HomeMy WebLinkAboutSpartan Tank Transmittal LetterISCM SPARTAN
To:
TRANSMITTAL LETTER
From:
Community Development Department Brad Smith
Attn: John Plano, Garfield County Chief Building Official Date: Project Number
108 8`h Street, Suite 401 4/1/2026 2SO08 _
Glenwood Springs, CO 81601
Project Name/Address:
FreeUp Storage Silt CO Water Tank
357 S 161" St. Silt, CO 81652
Re:
Garfield County Community Development Department-FreeUp Storage Silt CO Building Permit Review
The following items have been sent via:
Standard Postal Mail Overnight Delivery Client Pickup At Office
X UPS Overnight I Courier Service Other (Drop Off)
Item
1.
Copies
2
Date
4/1/2026
Drawing/Document #
7. Freeup Silt_PH Structural Permit_02-28-
2026
Description
FreeUp Storage Fire Pump House Structural Plans
(24"x36" two copies)
2.
2
4/1/2026
8.a FreeUp Silt Tank -PH MP-3-12-2026
FreeUp Storage Fire Pump House Micropile Plans
(24"x36" two copies)
3.
4.
5.
6.
7.
8.
9.
10.
11.
These are transmitted as checked below:
X
For Approval
For Review and Comment
Approved as Submitted
Approved as Noted
Resubmit Copies for Approval
Submit (_) Copies for Distribution
As Requested
Returned for Corrections
Return (_) Corrected Prints
For Your Use
Notes/Comments:
Please review and approve the attached documents in order to receive building permit approval. Let me know if
you have any questions or comments.
Sincerely,
Brad Smith I Real Estate Development Manager
Spartan Investment Group, LLC 117301 W. Colfax Ave. Suite 120, Golden, CO 80401
C:303.883.7586 1 hsmith soarlan-investors.com
Spartan-Investors.com I Invest in Our Volues
A Veterannr Owned Business
S PA RTA N
INVES"IMEN1 GROUP
CONDITIONS OF PERMIT
BLCO-01-26-9642
FREEUP STORAGE SILT LLC
WATER TANK AND PUMPHOUSE TO SUPPLY HYDRANTS,
FIRE SPRINKLER, AND RESTROOM
357 S. 16T" STREET, SILT
1) THE APPROVED PLANS ARE TO BE ON -SITE FOR INSPECTIONS.
2) SANITARY FACILITIES ARE REQUIRED TO BE PROVIDED FOR WORKERS.
3) A LIST OF REQUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
IS TO PERMIT AND APPROVE THE ELECTRICAL WORK.
HTTPS://WWW.COLORADO.GOV/PACIFIC/DORA/DPO ELECTRICAL PLUMBING PE
RMITS
4) UNDERGROUND UTILITY LOCATES IS THE RESPONSIBILITY OF THE OWNER OR
CONTRACTOR. 811 IS THE COLORADO UTILITY LOCATE HOT LINE.
5) GEOTECHNICAL ENGINEER IS TO OBSERVE THE MICROPILE INSTALLATION AND
PROVIDE A STAMPED LETTER THATTHE PILES ARE INSTALLED PER
SPECIFICATIONS.
6) DRAINAGE ACROSS PROPERTY LINES SHALL NOT EXCEED THAT WHICH EXISTED
PRIOR TO GRADING. EXCESS OR CONCENTRATED DRAINAGE SHALL BE
CONTAINED ON SITE OR DIRECTED TO AN APPROVED DRAINAGE FACILITY.
EROSION OF THE GROUND IN THE AREA OF DISCHARGE SHALL BE PREVENTED BY
INSTALLATION OF NON -EROSIVE DOWN DRAINS OR OTHER DEVICES.
7) ALL BACKFLOW PREVENTERS ARE REQUIRED TO BE TESTED AND CERTIFIED BY A
LICENSED BACKFLOW SPECIALIST AFTER INSTALLATION AND PRIOR TO ISSUANCE
OF THE CERTIFICATE OF OCCUPANCY.
8) ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
9) ANY WATER SUPPLY THAT FEEDS AFIRE SUPPRESSION SYSTEM IS TO BE
INSPECTED BY THE FIRE MARSHAL FOR THAT FIRE DISTRICT PRIOR TO
BACKFILLING.
10) PLEASE PROVIDE SPECIAL INSPECTIONS REPORTS TO THE BUILDING
DEPARTMENT, WELDING AND BOLTING IS MINIMUM.
11)COMBUSTIBLE MATERIAL IS LIMITED IN TYPE I AND TYPE II CONSTRUCTION. SEE
IBC 603 FOR ALLOWED COMBUSTIBLE MATERIALS.
12)ALL EXTERIOR LIGHTING IS TO BE DOWNCAST AND SHIELDED.
13)ALL ACCESSIBLE DOOR HARDWARE SHALL HAVE A SHAPE THAT IS EASY TO GRIP,
INCLUDING POCKET AND SLIDING DOORS. (ANSI Al 17.1 - 404.2.6)
14) UFER GROUNDS ARE REQUIRED TO BE INSPECTED AT FOOTING INSPECTION
15)ANY EXPOSED FOAM IS TO BE COVERED WITH AN IGNITION BARRIER OR A
THERMAL BARRIER BASED ON LOCATION. (IRC R316)
16) CONTROL NOXIOUS WEEDS. TREAT EXISTING WEEDS PRIOR TO RELOCATING
PLANTS AND SEEDS.
17) REVEGITATE ALL DISTURBED AREAS THAT ARE NOT PART OF A ROAD OR NON -
SEEDED AREA.
18) PROVIDE EROSION CONTROLS UNTIL SEEDED AREAS CAN BE ESTABLISHED.
19) PROVIDE DUST CONTROL AS REQUIRED DURING CONSTRUCTION.
20) FOLLOW ENGINEERED PLANS. VERIFY ANY CHANGES WITH THE ENGINEER.
21) PROVIDE MEANS TO KEEP THE TANK AND PIPING FROM FREEZING.
PUMPHOUSE CONDITIONS
22)ANY PLUMBING IS TO BE INSPECTED AND APPROVED BY THE FIRE DISTRICT.
23)THE PUMPHOUSE STRUCTURAL DRAWINGS ARE TO BE A DEFERRED SUBMITTAL,
NO INSPECTIONS ARE TO BE PERFORMED ON THE PUMPHOUSE UNTIL APPROVED.
24)ANY REQUIREMENTS FROM THE FIRE DISTRICT BECOMES REQUIRED CONDITIONS
OF THE PERMIT.
25)THE PUMP HOUSE IS THE BE PROTECTED WITH FIRE SPRINKLERS
26)THE EXTERIOR WALLS ARE TO BE ONE -HOUR FIRE RESISTIVE, SEE THE 81h X 11.
27) INSULATION IS NOT SHOWN ON THE PLANS, FIELD VERIFY THAT THE THERMAL
ENVELOPE MEETS MINIMUM CRITERIA.
28) ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
AS 1r- -I E R7__ � -
ARCHITECTS
=INGINEERS
Date: 4/22/2026
To: Garfield County Community Development Department
From: Asher Architects+Engineers
RE: FreeUp Self Storage Silt Pump House
Dear Garfield County Community Development Department:
It is now proposed to provide a fire sprinkler system within the pump house
structure at the Free Up Storage facility along with a 1 hour rated wall system to
comply with NFPA 20 Requirements.
Per prescriptive code requirements of IBC Chapter 7 Table 722.6.2(1) a single layer
of 5/8" drywall on each side of the exterior steel stud walls will accomplish this
goal.
Wall Assembly:
5/8" drywall interior
= 30 Minutes
2x6 steel stud
= 0 Minutes
5/8" drywall exterior
= 30 Minutes
Metal siding exterior
= 0 Minutes
Total fire protection
= 1 Hour
Sincerely,
David A. Stranathan, AIA, NCARB, LEED AP BD+C
Principal Architect
Remit Email: David@asherarch.com www.AsherArch.com
4.12.1.1.2* Indoor fire pump rooms in non -high-rise buildings or in separate fire pump build-
ings shall be physically separated or protected by tiro -rated construction in accordance with
Table 4.12.1.1.2.
TABLE 4.12 1.L2 Equtpinenf Prorecti4on
Building(s) Exposing Pump
Pump Roont/House RoomlHouse Required Separation
Not sprinklered Not sprinklered 2 hour Fire -rated
Not sprinklered Fully sprinklered or
Fully sprinklered Not sprinklered 50 ft (15.3 ni)
Fully sprinklered Fully sprinklered I hour Fire -rated
or
50 ft (15.3 nr)
For the purposes of Table 4.12.1.1.2, a building with a fine protection system(s) supplied from
the fire pump is considered to be a building exposing the pump room house. There may also
be other buildings or hazards that expose the pump room.rhouse.
A.4.12.1.1.2 The purpose for the `Not Sprinklcred" column in Tablc 4.12.1.1.2 is to pro-
vide guidance for unsprinlcicrcd buildings. This does not permit sprinklers to be omittod from
pump rooms in full), sprinklered buildings.
4.12.1.1.3 The location of and access to the fire pump room shall be preplanned with the fire
department.
4.12.1.1.4* Except as permitted in 4.12.1.1.5, rooms containing fire pumps shall be tire from stor-
age., equipment and penetrations not essential to the operation of the pump and related components.
it is the Intent of the standard to prohibit the use of a fire pump room for the purposes of
storage. It is not the intent of the standard to prohibit the installation of other types of equip-
ment such as domestic water distribution equipment as indicated in 4.12.1.1.5. No materials or
equipment that add to the combustibility of the space should be placed in the fire pump room.
This provision Is intended to provide protection to equipment as well as operating personnel,
A.4.12.1.1.4 Equipment that increases the fire hazard (such as boilers) and is not related to
fire protection systems should not be in a fire pump room_