HomeMy WebLinkAbout2982 THE FOLLOWING ITEMS HAVE EITHER BEEN OMITTED FROM YOUR PLANS OR DID NOT COMPLY- WITH TUE • PROVISIONS OF THE UNIFORM BUILDING CODES. PLEASE CHECK ALL "x "ed ITEMS BEFORE BEGINNING CONSTRUCTION. All references are 1982 UBC unless otherwise noted. Y' 1. Structural concrete for footing and foundations and load bearing slabs on grade is is required to be 3000 PSI within 30 days. 2604(c)E and Standard 26 -1 A/2. Reinforcement steel for footings: 2 #4 rebars continuous 3. Frost protection for footings: 30" minimum to the TOP of the footing. 2907(a) x ',4. Foundations shall extend at least 6 inches above grade. 2907(a) 5. Provide for the drainage of surface /runoff water away from the building. 2905(f) 6. Foundation plates on mud sills shall be redwood or pressure treated wood. 2516(c)3 47. Foundation plates shall be bolted to the foundation with anchor bolts a minimum of 1/2" x 7" - 6 feet on center; 1/2" x 15" in unreinforced grouted masonry. 2907(e) 8. Solid blocking is required between joists at all bearing points. 2518(d)3 9. With joists @ 24" on center: minimum plywood thickness allowed is 3/4 ". Table 25 -R -1 10. Joists are insufficient for the spans: Minimum X - -0.C. Table 25 -U -J -1 11. Beam insufficient for loads /spans X MIN size allowed. Tables 25 and 2304 TX3 2 . A glu-lam or i red atS6l� - Tables 25 and 2304 ��13. All walls bearing two (2) floor loads are required to be a minimum of 3 x 4's or 2 x 6 - - studs with a maximum spacing of 16" on center. 2518(g) 1,3 2 (14. Shear bracing required: both sides of each corner and every 25 lineal feet. 2518(g)5 15. Brick ties; 1" x 22 gauge, spaced a minimum of 16 on cneter each way. UBC Standard 30 X16. Ceiling /floor headroom is required to be a minimum of 7'6" in all rooms except kitchens halls, bathrooms and storage areas which may be a minimum of 7'0 ". 1207(a) • 17. Minimum stairwell headroom measured from the nosing of tread is 6'6 ". 3305(p) STAIRS: MAXIMUM rise - 7 1/2 "; MINIMUM run - 10 "; MAXIMUM overall variation within X 18. ALL a flight of stairs is 3/8 ". 3305(c) (RESIDENTIAL EXCEPTION - 8" Rise & 9" Tread). )C19. Minimum width of stairways in a single - family dwelling is 30 ". 3305(b) 20. Handrails: minimum height - 30 "; maximum height - 34 ", handgrip portion shall be not less than 1 1/4" or more than 2 inches in cross sectional area. 3305(j) 21. Residential guardrails: minimum height -36". Open guardrails and stair railings shall have -ISOLATED COMMERCIAL MAY BE 2 " aP such sphere 6" )n diameter cannot pass through. 1711 1 22. Underfloor /crawl space ventilation is required. 2517(c)6 23. Access to underfloor areas shall be a minimum of 18" x 24 ". 2516(c)2 24. Windows in unfinished basements: 4' x 4' with a maximum sill height of 44" or area used for storage only and plans marked "STORAGE AREA ONLY ". 1204 (Item 26, below) 25. Windows located within 18" of the floor and 18" or wider are required to be tempered or protected. 5406(d)6 & 7 26. EVERY bedroom below the fourth (4th) floor without a door opening to the outside shall have a least one window that meets the following requirements: MAXIMUM sill height:- 44 inches MINIMUM net clear opening width: 20 inches MINIMUM net clear opening height:. 24 inches MINIMUM net clear opening: 5.7 square feet 1204 - 27. - Provide combustfon - air for- - furnace /water= heater. - = -UMC __007 - 28. Provide floor drain for water heater or pipe P & T relief valve to the outside of the - building. UPC 1007 29. Furnace and water heater must each be removable without moving the other. UMC 703 30. Each water closet shall have minimum clearances of 24" in front and 30" width (15' cent line to nearest sidewall). Sec 511 31. Bathrooms without windows shall be equipped with a fan vented to outside air. Sec 705 - 32. Attic access required; minimum opening: 22 x 30 inches. 3205(a) 33. Fireplace hearth: minimum depth in front of opening is 16 inches, sides 8 inches. 370; I 34. Attic ventilation required; minimum 1 /150th of the vented space. 3205(c) 35. One hour firewall with a self closing 1 3/8" solid core door is required between the house and the garage. 503(d) 36. A "wired in" electrical smoke detector is required in all bedroom access areas; for second story bedrooms, locate the detectors at the top of the stairway. Any other alarm trips other alarms. 1210(a) X 37. Headers over doors & windows will be on edge. Sec 2517(g)5 38. - 39. - 40. - 41. 42. I AGREE TO COMPLY WITH THE ABOVE REQUIREMENTS. C~ 4-c„,__‘e-__ _ DATE - - S.. j