITH BUTTERFLY DAMPERS AT TAP TO MAIN TRUNK DUCT. 12. PAINT ALL DUCTWORK VISIBLE BEHIND AIR DEVICES MATTE BLACK. al m ".1 mmn11Is] m1ll"l�►6y[oP►IOwlIAIII112 1:NIwe1m1 ".1 :a0611111a 14. RECTANGULAR DUCTWORK ASSOCIATED FAN COIL UNITS SHALL BE GALVANIZED SHEET METAL WITH 1/2", 3# FIBERGLASS DUCT LINING. 15. ROUND DUCTWORK IN ACCESSIBLE CEILING AREAS SHALL BE SNAP LOCK. 16. FLEX DUCTS SHALL BE INSULATED, NOT MORE THAN 5'-0" LONG; TAPE OFF ALL RAW EDGES OF INSULATION. 17. OUTSIDE AIR DUCTS SHALL BE INSULATED WITH 1" EXTERIOR DUCT WRAP, R8.0 MINIMUM. 18. INSULATE RIGID ROUND DUCTS ASSOCIATED WITH FAN COIL UNITS EXTERNALLY WITH R-6.0 "INSUL-SLEEVE". 19. INSTALL DUCTWORK PER SMACNA STANDARDS. 20. ALL THERMOSTAT WIRES SHALL BE ROUGHED IN USING 6-WIRE CABLE. 21. BEFORE STARTING WORK, SUBMIT EQUIPMENT SHOP DRAWINGS AND SUBMITTALS REQUIRED FOR PROJECT. IDENTIFY EACH ITEM WITH SUFFICIENT DATA TO CERTIFY COMPLIANCE WITH MECHANICAL EQUIPMENT LIST. PURPOSE OF SHOP DRAWINGS AND SUBMITTALS IS TO DEMONSTRATE THAT CONTRACTOR UNDERSTANDS DESIGN CONCEPT. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWINGS AND SUBMITTALS AND CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SUBMITTALS ARE PROCESSED, DESIGN DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE. ARCHITECT / ENGINEER REVIEW: ARCHITECT / ENGINEER REVIEW OF SHOP DRAWINGS AND SUBMITTALS AND ACTION INDICATED AS RESULT OF THIS REVIEW IS COURTESY EXTENDED TO CONTRACTOR BY REPRESENTATIVE OF OWNER. THIS SERVICE IS INTENDED TO MINIMIZE DELIVERY TO JOB SITE AND INSTALLATION OF MATERIALS THAT DO NOT MEET OWNER'S REQUIREMENTS FOR BUILDING. SUBMISSION OF MATERIAL FOR THIS ACTION DOES NOT ALTER BASIC INTENT OF SPECIFICATIONS AND CONTRACTOR'S RESPONSIBILITY TO COMPLY THEREWITH. 22. PROVIDE FOR AIR SIDE TEST AND BALANCE AT COMPLETION OF PROJECT. TEST AND BALANCE REPORT SHALL BE PROVIDED BY TABB OR NEBB CERTIFIED COMPANY OR OTHER SUB -CONTRACTOR AS APPROVED BY THE ENGINEER OF RECORD. TEST AND BALANCE REPORT SHALL BE SUBMITTED TO THE GENERAL CONTRACTOR AND ENGINEER PRIOR TO FINAL APPLICATION FOR PAYMENT. w F_ Z Q p rod V U 04 r �� V Z w�� Q J = _ O Q O co bow Z Z J a a cr cr �w^^ V, REVISION NO. DATE PERMIT 04/01/25 BCKGND REV 05/02/25 REV #2 10/22/25 REV #3 11/05/25 REV #4 02/02/26 'DRAWING TITLE: MAN LEVEL HVAC PLAN DATE: 03/14125 PROD. NO. 25-005 DRAWN 13Y:13A1 GHK'D 13Y: MAC DRAWING NO. M-1 PLUMBING FIXTURE ROUGH -IN SCHEDULE SYMBOL FIXTURE CONNECTIONS REMARKS CW HW WASTE VENT WC-1 WATER CLOSET (FLUSH TANK) 1/2 — 3 2 WC-2 WATER CLOSET (FLUSH TANK) - ACCESSIBLE 1/2 — 3 2 LV-1 LAVATORY 1/2 1/2 1-1/2 1-1/2 LV-2 ACCESSIBLE 1/2 1/2 1-1/2 1-1/2 SK-1 SINK 1/2 1/2 1-1/2 1-1/2 SH-1 SHOWER 1/2 1/2 1-1/2 1-1/2 FD/FS FLOOR DRAIN OR FLOOR SINK — — 3" 2" WB-1 ICE MAKER WALL BOX 1/2" HB-1 HOSE BIBB 3/4" NOTES: DIELECTRIC UNION (TYP)--� HW OUTLET CW INLE EXPANSION TANK SPECIFIED WITH WATER HEATER PROVIDE FULL-SIZE 4" DEEP SHEET METAL DRAIN PAN. - ASME PRESSURE RELIEF VALVE. WH PIPE TO FLOOR DRAIN. INSTALL WATER HEATER IN MEZZANINE 3/4" DRAIN LINE TO FLOOR DRAIN OR MOP SINK BASIN BELOW HOT WATER HEATER PIPING SCHEMATIC i - RESTROOM - LV-1 3/411 - EMPLOYEE KITCHEN - SK-1 1/2" -- - LOCKER ROOM - LV-1 ------ -1 � - SHOW ROOM - SK-1 - RESTROOM - LV-1 __q - RESTROOM - WC-2 - EMPLOYEE KITCHEN - SK-1 -� - EMPLOYEE KITCHEN - ICEMAKER BOX - LOCKER ROOM - LV-1 - - -� - LOCKER ROOM - WC-1 - - - - - SOUTH EXTERIOR - HB-2 - SHOW ROOM - SK-1 HW / CW DOMESTIC WATER MANIFOLD NOT TO SCALE NOTE: EXTEND 1/2" AQUA-PEX FROM EACH MANIFOLD TAP TO ASSOCIATED FIXTURE. GENERAL NOTES 1. ALL WORK SHALL COMPLY WITH AND BE COORDINATED WITH REQUIREMENTS OF ARCHITECTURAL PLANS AND EXISTING CONSTRUCTION AT THE TIME OF INSTALLATION 2. INSTALL NEW EQUIPMENT AND FIXTURES TO BE READILY ACCESSIBLE FOR SERVICE AND MAINTENANCE. REVIEW PROPOSED INSTALLATION WITH OWNER AND ARCHITECT PRIOR TO STARTING WORK. 3. ALL WORK SHALL CONFORM TO REQUIREMENTS OF THE BELOW REFERENCED CODES AS ADOPTED BY THE CITY OF CENTER. - 2021 INTERNATIONAL MECHANICAL CODE (IMC) - 2021 INTERNATIONAL PLUMBING CODE IPC) - 2021 INTERNATIONAL FUEL GAS CODE �IFGC) - 2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 4. ALL DOMESTIC WATER, WASTE, VENT AND GAS PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE IPC AND IFGC. 5. ALL PIPING INSTALLED THROUGH RATED WALL ASSEMBLIES SHALL BE PROTECTED IN ACCORDANCE WITH APPLICABLE THROUGH PENETRATION DETAILS AS SHOWN ON ARCHITECTURAL PLANS. WHERE PENETRATION DETAILS ARE NOT SPECIFICALLY PROVIDED, REFER PENETRATION TO ARCHITECT AND / OR ENGINEER FOR DETERMINATION OF PENETRATION PROTECTION REQUIREMENTS. 6. UNLESS OTHERWISE NOTED, ALL DOMESTIC HW / CW PIPING SERVING TWO OR MORE FIXTURES SHALL BE MINIMUM 3/4" COPPER, SEE PLANS FOR SIZING 3/4" AND UP. 7. INSULATE DOMESTIC HOT WATER PIPING LESS THAN 1-1/4" WITH 1" THICK PIPE INSULATION WITH CONDUCTIVITY OF 0.21-0.28 (R-3.6 TO R-4.8). INSULATION SHALL BE ONE PIECE FIBERGLASS WITH FACTORY APPLIED VAPOR BARRIER JACKET AND SELF SEALING LAP OR CLOSED CELL ELASTOMERIC WITH SELF SEALING LONGITUDINAL SEAM. 8. INSULATE DOMESTIC HOT WATER PIPING 1-1/2" AND LARGER WITH 1-1/2" THICK PIPE INSULATION WITH CONDUCTIVITY OF 0.21-0.28 (R-3.6 TO R-4.8). INSULATION SHALL BE ONE PIECE FIBERGLASS WITH FACTORY APPLIED VAPOR BARRIER JACKET AND SELF SEALING LAP OR CLOSED CELL ELASTOMERIC WITH SELF SEALING LONGITUDINAL SEAM. 9. NOT ALL PIPING OFFSETS AND TRANSITIONS REQUIRED TO INSTALL THE WORK IN THE AVAILABLE SPACE ARE SHOWN ON THIS DRAWING. FIELD MEASURE FOR EXACT REQUIREMENTS AND INSTALL ACCORDINGLY. 10. UNLESS OTHERWISE NOTED, DOMESTIC WATER PIPING SHALL BE TYPE L COPPER OR AQUA-PEX 11. UNLESS OTHERWISE NOTED, SANITARY WASTE PIPING SHALL BE SCHEDULE 40 PVC-DWV WITH SOLVENT FUSED JOINTS. 12. ALL PLUMBING VENT PIPING SHALL BE SCHEDULE 40 PVC DWV WITH SOLVENT FUSED FITTINGS. VENT PIPING INSTALLATION SHALL BE INSTALLED AS REQUIRED TO MEET THE 2021 INTERNATIONAL PLUMBING CODE. FIELD VERIFY ALL TERMINATIONS WITH ARCHITECT PRIOR TO ROUGH -IN. 13. ALL VENT TERMINATIONS SHALL BE MINIMUM 3" DIAMETER WITH ANY INCREASE IN VENT SIZE TO 3" BEING MADE NOT LESS THAN 1 FOOT INSIDE THE BUILDING THERMAL ENVELOPE. 14. PROVIDE CLEANOUTS WITH ACCESS AS REQUIRED PER CODE IN SANITARY DRAIN PIPING. 15. ALL FIXTURE BRANCH WASTE PIPING SHALL BE MIN 1-1/2" DIA. 16. UNLESS OTHERWISE NOTED OR PRE -APPROVED BY THE ENGINEER, ALL GAS PIPING SHALL BE SCHEDULE 40 STEEL WITH SCREWED FITTINGS. 17. ALL GAS PIPING INSTALLATIONS INCLUDING, BUT NOT LIMITED TO SHUT -OFFS, DRIP LEGS, AND FIREPLACE INSTALLATIONS SHALL BE INSTALLED PER MANUFACTURER SPECIFICATIONS, APPROVED LISTINGS, AND APPLICABLE PORTIONS OF THE 2018 IFGC. 18. NOTIFY GENERAL CONTRACTOR OF ANY STRUCTURAL OPENINGS REQUIRED TO COMPLETE PLUMBING INSTALLATION. ALL OPENINGS SHALL BE CUT UNDER G.C. SUPERVISION WITH STRUCTURAL ENGINEER APPROVAL. 19. PEX AND PVC PIPING 2" AND SMALLER SHALL BE SUPPORTED ON 5' CENTERS OR ALTERNATIVELY SUPPORTED ON 10' CENTERS AND PROVIDED WITH A MIDWAY PIPE GUIDE IN ACCORDANCE WITH THE REQUIREMENTS OF IPC 2021, TABLE 308.5, FOOTNOTE B. PLUMBING FIXTURE LIST AND EQUIPMENT SCHEDULE CP-1 DOMESTIC HOT WATER CIRCULATING PUMP GRUNDFOS MODEL UP 15-29 SUC / TLC 1 GPM, 9 FT. HD. 87 WATTS, 120 VOLTS PROVIDE COMPLETE WITH INTEGRAL TIMER INSTALL WITH CALEFFI MODEL 132432A BALANCE VALVE - SET FOR 0.5 GPM WH-1 ELECTRIC WATER HEATER STATE INDUSTRIES MODEL PCE-30-20RT 40 GALLON CAPACITY 4500 WATTS, 208 VOLT, 1 PHASE - 20.5 GPH RECOVERY AT 90F RISE - PROVIDE COMPLETE WITH AMTROL ST-5 THERMAL EXPANSION TANK WH-2 POINT OF USE ELECTRIC WATER HEATER STATE MODEL ES6-2-SMT 2.5 GALLON CAPACITY 1440 WATTS, 120 VOLT, 1 PHASE - 6.8 GPH RECOVERY AT 90F RISE 111a IItell] Its 11: 2112 ZURN MODEL 415B CAST IRON BODY WITH 2" BOTTOM OUTLET, MEMBRANE CLAMP, AND ADJUSTABLE COLLAR WITH SEEPAGE SLOTS AND TYPE "B" NICKEL BRONZE STRAINER. PROVIDE COMPLETE WITH ZURN Z1072 TRAP SEAL. HB-1 WALL FAUCET WOODFORD MODEL V26 TOP MOUNT INLET W/ POLYCARBONATE HANDLE AND VACUUM BREAKER HB-2 FROSTPROOF WALL FAUCET WOODFORD MODEL 17 TOP MOUNT INLET W/ POLYCARBONATE HANDLE AND VACUUM BREAKER LV-1 LAVATORY - WALL MOUNT PRO-FLO MODEL PF5514WH 20" X 18" - 3 HOLE / 4" CENTERSET PROVIDE COMPLETE WITH - ZURN Z1224 LAVATORY SUPPORT - PFWSC3007CP SINGLE HANDLE LAVATORY FAUCET LESS POP-UP DRAIN - GRID DRAIN - TAIL PIECE / P-TRAP - ANGLE SUPPLIES AND STOPS - FLEXIBLE WATER CONNECTIONS LV-2 LAVATORY - DROP -IN / ACCESSIBLE PRO-FLO MODEL PF21184WH 21" X 18" - RECTANGULAR - 4" CENTER SET PROVIDE COMPLETE WITH - PFWSC3007CP SINGLE HANDLE LAVATORY FAUCET LESS POP-UP DRAIN - GRID DRAIN - TAIL PIECE / P-TRAP - ANGLE SUPPLIES AND STOPS - FLEXIBLE WATER CONNECTIONS KS-1 KITCHEN SINK ELKAY MODEL GECR3321 DOUBLE BOWL / TOP MOUNT - 33" x 21-1/4" x 5-3/8" DEEP PROVIDE COMPLETE WITH: - DELTA FAUCET MODEL 100DST - SINK BASKET STRAINER - TAIL PIECE / P-TRAP - ANGLE SUPPLIES AND STOPS - FLEXIBLE WATER CONNECTIONS SH-1 SHOWER STERLING "TRAVERSE" - 72520100 48" x 34" - CENTER DRAIN PROVIDE COMPLETE WITH: PRO-FLO PF4001 PRESSURE BALANCED SHOWER VALVE PRO-FLO PF7611GLF SERIES TRIM KIT - LESS TUB SPOUT PRO-FLO 2" NO -CAULK SHOWER DRAIN SHOWER CURTAIN / DOORS TO BE PROVIDED BY OWNER 1111 l l i�►[y:mc;".1 ► 7-1/2" WIDE x MINIMUM 4" DEEP INSTALL 9" WIDE X 1.25" TALL x 36" LONG GALVANIZED STEEL TRENCH GRATE (FURNISHED BY OWNER, INSTALLED BY G.C.). TRENCH SHALL BE FIELD FORMED WITH SMOOTH CONCRETE BOTTOM, 1/8' PER FOOT SLOPE AND 1-1/4" DEEP X MINIMUM 3/4" WIDE RECESS BELOW FINISHED FLOOR FOR GRATE MOUNTING. WC-1 WATER CLOSET - ACCESSIBLE TANK TYPE / 1.0 GPF PRESSURE ASSIST ELONGATED BOWL RIGHT HAND TRIP LEVER PROVIDE COMPLETE WITH: - OPEN FRONT PLASTIC SEAT - ANGLE SUPPLY AND STOP - FLEXIBLE WATER CONNECTION 13A, _0 v, W ~ w �w Uz O J z o8E Q �w co Q Z 8 rVR � V W z a 0 rod V V o V �co �Z Q W J = Cn Q=O 0 3: 0 w Z J Q �W V, REVISION NO. DATE PERMIT 04/01/25 PRMT REV 05/02/25 REV #1 09/24/25 REV #4 02/02/26 'DRAWING TITLE: C1B411ffIAL NOTES, FDCrLFA-= LOT AND EOUF%13U 80HEDULE, AND DETAILS DATE: 04/0I/25 SCALE: N.r s. PROD. NO. 2.5-0& DRAWN 15Y: PAI 641K'D f3Y: MAP DRAWING NO. 7 P-0.1 UH 1 13 HB </* % 1 O `N' 1 EXISTING GAS METER - FIELD VERIFY 2# GAS SERVICE (REQUEST SERVICE UPGRADE IF NOT) NEW GAS SERVICE - 1600 MBH 1 O 6 EXTEND 1" RECYCLE WATER SERVICE TO HOSEBIBBS - PLAN NOTE 13. RE: DWG P-2 FOR DISTRIBUTION PIPING VALVE AND CAP 1" RECYCLE WATER LINE FOR FUTURE USE EXTEND 1" RECYLE WATER TO CUTTING MACHINES (3X) EXTEND 2" RECYCLE WATER FROM HYDROCLEAR UNIT EMPLOYEE AREA LV SHOWROOM / SALES WC 2 S K = ---- ------ - RESTRM INSTALL WH-1 WH 1 ON ROOF OF 1 EMPLOYEE RESTROOM K TCHEN 0 LOCKER ROOM L 1 �'- `3„ W I �� TEMPLOYEE 1 I RESTRM ______________________________________ -------------- P--- ---- ELEC CLOSET 2 � I w z � I i 00 I I 0 i J w i L` a I 0 J � i I I I i w � I z I 3 4" i r.lw._._._._............... 13 HB / / / lop T T T T T DOUBLE CHECK VALVE ASSEMBLY WATTS 007 OR APPROVED EQUAL T T T T T T 1_�_ _�_�_ _�_�_ l _ _� U �_ _ 1" CW MAKE-UP TO WATER RE-CLAIM SYSTEM RECLAIM WATER DISTRIBUTION PIPING SCHEMATIC NOT TO SCALE NOTES: 1. DISTRIBUTION PIIPNG ASSEMBLY SHALL BE INSTALLED ON WALL BEHIND HYDROCLEAR RECYCLING ASSEMBLY AT APPROXIMATELY 48" A.F.F. PIPING SHALL BE ROUTED OVERHEAD FROM MANIFOLD. 2. PIPING MANIFOLD AND INLET / OUTLET CONNECTIONS TO OVERHEAD DISTRIBUTION SHALL BE TYPE L COPPER. AQUA-PEX MAY BE USED FOR OVERHEAD DISTRIBUTION INSTALLATION - SUBJECT TO OWNER APPROVAL. 13 HB 1-1-------- �!77777 CIE HB 2 -- --- _ ----- - b �vi t 0 1 12 HV HYLROCLEAR V SH RECYCLING S` I FLOW LINE SLOPE 1/8" / FT FABRICATION SHOP / STORAGE 7'7= r_=III®III= FLOW LINE SLOPE 1/8" / FT I 13 H ]Q� I=III 77777 77777 I FLOW LINE i SLOPE 1/8" / FT 7= 7=17Z=11177777117= 7=1 =17777711 ® I HB 13 MAIN LEVEL PLUMBING FLOOR PLAN SCALE: 1/8" = 1'-0" NOTE: - TOTAL TRENCH DRAIN LENGTH IS ESTIMATED AT 226 L.F. AT 1/8" / FOOT FALL, TOTAL MINIMUM FALL IS 28.5". PLAN NOTES O1 EXTEND 3" WASTE DOWN NEXT TO EXTERIOR WALL TO APPROXIMATELY 24" ABOVE MAIN SLAB LEVEL. TURN HORIZONTAL AS REQUIRED AND EXTEND THROUGH WALL AND THEN DOWN AS REQUIRED TO ROUTE BELOW THE MAIN LEVEL SLAB. O2 EXTEND 3" WASTE HORIZONTALLY BELOW MAIN LEVEL SLAB TO CONNECTION WITH EXISTING SANITARY WASTE. O3 FIELD VERIFY LOCATION OF BUILDING DOMESTIC WATER SERVICE AND MAKE 1" NEW VALVED CONNECTION AS REQUIRED. O4 INSTALL WH-1 BELOW LV-1. MAKE 1/2" CW CONNECTION AND EXTEND 1/2" HW FROM WH-1 UP TO SERVE LV-1. O EXTEND 1/2" CW DN IN WALL. MAKE 1/2" TAP TO LV-1 FAUCET AND EXTEND 1/2" CW SERVICE TO WH-1. O EXTEND 1-1/4" GAS INTO WEST BAY AND CAP FOR FUTURE USE. O EXTEND 1-1/4" CW SERVICE UP NEXT TO INTERIOR WALL. ROUTE HORIZONTALLY APPROXIMATELY 12" BELOW FINISHED CEILING LEVEL. O INSTALL DOMESTIC HOT AND COLD WATER AQUA-PEX MANIFOLDS IN CEILING SPACE. RE: PIPING SCHEMATIC THIS SHEET FOR MANIFOLD REQUIREMENTS. HB 13 1 T-------------- '12 -- /LN 5 21 /4" W( O9 FURNISH AND INSTALL MANUAL SHUT-OFF VALVE AND GAS PRESSURE REGULATOR RATED FOR 100 MBH / 2# TO 14" 10 NOT USED. 11 NOT USED 12 EXTEND 1" DOMESTIC WATER MAKE-UP TO RECLAIM SYSTEM. RE: PIPING SCHEMATIC THIS SHEET. 13 SURFACE MOUNT RECLAIM WATER HOSE-BIBB HB-1 AT 48" A.F.F. FIELD COORDINATE FINAL LOCATIONS WITH OWNER'S REPRESENTATIVE. 14 RECLAIM WATER COLLECTION PIT. RE: STRUCTURAL PLAN FOR DETAILS. 15 EXTEND 3/4" GAS SERVICE TO APPLIANCE (GAS FIREPLACE). MAKE FINAL CONNECTION (INCLUDING LOCAL SHUT-OFF) PER MFR RECOMMENDATIONS. i 2-� w F_ Z Q 0 rod V U 04 0� co > Z w�0. Q J = cf) _ O Q 0 ♦^ V, 0 W Z W Z J a C5 or or w REVISION NO. DATE PERMIT 04/01/25 PRMT REV 05/02/25 REV #1 09/24/25 REV #4 02/02/26 DRAWING TITLE: MAIN LEVEL PLUMBING PLAN /DATE: 03/14/2-5 SCALE: 1/r = I'-e PROD. NO. 25-005 DRAWN 13Y:13A1 6 K'D 13Y- MA 5 J DRAWING NO. 7 P-1 EXISTING ELECTRICAL SERVICE ENTRY / MAIN DISTRIBUTION RE: EXISTING AND NEW ONE -LINE DIAGRAMS - DWG E-0.1 UPPER LEVEL ELEC RM LTG PLAN SCALE: 1/8" = 1'-0" PLAN NOTES O EXTEND BB-1 POWER SERVICE FROM CONTACTOR - RE: PLAN NOTE 2. 20 INSTALL 4-POLE SINGLE PHASE CONTACTOR IN STORAGE CLOSET AND EXTEND POWER CONDUCTORS AS REQUIRED TO BB-1 BASEBOARDS. CONTACTOR SHALL BE CONTROLLED BY OUTSIDE AIR TEMPERATURE (START BB-1 ON OUTSIDE AIR TEMERATURE DROPPING BELOW 30F) - CONTACT CLOSURE TEMPERATURE CONTROL SHALL BE ADJUSTABLE. 30 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER PROVIDED CNC MILL. POWER INSTALLATION SHALL CONFORM TO MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAM SHALL BE ON -SITE AND AVAILABLE FOR REVIEW BY ENGINEER DURING INSTALLATION. 40 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER PROVIDED BRIDGE SAW. POWER INSTALLATION SHALL CONFORM TO MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAM SHALL BE ON -SITE AND AVAILABLE FOR REVIEW BY ENGINEER DURING INSTALLATION. 50 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER PROVIDED HYDROCLEAR WATER RECYCLING SYSTEM. POWER INSTALLATION SHALL CONFORM TO MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAM SHALL BE ON -SITE AND AVAILABLE FOR REVIEW BY ENGINEER DURING INSTALLATION. PANEL SCHEDULE - LP1 OFFICE POWER AND LIGHTING PANEL PANEL TYPE: LOAD CENTER MAIN BREAKER: 200 A BUS SIZE: 225 A PHASES: 3 WIRES: 4 MOUNTING: FLUSH VOLTAGE: 120 208 V CONNECTED: XXX W DEMAND: XXX W PHASE A CONNECTED: XXX W PHASE B CONNECTED: XXX W PHASE C CONNECTED: XXX W LOAD TYPE AND DESCRIPTION A M P S P 0 L E S C K T # P H A S E C K T # P 0 L E S A M P S LOAD TYPE AND DESCRIPTION LIGHTING: SHOWROOM SALES 20A 1P 1 1 1A 2 12P 170A MECH- H&C: FC-1 LIGHTING: EMPLOYEE AREA LOCKER RM KITCH 20A 1P 3 B 4 -- --- MECH- H&C: --- LIGHTING: 24 7 SECURITY 15A 1P 5 C 6 2P 50A MECH- H&C: HP-1 RECEPTACLE: ADMIN DESK 20A 1P 7 A 8 -- --- MECH- H&C: --- RECEPTACLE: ADMIN DESK 20A 1P 9 B 10 1P 15A MECH- HEAT: BB-1 RECEPTACLE: SHOWROOM SALES 20A 1P 11 C 12 1P 15A MECH- HEAT: BB-1 RECEPTACLE: RESTROOM 20A 1P 13 A 14 1P 15A MECH- HEAT: BB-1 RECEPTACLE: KITCHEN - COUNTER 20A 1P 15.13 16 1P 15A MECH- HEAT: BB-1 RECEPTACLE: KITCHEN - COUNTER 20A 1P 17 C 18 1P 20A MECH- H&V: BB-2 RECEPTACLE: KITCHEN - MICROWAVE 20A 1P 19 A 20 1P 20A MECH- VENT: EF-1 RECEPTACLE: KITCHEN - REFRIGERATOR 20A 2P 21 B 22 2P 30A MISC: WH-1 MISC: KITCHEN - RANGE 40A -- 23 C 1 24 -- --- MISC: --- MISC: --- --- 1P 25 A 26 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: SHOWER ROOM 20A 1P 27 B 28 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: EMPLOYEE AREA LOCKER ROOM 20A 1P 29 C 30 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: EXTERIOR - NORTH 20A 1P 31 A 32 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: EXTERIOR - SOUTH 20A 1P 33 B 1 34 1P 20A SPARE: UNALLOCATED FUTURE SPARE: UNALLOCATED FUTURE 20A 1P 35 C 36 11P 20A SPARE: UNALLOCATED FUTURE SPARE: UNALLOCATED FUTURE 20A -- 37 A 38 -- --- SPACE: --- SPACE: --- --- -- 39 B 40 -- --- SPACE: --- SPACE: --- 41 C 42 ISPACE. --- O FIELD VERIFY EXISTING WATER SERVICE POWER REQUIREMENTS AND RE - POWER AS REQUIRED. 70 EXTEND 1/2" EMT DOWN EXISTING COLUMN AND MOUNT RECEPTACLE AT 48" A.F.F. OEXTEND 1/2" EMT DOWN FROM CEILING SPACE EXPOSED ON INTERIOR WALL. MOUNT RECEPTACLE AT 48" A.F.F. O EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER PROVIDED HONER AND POLISHER MACHINES. POWER INSTALLATIONS SHALL CONFORM TO MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAMS SHALL BE ON -SITE AND AVAILABLE FOR REVIEW BY ENGINEER DURING INSTALLATION. PANEL SCHEDULE - LP2 FABRICATION SHOP / STORAGE / OFFICE PANEL TYPE: LOAD CENTER MAIN BREAKER: 200 A BUS SIZE: 225 A PHASES: 3 WIRES: 4 MOUNTING: FLUSH VOLTAGE: 120 208 V CONNECTED: XXX W DEMAND: XXX W PHASE A CONNECTED: XXX W PHASE B CONNECTED: XXX W PHASE C CONNECTED: XXX W LOAD TYPE AND DESCRIPTION A M P S P 0 L E S C K T # P H A S E C K T # P 0 L E A M P S LOAD TYPE AND DESCRIPTION LIGHTING: EAST FAB STORAGE 20A 1P I 1 A 2 -- 20A SPARE: UNALLOCATED FUTURE LIGHTING: WEST FAB STORAGE 20A 1P 3 B 4 -- 20A SPARE: UNALLOCATED FUTURE LIGHTING: 24 7 SECURITY EXTERIOR 20A 1P 5 C 6 - - RECEPTACLE: EAST FAB STORAGE 20A 1P 7 A 8 1P 20A MECH- HEAT: UH-1 RECEPTACLE: WEST FAB STORAGE 20A 1P 9 B 10 -- --- MECH- VENT: - 20A 1P 11 C 12 3P 30A MECH- VENT: EF-1 SPARE: UNALLOCATED FUTURE 20A 1P 13 A 14 - 20A 1P 15113 2P 30A SPARE: UNALLOCATED FUTURE MISC: NORTH OVERHEAD DOOR 20A 1P 17 C-- --- PAR : --- RECEPTACLE: EAST RESTROOM 20A 1P 19 A R22 P - RECEPTACLE: WEST RESTROOM 20A 1P 21 B 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: EAST FAB STORAGE - SOUTH 20A 1P 23 C 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: EAST FAB STORAGE - NORTH 20A 1P 25 A 26 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: WEST FAB STORAGE - SOUTH 20A 1P 27 B 28 1P 20A SPARE: UNALLOCATED FUTURE RECEPTACLE: WEST FAB STORAGE - NORTH 20A 1P 29 C 30 1P 20A SPARE: UNALLOCATED FUTURE SPARE: UNALLOCATED FUTURE 20A 1P 31 A 32 1P 20A SPARE: UNALLOCATED FUTURE SPARE: UNALLOCATED FUTURE 20A 1P 1 33 B 1 34 1P 20A SPARE: UNALLOCATED FUTURE SPARE: UNALLOCATED FUTURE 20A 1P 35 CW42-- 20A SPARE: UNALLOCATED FUTURE SPACE: --- --- -- 37 A--- SPACE: --- SPACE: --- --- -- 39 B--- SPACE: --- SPACE: --- --- -- 41 CSPACE: --- ,!q' LICC ��O�a�'P�y c-' 0 U Z W ~ w Q W 3 . Uz O� o� W mo Q Z 0 J N co Q cy Q Z 09 oc 8 O O W F_ Z Q 0 � U C� N (n c�0 cd>- Z Q � a:W � J = (1) cr 0 C) Q=0 mco0 c 3:: 0 w z Z W Q J cr 0 cr w INN/ REVISION NO. DATE PERMIT 04/01/25 BCKGND REV 05/02/25 REV #3 12/01/25 REV #4 02/02/26 PRAWINO TITLE: MAIN LEVEL POWER PLAN AND PANEL SCHEDULES PATE: 03/31/2-5 PROD. NO. ZFrppS PRAWN f5Y: PAI GHK'P f5Y: MAC PRAWIN6 NO. E-1 J UPPER LEVEL ELEC RM LTG PLAN D MANUFACTURER VOLTAGE BALLAST TYPE DESCRIPTION E CATALOG NUMBER MOUNTING LAMP TYPE S # OF LAMPS WATTS COLUMBIA LIGHTING 120 ELECTRONIC CENTER LENS TROFFER - 23.88" x 47.88" x 4" DEEP, A CCL24-LSCS CEILING LED FROSTED ACRYLIC LENS, 80+CRI, 4000K (SWITCHABLE) - 32 SWITCHABLE LUMEN 4200 - 6000), 0-10 VOLT DIMMING COLUMBIA LIGHTING 120 ELECTRONIC CENTER LENS TROFFER - 23.88" x 23.88" x 4" DEEP, Al CCL22-LSCS CEILING LED FROSTED ACRYLIC LENS, 80+CRI, 4000K (SWITCHABLE) - - 25 SWITCHABLE LUMEN 2900 - 4400), 0-10 VOLT DIMMING COLUMBIA LIGHTING 120 ELECTRONIC RECESSED LINEAR, 47.75" x 4.72" x 3.82" DEEP, B NRL4-LSCS CEILING RECESSED LED FROSTED POLYCARBONATE LENS, 80+CRI, 4000K, SWITCHABLE - 21 LUMEN 2500 - 4500), 0-10 VOLT DIMMING, 5-WIRE FLEX COLUMBIA LIGHTING 120 ELECTRONIC LINEAR WALL BRACKET, 4.8" x 36" x 3.9" TALL, SQUARE C W36 4 _ _ 35 XW SFZ ED U WALL MOUNT LED FROSTED ACRYLIC LENS, 3500 K, 2700 LUMEN, 0-10 VOLT - - 21 DIMMING. COLUMBIA LIGHTING 120 ELECTRONIC SUSPENDED HIGH -BAY, 22.7" x 10" x 2.3" DEEP, D CLB2 40 LX W EDU CEILING SUSPENDED LED 10,000 LUMEN, WIDE DIST., 0-10 V DIMMING, LHVQM5 - 75.9 60" ADJUSTABLE CABLE MTG., BEACON 120 ELECTRONIC AREA LIGHT - CAST ALUM, 8" x 12-1/4" x 5-1/4" TALL, E RWL1 48L-35 4K8 2 120 DBT WALL SURFACE LED 4500 LUMEN, 4000K, DARK BRONZE TEXTURED, BUTTON PC - 36.9 PHOTOCELL. INSTALL AT 18-0" A.F.F. BEACON 120 ELECTRONIC AREA LIGHT - CAST ALUM, 8" x 12-1/4" x 5-1/4" TALL, E RWL1 48L-35 4K8 2 120 DBT WALL SURFACE LED 4500 LUMEN, 4000K, DARK BRONZE TEXTURED, BUTTON T.B.D. 120 ELECTRONIC SUSPENDED ARCHITECTURAL LINEAR LUMINAR - SLOPED CLG F CEILING SUSPENDED LED 4000 K, 3,000 LUMEN (+/-), DIMMABLE - 42 COLUMBIA LIGHTING 120 ELECTRONIC FLAT PANEL - 11.9" X 47.8" X 2" DEEP, ALUMINUM LENS G CBT 14 A LSCS EDD CEILING SURFACE LED FRAME, 4000 K (SWITCHABLE), 3,000 - 4760 LUMEN, - - 39 DIMMABLE Sl LCS 2 40 ML E U CSHC CEILING SUSPENDED LED FIXED OUTPUT, 4000K T.B.D. 120 ELECTRONIC SINGLE CIRCUIT TRACK LIGHT, 4'-0" LONG, 3 HEADS, T TRACK LIGHT CEILING SURFACE LED 4000K, DIMMABLE T.B.D. 120 ELECTRONIC 2-CIRCUIT TRACK LIGHT, 6'-0" LONG, 6 HEADS, 4000K, T1 TRACK LIGHT CEILING SURFACE LED DIMMABLE X CCRHOSQ WALL MOUNT LED RED LETTERS, INSTALL AT 8'-6' A.F.F. - 3.9 COMPASS LIGHTING 120 ELECTRONIC EXTERIOR EGRESS - 9.1" x 6.3" x 2.5" DEEP, 4000K, X1 CUSO 4DBH ND WALL MOUNT LED PHOTO -SENSOR, HEATER, DARK BRONZE, INSTALL AT 9'-0" - - 3.9 ABOVE GRADE MAIN LEVEL ELECTRICAL LIGHTING PLAN SCALE: 1/8" = l'-0" LIGHTING CONTROL NOTES 1024/7 SECURITY - ALWAYS ON. CIRCUIT DIRECT FROM PANEL. >MANUAL DIMMING SWITCH. <�>`OCCUPANCY SWITCH - OFF AFTER 30 MINUTES (ADJUSTABLE). >OCCUPANCY SWITCH - CEILING SENSOR, OFF AFTER 30 MINUTES (ADJUSTABLE). >MANUAL ON - OFF AFTER 60 MINUTES (ADJUSTABLE). UPPER LEVEL STAIR LIGHTING PLAN BAt, U Z W ~ a w Q 01 W 30- . Uz O� o� 0- W mo Q Z 0 J N co Q a) Q QZ 09 v ml O O m w F_ z Q 0 � U C� N (n c�O cd>_Z w�� Q� J = � 0 C) T 0 �(00 0 w z Z w Q J or 0 cr w INN/ REVISION NO. DATE PERMIT 04/01/25 PRMT REV 05/02/25 REV #3 12/01/25 REV #4 02/02/26 DRAWING TITLE: MAN LEVEL L.K11- rM PLAN DATE: 03/31/2-5 SGAL : I/r PROD. NO. 2.5-00 DRAWN 15Y: PAI GHK'D f3Y: MAC DRAWING NO. 7 E-2