HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT
BLCO-06-26-9951-KITCHEN
BLCO-06-26-9950 -LEARNING LAB
AVLT - COFFMAN RANCH
TWO PERMITS ARE COVERED WITHIN THE PLANS
1837 COUNTY ROAD 100
CARBONDALE, PARCEL: 239336321001
1) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY ON THE LEARNING LAB
AND THE KIT(--I-IEnI BUILDINGS, THE APPLICANT SHALL PROVIDE THE NEW \niEi I_
PERMIT AND WELL WATER QUALITY TEST REPORTS AND PUMP TEST. PRIOR TO
THE ISSUANCE OF THE CO'S THE CURRENT AGRITOURISM OPERATIONS MAY
CONTINUE AS ALLOWED UNDER THE LUDC.
2) GEOTECHNICAL OBSERVATION IS REQUIRED WHEN THE EXCAVATION IS
COMPLETE AND WRITTEN VERIFICATION BE SUPPLIED AT FOOTING INSPECTION,
3000 PSF.
3) IT APPEARS THE SITE PLAN/CIVILS HAVE CHANGED SINCE THE POLE BARN
WAS ISSUED. THE ACCESSIBLE ROUTE TO THE POLE BARN IS NOT SHOWN IN
THESE DRAWINGS. BASED ON THE NEW DESIGN, AN ACCESSIBLE ROUTE
FROM THE LEARNING CENTER TO THE TO THE KITCHEN AND BARN IS
REQUIRED. I'M NOT THE DESIGNER BUT I WOULD SUGGEST THE 6" STEP OFF
THE DECK BE A SMALL RAMP. IBC 1012.8 AND ANSI A117.1 405.8 WAIVES
HANDRAIL FOR RAMPS 6" OR LESS. BUT EDGE PROTECTION IS STILL
REQUIRED. 405.9.
4) IF ANY OF THE DECK IS OVER 30" ABOVE GRADE, A 42" TALL GUARDRAIL WILL
BE REQUIRED.
5) ALL nECK FRAMING IS TO BE NATURALLY DURABLE WOOD OR PRESSURE
TREATED FOR AGAINST DECAY. (IBC 2304.12.2.3)
6) EMERGENCY LIGHTS AND EXIT SIGNS ARE REQUIRED IN THE LEARNING LAB.
7) THE WALLS SURROUNDING THE TOILET ARE TO BE NON -ABSORBENT FOR A
HEIGHT OF 48" AND 2' PAST ON EACH SIDE OF THE TOILET.
8) DOOR HARDWARE IS NOT SPECIFIED. ALL ACCESSIBLE DQQR PAPM TARE gHALL
HAVE A SHAPE THAT IS EASY TO GRIP, INCLUDING POCKET AND SLIDING DOORS.
(ANSI Al 17.1 - 404.2.6)
9) THE ACCESSIBLE PARKING SPACES SHALL HAVE SI(---J^JAG-.
10)THE ACCESSIBLE STALL DOORS ARE TO MAINTAIN 32" !N THE CLEAR. THE
DRAWINGS ARE SPECIFYING 2'6" DOORS, WHICH DOES NOT COMPLY.
11)THE 3 COMPARTMENT SINK WASTE LINE IS TO HAVE A GREASE TRAP AND AN AIR
GAP.
m
12)THE APPROVED PLANS ARE TO BE ON -SITE FOR INSPECTIONS.
13) SANITARY FACILITIES ARE REQUIRED TO BE PROVIDED FOR WORKERS.
14)A LIST OF REQUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
IS TO PERMIT AND APPROVE THE ELECTRICAL WORK.
HTTPS•//WWW COLORADO GOV/PACIFIC/DORA/DPO ELECTRICAL PLUMBING PE
RM ITS
15) UNDERGROUND UTILITY LOCATES IS THE RESPONSIBILITY OF THE OWNER OR
CONTRACTOR. 811 IS THE COLORADO UTILITY LOCATE HOT LINE.
16) DRAINAGE ACROSS PROPERTY LINES SHALL NOT EXCEED THAT WHICH EXISTED
PRIOR TO GRADING. EXCESS OR CONCENTRATED DRAINAGE SHALL BE
CONTAINED ON SITE OR DIRECTED TO AN APPROVED DRAINAGE FACILITY.
EROSION OF THE GROUND IN THE AREA OF DISCHARGE SHALL BE PREVENTED BY
INSTALLATION OF NON -EROSIVE DOWN DRAINS OR OTHER DEVICES.
17)ANY RETAINING WALL OVER 48" TALL REQUIRES TO BE DESIGNED BY A
STRUCTURAL OR CIVIL ENGINEER DEPENDING ON THE TYPE OF MATERAIL USED.
THE 48" HEIGHT IS MEASURED FROM THE BOTTOM OF THE FOOTING THAT IS
BELOW GRADE, NOT THE FACE OF THE WALL.
18) ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
19) INTERIOR SLABS ARE REQUIRED TO HAVE A 6 MIL VAPOR BARRIER.
20)ALL EXTERIOR LIGHTING IS TO BE DOWNCAST AND SHIELDED.
21) SAFETY GLAZING IS NOT DESIGNATED ON THE PLANS. SAFETY GLAZING WILL BE
CHECKED DURING THE FRAMING AND FINAL INSPECTION. (IBC 2406.4)
22)A PASSING BLOWER DOOR TEST IS REQUIRED TO BE SUBMITTED PRIOR TO
ISSUING THE CERTIFICATE OF OCCUPANCY.
23) UFER GROUNDS ARE REQUIRED TO BE INSPECTED AT FOOTING INSPECTION
24)ANY EXPOSED FOAM IS TO BE COVERED WITH AN IGNITION BARRIER OR A
THERMAL BARRIER BASED ON LOCATION. (IRC R316)
25) INSTALL STORMWATER CONTROLS PRIOR TO ANY DIRT WORK.
26) CONTROL NOXIOUS WEEDS. TREAT EXISTING WEEDS PRIOR TO RELOCATING
PLANTS AND SEEDS.
27) PROVIDE EROSION CONTROLS UNTIL SEEDED AREAS CAN BE ESTABLISHED.
28) PROVIDE DUST CONTROL AS REQUIRED DURING CONSTRUCTION.
29) KITCHEN HOODS OVER 400 CFM REQUIRE MAKE-UP AIR. THE STOVE
MANUFACTURER DICTATES THE REQUIRED CFM'S REQUIRED.
30) SEPARATE SIGN PERMITS ARE REQUIRED FOR ANY EXTERNAL SIGNS. PLEASE
CONTACT THE COUNTY PLANNER FOR THE APPLICATION.
31)A KNOX BOX MAY BE REQUIRED, IT IS TO BE MOUNTED ADJACENT TO THE FRONT
DOOR. PLEASE CONTACT THE LOCAL FIRE DISTRICT FOR NEED AND EXACT
LOCATION.
32) GRAB BAR BACKING IS TO BE IN PLACE FOR ALL ACCESSIBLE TOILETS.