HomeMy WebLinkAboutStamped Plans 02.02.26 rev4PLAN NOTES
O1 TERMINATE EF-2 EXHAUST DUCT WITH PAINTABLE WALL CAP.
l 2 RE: ELECTRICAL POWER PLANS FOR BB-1 / BB-2 CONTROL REQUIREMENTS.
MAIN LEVEL MECHANICAL FLOOR PLAN
SCALE: 1/8" = 1'-0"
MECHANICAL EQUIPMENT LIST AIR DEVICES
BB-1 ELECTRIC BASEBOARD
RUNTAL MODEL E133-72-120D
879 WATTS, 3000 BTUH
120 VOLT
BB-2 ELECTRIC BASEBOARD
RUNTAL MMODEL EB-120-120D
1466 WATTS, 5000 BTUH
120 VOLT
EF-1 ADMINISTRATION EXHAUST FAN
COOK MODEL SQN-D 100SQN
700 CFM, 0.5" S.P.
1/3 HP, 120 VOLT
EF-2 RESTROOM EXHAUST FAN
PANASONIC MODEL FV 0511 VF1
80 CFM, 0.25 E.S.P.
Q d WATTC 190 \/Ol TC
EF-3 CRAWLSPACE VENTILATION FAN
FANTECH MODEL FG 8
300 CFM, 0.25" S.P.
1.2 AMPS, 120 VOLTS
PROVIDE COMPLETE WITH SOLID STATE SPEED CONTROLLER
RATED FOR 5.0 AMPS AND LINE VOLTAGE HUMIDISTAT (START
ON HUMIDITY RISE). HUMIDISTAT SHALL BE INSTALLED
WITH -IN 3' OF CENTER OF NORTHEAST CRAWLSPACE WALL.
limmyp1ri►[ewile1r1e
VENTILATION FAN HAS BEEN SELECTED BASED ON 2 ACH
VENTILATION RATE OVER 1500 S.F. AREA x 5' MAX.
HEIGHT.
FC-1 FAN COIL UNIT - SERVICE TO ADMINISTRATION
ARMSTRONG MODEL 77 AH 2 A E 60 P X-71
1700 CFM, 700 CFM 0/A, 0.5" S.P.
36.2 MBH SENS. CLG, 42.6 MBH TOTAL CLG
49.0 MBH HEATING (HEAT PUMP)
12.5 KW ELECTRIC HEAT (AUXILIARY)
1 HP BLOWER MOTOR
66 MCA, 70 MFS
208 VOLT, 1 PHASE - SINGLE POINT CONNECTION
PROVIDE COMPLETE WITH 2" MERV 13 PLEATED MEDIA FILTER
FC-2 NOT USED
HP-1 HEAT PUMP - ASSOCIATED WITH FC-1
ARMSTRONG MODEL 4 SHP 17 LE 1 60 P - 51 A
NOMINAL 5-TON HEATING / COOLING CAPACITY
26.5 FLA, 32.5 MCA, 50 MCA
208 VOLT, 1 PHASE
PROVIDE COMPLETE WITH 1-1/8" x 3/8" REFRIGERANT LINE SET
171��►Ce>tt1L���7
RT-1 EXISTING ELECTRIC / GAS ROOFTOP HVAC UNIT
TRANE MODEL YCD 360 B E P 2
30 TON COOLING - NOMINAL CAPACITY
600,000 BTUH HEATING, 355,200 BTUH OUTPUT, 6,500 FT. ELEV.
12,000 CFM NOMINAL S/A, BALANCE TO 4100 CFM MINIMUM O/A
150.4 FLA, 185 MCA, 225 MOP
208 VOLT, 3 PHASE
SEE RE -COMMISSIONING REQUIREMENTS - DRAWING M-2 - FOR START-UP /
COMMISSIONING
UH-1 GAS FIRED UNIT HEATER
REZNOR MODEL UDAS 100
100 MBH INPUT, NATURAL GAS
64.1 MBH OUTPUT, 6,600 FT. ELEV.
3.9 AMPS, 120 VOLTS
TYPICAL OF TWO UNITS
LV-1 ADMINISTRATION OFFICE OUTSIDE AIR
RUSKIN ELF 375 DX
24" x 12" TALL
LV-2 ADMINISTRATION OFFICE EXHAUST
RUSKIN ELF 375 DX
24" x 12" TALL
SA-1 SUPPLY AIR REGISTER
KRUEGER MODEL 5880 - DOUBLE DEFLECTION
14" x 6" W/ HORIZONTAL FRONT BLADES
PROVIDE WITH OPPOSED BLADE BALANCING DAMPER
AND FRAME FOR GYPBOARD WALL MOUNTING
SA-2 IS SIMILAR EXCEPT PROVIDE FRAME FOR SHEET
METAL MOUNTING
SA-3 CEILING DIFFUSER
KRUEDGER 1400 SERIES
4-CONE WITH FRAME FOR GRID CEILING INSTALLATION
01141:00111 FA9W: _l04iA01[I :N:i1P►MilljM1lll819 1111•yp0
RA-1 RETURN AIR GRILLE
KRUEGER S580 - 35° BLADE DEFLECTION
30" x 12" TALL
PROVIDE WITH FRAME FOR GYPBOARD WALL MOUNTING
EA-1 EXHAAUST AIR GRILLE
KRUEGER S80P
10" x 10"
PROVIDE WITH FRAME FOR GYPBOARD CEILING MOUNTING
AND OPPOSED BLADE BALANCING DAMPER.
EA-2 EXHAUST AIR GRILLE
KRUEGER S580 - 35° BLADE DEFLECTION
18" x 10" TALL
PROVIDE WITH FRAME FOR GYPBOARD WALL MOUNTING
AND OPPOSED BLADE BALANCING DAMPER.
TCHES SHALL BE
E-1 .
S/A TRUNK DUCT.
ONNECTION TO SA-4.
AIIV, iil>ilCi1PI:aD11[It 8
RIFY MINIMUM
FIELD FABRICATE
% FREE AREA TO COVER
10 OODINATE WITH G.C. AS REQUI D TO PROVID 1" DOOR UNDE -CU .
11 SUPPLY AIR DUCT SHALL BE COVERED WITH A HORIZONTAL CHASE /
SOFFIT INSTALLED ON BACK WALL OF OFFICE AREA. FIELD COORDINATE
DUCTWORK INSTALLATION AS REQUIRED.
INSTALL EF-3 (CRAWLSPACE VENTILATION FAN) IN CRAWLSPACE. FIELD
COORDINATE FLOOR ACCESS PANEL WITH G.C.
13 EXTEND 8"0 E/A DUCT FROM EF-3 TO BUILDING EXTERIOR. FIELD
COORDINATE TERMINATION WITH G.C. AS REQUIRED TO INSTALL APPROX.
18" ABOVE FINISHED GRADE TO BOTTOM. TERMINATE WITH PAINTABLE
METAL WALL CAP.
14 INSTALL 8"0 PAINTABLE METAL WALL CAP WITH INSECT SCREEN MINIMUM
5'-0" FROM EF-3 TERMINATION AND MINIMUM 18" ABOVE FINISHED GRADE
FOR CRAWLSPACE MAKE-UP AIR. EXTEND DUCT DOWN INTO CRAWLSPACE AND
TERMINATE WITHIN 12" OF CRAWLSPACE FLOOR.
15 EXTEND EF-3 EXHAUST DUCT TO WITHIN 24" OF SOUTHEAST WALL OF CRAWL
SPACE.
GENERAL NOTES
1. PROVIDE LABOR AND MATERIALS REQUIRED FOR COMPLETE AND OPERATIONAL
MECHANICAL (HVAC) SYSTEMS.
2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE GOVERNING CODE
AUTHORITIES.
3. ALL WORK SHALL COMPLY WITH AND BE COORDINATED WITH REQUIREMENTS OF
ARCHITECTURAL PLANS AND EXISTING CONSTRUCTION AT THE TIME OF
INSTALLATION.
4. WHERE DESIGN INFORMATION IS IN -ADEQUATE OR INCOMPLETE WITH REGARD TO
PROJECT SCOPE OR CODE / ORDINANCE COMPLIANCE IN ORDER TO PROVIDE A
COMPLETE PROJECT BID OR PRICE, THE MECHANICAL AND / OR PLUMBING
SUB -CONTRACTORS) SHALL BRING SUCH TO THE ATTENTION OF THE ARCHITECT OR
ENGINEER PRIOR TO BIDDING OR PRICING THE PROJECT.
IMPLICIT IN SUBMISSION OF A BID OR PRICE TO DO THE WORK IS THE STATEMENT
THAT THE PROJECT SCOPE AS SHOWN ON THE PLANS WILL BE INSTALLED COMPLETE,
OPERATIONAL, AND IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS.
5. INSTALL EQUIPMENT TO BE READILY ACCESSIBLE FOR SERVICE AND MAINTENANCE.
REVIEW PROPOSED INSTALLATION WITH OWNER AND ARCHITECT PRIOR TO STARTING
WORK.
6. OBTAIN WRITTEN APPROVAL FROM THE ARCHITECT OR STRUCTURAL ENGINEER
BEFORE NOTCHING, CHIPPING, BURNING, DRILLING OR WELDING OF STRUCTURAL
MEMBERS.
7. MAKE ALL DUCT CONNECTIONS TO FAN COIL UNITS, MAKE-UP AIR UNIT, AND EXHAUST
FANS WITH FLEXIBLE CONNECTIONS.
8. COORDINATE FINAL CEILING GRILLE AND EXHAUST FAN LOCATIONS WITH GENERAL
CONTRACTOR AND LIGHTING LAYOUT PRIOR TO ROUGH -IN.
9. SEAL ALL DUCT JOINTS AND CONNECTIONS TO EQUIPMENT AIR TIGHT.
10. NOT ALL DUCTWORK OFFSETS AND TRANSITIONS REQUIRED TO INSTALL THE WORK IN
THE AVAILABLE SPACE ARE SHOWN ON THIS DRAWING. FIELD MEASURE FOR EXACT
REQUIREMENTS AND INSTALL ACCORDINGLY.
11. UNLESS OTHERWISE NOTED, ALL DIFFUSER RUN -OUT DUCTS IN ACCESSIBLE
LOCATIONS SHALL BE INSTALLED WITH BUTTERFLY DAMPERS AT TAP TO MAIN TRUNK
DUCT.
12. PAINT ALL DUCTWORK VISIBLE BEHIND AIR DEVICES MATTE BLACK.
al m ".1 mmn11Is] m1ll"l�►6y[oP►IOwlIAIII112 1:NIwe1m1 ".1 :a0611111a
14. RECTANGULAR DUCTWORK ASSOCIATED FAN COIL UNITS SHALL BE GALVANIZED
SHEET METAL WITH 1/2", 3# FIBERGLASS DUCT LINING.
15. ROUND DUCTWORK IN ACCESSIBLE CEILING AREAS SHALL BE SNAP LOCK.
16. FLEX DUCTS SHALL BE INSULATED, NOT MORE THAN 5'-0" LONG; TAPE OFF ALL RAW
EDGES OF INSULATION.
17. OUTSIDE AIR DUCTS SHALL BE INSULATED WITH 1" EXTERIOR DUCT WRAP, R8.0
MINIMUM.
18. INSULATE RIGID ROUND DUCTS ASSOCIATED WITH FAN COIL UNITS EXTERNALLY WITH
R-6.0 "INSUL-SLEEVE".
19. INSTALL DUCTWORK PER SMACNA STANDARDS.
20. ALL THERMOSTAT WIRES SHALL BE ROUGHED IN USING 6-WIRE CABLE.
21. BEFORE STARTING WORK, SUBMIT EQUIPMENT SHOP DRAWINGS AND SUBMITTALS
REQUIRED FOR PROJECT.
IDENTIFY EACH ITEM WITH SUFFICIENT DATA TO CERTIFY COMPLIANCE WITH
MECHANICAL EQUIPMENT LIST.
PURPOSE OF SHOP DRAWINGS AND SUBMITTALS IS TO DEMONSTRATE THAT
CONTRACTOR UNDERSTANDS DESIGN CONCEPT. IF DEVIATIONS, DISCREPANCIES, OR
CONFLICTS BETWEEN SHOP DRAWINGS AND SUBMITTALS AND CONTRACT
DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SUBMITTALS ARE
PROCESSED, DESIGN DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE.
ARCHITECT / ENGINEER REVIEW: ARCHITECT / ENGINEER REVIEW OF SHOP DRAWINGS
AND SUBMITTALS AND ACTION INDICATED AS RESULT OF THIS REVIEW IS COURTESY
EXTENDED TO CONTRACTOR BY REPRESENTATIVE OF OWNER. THIS SERVICE IS
INTENDED TO MINIMIZE DELIVERY TO JOB SITE AND INSTALLATION OF MATERIALS
THAT DO NOT MEET OWNER'S REQUIREMENTS FOR BUILDING. SUBMISSION OF
MATERIAL FOR THIS ACTION DOES NOT ALTER BASIC INTENT OF SPECIFICATIONS AND
CONTRACTOR'S RESPONSIBILITY TO COMPLY THEREWITH.
22. PROVIDE FOR AIR SIDE TEST AND BALANCE AT COMPLETION OF PROJECT. TEST AND
BALANCE REPORT SHALL BE PROVIDED BY TABB OR NEBB CERTIFIED COMPANY OR
OTHER SUB -CONTRACTOR AS APPROVED BY THE ENGINEER OF RECORD. TEST AND
BALANCE REPORT SHALL BE SUBMITTED TO THE GENERAL CONTRACTOR AND
ENGINEER PRIOR TO FINAL APPLICATION FOR PAYMENT.
w
F_
Z
Q
p
rod
V
U
04
r ��
V
Z
w��
Q
J
=
_
O
Q
O
co
bow
Z
Z
J
a
a
cr
cr
�w^^
V,
REVISION NO. DATE
PERMIT 04/01/25
BCKGND REV 05/02/25
REV #2 10/22/25
REV #3 11/05/25
REV #4 02/02/26
'DRAWING TITLE:
MAN LEVEL
HVAC PLAN
DATE: 03/14125
PROD. NO. 25-005
DRAWN 13Y:13A1
GHK'D 13Y: MAC
DRAWING NO.
M-1
PLUMBING FIXTURE ROUGH -IN SCHEDULE
SYMBOL
FIXTURE
CONNECTIONS
REMARKS
CW
HW
WASTE
VENT
WC-1
WATER CLOSET (FLUSH TANK)
1/2
—
3
2
WC-2
WATER CLOSET (FLUSH TANK) - ACCESSIBLE
1/2
—
3
2
LV-1
LAVATORY
1/2
1/2
1-1/2
1-1/2
LV-2
ACCESSIBLE
1/2
1/2
1-1/2
1-1/2
SK-1
SINK
1/2
1/2
1-1/2
1-1/2
SH-1
SHOWER
1/2
1/2
1-1/2
1-1/2
FD/FS
FLOOR DRAIN OR FLOOR SINK
—
—
3"
2"
WB-1
ICE MAKER WALL BOX
1/2"
HB-1
HOSE BIBB
3/4"
NOTES:
DIELECTRIC
UNION
(TYP)--�
HW OUTLET
CW INLE
EXPANSION TANK SPECIFIED
WITH WATER HEATER
PROVIDE FULL-SIZE 4" DEEP
SHEET METAL DRAIN PAN. -
ASME PRESSURE RELIEF VALVE.
WH PIPE TO FLOOR DRAIN.
INSTALL WATER HEATER
IN MEZZANINE
3/4" DRAIN LINE TO
FLOOR DRAIN OR MOP SINK BASIN BELOW
HOT WATER HEATER PIPING SCHEMATIC
i - RESTROOM - LV-1
3/411
- EMPLOYEE KITCHEN - SK-1
1/2" -- - LOCKER ROOM - LV-1
------ -1
� - SHOW ROOM - SK-1
- RESTROOM - LV-1
__q
- RESTROOM - WC-2
- EMPLOYEE KITCHEN - SK-1
-�
- EMPLOYEE KITCHEN - ICEMAKER BOX
- LOCKER ROOM - LV-1
- - -�
- LOCKER ROOM - WC-1
-
- - -
- SOUTH EXTERIOR - HB-2
- SHOW ROOM - SK-1
HW / CW DOMESTIC WATER MANIFOLD
NOT TO SCALE
NOTE:
EXTEND 1/2" AQUA-PEX FROM EACH MANIFOLD TAP TO ASSOCIATED FIXTURE.
GENERAL NOTES
1. ALL WORK SHALL COMPLY WITH AND BE COORDINATED WITH REQUIREMENTS
OF ARCHITECTURAL PLANS AND EXISTING CONSTRUCTION AT THE TIME OF
INSTALLATION
2. INSTALL NEW EQUIPMENT AND FIXTURES TO BE READILY ACCESSIBLE FOR
SERVICE AND MAINTENANCE. REVIEW PROPOSED INSTALLATION WITH
OWNER AND ARCHITECT PRIOR TO STARTING WORK.
3. ALL WORK SHALL CONFORM TO REQUIREMENTS OF THE BELOW REFERENCED
CODES AS ADOPTED BY THE CITY OF CENTER.
- 2021 INTERNATIONAL MECHANICAL CODE (IMC)
- 2021 INTERNATIONAL PLUMBING CODE IPC)
- 2021 INTERNATIONAL FUEL GAS CODE �IFGC)
- 2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
4. ALL DOMESTIC WATER, WASTE, VENT AND GAS PIPING SHALL BE SUPPORTED
IN ACCORDANCE WITH THE REQUIREMENTS OF THE IPC AND IFGC.
5. ALL PIPING INSTALLED THROUGH RATED WALL ASSEMBLIES SHALL BE
PROTECTED IN ACCORDANCE WITH APPLICABLE THROUGH PENETRATION
DETAILS AS SHOWN ON ARCHITECTURAL PLANS. WHERE PENETRATION
DETAILS ARE NOT SPECIFICALLY PROVIDED, REFER PENETRATION TO
ARCHITECT AND / OR ENGINEER FOR DETERMINATION OF PENETRATION
PROTECTION REQUIREMENTS.
6. UNLESS OTHERWISE NOTED, ALL DOMESTIC HW / CW PIPING SERVING TWO
OR MORE FIXTURES SHALL BE MINIMUM 3/4" COPPER, SEE PLANS FOR
SIZING 3/4" AND UP.
7. INSULATE DOMESTIC HOT WATER PIPING LESS THAN 1-1/4" WITH 1"
THICK PIPE INSULATION WITH CONDUCTIVITY OF 0.21-0.28 (R-3.6 TO
R-4.8). INSULATION SHALL BE ONE PIECE FIBERGLASS WITH FACTORY
APPLIED VAPOR BARRIER JACKET AND SELF SEALING LAP OR CLOSED
CELL ELASTOMERIC WITH SELF SEALING LONGITUDINAL SEAM.
8. INSULATE DOMESTIC HOT WATER PIPING 1-1/2" AND LARGER WITH 1-1/2"
THICK PIPE INSULATION WITH CONDUCTIVITY OF 0.21-0.28 (R-3.6 TO
R-4.8). INSULATION SHALL BE ONE PIECE FIBERGLASS WITH FACTORY
APPLIED VAPOR BARRIER JACKET AND SELF SEALING LAP OR CLOSED
CELL ELASTOMERIC WITH SELF SEALING LONGITUDINAL SEAM.
9. NOT ALL PIPING OFFSETS AND TRANSITIONS REQUIRED TO INSTALL THE
WORK IN THE AVAILABLE SPACE ARE SHOWN ON THIS DRAWING. FIELD
MEASURE FOR EXACT REQUIREMENTS AND INSTALL ACCORDINGLY.
10. UNLESS OTHERWISE NOTED, DOMESTIC WATER PIPING SHALL BE TYPE L
COPPER OR AQUA-PEX
11. UNLESS OTHERWISE NOTED, SANITARY WASTE PIPING SHALL BE SCHEDULE
40 PVC-DWV WITH SOLVENT FUSED JOINTS.
12. ALL PLUMBING VENT PIPING SHALL BE SCHEDULE 40 PVC DWV WITH SOLVENT
FUSED FITTINGS. VENT PIPING INSTALLATION SHALL BE INSTALLED AS
REQUIRED TO MEET THE 2021 INTERNATIONAL PLUMBING CODE. FIELD
VERIFY ALL TERMINATIONS WITH ARCHITECT PRIOR TO ROUGH -IN.
13. ALL VENT TERMINATIONS SHALL BE MINIMUM 3" DIAMETER WITH ANY
INCREASE IN VENT SIZE TO 3" BEING MADE NOT LESS THAN 1 FOOT INSIDE
THE BUILDING THERMAL ENVELOPE.
14. PROVIDE CLEANOUTS WITH ACCESS AS REQUIRED PER CODE IN SANITARY
DRAIN PIPING.
15. ALL FIXTURE BRANCH WASTE PIPING SHALL BE MIN 1-1/2" DIA.
16. UNLESS OTHERWISE NOTED OR PRE -APPROVED BY THE ENGINEER, ALL GAS
PIPING SHALL BE SCHEDULE 40 STEEL WITH SCREWED FITTINGS.
17. ALL GAS PIPING INSTALLATIONS INCLUDING, BUT NOT LIMITED TO
SHUT -OFFS, DRIP LEGS, AND FIREPLACE INSTALLATIONS SHALL BE
INSTALLED PER MANUFACTURER SPECIFICATIONS, APPROVED LISTINGS, AND
APPLICABLE PORTIONS OF THE 2018 IFGC.
18. NOTIFY GENERAL CONTRACTOR OF ANY STRUCTURAL OPENINGS REQUIRED TO
COMPLETE PLUMBING INSTALLATION. ALL OPENINGS SHALL BE CUT UNDER
G.C. SUPERVISION WITH STRUCTURAL ENGINEER APPROVAL.
19. PEX AND PVC PIPING 2" AND SMALLER SHALL BE SUPPORTED ON 5'
CENTERS OR ALTERNATIVELY SUPPORTED ON 10' CENTERS AND PROVIDED
WITH A MIDWAY PIPE GUIDE IN ACCORDANCE WITH THE REQUIREMENTS OF
IPC 2021, TABLE 308.5, FOOTNOTE B.
PLUMBING FIXTURE LIST AND EQUIPMENT SCHEDULE
CP-1 DOMESTIC HOT WATER CIRCULATING PUMP
GRUNDFOS MODEL UP 15-29 SUC / TLC
1 GPM, 9 FT. HD.
87 WATTS, 120 VOLTS
PROVIDE COMPLETE WITH INTEGRAL TIMER
INSTALL WITH CALEFFI MODEL 132432A BALANCE VALVE
- SET FOR 0.5 GPM
WH-1 ELECTRIC WATER HEATER
STATE INDUSTRIES MODEL PCE-30-20RT
40 GALLON CAPACITY
4500 WATTS, 208 VOLT, 1 PHASE
- 20.5 GPH RECOVERY AT 90F RISE
- PROVIDE COMPLETE WITH AMTROL ST-5 THERMAL EXPANSION TANK
WH-2 POINT OF USE ELECTRIC WATER HEATER
STATE MODEL ES6-2-SMT
2.5 GALLON CAPACITY
1440 WATTS, 120 VOLT, 1 PHASE
- 6.8 GPH RECOVERY AT 90F RISE
111a IItell] Its 11: 2112
ZURN MODEL 415B
CAST IRON BODY WITH 2" BOTTOM OUTLET, MEMBRANE CLAMP, AND
ADJUSTABLE COLLAR WITH SEEPAGE SLOTS AND TYPE "B" NICKEL
BRONZE STRAINER. PROVIDE COMPLETE WITH ZURN Z1072 TRAP SEAL.
HB-1 WALL FAUCET
WOODFORD MODEL V26
TOP MOUNT INLET W/ POLYCARBONATE HANDLE AND VACUUM BREAKER
HB-2 FROSTPROOF WALL FAUCET
WOODFORD MODEL 17
TOP MOUNT INLET W/ POLYCARBONATE HANDLE AND VACUUM BREAKER
LV-1 LAVATORY - WALL MOUNT
PRO-FLO MODEL PF5514WH
20" X 18" - 3 HOLE / 4" CENTERSET
PROVIDE COMPLETE WITH
- ZURN Z1224 LAVATORY SUPPORT
- PFWSC3007CP SINGLE HANDLE LAVATORY FAUCET
LESS POP-UP DRAIN
- GRID DRAIN
- TAIL PIECE / P-TRAP
- ANGLE SUPPLIES AND STOPS
- FLEXIBLE WATER CONNECTIONS
LV-2 LAVATORY - DROP -IN / ACCESSIBLE
PRO-FLO MODEL PF21184WH
21" X 18" - RECTANGULAR - 4" CENTER SET
PROVIDE COMPLETE WITH
- PFWSC3007CP SINGLE HANDLE LAVATORY FAUCET
LESS POP-UP DRAIN
- GRID DRAIN
- TAIL PIECE / P-TRAP
- ANGLE SUPPLIES AND STOPS
- FLEXIBLE WATER CONNECTIONS
KS-1 KITCHEN SINK
ELKAY MODEL GECR3321
DOUBLE BOWL / TOP MOUNT
- 33" x 21-1/4" x 5-3/8" DEEP
PROVIDE COMPLETE WITH:
- DELTA FAUCET MODEL 100DST
- SINK BASKET STRAINER
- TAIL PIECE / P-TRAP
- ANGLE SUPPLIES AND STOPS
- FLEXIBLE WATER CONNECTIONS
SH-1 SHOWER
STERLING "TRAVERSE" - 72520100
48" x 34" - CENTER DRAIN
PROVIDE COMPLETE WITH:
PRO-FLO PF4001 PRESSURE BALANCED SHOWER VALVE
PRO-FLO PF7611GLF SERIES TRIM KIT - LESS TUB SPOUT
PRO-FLO 2" NO -CAULK SHOWER DRAIN
SHOWER CURTAIN / DOORS TO BE PROVIDED BY OWNER
1111 l l i�►[y:mc;".1 ►
7-1/2" WIDE x MINIMUM 4" DEEP
INSTALL 9" WIDE X 1.25" TALL x 36" LONG GALVANIZED STEEL TRENCH
GRATE (FURNISHED BY OWNER, INSTALLED BY G.C.). TRENCH SHALL BE
FIELD FORMED WITH SMOOTH CONCRETE BOTTOM, 1/8' PER FOOT SLOPE
AND 1-1/4" DEEP X MINIMUM 3/4" WIDE RECESS BELOW FINISHED
FLOOR FOR GRATE MOUNTING.
WC-1 WATER CLOSET - ACCESSIBLE
TANK TYPE / 1.0 GPF PRESSURE ASSIST
ELONGATED BOWL
RIGHT HAND TRIP LEVER
PROVIDE COMPLETE WITH:
- OPEN FRONT PLASTIC SEAT
- ANGLE SUPPLY AND STOP
- FLEXIBLE WATER CONNECTION
13A,
_0
v,
W
~ w
�w
Uz
O
J
z o8E
Q �w
co
Q Z
8
rVR �
V
W
z
a 0
rod V
V
o V
�co �Z
Q
W
J = Cn
Q=O
0
3:
0 w
Z J
Q
�W
V,
REVISION NO. DATE
PERMIT 04/01/25
PRMT REV 05/02/25
REV #1 09/24/25
REV #4 02/02/26
'DRAWING TITLE:
C1B411ffIAL NOTES,
FDCrLFA-= LOT AND
EOUF%13U 80HEDULE,
AND DETAILS
DATE:
04/0I/25
SCALE:
N.r s.
PROD. NO.
2.5-0&
DRAWN 15Y: PAI
641K'D f3Y:
MAP
DRAWING NO.
7
P-0.1
UH
1
13 HB
</* % 1
O `N' 1
EXISTING GAS METER -
FIELD VERIFY 2# GAS
SERVICE (REQUEST SERVICE
UPGRADE IF NOT)
NEW GAS SERVICE -
1600 MBH
1 O
6
EXTEND 1" RECYCLE WATER
SERVICE TO HOSEBIBBS -
PLAN NOTE 13. RE: DWG P-2
FOR DISTRIBUTION PIPING
VALVE AND CAP 1" RECYCLE
WATER LINE FOR FUTURE USE
EXTEND 1" RECYLE WATER TO
CUTTING MACHINES (3X)
EXTEND 2" RECYCLE WATER
FROM HYDROCLEAR UNIT
EMPLOYEE AREA
LV
SHOWROOM / SALES WC 2
S K = ---- ------ - RESTRM
INSTALL WH-1 WH 1
ON ROOF OF 1 EMPLOYEE
RESTROOM K TCHEN
0 LOCKER ROOM
L 1 �'- `3„
W I �� TEMPLOYEE
1 I RESTRM
______________________________________ -------------- P--- ----
ELEC
CLOSET
2 � I
w
z
� I
i
00
I I
0
i
J w
i
L` a
I
0
J
�
i
I
I
I
i
w � I
z I
3 4"
i
r.lw._._._._...............
13 HB
/
/
/
lop
T
T
T
T
T
DOUBLE CHECK VALVE ASSEMBLY
WATTS 007 OR APPROVED EQUAL
T
T T
T
T
T
1_�_
_�_�_
_�_�_
l
_ _� U �_ _ 1" CW MAKE-UP TO
WATER RE-CLAIM SYSTEM
RECLAIM WATER DISTRIBUTION PIPING SCHEMATIC
NOT TO SCALE
NOTES:
1. DISTRIBUTION PIIPNG ASSEMBLY SHALL BE INSTALLED ON WALL BEHIND
HYDROCLEAR RECYCLING ASSEMBLY AT APPROXIMATELY 48" A.F.F.
PIPING SHALL BE ROUTED OVERHEAD FROM MANIFOLD.
2. PIPING MANIFOLD AND INLET / OUTLET CONNECTIONS TO OVERHEAD
DISTRIBUTION SHALL BE TYPE L COPPER. AQUA-PEX MAY BE USED FOR
OVERHEAD DISTRIBUTION INSTALLATION - SUBJECT TO OWNER APPROVAL.
13 HB
1-1--------
�!77777 CIE
HB
2
-- --- _ ----- - b �vi
t 0 1 12
HV HYLROCLEAR V
SH
RECYCLING S`
I
FLOW LINE
SLOPE 1/8" / FT
FABRICATION SHOP / STORAGE
7'7= r_=III®III=
FLOW LINE
SLOPE 1/8" / FT
I
13 H
]Q� I=III 77777 77777
I
FLOW LINE i
SLOPE 1/8" / FT
7= 7=17Z=11177777117= 7=1 =17777711
® I
HB 13
MAIN LEVEL PLUMBING FLOOR PLAN
SCALE: 1/8" = 1'-0"
NOTE:
- TOTAL TRENCH DRAIN LENGTH IS ESTIMATED AT 226 L.F. AT 1/8" / FOOT FALL,
TOTAL MINIMUM FALL IS 28.5".
PLAN NOTES
O1 EXTEND 3" WASTE DOWN NEXT TO EXTERIOR WALL TO APPROXIMATELY
24" ABOVE MAIN SLAB LEVEL. TURN HORIZONTAL AS REQUIRED AND
EXTEND THROUGH WALL AND THEN DOWN AS REQUIRED TO ROUTE
BELOW THE MAIN LEVEL SLAB.
O2 EXTEND 3" WASTE HORIZONTALLY BELOW MAIN LEVEL SLAB TO
CONNECTION WITH EXISTING SANITARY WASTE.
O3 FIELD VERIFY LOCATION OF BUILDING DOMESTIC WATER SERVICE AND
MAKE 1" NEW VALVED CONNECTION AS REQUIRED.
O4 INSTALL WH-1 BELOW LV-1. MAKE 1/2" CW CONNECTION AND EXTEND 1/2"
HW FROM WH-1 UP TO SERVE LV-1.
O EXTEND 1/2" CW DN IN WALL. MAKE 1/2" TAP TO LV-1 FAUCET AND EXTEND
1/2" CW SERVICE TO WH-1.
O EXTEND 1-1/4" GAS INTO WEST BAY AND CAP FOR FUTURE USE.
O EXTEND 1-1/4" CW SERVICE UP NEXT TO INTERIOR WALL. ROUTE
HORIZONTALLY APPROXIMATELY 12" BELOW FINISHED CEILING LEVEL.
O INSTALL DOMESTIC HOT AND COLD WATER AQUA-PEX MANIFOLDS IN
CEILING SPACE. RE: PIPING SCHEMATIC THIS SHEET FOR MANIFOLD
REQUIREMENTS.
HB 13
1
T--------------
'12 -- /LN
5
21
/4" W(
O9 FURNISH AND INSTALL MANUAL SHUT-OFF VALVE AND GAS PRESSURE
REGULATOR RATED FOR 100 MBH / 2# TO 14"
10 NOT USED.
11 NOT USED
12 EXTEND 1" DOMESTIC WATER MAKE-UP TO RECLAIM SYSTEM. RE: PIPING
SCHEMATIC THIS SHEET.
13 SURFACE MOUNT RECLAIM WATER HOSE-BIBB HB-1 AT 48" A.F.F. FIELD
COORDINATE FINAL LOCATIONS WITH OWNER'S REPRESENTATIVE.
14 RECLAIM WATER COLLECTION PIT. RE: STRUCTURAL PLAN FOR DETAILS.
15 EXTEND 3/4" GAS SERVICE TO APPLIANCE (GAS FIREPLACE). MAKE FINAL
CONNECTION (INCLUDING LOCAL SHUT-OFF) PER MFR RECOMMENDATIONS.
i
2-�
w
F_
Z
Q
0
rod
V
U
04
0�
co
>
Z
w�0.
Q
J
=
cf)
_
O
Q
0
♦^
V,
0
W
Z
W
Z
J
a
C5
or
or
w
REVISION NO. DATE
PERMIT 04/01/25
PRMT REV 05/02/25
REV #1 09/24/25
REV #4 02/02/26
DRAWING TITLE:
MAIN LEVEL
PLUMBING PLAN
/DATE: 03/14/2-5
SCALE: 1/r = I'-e
PROD. NO. 25-005
DRAWN 13Y:13A1
6 K'D 13Y- MA 5 J
DRAWING NO.
7
P-1
EXISTING ELECTRICAL
SERVICE ENTRY /
MAIN DISTRIBUTION
RE: EXISTING AND NEW
ONE -LINE DIAGRAMS -
DWG E-0.1
UPPER LEVEL ELEC RM LTG PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES
O EXTEND BB-1 POWER SERVICE FROM CONTACTOR - RE: PLAN NOTE 2.
20 INSTALL 4-POLE SINGLE PHASE CONTACTOR IN STORAGE CLOSET AND
EXTEND POWER CONDUCTORS AS REQUIRED TO BB-1 BASEBOARDS.
CONTACTOR SHALL BE CONTROLLED BY OUTSIDE AIR TEMPERATURE
(START BB-1 ON OUTSIDE AIR TEMERATURE DROPPING BELOW 30F) -
CONTACT CLOSURE TEMPERATURE CONTROL SHALL BE ADJUSTABLE.
30 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER
PROVIDED CNC MILL. POWER INSTALLATION SHALL CONFORM TO
MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND
ASSOCIATED WIRING DIAGRAM SHALL BE ON -SITE AND AVAILABLE FOR
REVIEW BY ENGINEER DURING INSTALLATION.
40 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER
PROVIDED BRIDGE SAW. POWER INSTALLATION SHALL CONFORM TO
MANUFACTURER INSTALLATION INSTRUCTIONS. INSTRUCTIONS AND
ASSOCIATED WIRING DIAGRAM SHALL BE ON -SITE AND AVAILABLE FOR
REVIEW BY ENGINEER DURING INSTALLATION.
50 EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER
PROVIDED HYDROCLEAR WATER RECYCLING SYSTEM. POWER
INSTALLATION SHALL CONFORM TO MANUFACTURER INSTALLATION
INSTRUCTIONS. INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAM
SHALL BE ON -SITE AND AVAILABLE FOR REVIEW BY ENGINEER DURING
INSTALLATION.
PANEL SCHEDULE - LP1 OFFICE POWER AND LIGHTING PANEL
PANEL TYPE: LOAD CENTER
MAIN BREAKER: 200 A
BUS SIZE: 225 A
PHASES: 3
WIRES: 4
MOUNTING: FLUSH
VOLTAGE: 120 208 V
CONNECTED: XXX W
DEMAND: XXX W
PHASE A CONNECTED: XXX W
PHASE B CONNECTED: XXX W
PHASE C CONNECTED: XXX W
LOAD TYPE AND DESCRIPTION
A
M
P
S
P
0
L
E
S
C
K
T
#
P
H
A
S
E
C
K
T
#
P
0
L
E
S
A
M
P
S
LOAD TYPE AND DESCRIPTION
LIGHTING: SHOWROOM SALES
20A
1P
1 1
1A
2
12P
170A
MECH- H&C: FC-1
LIGHTING: EMPLOYEE AREA LOCKER RM KITCH
20A
1P
3
B
4
--
---
MECH- H&C: ---
LIGHTING: 24 7 SECURITY
15A
1P
5
C
6
2P
50A
MECH- H&C: HP-1
RECEPTACLE: ADMIN DESK
20A
1P
7
A
8
--
---
MECH- H&C: ---
RECEPTACLE: ADMIN DESK
20A
1P
9
B
10
1P
15A
MECH- HEAT: BB-1
RECEPTACLE: SHOWROOM SALES
20A
1P
11
C
12
1P
15A
MECH- HEAT: BB-1
RECEPTACLE: RESTROOM
20A
1P
13
A
14
1P
15A
MECH- HEAT: BB-1
RECEPTACLE: KITCHEN - COUNTER
20A
1P
15.13
16
1P
15A
MECH- HEAT: BB-1
RECEPTACLE: KITCHEN - COUNTER
20A
1P
17
C
18
1P
20A
MECH- H&V: BB-2
RECEPTACLE: KITCHEN - MICROWAVE
20A
1P
19
A
20
1P
20A
MECH- VENT: EF-1
RECEPTACLE: KITCHEN - REFRIGERATOR
20A
2P
21
B
22
2P
30A
MISC: WH-1
MISC: KITCHEN - RANGE
40A
--
23
C
1 24
--
---
MISC: ---
MISC: ---
---
1P
25
A
26
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: SHOWER ROOM
20A
1P
27
B
28
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: EMPLOYEE AREA LOCKER ROOM
20A
1P
29
C
30
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: EXTERIOR - NORTH
20A
1P
31
A
32
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: EXTERIOR - SOUTH
20A
1P
33
B
1 34
1P
20A
SPARE: UNALLOCATED FUTURE
SPARE: UNALLOCATED FUTURE
20A
1P
35
C
36
11P
20A
SPARE: UNALLOCATED FUTURE
SPARE: UNALLOCATED FUTURE
20A
--
37
A
38
--
---
SPACE: ---
SPACE: ---
---
--
39
B
40
--
---
SPACE: ---
SPACE: ---
41
C
42
ISPACE. ---
O FIELD VERIFY EXISTING WATER SERVICE POWER REQUIREMENTS AND RE -
POWER AS REQUIRED.
70 EXTEND 1/2" EMT DOWN EXISTING COLUMN AND MOUNT RECEPTACLE AT
48" A.F.F.
OEXTEND 1/2" EMT DOWN FROM CEILING SPACE EXPOSED ON INTERIOR
WALL. MOUNT RECEPTACLE AT 48" A.F.F.
O EXTEND POWER SERVICES FROM LOCAL DISCONNECT TO OWNER
PROVIDED HONER AND POLISHER MACHINES. POWER INSTALLATIONS
SHALL CONFORM TO MANUFACTURER INSTALLATION INSTRUCTIONS.
INSTRUCTIONS AND ASSOCIATED WIRING DIAGRAMS SHALL BE ON -SITE
AND AVAILABLE FOR REVIEW BY ENGINEER DURING INSTALLATION.
PANEL SCHEDULE - LP2 FABRICATION SHOP / STORAGE / OFFICE
PANEL TYPE: LOAD CENTER
MAIN BREAKER: 200 A
BUS SIZE: 225 A
PHASES: 3
WIRES: 4
MOUNTING: FLUSH
VOLTAGE: 120 208 V
CONNECTED: XXX W
DEMAND: XXX W
PHASE A CONNECTED: XXX W
PHASE B CONNECTED: XXX W
PHASE C CONNECTED: XXX W
LOAD TYPE AND DESCRIPTION
A
M
P
S
P
0
L
E
S
C
K
T
#
P
H
A
S
E
C
K
T
#
P
0
L
E
A
M
P
S
LOAD TYPE AND DESCRIPTION
LIGHTING: EAST FAB STORAGE
20A
1P
I 1
A
2
--
20A
SPARE: UNALLOCATED FUTURE
LIGHTING: WEST FAB STORAGE
20A
1P
3
B
4
--
20A
SPARE: UNALLOCATED FUTURE
LIGHTING: 24 7 SECURITY EXTERIOR
20A
1P
5
C
6
- -
RECEPTACLE: EAST FAB STORAGE
20A
1P
7
A
8
1P
20A
MECH- HEAT: UH-1
RECEPTACLE: WEST FAB STORAGE
20A
1P
9
B
10
--
---
MECH- VENT: -
20A
1P
11
C
12
3P
30A
MECH- VENT: EF-1
SPARE: UNALLOCATED FUTURE
20A
1P
13
A
14
-
20A
1P
15113
2P
30A
SPARE: UNALLOCATED FUTURE
MISC: NORTH OVERHEAD DOOR
20A
1P
17
C--
---
PAR : ---
RECEPTACLE: EAST RESTROOM
20A
1P
19
A
R22
P
-
RECEPTACLE: WEST RESTROOM
20A
1P
21
B
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: EAST FAB STORAGE - SOUTH
20A
1P
23
C
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: EAST FAB STORAGE - NORTH
20A
1P
25
A
26
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: WEST FAB STORAGE - SOUTH
20A
1P
27
B
28
1P
20A
SPARE: UNALLOCATED FUTURE
RECEPTACLE: WEST FAB STORAGE - NORTH
20A
1P
29
C
30
1P
20A
SPARE: UNALLOCATED FUTURE
SPARE: UNALLOCATED FUTURE
20A
1P
31
A
32
1P
20A
SPARE: UNALLOCATED FUTURE
SPARE: UNALLOCATED FUTURE
20A
1P
1 33
B
1 34
1P
20A
SPARE: UNALLOCATED FUTURE
SPARE: UNALLOCATED FUTURE
20A
1P
35
CW42--
20A
SPARE: UNALLOCATED FUTURE
SPACE: ---
---
--
37
A---
SPACE: ---
SPACE: ---
---
--
39
B---
SPACE: ---
SPACE: ---
---
--
41
CSPACE:
---
,!q' LICC
��O�a�'P�y
c-'
0
U
Z
W
~ w
Q W 3 .
Uz
O� o�
W
mo
Q Z 0
J N co
Q cy
Q Z 09
oc 8
O
O
W
F_
Z
Q
0
�
U
C�
N
(n
c�0
cd>-
Z
Q �
a:W
�
J
=
(1)
cr
0
C)
Q=0
mco0
c
3::
0
w
z
Z
W
Q
J
cr
0
cr
w
INN/
REVISION NO. DATE
PERMIT 04/01/25
BCKGND REV 05/02/25
REV #3 12/01/25
REV #4 02/02/26
PRAWINO TITLE:
MAIN LEVEL
POWER PLAN AND
PANEL SCHEDULES
PATE: 03/31/2-5
PROD. NO. ZFrppS
PRAWN f5Y: PAI
GHK'P f5Y: MAC
PRAWIN6 NO.
E-1
J
UPPER LEVEL ELEC RM LTG PLAN
D
MANUFACTURER
VOLTAGE
BALLAST TYPE
DESCRIPTION
E
CATALOG NUMBER
MOUNTING
LAMP TYPE
S
# OF LAMPS
WATTS
COLUMBIA LIGHTING
120
ELECTRONIC
CENTER LENS TROFFER - 23.88" x 47.88" x 4" DEEP,
A
CCL24-LSCS
CEILING
LED
FROSTED ACRYLIC LENS, 80+CRI, 4000K (SWITCHABLE)
-
32
SWITCHABLE LUMEN 4200 - 6000), 0-10 VOLT DIMMING
COLUMBIA LIGHTING
120
ELECTRONIC
CENTER LENS TROFFER - 23.88" x 23.88" x 4" DEEP,
Al
CCL22-LSCS
CEILING
LED
FROSTED ACRYLIC LENS, 80+CRI, 4000K (SWITCHABLE)
-
-
25
SWITCHABLE LUMEN 2900 - 4400), 0-10 VOLT DIMMING
COLUMBIA LIGHTING
120
ELECTRONIC
RECESSED LINEAR, 47.75" x 4.72" x 3.82" DEEP,
B
NRL4-LSCS
CEILING RECESSED
LED
FROSTED POLYCARBONATE LENS, 80+CRI, 4000K, SWITCHABLE
-
21
LUMEN 2500 - 4500), 0-10 VOLT DIMMING, 5-WIRE FLEX
COLUMBIA LIGHTING
120
ELECTRONIC
LINEAR WALL BRACKET, 4.8" x 36" x 3.9" TALL, SQUARE
C
W36 4 _ _ 35 XW SFZ ED U
WALL MOUNT
LED
FROSTED ACRYLIC LENS, 3500 K, 2700 LUMEN, 0-10 VOLT
-
-
21
DIMMING.
COLUMBIA LIGHTING
120
ELECTRONIC
SUSPENDED HIGH -BAY, 22.7" x 10" x 2.3" DEEP,
D
CLB2 40 LX W EDU
CEILING SUSPENDED
LED
10,000 LUMEN, WIDE DIST., 0-10 V DIMMING,
LHVQM5
-
75.9
60" ADJUSTABLE CABLE MTG.,
BEACON
120
ELECTRONIC
AREA LIGHT - CAST ALUM, 8" x 12-1/4" x 5-1/4" TALL,
E
RWL1 48L-35 4K8 2 120 DBT
WALL SURFACE
LED
4500 LUMEN, 4000K, DARK BRONZE TEXTURED, BUTTON
PC
-
36.9
PHOTOCELL. INSTALL AT 18-0" A.F.F.
BEACON
120
ELECTRONIC
AREA LIGHT - CAST ALUM, 8" x 12-1/4" x 5-1/4" TALL,
E
RWL1 48L-35 4K8 2 120 DBT
WALL SURFACE
LED
4500 LUMEN, 4000K, DARK BRONZE TEXTURED, BUTTON
T.B.D.
120
ELECTRONIC
SUSPENDED ARCHITECTURAL LINEAR LUMINAR - SLOPED CLG
F
CEILING SUSPENDED
LED
4000 K, 3,000 LUMEN (+/-), DIMMABLE
-
42
COLUMBIA LIGHTING
120
ELECTRONIC
FLAT PANEL - 11.9" X 47.8" X 2" DEEP, ALUMINUM LENS
G
CBT 14 A LSCS EDD
CEILING SURFACE
LED
FRAME, 4000 K (SWITCHABLE), 3,000 - 4760 LUMEN,
-
-
39
DIMMABLE
Sl
LCS 2 40 ML E U CSHC
CEILING SUSPENDED
LED
FIXED OUTPUT, 4000K
T.B.D.
120
ELECTRONIC
SINGLE CIRCUIT TRACK LIGHT, 4'-0" LONG, 3 HEADS,
T
TRACK LIGHT
CEILING SURFACE
LED
4000K, DIMMABLE
T.B.D.
120
ELECTRONIC
2-CIRCUIT TRACK LIGHT, 6'-0" LONG, 6 HEADS, 4000K,
T1
TRACK LIGHT
CEILING SURFACE
LED
DIMMABLE
X
CCRHOSQ
WALL MOUNT
LED
RED LETTERS, INSTALL AT 8'-6' A.F.F.
-
3.9
COMPASS LIGHTING
120
ELECTRONIC
EXTERIOR EGRESS - 9.1" x 6.3" x 2.5" DEEP, 4000K,
X1
CUSO 4DBH ND
WALL MOUNT
LED
PHOTO -SENSOR, HEATER, DARK BRONZE, INSTALL AT 9'-0"
-
-
3.9
ABOVE GRADE
MAIN LEVEL ELECTRICAL LIGHTING PLAN
SCALE: 1/8" = l'-0"
LIGHTING CONTROL NOTES
1024/7 SECURITY - ALWAYS ON. CIRCUIT DIRECT FROM PANEL.
>MANUAL DIMMING SWITCH.
<�>`OCCUPANCY SWITCH - OFF AFTER 30 MINUTES (ADJUSTABLE).
>OCCUPANCY SWITCH - CEILING SENSOR, OFF AFTER 30 MINUTES (ADJUSTABLE).
>MANUAL ON - OFF AFTER 60 MINUTES (ADJUSTABLE).
UPPER LEVEL STAIR LIGHTING PLAN
BAt,
U
Z
W
~ a w
Q 01
W 30-
.
Uz
O� o�
0-
W
mo
Q Z 0
J N co
Q a)
Q QZ 09
v ml
O
O
m
w
F_
z
Q
0
�
U
C�
N
(n
c�O
cd>_Z
w��
Q�
J
=
�
0
C)
T
0
�(00
0
w
z
Z
w
Q
J
or
0
cr
w
INN/
REVISION NO. DATE
PERMIT 04/01/25
PRMT REV 05/02/25
REV #3 12/01/25
REV #4 02/02/26
DRAWING TITLE:
MAN LEVEL
L.K11- rM PLAN
DATE: 03/31/2-5
SGAL : I/r
PROD. NO. 2.5-00
DRAWN 15Y: PAI
GHK'D f3Y: MAC
DRAWING NO.
7
E-2